Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.7 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹43.9 L+₹8.1 L (22.7%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹43.9 L+₹8.1 L (22.8%)Rejected-Finance NO 3 WD BUILDING JP AGARWALLA ROAD BHARALUMUKH KAMRUP ASSAM 781009 UDYAM AS 03 0009483 | KAMRUP METRO | ASSAM | 781009 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹44.4 L+₹8.6 L (24.1%)Rejected-Finance CHANDMARI WARD NO 19 PO PS TEZPUR DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784001 | L4 | Rejected-Finance Other than L1 | |
| 5 | L5₹44.8 L+₹9.0 L (25.3%)Rejected-Finance B S ROAD KOLIBARI TEZPUR 784 001 DIST SONITPUR ASSAM | SONITPUR | ASSAM | 784001 | L5 | Rejected-Finance Other than L1 |
Tender Value
₹50.0 L
EMD Value
₹99,980
Closing Date
9 Sept 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE (NORTH) TEZPUR
GE (NORTH) TEZPUR, C/O 99 APO
SPL REPAIR /REPLACEMENT TO LT OVER HEAD ELECTRIC DISTRIBUTION LINE FOR JCOs AND OR MD ACCN AT ZONE 8 NAA UNDER GE (NORTH) TEZPUR
2023_MES_613594_1
GE(N)/TEZ/2023-2024/8745
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (NORTH) TEZPUR
As per tender documents
8 documents required · 8 mandatory
₹500
GE (NORTH) TEZPUR
₹99,980
16 Oct 2023
12 Aug 2023
16 Sept 2023
12 Aug 2023
9 Sept 2023
26 Aug 2023
Amount
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or water supply pipes lines etc or not exceeding 10 sqm on plan and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and as directed.
Supply & spreading in trenches sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
M & L for laying of bricks locally available sub class 'B' bricks (old size) for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 240 Sqmm x 3.5 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 150 Sqmm x 3.5 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 Sqmm x 3.5 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 25 Sqmm x 4 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 Sqmm x 4 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply, Laying, testing & commissioning of UG LT cable XLPE insulated screened PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 Sqmm x 4 core including connecting the cables at both ends by providing suitable size aluminium lugs at the termination ends and necessary saddle clamp all as specified and directed by Engg-In-charge.
Supply,installation,testing and commissioning 3 phase and neutral , 415 volts out door type , CPRI approved, factory made free standing , floor mounting ,dust and vermin proof, cubical type LT panel (size of panel recommended/approved by Engineer-In-charge or as per direction) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shell, with angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type, double door system, hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 250 Amps ( Size of copper strip should not be less than 25 x 8 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands , cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box / LT Panel with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. (Panel 1) (A) Incoming (i) MCCB 160 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 125-160 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 36 kA --- 01 Nos (Make:- Legrand) (ii) Digital Ammeter---01 Nos with Suitable CT and wiring. (iii) Digital Voltmeter - 01 No (iv) Three indication lamp (v) Neon type for three phase. (vi) Slector switch - 2 Nos (B) Outgoing (i) MCCB 125 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 100-125 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 02 Nos (Make:- Legrand) (ii) MCCB 63 Amps rating, 4 pole , ,415 V, AC, 50 HZ, thermal release range 50-63 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 01 Nos (Make:- Legrand) (ii) MCB SPN, 240 , 50 HZ, C curve, 10 KA-01 No. (Make:- Legrand)
Supply,installation,testing and commissioning 3 phase and neutral , 415 volts out door type , CPRI approved, factory made free standing , floor mounting ,dust and vermin proof, cubical type LT panel (size of panel recommended/approved by Engineer-In-charge or as per direction) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shell, with angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type, double door system, hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 200 Amps ( Size of copper strip should not be less than 25 x 6 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands , cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box / LT Panel with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. (Panel 2)(A) Incoming (i) MCCB 125 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 100-125 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA --- 01 Nos (Make:- Legrand) (ii) Digital Ammeter---01 Nos with Suitable CT and wiring. (iii) Digital Voltmeter - 01 No(iv) Three indication lamp (v) Neon type for three phase. (vi) Slector switch - 2 Nos (B) Outgoing (i) MCCB 63 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 32-40 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 07 Nos (Make:- Legrand) (ii) MCB SPN 16 Amp, 240 , 50 HZ, C curve, 10 KA- 01 No.(Make:- Legrand)
Supply,installation,testing and commissioning 3 phase and neutral , 415 volts out door type , CPRI approved, factory made free standing , floor mounting ,dust and vermin proof, cubical type LT panel (size of panel recommended/approved by Engineer-In-charge or as per direction) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shell, with angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type, double door system, hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 600 Amps ( Size of copper strip should not be less than 2 x 40 x 6 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands , cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box / LT Panel with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. (Panel 3 and Panel 5) (A) Incoming (i) MCCB 320 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 400-500 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 36 kA --- 01 Nos (Make:- Legrand) (ii) Digital Ammeter---01 Nos with Suitable CT and wiring. (iii) Digital Voltmeter - 01 No (iv) Three indication lamp (v) Neon type for three phase. (vi) Slector switch - 2 Nos (B) Outgoing (i) MCCB 160 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 100-125 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 01 Nos.(Make:- Legrand) (ii) MCCB 63 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 32-40 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 09 Nos (Make:- Legrand) (iii) MCB SPN 16 Amp , 240 , 50 HZ, C curve, 10 KA-01 No.(Make:- Legrand)
Supply,installation,testing and commissioning 3 phase and neutral , 415 volts out door type , CPRI approved, factory made free standing , floor mounting ,dust and vermin proof, cubical type LT panel (size of panel recommended/approved by Engineer-In-charge or as per direction) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shell, with angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type, double door system, hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 400 Amps ( Size of copper strip should not be less than 40 x 8 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands , cable connection with proper lugs ,PCC foundation and pedestal for fixing piller feeder box / LT Panel with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel. The plateform shall be of 450 mm height above ground level all as specified with supply and fixing the following. (Panel 4 and Panel 6) (A) Incoming (i) MCCB 160 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 200-250 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 36 kA --- 01 Nos (Make:- Legrand) (ii) Digital Ammeter---01 Nos with Suitable CT and wiring. (iii) Digital Voltmeter - 01 No. (iv) Three indication lamp. (v) Neon type for three phase. (vi) Slector switch - 2 Nos (B) Outgoing (i) MCCB 63 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 32-40 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 25 kA - 09 Nos (Make:- Legrand) (ii) MCB SPN 16 Amp, 240 , 50 HZ, C curve, 10 KA-01 No.(Make:- Legrand)
Supply,installation,testing and commissioning 3 phase and neutral , 415 volts out door type , CPRI approved, factory made free standing , floor mounting ,dust and vermin proof, cubical type LT panel (size of panel recommended/approved by Engineer-In-charge or as per direction) fabricated from 3.15 mm thick CRCA sheet for outer shell and 2.0 mm for inner shell, with angle iron frame of 50 x 50 x 6 mm , double door , front and back openable type, double door system, hinged opening , rubber lining,locking arrangement,with anticorrosive coating and finally epoxy polyester power coating with pure polyster Siemens grey structural RAL-7032 shade , protection class IP-54 fully compartmentalize design with 4 nos of bus bar made of copper of ETP grade suitable for 800 Amps ( Size of copper strip should not be less than 2 x 40 x 10 mm for each phase and neutral) pre-wired with suitable size of copper strip/ copper wire with colour code for connecting out going MCCB/ MCB`s, including suitable aluminium earth strips conforming to IS with danger notice plate , necessary cable glands , cable connection with proper lugs ,PCC foundation and pedestal for fixing LT Panel with PCC 1:5:10 , 15 cm thick in foundation , brick (Fly ash) / PCC block work in CM 1:6 , rendering 1:6 on exposed surface and 100 mm thick PCC 1:3:6 type C1 using 20 mm graded stone aggregate as in padding on top and grouting bolts etc for panel all as specified with supply and fixing the following. (Main Panel) (A) Incoming (i) MCCB 630 amps rating, 4 pole ,415 V, AC, 50 HZ, draw out type, Microprocessor Based, Mannuly operated type, Breaking capacity Icu = Ics = Icw (1Sec) --- 01 Nos (Make:-Legrand) (ii) Digital Ammeter---01 Nos with Suitable CT and wiring.(iii) Digital Voltmeter - 01 No (iv) Three indication lamp (v) Neon type for three phase. (vi) Slector switch - 2 Nos (B) Outgoing (i) MCCB 320 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 400-500 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 36 KA --- 02 Nos (Make:- Legrand) (ii) MCCB 200 Amps rating, 4 pole ,415 V, AC, 50 HZ, thermal release range 200-250 Amp with adjustable overload setting and , short circuit setting, Ics-100 % Icu , service breaking capacity 36 KA --- 01 Nos (Make:- Legrand) (iii) MCB 40 Amp Four Pole (FP) , ultimate breaking capacity 10 KA , C curve - 02 No (Make:- Legrand) (iv) MCB 25 Amp Double Pole (DP) , ultimate breaking capacity 10KA , C curve - 02 No(Make:- Legrand) Note:- (i) Drawing of LT panel and make of items shall be get approved from GE before ordering the panel. (ii) Cost of lugs for cable and cable gland etc also included in unit rate of panel. (iii) Cost included taking out existing cable from old panel and refixing and connecting to new panel. (Iv) Rotary handle to be provided for MCCB for control and operation of MCCB. (v) The copper extesion link from bus bar to out going MCCB / MCB`s shall not be less than 1.5 times the rated current of individual out going feeders. (vi) Independent Amper meter with CTs to be provided for each out going feeder. (vii) Spreader terminals and Phase barriers to be provided with all MCCB`s
Taking down/out cable any type any size from over head line to building main switch board(over head or on air /under ground) complete all as directed by EIC.
Dismantling ACSR or AAC conductors from HT oh lines/structures and removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside by diconnecting all electrical connections for re-use or removing to store or for schedule of credit all as directed by Engr-in-Charge
Dismantling HT/LT insulators any type, any size by diconnecting all electrical connections complete all as specified and as directed.
M&L for laying 50 mm bore GI pipe, medium grade with all fittings, in crossing road/path or in pole/wall up to junction box/DBs/Main switch board etc including necessary clamping etc. complete all as specified and as directed by Engineer-in-Charge.
M&L for laying 80 mm bore GI pipe, light grade with all fittings, in crossing road/path or in pole including necessary clamping etc. complete all as specified and as directed by Engineer-in-Charge.
M&L for laying 100 mm bore GI pipe, light grade with all fittings, in crossing road/path or in pole including necessary clamping etc. complete all as specified and as directed by Engineer-in-Charge.
Labour and T&P required for horizontal boring under road/path for insertion of pipe/cable up to 100 mm bore by manual /machine complete all as specified and directed by Engineer-In-charge.
S& F cable route marker made up of cast iron (Round Dia ) of 100 mm round plate, 3 mm thick fixed on MS angle iron of size 25 x 25 x 5 mm, 800 height fixed in ground over the cable route including PCC 1:2:4(size of foundation recommended by Engineer-In-Charge) complete all as specified and directed by Engineer in charge.
M & L for Earthing with galvanised steel pipe electrode, 40 mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 32 x 6 GI strip all as shown in Plate No. 2 ( SSR Part-1) to the earthing test point all as specified and indicated , necessary excavation any type of soil, CI chamber cover 10 mm with 6 mm rod , wire mess, funnel, test point, 20 mm dia GI protection pipe medium grade etc complete and testing on completion all as specified and directed by Engr-in-charge (4 mm wire lead upto 7.5 RM will be included in the item rate . (Note :- Fresh agriculture soil / black dirt or soil with a high organic conten will be used for filling the dug as required when rocky /sandy soil found at site to achieve the desired resistance from out side without any extra cost.
S & F Thermoplastic cable junction box of size 205 mm x 255 mm x 112 mm , IP 66 , halogen free and weather proof with locking arrangement and necessary mounting arrangement on pole with MS clamp , nut , bolt ,washer , for out door installation complete with connector terminal for connecting cable, knockouts for cable entry up to the size of 25 Sqmm x 4 core, cable by providing suitable size cable lugs & cable gland complete all as specified and directed by Engineer-in-charge.
S & F Non metallic PVC medium grade conduit 20 mm dia for drawing aluminium conductor cable between pole junction box and light fitting including fixing clamp made of GI strips and nut and bolts (Minimum 3 clamp in each pole to be provided.) complete all as specified and directed.
Material and labour for cutting of PCC/hard surface for laying of pipe (up to 100 mm) including providing cement conceret 1:3:6 type C1 (Using 20mm graded aggregate) cutting chases on walls / surface /floor and making good disturbed surfaces with finishing complete all as specified and directed
M&L for Flexible PVC insulated multicore FR PVC sheathed multistranded copper conductor cable of 1.5 Sqmm x 3 core for voltage grade up to 1100 V conforming to IS 694 : 2010 for connection of light fitting from junction box or from over head conductors to fitting complete all as specified and as directed by Engineer-in-Charge.
shyam constructions
PURBANCHAL BUILDERS
MAHANTA ENTERPRISES
Anil Kumar Sarmah
M/S S K ENTERPRISES
M/S JIWA SINGH S GILL
S and B Electricals
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .