Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹71.1 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹80.8 L+₹9.6 L (13.5%)Rejected-AOC | L2 | Rejected-AOC L2 | |
| 3 | L3₹85.4 L+₹14.3 L (20.1%)Rejected-AOC | L3 | Rejected-AOC L3 |
Tender Value
₹72.1 L
EMD Value
₹72,070
Closing Date
18 Nov 2019, 4:00 pmClosed
Superintending Engineer, Irrigation Central Circle
O/o The Superintending Engineer, Irrigation Central Circle, Chembukavu, Thrissur - 680 020.
Electrical works.
2019_Irrig_311019_1
KL/WRD/DRIP/NCB/SE/ICC/02/ELE
Open Tender
Electrical Works
Item Rate
180 days
Chimoni Dam
Please refer tender documents.
7 documents required · 7 mandatory
₹3,186
Yes
online
₹72,070
Yes
Thrissur
12 Mar 2020
19 Oct 2019
23 Nov 2019
19 Oct 2019
18 Nov 2019
2 Nov 2019
20 Oct 2019 - 18 Nov 2019
2 Nov 2019
Amount
Part I - Electrification
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper, required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular Accessories). Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Independent plug - Short point.
Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.50 mm dia GI pipe.
Supply ,conveyance and erection of the lighting poles for post top lantern fittings of all types Klite KP-4801 single arm 2440mm pole Mettalic colour or equivalent (MR).
Supply installation testing commissioning of Octogaonal Pole made of hot dip galvanised GI sheet 70mm top diameter, 130mm bottom diameter thickness 3mm base plate dimensions of 200x200x12mm suitable for wind speed as per IS 875 Part III single arm bracket 0.5mt including connector foundation bolt 4 nos fixed in existing RCC foundation and junctions box etc.complete 5 Meters.
Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer).
Supply ,erection , testing and commisioning of LED Underwater BCP 170 of make M/s Philips, IP 68 or equivalent make including supply of under water cable, male/ female plug and socket etc complete (for replacing the exisiting fitting in gallery).
Supply , Conveyance and fitting 20A, HRC Fuse Base with suitable HRC Fuse link.
Supply and installation of 6 way connector.
Supply & installation of light fittings on 'C/U' shaped flat iron bracket<br>Supply, conveyance, installation,testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1x28wT5 fitting with APF electronic ballast suitable for continuous operation with THD less than 10%, power factor greater than 0.98, RoHS compliant, high lumen tube.
Supply, conveyance, installation, testing and commissioning of pre-wired light fitting of the following types complete with all accessories and lamps etc. in the existing GI pipe and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.Post top luminaire make 27W LED- Klite make Prince orna midi 5391 or equivalant with lamps and all accessories.
Supply, conveyance, installation, testing and commissioning of pre-wired light fitting of the following types complete with all accessories and lamps etc. in the existing GI pipe and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.Flood light fitting Bajaj make BJENF 400MH Complete with all accessories and lamps.(MR).
Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover suitable for 7 W LED to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required including 7 W LED lamp.
Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
Supply, conveyance, installation, testing and commissioning of the following sizes of exhaust fans in the existing opening, fixing necessary bolt and nuts, making good the damages etc. as required including giving connections with required length of 24/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS. - 300/ 305 mm, single phase 1400 rpm heavy duty exhaust fan in metal frame.
Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required. 1200mm sweep -5star rated ceiling fan complete with 300mm down rod, canopies, shackeles and blades and resistance type regulator working on 230V/240V single phase A/C.
Supply and fixing the following sizes of PVC Conduit conforming to IS 9537 / 1983 part III along with all required accessories on surface including making good the damages etc as required. - 20 mm dia light gauge .
Supply and fixing the following sizes of PVC Conduit conforming to IS 9537 / 1983 part III along with all required accessories on surface including making good the damages etc as required. - 32 mm dia light gauge .
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.<br>2 x 1 sq. mm.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 1.5 sq. mm.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 2.5 sq. mm.
Supply and drawing the following sizes of multi-core PVC insulated & FRLS PVC sheathed 650/1100 V grade copper conductor round flexible cables conforming to IS 694 part I 1960 in the existing surface / recess conduit as required including giving necessary connections of the following sizes.3 core 1.50 sq mm.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm).
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet.
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link,<br>earth bus and DIN rail suitable for fixing MCB/isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall ,<br>making good the damages, colour washing etc. as required. - 4P/3P enclosure for independent mounting of MCB/RCCB/RCBO.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door.
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - three phase double cover (IP 42/43).
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required6 way (8+18) - three phase double cover (IP 42/43).
Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP 42/43).
Supply and installation of Modular time switch(4127 90)Micro rex QT daily time switch legrand make or equivalent.
Supply and installation of 25A Power contactor for DX3 time switches (4125 44) power contactor CX3 legrand make or equivalent.
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>25/32 amps.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>25/32 amps.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps.
Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.25 amps.
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole.
Supplying and fixing 40 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>Triple pole.
Supplying and fixing 50/63 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.<br>Triple pole.
Supply and providing following pluggable type surge arrester Class B+C/ Class 1 + 2 as per IEC 61643 (IP 20) with potential free contact, thermal disconnecter & provision for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse & cooling gel (L to N) & spark gap encapsulated / non exhausting (N to E) Nominal discharge current-30 kA (8/20μ sec) for Line to Neutral & 50 kA(8/20μ sec) for Neutral to Earth, max discharge current 50 kA (8/20μ sec) voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E), lightning impulse current 7 kA ( L to N) & 25 kA (N to E) DIN rail mounting type etc complete with back up fuse as required and as directed.Surge Protection Device- Single Phase: V25B+C/1+NPE 320V.
Supply and providing following pluggable type surge arrester Class B+C/ Class 1 + 2 as per IEC 61643 (IP 20) with potential free contact, thermal disconnecter & provision for inbuilt common remote indication for defective arresters to connect between Line and Neutral and one number arrester Spark Gap type to connect between Neutral and Earth of following ratings including base element & pluggable arresters. Nominal voltage -230V 50Hz, type single MOV with built in thermal fuse & cooling gel (L to N) & spark gap encapsulated / non exhausting (N to E) Nominal discharge current-30 kA (8/20μ sec) for Line to Neutral & 50 kA(8/20μ sec) for Neutral to Earth, max discharge current 50 kA (8/20μ sec) voltage protection level 1300V (L to N) & 1200V (N to E). Operating temp -40º to +80ºC. Response time <25 nano sec (L to N), < 100 nano sec (N to E), lightning impulse current 7 kA ( L to N) & 25 kA (N to E) DIN rail mounting type etc complete with back up fuse as required and as directed.Surge Protection Device-Three Phase: V25B+C/3+NPE 320V.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 4 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in ground including excavation of trench of size 35 x 75 cm, refilling the trench etc. as required but excluding sand cushioning and protective covering (in ordinary soil).2 core 6 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 4 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.2 core 6 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 6 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 25 sq mm.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 4 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.2 core 6 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 4 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 6 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3 core 10 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 25 sq mm with factory made clamp.
Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 185 sq mm.
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.
Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench<br>40/32mm or nearest size.
Supplying and making end termination with brass compression gland and aluminium lugs for <br>following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV <br>grade as required.<br>2X 4 sq. mm (19mm).
Supplying and making end termination with brass compression gland and aluminium lugs for <br>following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV <br>grade as required.<br>4 X 4 sq. mm (19mm).
Supplying and making end termination with brass compression gland and aluminium lugs for <br>following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV <br>grade as required.<br>4 X 6 sq. mm (19mm).
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm).
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 X 10 sq. mm (22mm).
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm).
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm).
Supplying and providing earth clamps made out of copper strips of the following sizes including cutting and bending the flat exactly to the shape of the<br>gland, drilling necessary holes for nut & bolt, tinning the points of contacts and giving connections to the main earthing system as required.<br>(20 x 3 mm for earthing glands of size 120 sq mm to 185 sq mm).
Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of<br>glands for the following sizes of cables as required.(4 sq - 16sq mm with 12 mm wide x 1.20 mm thick clip).
Supplying henzel -SYNTEC THREADED CABLE GLANDS<br>IP 68 WITH LAMELLAR TECHNOLOGY for PVC insulated and PVC sheathed armoured aluminium/ copper conductor cable 1.1 KV grade, and making end termination suitable for 2/ 3/ 3½/ 4 core cable of the following sizes as required.suitable for 1 sqmm copper round flexible cable.
Supplying henzel -SYNTEC THREADED CABLE GLANDS<br>IP 68 WITH LAMELLAR TECHNOLOGY for PVC insulated and PVC sheathed armoured aluminium/ copper conductor cable 1.1 KV grade, and making end termination suitable for 2/ 3/ 3½/ 4 core cable of the following sizes as required.4/6 sq mm or nearest.
Earthing with G.I. earth plate 600 mm X 600 mm X 6.3 mm thick including accessories, and<br>providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.15 metre long etc. with charcoal/ coke and salt as required.
Supply and providing the following sizes of cast iron gully trap with covering at the top of the inspection chamber of earth pit as required . - 300 x 300 x 10 mm cast iron gully trap with covering.
Providing and fixing testing joint made of 2 no. strips as mentioned below of Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required.2*25*3 Copper strip.
Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25*3 copper strip.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 2.00 mm copper conductor (14 SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 2.65 mm copper conductor (12 SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 3.15 mm copper conductor (10 SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 4.00 mm copper conductor (8 SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 4 mm GI conductor (8 SWG) Net.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 3.15 mm GI conductor (10 SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 20X3 Aluminium strip.
Supplying and clamping the following sizes of strips on surface of wall/parapet/existing cable tray using clamps fabricated from 20 x3 mm GI flat duly painted or heavy duty GI spacer saddles, spacing of clamps not exceeding 1m, making good the damages, colour washing etc as required. 20 mm X 3mm Aluminium strip .
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required. - 2.00 mm (14 SWG).
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required.- 2.65 mm (12 SWG).
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required.- 3.14 mm (10SWG).
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required.-4 mm (8 SWG).
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 12 x 3mm.
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 3 mm brass bolt & nut.
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 6 mm brass bolt & nut.
Supplying , threading , laying and jointing of the following sizes of GI pipe with all required accessories in ground in the existing trench as protective covering to earth leads.15 mm dia.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.<br>15 mm dia with HG company fabricated clamps.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.32 mm dia with HG company fabricated clamps.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.40 mm dia with clamps made from 20 x 3 mm MS flat.
Part 2 - Generator Panel Board and Other Installations.
Fabrication, supply, conveyance, installation testing and commissioning of floor or wall mounting, dust and vermin proof, cubicle type MV panel board comprising of the following components/ devices & complying to IS 8623.<br>Fabrication of fully partitioned, dust and vermin proof enclosure for panel assembly as per form 4 of IS 8623 (with latest amendments) using CRCA sheet as per approved design and requirement, with front and rear access facility, bus bar chambers, hinged doors for all switch gear compartments, earthing the doors using 4 sq mm braided copper conductor, providing necessary cut-outs for mounting meters, relays, indication lamps, bus bar interconnection etc, detachable covers for bus bar chamber and cable alley, powder coating the assembly after subjecting to 7 tank process etc as required. CRCA sheet alone be used for the fabrication. Angles/ flats/ slotted angles etc shall not be used for the fabrication of panel assembly. The measurments will be taken the area of the complete sheets used for panel board including partitions, folding, shrouding etc.Supply and fabrication of MV panel board using 1.6mm CRCA sheet, powder coated (excluding base frame).
Supply and providing 2mm SMC sheet as shrouding for bus interconnection / terminations etc. including required nut & bolt etc.
Supply and providing heavy duty 'A' section neoprene gasket in the panel boardA' section neoprene beeding suitable for 1.60/ 2.00 mm sheet.
Supply and fabrication conveyance and installation of base frame of panel board using 75 x 40 mm rolled steel channel (ISMC).
Supply and providing copper bus bars including finger type SMC bus bar supports in the bus chamber, suitable size nut & bolt, providng heat shrink sleeves etc. as required.
Supply and providing copper earth bus in the panel board.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.125 Amp TP & N.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.63 Amp TP & N.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required.100 Amp TP&N.
MCCB AccessoriesSupply and fixing kastel interlock kit up to 250A.
Supply and providing LED indicators for all voltage ranges - Red, Green, Black, Yellow or Orange Colour.
Supply and fitting Digital Multifunction meter to read:W, Wh, PF or VA, Vah, PF or V AR, V ,A Rh, PF - 3. phase accuracy class 1 LED.
CURRENT TRANSFORMER - 100/5 A, 5 VA, accuracy class 0.5, Resin Cast Metering CT.
S/F Bus bar chamber, 100 x 40 mm aluminium anodised legend plates.
S/F Cable alley, 100 x 40 mm aluminium anodised legend plates.
Supply , Conveyance and fitting 20A, HRC Fuse Base with suitable HRC Fuse link.
Carrying out control wiring for panel with normal meters and indication lamps for interconnecting the control devices/ equipments including providing<br>suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring,<br>keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.-1.50 sq mm single run with required sockets.
Carrying out control wiring for panel with normal meters and indication lamps for interconnecting the control devices/ equipments including providing<br>suitable size insulated sockets at the termination points or soldered properly, providing numbering ferrules for the proper identification of the wiring,<br>keeping the wiring firm by suitable tie/ tie mounts/ PVC duct etc as required.2.50 sq mm single run with required sockets.
Supplying and installation including all manner of supports/ suspenders, anchor bolts etc for cable trays made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.
Supplying and installation of supports, anchor bolts etc made out of suitable size single section angles/flats etc as required including painting with 2 coats of synthetic enamel paint.
Supply and providing 5 Kg. Dry Chemical Powder type Fire Extinguisher with hose and clamps including fixing it to wall as required.
Supply and providing 9 Litre capacity GI Fire Bucket painted in post office red with primer coat of red oxide and written with white paint 'FIRE' mounted on MS angle frame work/ wall bracket filled with fine sand, painting the bracket/ floor stand including making good the damages, colour washing etc. as required.
Supply and providing First Aid Chart duly framed and placed in a conspicuous location for clear vision.
Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height.
Supply and providing 2mm thick Elastomeric fire retardent insulating mat as per IS 15652/2006 to withstand 11 KV dielectric strength.
Supply and installation of dust and vermin proof wall mounting , sintex make thermoplastic meter box of size 570X280X330 mm GSMB 5728 ( IP65 ) suitable for fixing KSEB meter,fuse units,CT etc hinged door construction for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry and exit IP65 with neutral CT as required including fixing it on transformer plinth making good the damages etc. as required.
Supply , Conveyance and fitting 32A, HRC Fuse Base with suitable HRC Fuse link.
Supply , Conveyance and fitting 32 A, 2 Way neutral links in the existing Meter box.
Charges for dismantling the existing generator from the concrete foundation and removing from generator room.
Charges for cutting an removing the tar on the surface of road for formation of cable trench.
Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Providing brick work (in width 225 mm or more) with F.P.S. bricks of class designation 7.5 in cement mortar 1:4 (1 cement : 4 coarse sand) at all levels.
Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete.
Colour washing, 2 coats.
Scrapping,cleaning and painting the existing 2.5 m long light poles with two coats of epoxy paint.
Supply and providing 1.6mm thick MS cover for the junction box painted with epoxy paint in place of damaged one.
Dismantling the 6-25 HP motor into stator and rotor, cleaning the windings attending minor repairs, re taping the coils if necessary, varnishing the coils with best quality insulation varnish, cleaning and greasing the bearings with good quality grease, heating the windings, reassembling, test running including scrapping, cleaning and painting with enamel paint.
Refitting the 5-10 HP motor on base plate, leveling and correcting alignment with the pump coupling the same giving connection, testing and trail run on full load.
Dismantling the 6 - 10 HP starters by parts draining out the oil, cleaning the tank, terminal contacts, cutting, leveling and polishing the contacts wherever necessary, checking the tripping mechanism, replacing the damaged wires, attending minor repairs, cleaning the oil,(in case of oil starters ), refitting, resetting and making the starter in good working condition including scrapping, cleaning and painting with a coat of enamel paint.
Part 3 - High mast light
Supply installation testing and commissioning of High Mast using Octogaonal Pole made single/two sections of hot dip galvanised GI sheet 100mm top diameter, 360mm bottom diameter thickness 3mm mm suitable for wind speed as per IS 875 Part III with head frame assembly two point suspension system with steel wire rope 5mm dia double drum winching system w and including round arm galvanized luminary carriage suitable to install 6/8 nos luminaries in symmetrical arrangement control gear box and lighting spikes with single phase operation power tool installed inside the base compartment including connector foundation bolt 4 nos fixed in existing RCC foundation and junction box etc, complete 12 Meters.
Supply Conveyance, installation, testing and commissioning of 120W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/ Lumilled/ Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer).
Earthing with G.I. earth plate 600 mm X 600 mm X 6.3 mm thick including accessories, and<br>providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.15 metre long etc. with charcoal/ coke and salt as required.
Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
Steel reinforcement for RCC Work including straightening, cutting, bending, placing in position and binding all complete.
Providing 15mm thick cement plaster of mix 1:4 (1 cement : 4 fine sand) at all levels.
Providing and fixing testing joint made of 2 no. strips as mentioned below of Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required.2*25*3 GI strip.
Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25*3 GI strip.
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 6 mm brass bolt & nut.
Supplying , threading , laying and jointing of the following sizes of GI pipe with all required accessories in ground in the existing trench as protective covering to earth leads.15 mm dia.
Excavation for foundation in soft soil including dressing of sides and ramming of bottoms, lift upto 1.5 m including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 metres.
Providing and laying in position cement concrete 1 :3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required.
Colour washing, 2 coats.
Charges for cutting an removing the tar on the surface of road for formation of cable trench.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 10 sq mm.
Supply & laying of one number PVC insulated and PVC sheathed armoured aluminium power cable of 1.1KV grade of the following sizes in the existing RCC/ HUME / STONE WARE/ GI/ DWC pipe as required.4 core 16 sq mm.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 10 sq mm with factory made clamp.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.4 core 16 sq mm with factory made clamp.
Supply & laying of DWC pipe in ordinary soil 1.2 m below ground level including excavation63/50 mm or nearest size.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm).
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm).
Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of<br>glands for the following sizes of cables as required.(4 sq - 16sq mm with 12 mm wide x 1.20 mm thick clip).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 3.15 mm copper conductor (10 SWG).
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required.- 3.14 mm (10SWG).
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 3 mm brass bolt & nut.
Supplying and installation of supports, anchor bolts etc made out of suitable size single section angles/flats etc as required including painting with 2 coats of synthetic enamel paint.
Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 2.50 cm, 4 cm or 5 cm height.
Painting letters or figures of the following sizes with enamel paint as identification mark to SB, DB, panel board etc as required- 6.5 cm, 8 cm or 13 cm height.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.50 mm dia with clamps made from 25 x 3 mm MS flat.
Part 4 - Providing DG Set.
Supply installation ,testing and commissioning of 62 KVA , Diesel Generator with standard panel.
Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy guage specials such as bends,<br>flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the<br>pipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any ther<br>mechanical support etc as required.- 125 mm dia B class MS pipe as extended exhaust pipe.
Supply and providing the following size of B class MS pipe conforming to relevant IS specifications complete with heavy guage specials such as bends,<br>flanges etc welded and fixed at appropriate locations, providing cork sheet in between the flanges at the joints, bolting the flanges together, painting the<br>pipe, flange etc with 2 coats of heat resistant paint suitable for outdoor applications, fixing the pipe firmly with fabricated structure/wall/any ther<br>mechanical support etc as required.- 100 mm dia B class MS pipe as extended exhaust pipe.
Earthing with G.I. earth plate 600 mm X 600 mm X 6.3 mm thick including accessories, and<br>providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.15 metre long etc. with charcoal/ coke and salt as required.
Supply and providing the following sizes of cast iron gully trap with covering at the top of the inspection chamber of earth pit as required . - 300 x 300 x 10 mm cast iron gully trap with covering.
Providing and fixing testing joint made of 2 no. strips as mentioned below of Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required.2*25*3 Copper strip.
Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25*3 copper strip.
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 5.9 mm copper conductor (4 SWG).
Supplying and laying 4 SWG copper earthing conductor at 0.60 meter below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt & spring washer spaced at 50 mm).
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 6 mm brass bolt & nut.
Supplying , threading , laying and jointing of the following sizes of GI pipe with all required accessories in ground in the existing trench as protective covering to earth leads.15 mm dia.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.<br>15 mm dia with HG company fabricated clamps.
Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required.3.5 core 50 sq mm with factory made clamp.
Supply & laying of one No. PVC insulated and PVC sheathed armoured aluminium power cable of 1.1 KV grade of the following sizes in the existing masonry open duct as required.3.5 core 50 sq mm.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 50 sq. mm (35mm).
Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of<br>glands for the following sizes of cables as required.(25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip).
Charges for preperation of Electrical Schematic per A3 sheet.
Copying charges for additional copies per A3 sheet.
Part 5 - Electrification of flat type quarters and camp office cum watchman cabin.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Single Control light point with 6A, plate ceiling rose - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single control light point without ceiling rose - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories). Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Call bell point with 6 A bell push at one end and 6 A, 3 plate ceiling rose at other end - Short point.
Supply and wiring points according to IS 732-1989 using rigid PVC conduit of minimum size 20 mm with specials conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm FRLS PVC insulated stranded single core copper conductor cable 650V grade, including providing switch board main and continuous earthing with No.14 SWG bare copper,required quantity of copper earth socket, brass bolt and nut crimping/ soldering etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6A modular type SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. (RoHS compliant modular accessories).Combined plug point with 6 A, 5 pin plug socket controlled by 6 A, switch in the same switch board as that of light points.
Supply & installation of light fittings on 'C/U' shaped flat iron bracket<br>Supply, conveyance, installation, testing and commissioning the light fittings of following types made from 0.5mm CRCA sheet complete with all accessories and lamps etc. directly on wall using 2 nos. 'C/U' brackets made from 20 x 3 mm MS flat, painting the flat iron bracket and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required.1200 mm 1X20W LED Lamp with box type fixture.
Supply & installation of light fittings suspended on ball & socket arrangement with 19 mm down rod<br>Supply, conveyance, installation, testing and commissioning the light fittings of following types made of .5mm thick CRCA sheet accessories and lamps etc. including supplying and fixing ball and socket arrangements on PVC round block, suspension down rod of 19mm dia MS conduit up to 2x30cm length including painting and wiring the down rod with 16/0.20mm 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connections etc. a required.1200 mm 1X20W LED Lamp with box type fixture.
Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
Supply, conveyance, installation, testing and commissioning of ceiling fans of the following sizes using standard accessories excluding resistance type regulator, wiring the down rod with 16/0.20mm PVC insulated and PVC sheathed 650/1100V grade 3 core round copper conductor flex wire or with extended original wiring etc. as required.1200mm sweep -5star rated ceiling fan complete with 300mm down rod, canopies, shackeles and blades and resistance type regulator working on 230V/240V single phase A/C.
Charges for cutting holes suitable for accommodating exhaust fans up to 305mm sweep including plastering colour washing etc. as required.
Supply,Conveyance, installation , testing and commissioning of exhaust fans of size 200 mm sweep Light Duty Exhaust fan in plastic body with self opening lowers working on 230v single phase A/C in the existing opening, fixing necessary anchor bolts / bolt and nuts etc., as required including giving connections with the supplied wire along with the exhaust fan.
Supply and fixing cast aluminium stove enameled bulk head fitting with deep drawn anodised aluminium body, epoxy powder coated, heat resistant prismatic glass cover suitable for 7 W LED to wall / ceiling including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming to relevant ISS or extending the original wiring and making good the surface as required including 7 W LED lamp.
Supply and fixing angle / straight brass lined skirt type, bakelite batten holder with 200 mm polished plastic shade and 7 W LED bulb including giving connection etc as required.
Supplying and fixing metal box of following sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.75 mm X 75 mm X 60 mm deep.
Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Gong bell 75mm-without MS box.
Supply, fabrication, conveyance and fixing the following sizes of B class GI pipe bent to shape / cut and welded to shape and fixing the same to wall / parapet using clamps as noted along with each size, painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required.25 mm dia with HG company fabricated clamps.
Supply Conveyance, installation, testing and commissioning of 20W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/ Lumilled /Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD Less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer).
Supply and fixing the following sizes of PVC Conduit conforming to IS 9537 / 1983 part III along with all required accessories on surface including making good the damages etc as required. - 20 mm dia light gauge .
Supply and fixing the following sizes of PVC Conduit conforming to IS 9537 / 1983 part III along with all required accessories on surface including making good the damages etc as required. - 25 mm dia light gauge .
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.6 x 1.5 sq. mm.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm.
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.2 x 4 sq. mm.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet.
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.3 Module (100mmX75mm).
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.8 Module (125mmX125mm).
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module.
Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.8 Module.
supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required.- 3.14 mm (10SWG).
Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. - 3.15 mm copper conductor (10 SWG).
Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required - 25 x 3 mm brass bolt & nut.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator12 way, Double door.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole.
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps.
Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residualcurrent circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps.
Earthing with G.I. earth plate 600 mm X 600 mm X 6.3 mm thick including accessories, and<br>providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.15 metre long etc. with charcoal/ coke and salt as required.
Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25*3 GI strip.
Providing and fixing testing joint made of 2 no. strips as mentioned below of Supply and providing test joint for the earthing system using 2 Nos of the following sizes of strips including cutting and bending to shape, drilling necessary holes and fixed to the watering pipe etc as required.2*25*3 GI strip.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Supply and providing the following sizes of cast iron gully trap with covering at the top of the inspection chamber of earth pit as required . - 300 x 300 x 10 mm cast iron gully trap with covering.
Supply and installation of dust and vermin proof wall mounting , sintex make thermoplastic meter box of size 350*250*150 mm GSMB 3525 ( IP65 ) suitable for fixing KSEB meter,fuse units,CT etc hinged door construction for the front side with compartments if necessary,providing vision panel for the meter compartment knock out for cable entry and exit IP65 with neutral CT as required including fixing it on transformer plinth making good the damages etc. as required.
Supply , Conveyance and fitting 32 A, 2 Way neutral links in the existing Meter box.
Supply , Conveyance and fitting 32A, HRC Fuse Base with suitable HRC Fuse link
ABM Electricals
Franjo Engineering Corporation
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_427620.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .