Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹25,000
Closing Date
2 Mar 2024, 6:00 pmClosed
Sinnar Municipal Council, Sinnar
Sinnar Municipal Council, Sinnar
Performing annual Operation and maintenance of SCADA system (From raw water source at kadwa dam to ESRs) for financial year 2023-2024 for water supply dept of sinnar municipal council.
2024_DMA_1015563_1
SMC/Water/RE2/SCADA/2023-24
Open Tender
Miscellaneous Services
Item Rate
365 days
Sinnar Municipal Council, Sinnar
As Per Tender Document
2 documents required · 2 mandatory
₹5,000
₹25,000
31 Jul 2024
24 Feb 2024
4 Mar 2024
24 Feb 2024
2 Mar 2024
24 Feb 2024
Amount
Raw Water Pump house
Ultrasonic level transmitter/ for pure water sump/ MBR/ ESR/ Wash Water Tank/ Filter bed
Designing, Supplying, Installing, commissioning & testing of Ultrasonic level transmitter CE marked with following technical parameters Interfacing with PLC panel including mounting arrangement
Ultrasonic level transmitter raddar type level transmeter for raw water pumping station
Designing, Supplying, Installing, commissioning & testing of Ultrasonic Raddar type Ultrasonic level transmitter CE marked with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement
Pressure Transmitter for raw & pure water pumping station
Designing, Supplying, Installing, commissioning & testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including mounting arrangement
Power Analyser
Designing, Supplying, Installing, commissioning & testing of Power Analyser interfacing to PLC Panel with modbus communicatuion port , as per IEC 62053 and in the prescribed format including mounting arrangement.
PLC panel for Raw water pump House with two Pumps
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm (LBH), fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at Raw water Pumphouse. PLC shall have Ethernet port & protocal for Modbus TCP communication with following IO
PLC panel for Raw water pump House with four Pumps
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm (LBH), fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at Raw water Pumphouse. PLC shall have Ethernet port & protocal for Modbus TCP communication with following IO
DI –16 num DO – 16 num AI –16 num AO – 8 num 7 inch color TFT HMI complete with programming shall be provided to interact with PLC. The panel shall include all the accessories (not limited to following) to achieve purpose of smooth & trouble free operation of pump house.
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 1000 mm X 700 mm X 1500mm (LBH), fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at Raw water Pumphouse PLC shall have Ethernet port & protocal for Modbus TCP communication with following IO.
Scada system for Raw water pump House
Design, manufacture, supply, installation, testing and commissioning of SCADA System for pump house. Windows based PC with latest configuration & OS complete with necessory office & antivirus softwares. PC configuration shall not be less than Intel i5 10th Gen CPU, 16 GB Ram, 128 GB SDD, 500 GB HDD, DVD RW, Rs232 & Rs485 port, 2 RJ45 ports, Keyboard, Optical Mouse, 32 inch color TFT Monitor, Latest Windows Pro OS, Microsoft Office & Antivirus & Internet Sequrity software for 3 years license.
Power Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 2 C x 1.5 sq.mm as per IS 694 twisted shielded copper armoured conductor on wall in GI tray or in ground suitable for supplied D. C. Voltage.
Communication Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of CAT As per PWD CSR Terminating & Interfacing of CAT 6 as per ISO/IEC-11801 std.cable for networking on wall in GI tray or on ground etc.
Signal Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 2 Pair x 1 sq.mm as per IS 694 copper Shielded twisted, multistranded armoured cablew on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 3 Pairs x1 sq.mm. as per IS 694 copper Shielded, twisted, multi stranded armoured cable on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 4.5 Pairs x 1.0 sq.mm as per IS 694 copper shielded, twisted, multi stranded armoured cable on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 8 Pairs x 1.0 sq.mm as per IS 694 copper shielded, twisted, multi stranded armoured cable on wall in GI tray or on ground
Surveillance System
Desiging, supplying, installing, commissioning & testing of CCTV IR water proof camera suitable for upto 100ft. with control key board, DVR, Hard Disk,cables, UPT transreceivers etc. complete with not less than following specifications. 1. Four numbers of IP Camera with night vision functionality with range up to 30 meters. Camera construction shall be suitable for weather proof outdoor installation. 2. Eight Channel DVR with metal body construction, having software features of motion detect recording. 3. 3.5 inch 2 GB HDD 4. 8 port POE Switch 5. 32 inch LED Screen, Keyboard & mouse.
Water Treatment Plant
Aeration Fountain
Open channel type ultrasonic flowmeter with FIT
Design, Supply, Installation, Testing & calibration of open chanel type ultrasonic flow Transmitter CE marked with following technical parameters at Raw Water channel and Interfacing with PLC panel including mounting arrangement.
PH analyser
Design, Supply, Installation, Testing of pH analyser as per IUPAC( International Union for Pure & Applied Chemistry)at A.F. and Interfacing with PLC panel including mounting arrangement. Range : 0 ‐14 , pH Accuracy : Better than 0.1% of full scale , Supply Voltage : 24V dc, Output : 4‐20 mA /HART As per IEC 61000-6-2 & IEC 61000-6-3
Turbidity Analyser
Design, Supply, Installation, commissioning, testing of Turbidity Anayser as per ISO 7027 scattering light method at A.F. and Interfacing with PLC panel. Turbidity analyser shall comprises of 3 components i.e. sensors,signal distributor and transmitter with indicator. with 2 Outputs, 1 to PLC & anather to Local Display with mounting arrangement.
Level transmitter
Designing, Supplying, installing, commissioning & testing of Ultrasonic level transmitter CE marked at each filter bed with following technical parameters Interfacing with PLC panel including mounting arrangement.
Power Analyser
Designing, Supplying, Installing, commissioning & testing of Power Analyser interfacing to PLC Panel with modbus communicatuion port, as per IEC 62053 and in the prescribed format including mounting arrangement.
PLC with HMI for sand filter ( with 2 Filter beds )
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 1200 mm X 700 mm X 1500mm (LBH), fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at WTP Plant (sand filter bed wasing & operation).
PLC with HMI for sand filter ( with 4 Filter beds )
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 1200 mm X 700 mm X 1500mm (LBH), fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at WTP Plant (sand filter bed wasing & operation).
Control Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 2 C x 1.5 sq.mm as per IS 694 twisted shielded copper armoured conductor on wall in GI tray or in ground suitable for supplied DC Voltage
Communication Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of CAT 6 as per ISO/IEC-11801 std.cable for networking on wall in GI tray or on ground etc.
Signal Cable
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 2 pair x 1.0 sq.mm. as per IS 694 copper shieled, twisted, multistraned armoured cable on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 3 pair x 1.0 sq.mm. as per IS 694 copper shieled, twisted, multistraned armoured cable on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 4.5 pair x 1.0 sq.mm. as per IS 694 copper shieled, twisted, multistraned armoured cable on wall in GI tray or on ground.
Designing, Supplying, Installing, commissioning & testing with Terminating & Interfacing of 8 pair x 1.0 sq.mm. as per IS 694 copper shieled, twisted, multistraned armoured cable on wall in GI tray or on ground.
Blower
Pressure Transmitter for Blower
Designing, Supplying, Installing, commissioning & testing of pressure transmitter CE markd with following technical parameters at Blower delivery and Interfacing with PLC panel.
Ultrasonic Level Transmitter for Wash Water Tank
Designing, Supplying, Installing, commissioning & testing of Ultrasonic level transmitter CE As Above marked with following technical parameters and Interfacing with PLC panel including Mounting accessories
Surveillance system
Desiging, supplying, installing, commissioning & testing of CCTV IR water proof camera suitable for upto 100ft. with control key board, DVR, Hard Disk,cables, UPT transreceivers etc. complete with not less than following specifications 1. Four numbers of IP Camera with night vision functionality with range up to 30 meters. Camera construction shall be suitable for weather proof outdoor installation. 2. Eight Channe DVR withmetal body consturction, having software features of motion detect recording. 3. 3.5 inch 2 GB HDD 4. 8 port POE Switch 5. 32 inch LED Screen, Keyboard & mouse.
Valves with actuator
Design, Supply, Installation, Testing of Motor Actuated Valve / Gate at all required sizes and places of filter beds,Clarifier Drains,blowers and Interfacing with PLC panel, Supply Voltage : 415 V ac, Manual Operation : Hand wheel Position Indication : 01 Nos. Limit Switch for open, close Overload Protection : Torque Overload Limit Switch
Pure Water Pump house
Ultrasonic level transmitter
Designing, Supplying, Installing, commissioning & testing of Ultrasonic level transmitter CE marked with following technical parameters at pure Water Pump House and Interfacing with PLC panel including Mounting accesories.
Pressure Transmitter
Designing, Supplying, Installing, commissioning & testing of pressure transmitter CE markd with following technical parameters at Raw Water Pump House and Interfacing with PLC panel including Mounting arrangement.
pH analyser
Design, Supply, Installation, Testing of pH Analyser as per IUPAC ( International Union for Pure & Applied Chemistry)at A.F. and Interfacing with PLC panel including Mounting arrangement. Range : 0 ‐14 , pH Accuracy : Better than 0.5% of full scale , Supply Voltage : 24V dc, Output : 4‐20 mA As per IEC 61000-6-2 & IEC 61000-6-3
Turbidity meter / analyser
Design, Supply, Installation, Commissioning & Testing of Turbidity Analyser as per ISO 7027 scattering light method at A.F. and Interfacing with PLC panel. Turbidity Analyser shall comprises of 3 components i.e. sensors,signal distributor and transmitter with indicator with 2 outputs, 1 to PLC & another to local display including Mounting arrangement. Overall Range : 0 ‐ 100 NTU Accuracy : +/‐ 0.02 NTU Supply Voltage : 230 V ac Output : 4‐20 mA
Residual chlorine analyser
Design, Supply, Installation,Testing of Residual chlorine analyser / meter must have automatic sensor cleaning facility at pure water sump and Interfacing with PLC panel. Residual Chlorine meter shall comprises of 3 components i.e. sensors,flow through assembly and transmitter with indicator and gives 2 outputs one to Local display & other to PLC including Mounting arrangement. Overall Range : 0 ‐ 8 mg/l (ppm) Accuracy : 2% of full scale Supply Voltage : 230 V ac Output : 4‐20 mA Membrane free sensor of 2 gold plated electrodes for long term stability and reference electrode (ag/Agcl) must be provided to avoid maintenance. IP 65 Nema 4 housing protection class required.
Power Analyzer
Designing, Supplying, Installing, commissioning & testing of Power Analyzer interfacing to PLC Panel with Modbus Communication Port, as per IEC 62053 and in the prescribed format including Mounting arrangement.
PLC panel for Pure water pump House
PLC panel for Pure water pump House with two Pumps
PLC panel for Pure water pump House with four Pumps
PLC panel for Pure water pump House with six Pumps
SCADA Software
PLC Panel for WTP Automation
SCADA system for WTP
Design, manufacture, supply, installation, testing and commissioning of SCADA System for WTP Plant, Sand Filter beds & pump house. Windows based PC with latest configuration & OS complete with necessory office & antivirus softwares. PC configuration shall not be less than Intel i5 10th Gen CPU, 16 GB Ram, 128 GB SDD, 500 GB HDD, DVD RW, Rs232 & Rs485 port, 2 RJ45 ports, Keyboard, Optical Mouse, 32 inch color TFT Monitor, Latest Windows Pro OS, Microsoft Office & Antivirus & Internet Sequrity software for 3 years license.
SCADA Software of reputed company with developer & runtime license with minimum 512 number of Tags with following features & functions. 1. Supervise real-time data in the form of graphical presentation 2. Control WTP processes locally or through Remote locations. 3. Dynamic process Graphic, It should resemble the process mimic. SCADA should have good library of symbols so that develop the mimic as per required. When operator sees the screen he should know what’s going in plant. 4. Alarm summery & Alarm history, SCADA system must be able to detect, display, and log alarms and events. When there are problems the SCADA system must notify the operators to take corrective action. 5. Acquire real-time data as well as logs data with Real time trend & Historical time trend. 6. Web Connectivity, Real-time displays can be accessed on remotely attached PCs and notebooks using internet.
SCADA Programming shall be done so as operator can visualize and control complete WTP operation from operator desk. All important alarms & events shall be logged. All the data from field instruments & equipments shall be logged. There shall be provision to take reports in required formats of real time & historical data, events & alarms. There shall be provision of broadcasting messages, emails of reporting information. There shall be provision of access sequrity.
An Industrial grade Din rail mounting ethernet switch with 5 ports shall be provided. An Industrial grade modem with 4G/5G GSM connectivity shall be provided.
Secondary work station PC
Windows based PC with latest configuration & OS complete with necessory office & antivirus softwares. PC configuration shall not be less than Intel i5 10th Gen CPU, 16 GB Ram, 128 GB SDD, 500 GB HDD, DVD RW, Rs232 & Rs485 port, 2 RJ45 ports, Keyboard, Optical Mouse, 32 inch color TFT Monitor, Latest Windows Pro OS, Microsoft Office & Antivirus & Internet Sequrity software for 3 years license.
Supply, Installation, Testing, Intgeration & Commissioning of 49" LCD monitor at Conf. Room for display of total water system (Online)
MBR / GSR / ESR
Providing, installing, testing and commissioning of following equipments with satisfactory test and trial etc.as per detailed specification attached
Ultrasonic level transmitter
Medium- Water
Range- 0 - 5 mtrs
Output-4-20 mA / HART
Power supply - 24V DC ext.
Display - Large LED
Accuracy - +/- 0.25% of Full Scale or better
Enclosure- IP 68
RTU (Remote terminal control & communication unit at each GSE/ESR)
Design, manufacture, supply, installation, testing and commissioning of indoor type PLC panel of size approx. 800 mm X 700 mm X 800mm (LBH) , fabricated out of min. 2 mm thick CRCA sheet powder coated to Siemens gray color. The Panel shall be provided with reputed make PLC with following accessories as well as input output configuration. The PLC shall be programmed with IEC 61131 standards for control, monitoring and communication of equipments & instruments at GSR/ESR Tank.
SCADA System for MBR/GSR/ESR with PLC based control valves Management system
field instruments & equipments shall be logged. There shall be provision to take reports in required formats of real time & historical data, events & alarms. There shall be provision of broadcasting messages, emails of reporting information. There shall be provision of access sequrity
Solar Panel with Battery
Designing, Supplying, installing commissioning & testing of photovoltaic solar panel with its charger, MS Stand for mounting solar panel so as to have maximum exposure of sunlight for desired location and maintenance free battery with 3 days battery backup.
ESR Management Systems (RMS)
( For Inlet / outlet)
Designing, Supplying, Installing, Commissioning & testing of Flow Control Valve / Pressure reducing valve for inlet with flow measuring, flow controlling, pressure monitering & web based with cable, PLC etc. complete. Hydraulically operated self-actuated Flow & Level Control Valve (either with float or altitude pilot) with downstream orifice having Ductile Iron valve body, Y-Pattern, Double chamber unitized actuator, Fusion bonded Epoxy coating, Copper control tubing, with Latching Solenoid & Pilot operated as per design, additional Speed control feature, drip tight sealing, Iֺn-line serviceable, Internals Stainless steel & protected diaphragm suitable for drinking water WRAS/NSF/DVGW approved.
80 mm Dia
100 mm Dia
150 mm Dia
200 mm Dia
250 mm Dia
300 mm Dia
350 mm Dia
400 mm Dia
450 mm Dia
500 mm Dia
600 mm Dia
( Pressure Reducing valve ) 80 mm to 600 mm
Pressure Reducing Valve - Designing, Supplying, Installing, Commissioning & testing ofPilot operated hydraulically controlled Pressure reducing Valve for ESR/MBR outlet or distribution with pressure controlling / limiting application which maintains a constant downstream pressure regardless of fluctuations in inlet pressure or flow with fixed set points inclusive of all the accesories like pressure gauge etc. complete as per given specifications
( Flow cum Altitude Control valve ) 80 mm to 600 mm
Hydraulically operated selfactuated Flow & Level Control Valve (either with float or altitude pilot) with downstream orifice having Ductile Iron valve body, YPattern, Double chamber unitized actuator, Fusion bonded Epoxy coating, Copper control tubing, with Latching Solenoid & Pilot operated as per design, additional Speed control feature, drip tight sealing, Iֺn-line serviceable, Internals Stainless steel & protected diaphragm suitable for drinking water WRAS/NSF/DVGW approved.
( Solonoid operated On / Off Valve with timer Controler ) 80 mm to 600 mm
Solonoid Operated On/Off Valve with Timer Controller - Designing, Supplying, Installing, Commissioning & testing of Solonoid operated hydraulically controlled On/Off Valve with Timer Controller for ESR outlet with time based On-Off application which performs Opening and Closing operations on pre -set timings. The valve The valve should offer minimum restriction while allowing the flow inclusive of all the accesories like inbuilt timer controller, batteries etc. complete... as per given specifications
(Third party inspection of 15% Quanity minimum)
Comprehensive O & M
Operation and Maintenance Charges of the whole water supply scheme on SCADA and generation of daily report of water quality parameters and electrical parameters with specific consumption in kWh/ml . The report shall be mailed daily to the head quarters for monitoring purpose.
Note : For Schemes upto 5 MLD capacity simple Automation shall be adopted.
Simple Automation
Simple Automation shall consist of following
1) GSM /GPRS base pump operating system (specifications as below) (one for each pump )
Supplying , Installing and Commissioning of SMS based ON / OFF operation of pumps at remote locations with test & trial including one year guaranty & two year comprehensive maintenance including SIM card & SMS charges. Wireless Motor Controller is suitable for all range of electrical motors and starters and pump sets. It shall protect pump set from dry run. Controller shall have inbuilt battery and charges automatically. Controller shall be controlled through SMS, Call, IVRS or Smart Phone application (All controlling modes are must). It shall have following features as, a. Auto Mode operation – Pump shall
be operated with time inputs & limits. Pump shall be also programmed for the specific time pumping. b. Feedback - Shall produce feedback of Voltage, Current & power factor parameters. c. Cyclic timer – For daily operation d. Dry Run Protection e. Overload Protection. f. Phase fail – Phase imbalance / Low Voltage. g. It shall have RS 485 port for optional operations.
h. High gain antenna for healthy reception of the signals. i. High durability PC-ABS-FR enclosure. j. Additional sensor interface. k. Shall have Pump house lamp control through remote signal.
2)Pressure transmitter suitable for operating system
3) Level Transmitter for.Raw/ Pure water pumping station,ESR/MBR/GSR
4) Residual chlorine Analyzer and transmitter for pure wate pumping station.
5) Solar panel with battery backup of 3days
6)Providing, installing, testing and commissioning of Laptop or computer station with programming software ( web based) run time version along with required cables and communication devices for PLC and programming (HTML /PHP based)
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .