Superintending Engineer [Electrical]
SITC of New Electrical Sub Station Work in Devi C Block Girls Hostel at Civil Hospital Campus, Asarwa, Ahmedabad.
339812
74/10 of 2026/2027
Open
Electrical
Works
Gandhinagar
8 documents required · 8 mandatory
₹3,600
PIU-General Fund A/c 11-114
₹1.4 L
29 Aug 2026
29 Aug 2026
29 Aug 2026
10 Sept 2026
29 Aug 2026
Memorandum showing items of works to be carried out
NO Quantity Item of Work Unit Estimated Rates In Words AMOUNT
:Excavation for foundation upto 1.5 mt.depth All kind of Soil.Including Hard
Murram and Soft Rock etc including strutting, sorting & Dewatering out and
stacking of unuseful materials and disposing off the excavated stuff upto any lead
and lift.(Excavated earth / Stuff to be stacked and surplus earth/unuseble Rupees One Hundred Forty Nine
material to be disposed with the permission of local authority any lavies/charges and Paisa Sixty Seven Only
to be paid by agencies and no extra payments will be made and disposed at non
objectinable place to be found by the Contractor. )
Excavation for foundation for 1.5 mt. to 3.0 mt. All kind of Soil. Including Hard
Murram, Soft Rock & Hard Rock (Not Required Blasting) etc. including
strutting, sorting & Dewatering out and stacking of useful materials and
disposing off the excavated stuff upto any lead and lift (Excavated earth / Stuff
Rupees One Hundred Sixty Two
2 234.92 to be stacked and surplus earth/unuseble material to be disposed with the Cmt 162.38
and Paisa Thirty Eight Only
permission of local authority any lavies/charges to be paid by agencies and no
extra payments will be made and disposed at non objectinable place to be found
by the Contractor.)
General Note : This shall be applicable to all concrete plan as well as work.
1. Providing and laying in position Ready Mixed specified grade concrete for
PCC & reinforced cement conctere work , using cement content as per approved
Design Mix manufactured in fully automatic batching plant and transported to
site of work in transit mixer for a lead up to 10 kms having continuous agitated
mixer, manufactured as per mix design of specified grade for reinforced cement
concrete work including pumping of R.M.C. from transit mixer to site of laying,
All Concrete Work content as per grade (without fly ash as per item description)
Rupees Three Thousand Six
3 14.57 and as per latest IS 456 for all PCC & RCC elements of all shape, all size, at all Cmt 3,697.91 Hundred Ninety Seven and Paisa
places and heights/ depths including transporting, laying of concrete to site by
Ninety One Only
any means like pumping or tower crane etc., finishing and curing etc. and
including Admixtures in recommended proportions as per IS 9103 to accelerate,
retard setting of concrete as per direction of Engineer-in-charge. Rate shall be
inclusive of providing grooves, drip moulds, ghisis, pockets, cutouts etc. and
labour for insert sleeves if any wherever required while casting. Rate also to
include lift charges and scaffolding for any heights / depths from FFL/GL.(unless
otherwise specified)
Including for provide all formwork should be rigid & water tight using best
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering & Providing formwork of
steel cup lock system including centring shuttering strutting and propping etc.
propping and centering below supporting floor to ceiling and removal of the same Rupees Five Thousand Forty Two
for in situ reinforced concrete and plain concrete work in flat surfaces such as and Paisa Nine Only
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
engineer in charge and approved , rates includes all levels , heights Up to
mtr, excluding reinforcement.
(No extra will be paid in variation of cement level, minimum cement level will be
as per IS 456) for reinforced concrete work in:
Filling available selected / approved stacked excavated earth (excluding rock)
(Earth which is stacked at any location outside the campus non- objectionable
place shall be found by the contractor) in trenches, plinth, sides of foundations Rupees One Hundred Thirty and
etc. in layers not exceeding 20 cm. in depth consolidating 95% of MDD each Paisa Thirty Nine Only
deposited layer by ramming and watering and Compaction with Mechanical
equipments if possible
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering & Providing formwork of
steel cup lock system including centring shuttering strutting and propping etc.
Rupees Six Thousand Four
6 9.10 propping and centering below supporting floor to ceiling and removal of the same Cmt 6,401.97 Hundred One and Paisa Ninety
for in situ reinforced concrete and plain concrete work in flat surfaces such as
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
engineer in charge and approved , rates includes all levels , heights Up to 6.0 mt,
excluding reinforcement.
(No extra will be paid in variation of cement level, minimum cement level will be
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick
water proof ply with Exposed work in centring, shuttering & Providing formwork
Rupees Six Thousand Five
7 13.14 of steel cup lock system including centring shuttering strutting and propping etc. Cmt 6,505.60 Hundred Five and Paisa Sixty
propping and centering below supporting floor to ceiling and removal of the same
for in situ reinforced concrete and plain concrete work in flat surfaces such as
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
engineer in charge and approved , rates includes all levels , heights Up to
mtr, excluding reinforcement.
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick
water proof ply with Exposed work in centring, shuttering & Providing formwork
Rupees Six Thousand Five
8 7.47 of steel cup lock system including centring shuttering strutting and propping etc. Cmt 6,545.85 Hundred Forty Five and Paisa
propping and centering below supporting floor to ceiling and removal of the same
Eighty Five Only
for in situ reinforced concrete and plain concrete work in flat surfaces such as
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
engineer in charge and approved , rates includes all levels , heights Up to
mtr, excluding reinforcement.
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick Rupees Six Thousand Two
9 1.07 water proof ply with Exposed work in centring, shuttering & Providing formwork Cmt 6,228.61 Hundred Twenty Eight and Paisa
of steel cup lock system including centring shuttering strutting and propping etc. Sixty One Only
propping and centering below supporting floor to ceiling and removal of the same
for in situ reinforced concrete and plain concrete work in flat surfaces such as
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
Providing charge and in
laying approved
position, rates
grade all levels , for
concrete heights Up to
reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick
water proof ply with Exposed work in centring, shuttering & Providing formwork
Rupees Six Thousand Two
10 1.07 of steel cup lock system including centring shuttering strutting and propping etc. Cmt 6,268.86 Hundred Sixty Eight and Paisa
propping and centering below supporting floor to ceiling and removal of the same
Eighty Six Only
for in situ reinforced concrete and plain concrete work in flat surfaces such as
soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per IS:9103
to accelerated, retard, setting of concrete, improve workability as per direction of
engineer in charge and approved , rates includes all levels , heights Up to
mtr, excluding reinforcement.
Providing, laying controlled cement concrete M 250 and curing complete
Rupees Seven Thousand One
including the cost of form work (rates for centering, shuttering, formwork staging
11 30.12 Cmt 7,130.08 Hundred Thirty and Paisa Eight
scaffolding for considering up to 6.00 m height) but excluding reinforcement for
reinforced concrete work in: (C) RCC Slab i) up to Ground Floor slab level
Providing, laying controlled cement concrete M 250 and curing complete
including the cost of form work (rates for centering, Rupees Seven Thousand One
12 19.61 shuttering, formwork staging scaffolding for considering up to 6.00 m height) but Cmt 7,190.14 Hundred Ninety and Paisa
excluding reinforcement for reinforced concrete Fourteen Only
work in: (C) RCC Slab i) First Floor slab level
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick
water proof ply with Exposed work in centring, shuttering & Providing formwork
of steel cup lock system including centring shuttering strutting and propping etc. Rupees Seven Thousand Forty
propping and centering below supporting floor to ceiling and removal of the Five and Paisa Eighty Three Only
same for in situ reinforced concrete and plain concrete work in flat surfaces such
as soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per
IS:9103 to accelerated, retard, setting of concrete, improve workability as per
direction of engineer in charge and approved , rates includes all levels , heights
Up to 6.00 mtr, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum
Providing and laying in position M-250 grade concrete for reinforced cement
concrete work, using cement concrete work using cement content as per
approved Design Mix manufactured in fully automatic batching plant and
transported to site of work in transit mixer for any lead having continuous
agitated mixer, manufactured as per mix design of specified grade for reinforced
cement concrete work including pumping of batching plant from transit mixer to
site of laying, cost of water tight Centering , shuttering by using 18 mm thick
water proof ply with Exposed work in centring, shuttering & Providing formwork
of steel cup lock system including centring shuttering strutting and propping etc. Rupees Seven Thousand Eighty
propping and centering below supporting floor to ceiling and removal of the Six and Paisa Eight Only
same for in situ reinforced concrete and plain concrete work in flat surfaces such
as soffits of suspended floors slabs Landings walls, Fins and beams, column and
the like, floors etc & sides and soffits of beams, Haunching cantilevers Girders,
using grouting if required, admixture in recommended proposition as per
IS:9103 to accelerated, retard, setting of concrete, improve workability as per
direction of engineer in charge and approved , rates includes all levels , heights
Up to 6.00 mtr, excluding
reinforcement. (No extra will be paid in variation of cement level, minimum
Providing and laying TMT Bar FE 500/500D reinforcement for R.C.C. work and
straightening, cutting, bending, binding & placing in position completed upto any
Rupees Seventy Two and Paisa
15 18221.00 floor any level as per I.S. Standard. complete.as directed by EIC. Kg 72.72
Seventy Two Only
Providing and laying autoclave aerated concrete blocks as per drawing in single
or multiple layers with Ready mix joining mortar. Crushing strength of aerated
concrete block shall not be less than 40 KG/sqcm, minimum density in oven dry
condition between 651 to 750 KG/CUM, thermal conductivity shall not exceed
0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the
surface with necessary tool tackles The drying shrinkage shall be not more than
0.05 percent for Grade 1 blocks and 0.10 percent for Grade 2 blocks when tested Rupees Four Thousand Five
16 28.84 in accordance with IS : 6641 (Part-2)-1972 etc. at all floors, any heights, all Cmt 4,514.84 Hundred Fourteen and Paisa
depths, any levels (in foundation and superstructure) and all places including Eighty Four Only
curing, scaffolding, racking / flush jointing etc complete, as per drawing /
specification and approved by architect and as directed by Engineer Incharge for
all civil, plumbing, electrical & infrastructure work
a) Ground FLoor
Providing and laying autoclave aerated concrete blocks as per drawing in single
or multiple layers with Ready mix joining mortar . Crushing strength of aerated
concrete block shall not be less than 40 KG/sqcm, minimum density in oven dry
condition between 651 to 750 KG/CUM, thermal conductivity shall not exceed
0.30 w/mk, fire resistant 4 hours, in true line level and plumb and cleaning the
surface with necessary tool tackles The drying shrinkage shall be not more than
0.05 percent for Grade 1 blocks and 0.10 percent for Grade 2 blocks when tested Rupees Four Thousand Five
17 28.36 in accordance with IS : 6641 (Part-2)-1972 etc. at all floors, any heights, all Cmt 4,568.17 Hundred Sixty Eight and Paisa
depths, any levels (in foundation and superstructure) and all places including Seventeen Only
curing, scaffolding, racking / flush jointing etc complete, as per drawing /
specification and approved by architect and as directed by Engineer Incharge for
all civil, plumbing, electrical & infrastructure work
Providing & laying 15 mm Ready Mix cement mortor 1:4 (1 cement : 4 coarse
sand) cement plaster in single coat on brick/concrete wall for interior plastering
Rupees One Hundred Seventy
18 210.23 finished even and smooth including finishing etc complete. Including Water Smt 171.84
One and Paisa Eighty Four Only
cement Compound.
a) Ground floor
Providing & laying 15 mm Ready Mix cement mortor 1:4 (1 cement : 4 coarse
sand) cement plaster in single coat on brick/concrete wall for interior plastering
Rupees One Hundred Ninety Six
19 210.23 finished even and smooth including finishing etc complete. Including Water Smt 196.66
and Paisa Sixty Six Only
cement Compound.
Providing & laying 12mm thick cement plaster in single coat on ceilings and
sofits of stairs for interior plastering upto floor two level finished even and
Rupees One Hundred Twenty Two
20 87.20 smooth in C M 1:4 ( 1 cement 4 coarse sand) including finishing etc complete. Smt 122.84
and Paisa Eighty Four Only
a) Ground Floor
Providing & laying 12mm thick cement plaster in single coat on ceilings and
sofits of stairs for interior plastering upto floor two level finished even and
Rupees One Hundred Forty Seven
21 87.20 smooth in C M 1:4 ( 1 cement 4 coarse sand) including finishing etc complete. Smt 147.65
and Paisa Sixty Five Only
Providing & laying 20 mm thick double coat sand face/mala cement plaster for
all floor all height with use of Ready Mix mortar on interior/exterior Block, brick/
concrete work for plastering comprising of base coat of 12 mm thick cement
Rupees Three Hundred Sixteen
22 388.85 plaster in cement mortar (1 cement: 4 coarse sand) in rough finishing and 8 mm Smt 316.13
and Paisa Thirteen Only
thick top coat of cement mortar 1:2 ( 1 cement : 2 coarse sand) finished with
trovel including scaffolding curing etc. complete. Including Water cement
Applying two coats of acrylic lapy ( putty) & two coats of primer of approved
brand and manufacture on new wall surface to give an even shade including Rupees Forty and Paisa Fifty Nine
thoroughly brushing the surface free from mortar dropping and other foreign Only
matter and sand papered smooth.
Providing and applying Wall painting (three coats) with plastic emulsion paint of
approved brand and manufacture on under coated wall surface to give and even
Rupees One Hundred Twelve and
24 594.86 shade including throughly brushing the surface free from mortor droppings and Smt 112.95
Paisa Ninety Five Only
other foreign matter and sand paperd smooth on new work to give an even
shade.for all height
Finishing wall with weather proof low velocity ultima exterior emulsion paint on
wall surface (two coats) Including 2 coat primer and 2 Cost Putty (If required)
Rupees One Hundred Fifty Five
25 388.85 on wall surface to give an required shape even shade after thoroughly brushing Smt 155.11
and Paisa Eleven Only
the surface to remove all dirt, and remains of loose powdered materials. Etc
complete for all height
Providing and laying average 25 mm thick mirror polished kotah stone of
approved quality, selected and sorted for uniform colour in floor, otta, platform,
etc. of required sizes upto 600 x 600 mm fix size ( No Variation) as per design in
normal pattern (straight or staggered joint with square or rectangular shaped
stone) and residue as per drawing including 1:6 (1 cement : 6 sand) cement
mortar bedding of average 20 mm thickness jointed with grey cement and colour
pigment in proportion to match the shade of kota stone. Rubbing and polishing to Rupees Nine Hundred Ninety Two
be done with 2 coats of 60, 120 grades of emery, balckchapadi and gutka for and Paisa Sixty Six Only
special polish after it polishing to be done with 220, 320, 400, 600 grades of
emery till mirror finish is achieved. Curing, daily moping with water & kerosene
as directed for at least 15 days after final polishing etc. complete upto the
satisfaction of the Architect or Engineer-in-charge. (NO WAXING WILL BE
Providing and laying 18mm thick granite of specified size colour, shade and of
approved make, in skirting, risers of steps, dado, cladding , sill and jambs of
door, window & ventilation frame with mini. two coat of construction chemical
Rupees Two Thousand Four
and as per manufacture specification incl. rubbing and polishing, making edge
27 6.96 Smt 2,424.00 Hundred Twenty Four and Zero
moulding, making grooves (any nos.)rounding edge and All joints filled with
coloured cement putty as per architect detail and wiped to give sharp joints with
flush pointing and washed clean with acid as direction by E.I.C.
Providing and laying polished kota stone slab 25 mm thick in skirting, risers of
Rupees One Thousand One
steps, dedo and pllars laid on 10 mm thick cement mortar 1:3 (1 cement :
28 10.18 Smt 1,187.79 Hundred Eighty Seven and Paisa
coarse sand) and jointed with gray cement slurry including rubbing & polishing
Seventy Nine Only
Providing & laying china mosaic flooring of approvd make for plain and curved
surfaces at floor, dado, otta etc. comprising of 20 to 25 mm size broken pieces of
ceramic/ glazed tiles (only white colour) laid over 1:6 cement mortar bedding
including applying cement slurry at the rate of 2.75 kg per Sq.m. on plain or
sloped surfaces and filling joints with white cement. The flooring/ dado shall be
tampered with wooden rammer not exceeding 2 Kg in weight to bring the mortar
up to the surface including rounding of the junctions and extending them upto
cm along the parapet wall. The rate shall include any type of bands, vata, any
colour, any pattern or design as per drawing, curing, cleaning with water and Rupees Seven Hundred Forty
oxalic acid etc. complete as sample approved by Architect/ EIC. (Only plan area Seven and Paisa Twenty Nine Only
shall be measured including vata upto 150mm height). Rates should be inclusive
of acid washing and vata.
'All the waterproofing activities shall be carried out by in-house application
company of the principal material manufacturer and provide a written corporate
Supply Apply Corporate Warranty from the principal manufacturer that all work
executed will be free from defects in materials, workmanship and free of leaks
for a period of 10 years from the date of Work Completion, unless resulting from
structural defects or causes other than the work of this section. Said defects shall
Providing and laying IPS cement concrete flooring of mix 1:2:4 (1 cement:
coarse sand: 4 graded stone aggregate of 20mm nominal size) in a single layer,
including mixing, laying, compacting, and finishing the surface with a floating
coat of neat cement, with a slope as required for proper drainage. The work Rupees Three Hundred Fifty One
includes adding a waterproofing compound as per the manufacturer’s and Paisa Fifty Six Only
specifications to enhance the water resistance of the flooring. The thickness of
the IPS flooring shall be between 50mm to 75mm.
Providing cement vata (10 cm x 10 cm size) quarter round in cement mortar 1:1 Rupees Twenty Three and Paisa
31 42.60 including neat cement finishing, watering etc. complete.For all floor Rmt 23.68
Sixty Eight Only
Terrace Waterproofing
Surface Preparation for waterproofing: Cleaning and preparation of surface with
the help of wire brush or grinder. Cleaning by air blower, crack filling etc,
complete. Wrapping all pipes inserts with a two way adhesion tape of make Dr.
Fixit Bathseal tape and grouting the gaps space between the slab & parapet wall,
grout the pipe gaps with non-shrink grout Dr. Fixit Pidigrout 10M or by
preparing polymer modified mortar with Dr. Fixit Pidicrete URP in the ratio of
1:3 by adding polymer 10% by weight of the cement.
Rupees One Thousand Four
32 78.02 Angel Fillet: Providing 50 mm X 50 mm angle fillets on the vertical up-stands, Smt 1,479.65 Hundred Seventy Nine and Paisa
parapet wall junction corners, service units and properly dressed by preparing
Sixty Five Only
polymer modified mortar with Dr. Fixit Pidicrete URP in the ratio of 1:3 by
adding polymer 10% by weight of the cement.
Waterproofing: Supplying & applying 2 coats of pre packed 2 component
cementitious waterproof coating, Dr. Fixit Fastflex, with a mix ratio of (liquid:
Powder), parts by wt. - 1:1.4, in the slab areas & extending it to the wall up to
300mm height above FFL. This includes lying of a 150mm wide strip of an open
woven glass fiber mesh over the angle fillets on the 1st coat while it is still wet.
The coverage shall be min. 2 Kg/sq.mt in 2 coats, self-curing for 4 days,
Providing and fixing ISI marked 35mm thk. Flush door shutter conforming to IS:
2202 (Part - 1 1980). 35mm thk. Flush door of approved quality factory made
solid core flush door shutter in single and double leaf fixing on Granite stone
frame (Granite stone Frame shall be paid seperately)as per drawing. 1mm thk.
Laminate sheet of approved colour / shade on the both side of 35mm flush door.
The timber shall be free from decay and insect attack knots and knot holes. The
flush door shutter to be ready factory made with both side hardwood ply board
faced, pine - wood core in continous gapless section with butt joints tightly
Rupees One Thousand Nine
33 2.10 factory bonded with hot press process on both face of the core with plywood. Smt 1,989.70 Hundred Eighty Nine and Paisa
including ISI marked hardware door fitting of handle & lock complete in all
respects including anti-termite treatment.Handles:- SS Handle, Lock :- cylindrical
lock , Hinges :- 4 Nos SS Hinges –Heavy gauge each shutter, Tower Bolts:-
Nos stainless steel each shutter and Stopper, Also Vision Panel for 6 mm Clear
Glass with Polish bidding patti to fix it, all materials and labour etc. complete as
per detail drawing and instruction of engineer-in charge and consultant.
Providing and fixing Colour Anodized aluminium work for doors, windows,
ventilators and partitions (Sliding window
like Two TRA ck, Three TRA ck, Four TRA ck, fix window/ Openable window /
Fix-Partition, etc),with extruded built up
standard tubular sections/ appropriate Z sections and other sections of approved
make conforming to IS: 733 and IS :
1285, fixed with RA wl plugs and screws or with fixing clips, or with expansion
hold fasteners including necessary
filling up of gaps at junctions, at top, bottom and sides with required Rupees Three Hundred Ninety
PVC/neoprene felt etc. Aluminium sections shall One and Paisa Eighty Eight Only
be smooth, rust free, stRA ight, mitred and jointed mechanically wherever
required including cleat angle, Aluminium
snap beading for glazing / paneling, C.P. bRA ss / stainless steel screws, fixture
like aldrop, handle, hinges / pivots &
window Bearings & concealed lock etc all complete at all floors/all levels/all
heights as per architectuRA l dRA wings
and the directions of Engineer-in-charge. .(Glazing and paneling to be paid under
relevant Item) Nut & bolt.
Providing and fixing Compact Sheet of any size, any shape, any color, any
texture as per approved sample (approved by architect)
and specified thickness in aluminium fRA me and shutter work with necessary
cutting of sheet, single side, double side coloured
as per dRA wing & specifications including providing and fixing EPDM quality Rupees One Thousand Two
35 15.20 rubber/ silicon sealant/ adhesive tape/ screwing on Smt 1,247.35 Hundred Forty Seven and Paisa
the periphery of the sheet as per the required thickness etc. complete at all floors/ Thirty Five Only
all levels/ all heights as per the dRA wing &
directed by EIC / Architect. Cut edges of the compact sheet shall be provided
with masking tape. Actual installed quantity shall be
measured and paid. RA te shall be inclusive of all type of wastage.
Providing & fixing rolling shutters of approved make made of 80 mm. Wide M.S.
laths inter locked together theit entire length and jointed together at the end locks Rupees Three Thousand Five
36 26.25 mounted on specially designed pipe shaft with bracket plates, guide channels and Smt 3,503.41 Hundred Three and Paisa Forty
out side locking with mechanical gear operated device including the cost of One Only
Hood cover and spring including priming coat of red lead paint two coat of Oil
paint .etc complete.
Providing, fabricating, assembling, hoisting/ erecting and fixing in position at
any heights/ any levels/ all floors/ all shapes & sizes with all leads & lifts using
MS Rolled Steel Sections, Hollow sections, Tubular Sections, MS Plates,
Chequered Plates, MS Pipes, Perforated Sheet, Flats, Bright Bars, Angles, MS
Sheet, Girder, Beam. threaded J bolts, insert plate, support plate etc as per
drawing. all confirming to latest relevant IS codes for the work of steel structures
like staircases, railings, handrail, jali, gates, grills, bracings, platforms, brackets,
monkey ladder, cattle trap, grill door, pipe rack, rungs, false ceiling frame work,
Rupees One Hundred Twenty
37 1750.00 framing for facade, Roof canopy, fencing posts, M.S. Screen & fencing jali Kg 127.95
frame work etc. including straightening, cutting, bending, bolting and welding the Seven and Paisa Ninety Five Only
members all as per structural drawings and as per detailed specifications (for
materials & workmanship) including necessary scaffolding/ staging etc. complete
in the situations described hereinafter and comprising of : i) Profile Cutting of
components to required length/ width and shape/profile; ii) Smooth grinding/
machining of edges/ faces/ all welding joints; iii) Necessary welding (electric arc
welding) for required weld lengths and sizes. Fabrication shall be in a perfect
architectural workmanship manner and as provided in section V & VI of IS
& IS 7215. Welding shall be carried out by qualified welders/ fabricators. The
Electrical Work
Providing and erecting Approved make Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. at 415 V. having normal current rating
Rupees Eight Thousand Eight
125A. with Fixed thermal & magnetic release suitable to work on A.C.supply
38 2 Ea. 8861.74 Hundred Sixty One and Paisa
Hz. with all internal connections, spreader tinned copper & complete erected in
Seventy Four Only
existing 16 G.M.S. housing.-Cat-lll
Providing and erecting Approved make Four pole moulded case circuit breaker
having breaking capacity ICU of 35 KA. and above at 415 V . having normal
current rating 250A. with variable thermal & magnetic release suitable to work Rupees Twenty Three Thousand
on A.C.supply 50 Hz. with all internal connections, spreader tinned copper & Forty One and Paisa Thirteen Only
complete erected in existing 16 G.M.S. housing. Cat-lll
Providing and erecting Approved make Four pole moulded case circuit breaker
having breaking capacity ICU of 50 KA and above at 415 V having Normal
Rupees Twenty Seven Thousand
current rating 400A. with variable Thermal & magnetic release suitable to work
40 9 Ea. 27751.77 Seven Hundred Fifty One and
on A.C.supply 50 Hz. With all internal connections, spreader tinned copper &
Paisa Seventy Seven Only
complete erected in existing 16 G.M.S. housing. -cat-lll
Approved make standard Draw out type 4 Pole Air circuit breaker. Having 50 kA
breaking capacity with ICU=ICS=ICW (1 sec)Vsr=690 v, Ui=1kv ,impulse
voltage=12 kv with following type of relay and accessories.(B) with Rupees One Lakh Sixty One
41 3 microprocessor Release with over load, short circuit, earth fault protection and Ea. 161515.16 Thousand Five Hundred Fifteen
metering display in modular design with LED display and Test Trip button and Paisa Sixteen Only
facility, CTs and auxiliary contacts, of following current ratings. (iii) 1250Amp
Supplying and erecting triple pole & neutral 440V / 500V panel mounting
Copper Busbars with four equal Nos. of electrolyte bus having current density
not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly
Rupees Ten Thousand Five
wrapped with colour insulating tape for phase sequence of following current
42 8 Rn.Mtr 10559.55 Hundred Fifty Nine and Paisa Fifty
carrying capacity, erected with necessary bus bar supports /insulators, main cable
socket to each bar, erected in existing cubical panel with necessary connections.
(E) Suitable for 630 Amp. capacity
(G) Suitable for 1200 Amp. Capacity Rupees Sixteen Thousand Four
43 10 Rn.Mtr 16499.36 Hundred Ninety Nine and Paisa
Thirty Six Only
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C
Rupees Eight Hundred Eleven and
44 10 Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box Ea. 811.03
Paisa Three Only
having following capacity (c)63 Amp. Cat-lll
Providing and erecting metallic vitrified danger notice board as per language
Rupees Eighty One and Paisa
45 4 suggested by engineer incharge for HIGH VOLTAGE installation to be erected Ea. 81.81
Eighty One Only
as per IS.-2551.
Providing and erecting required size HOT deep Galvanised iron strip for earthing
Rupees Seventy Seven and Paisa
46 200 of H.T. , OCB/ ACB/ Transformer LT panel board, Motors etc. using proper Kg. 77.77
Seventy Seven Only
Providing and erecting Annealed bare Copper wire 4.064mm to 1.626mm. Rupees Seven Hundred Ninety
Four and Paisa Eighty Seven Only
Supplying & erecting earth pit of minimum bore dia.150mm size approved make
Earthing Electrode consisting Pipe-in-Pipe Technology as per IS 3043-1987
made of corrosion free hot dipped G.I.Pipes having Outer pipe dia of 50mm
having 80-200 Micron galvanising, Inner pipe dia of 25 mm having 200-250
Micron galvanising, connection terminal dia of 12mm with constant ohmic value
surrounded by highly conductive compound with high charge dissipation suitable
for following type of applications with chamber and heavy duty cover.
(A)(approved make OEM has to submit test certificate including value of earth
Rupees Five Thousand Seven
resistance of installation duly stamped and signed by agency and officer Incharge
48 30 Ea. Hundred Sixty and Paisa Three
has to ensure the value of earthing resistane mentioned in test Certificate) &
having back filling compound of (B) Inner chemical (CCM Compound)-
Resistivity:- 0.2 ohm / meter testing as per IEC 62561-2017, Voltage drop:- <
volt at no load & dry form, Sulphar content:- <2%(C) Back fill Compound :-
Earthing compound should be capable to retain moisture for long time Necessary
test report must be submitted by Agency. (b)For Electrical installation up to
11 kV in normal soil.
Length of Pipe : 2.00 mtrs
Back filling Compound :1 no. Bag of 25 Kg.
Providing & erecting weather proof, dust & vermin proof, floor mounted front
operated indoor type cubical panel board necessary IP-42 and above protection
as per approval from engineer incharge made from 14 SWG thick CRC M.S.
sheet for outer body & doors, 16 SWG thick CRC M.S.sheet for internal
partitions with necessary accesories , supporting angles/ flats channel including
cutting, bending, drilling, welding, riveting with internal partitions & cable alley
as per requirements & instruction of engineer-in-charge with erection of
supplied switch gears, BUSBARS, suitable size of inter connecting PVC copper
wire / copper-aluminium strips, rubber grommets, rib, bakelite control
fuses/MCB for measuring instruments, earth bus & earth bolts, foundation flange
- bolts-base Plates, sufficient nos. of hinged doors, handles with locking
arrangement and rubber gasket,heavy duty end terminal connection,danger notice
board,necessary ventilation,earthing strip complete. The Panel shall be painted
with epoxy powder coating.
(The rates excludes the cost of switchgears, bus bars, inter connecting mains &
Copper Aluminium strips, meters, Fuses etc. The dimension shall be measured
excluding base beams) The panel shall be supplied with following approved
manufacturers with following size.
(B) The standard companies switch gear shall be used and only manufacturers at Rupees Forty Thousand Nine
10 CPRI approved factory (iv) with 1000 mm. depth Sq.Mtr 40999.94 Hundred Ninety Nine and Paisa
Ninety Four Only
Design, Supplying, installing, testing of factory fabricated ready made Three
phase APFC Panel Cubical Panel fabrication should be type tested as per IEC
61921, 61439:1&2 Capacitor Duty Contactor for switching as per following
Steps Incomer Switch of MCCB type Icu=Ics=50KA at 400/440 Volts, with OC,
SC, internal earth fault protection Incomer Switch of MCCB type Icu=Ics=50KA
at 400/440 Volts, with OC, SC, internal earth fault protection,Copper tinned
insulated Busbar,Cubical panel should be indoor type with IP 43 and IK
10,Metalized polypropylene film tye3-phase 550Volt Capacitor,De tuning Rupees Seven Lakh Eighteen
50 1 Each 718985.67 Thousand Nine Hundred Eighty
Reactor for each capacitor,Panel having Short Circuit and Overload
Five and Paisa Sixty Seven Only
protection,Each step Capacitor having suitable MCB with Sc, OL, internal earth
fault relay,Each stage having Stage Contactor (Capacitor load rating),PF
regulator master controller having suitable steps with LCD display, Rs
Communication port, Indication LED Lamps for main incomer and ON-OFF for
each capacitor bank,MS Chanel for Floor mounting, Cable entry as per site
situation,Cooling fans for panel (g)250KVAR
Providing and erecting FRLS-XLPE(IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 kV. to be laid on wall with necessary Rupees One Thousand Eighty Five
clamps or in existing trench / pipe of following size of cables (H) 3 1/2 core and Paisa Seventy Five Only
185 Sq. mm ( 95 Sq. mm 1/2 core)
Providing and erecting FRLS-XLPE(IS:7098)(I)-88 ISI armoured cable
Rupees One Thousand Four
multistrand Aluminium conductor for 1.1 kV. to be laid on wall with necessary
52 700 Mtr. 1401.88 Hundred One and Paisa Eighty
clamps or in existing trench / pipe of following size of cables (I) 3 1/2 core
Sq. mm( 120 Sq. mm 1/2 core)
Providing and erecting ISI Marked 3core 185 Sq.mm XLPE insulated 11 KV Rupees One Thousand Nine
53 60 armoured cable Aluminium conductor IS-7098 to be laid on wall with clamps or Mtr 1961.42 Hundred Sixty One and Paisa Forty
in provided cable trench / pipe approved manner as directed. Two Only
Providing and erecting sandwitched type bus duct having following specification
: Sandwich type busbar for use as Feeder Busbar for interconnection between
separate electrical equipment/ load centers, and for use as Plug in busbar risers.
54 The busbar shall be suitable for operation in a 690V / 1000 V system with
frequency of 50 Hz .System can be either earthed or unearthed. Impulse voltage
should be 12 KV. Standards:
The busbar shall be designed and manufactured in accordance with the following
international standards for busbar trunking.
-IS 8623/ 1993 Part I & II : Particular requirements of busbar trunking System
-IEC 61439 Part I & VI : Particular requirements of busbar trunking System
-IEC- 60529 : Degree of protection TESTING
The busbars shall be type tested at a reputable national / International test
laboratory (ASTA or CPRI) for short circuit withstand. The test shall be for a
minimum duration of one second.
• Degree of ingress protection (IP rating) shall also be tested at any reputed
independent laboratory. This test shall be for IP 55 for Indoor and IP 65 for
Outdoor application.
• Short circuit and Degree of protection type test reports will be submitted for
vThe bsubars shall be of high conductivity Copper of 99.9% pure ETP grade and
high conductivity Aluminium of 99.59% pure 63401 grade.
Where as earth conductor is required, it shall be separate external earth
conductor, of high conductivity aluminium. Cross section of Earth Conductor
shall be as per IEC
It should be possible to provide a 200% Neutral where specified.
Phase cross over box should have busbars crossing over each other not cables.
The busbars shall be individually insulated with 2 layers of insulating film.
Layers of POLYSTER material class ‘F’, 155ºC.
The housing shall be made of 1.6 mm electrogalvanised sheet steel, with an
epoxy powder coated paint finish of RAL 7032 grade. Alternatively Aluminum
casing of 2.5mm may also be provided. The housings shall be profiled, to provide
higher strength and efficient heat dissipation. The width of the housings shall be
same for all ratings of busbars, in order to provide interchangeability of tap off
The joints between sections shall be made so as to provide flexibility during
installation and expansion / contraction of busbar during operation. The joints
shall be of the single bolt type. The joint construction must have the following
a) Thermal expansion of Busbars at joint of at least 4 mm per joint.
b) The joint insulation must be of one piece moulded design and not have any cut
edges which can absorb moisture.
c) Joint assembly shall be removable as separate sub-assembly so that it can be
inserted or removed without disturbing the adjacent sections.
d) The joint system must be designed in a way that the installer cannot insert the
busduct length too far and damage the bolt insulator.
e) The busbars ends shall not have any holes or slots at the joints – the electrical
continuity shall be through pressure plates, achieving a high area of joint cross
section and expansion capability.
a) Plug in boxes will be draw out type, contacts shall be silver plated and spring
b) The front operating handle will be interlocked with the plug-in boxes cover so
that MCCB can be operated only with suitable cover in close position.
c) The door shall be provided with the door knobs.
d) When the MCCB is in ‘ON’’ position, even with the door knobs unlocked, the
operator should not be able to remove the box or open the tap off location cover.
e) During insertion, the earth conductor shall make contact first before the phase
conductors. This should follow the sequence of first in last out concept.
f) When the box is open the live conductors shall be safe guarded by a
transparent insulator plate which allows for visible inspection but does not allow
touching of the live conductors.
g) The tap off unit arrangement must achieve IP 54 without requiring any
additional sealing at site.
h) The tap off boxes will be suitable for accommodating MCCBs or other
accessories, as required. The tap off units should allow the flexibility of
accommodating different, reputed MCCB makes, to be mutually agreed
depending on the tender requirements.
(A) Aluminium Bus (Maximum Current Density 130A/ sq.cm)
(f)1600 Amp. capacity Rupees Sixteen Thousand Eight
60 Mtr. 16820.54 Hundred Twenty and Paisa Fifty
Providing, erecting, testing & commissioning approved make oil immersed
ONAN cooled, double wound, core type indoor / outdoor copper wound 11kV/
433V step down transformer of following capacities operating on 3 phase, 50 Hz
4 wire & neutral earthed system continuously rated for a full temperature rise in
55 oil not exceeding 45 Deg.C.at maximum ambient temp. of 50 Deg. C. complete
with necessary radiator first filling of new transformer oil & standard fitting as
below complying with IS 1180( Part 1 ):2014 standards with energy efficiency
Off load tap changing range steps +2.5% to -5% on H.V for variation should be
provided. The H.V. shall be connected Delta & Secondary with star connection.
The transformer should have cable-end boxes on H.T. side suitable for up to
core 150 sq.mm. XLPE cable & on L.T. side suitable for bus duct or cables as per
requirement complete with test certificates from manufacturers
1. Oil conservator with filling Hole & Cap - One No.
2. Thermometer pocket with 6" dial type thermometer switch alarm &
trip contacts- Two nos.
3. Silica-gel breather with charge- One No.
4. Plain oil level gauge - One No.
5. Drain / Sampling / Filter valve- One No.
6. Top Filter Valve - One No.
7. Explosion vent with Diaphragm - One No.
8. Rating & Diagram plate - One No.
9. Additional neutral bushing for earthing - One No.
10. Bi directional Roller - Four Nos.
11. Earthing terminals - Two Nos.
12. Lifting lugs - Two Nos.
13. Air release plug. - One No.
14. Double float buchholz relay with Alarm and trip contacts.
15. Control cable as required from Transformer to VCB Panel is to be provided
with necessary connection to VCB relays for protection.
as per IS 1180 Latest levels norms
Rupees Seventeen Lakh Fifty Five
Max. allowable loses as per IS 1180 Latest levels norms at the time of tender Cat-
2 1755935.5 Thousand Nine Hundred Thirty
Five and Paisa Fifty Only
Providing, erecting, testing commissioning & getting Plan Approval as well as
NOC from Electrical Inspector for extensible H.T panel comprising of one
630A/800A/1250A. H.T. VCB incoming & Two outgoing 630/800/1250 A
Drawout type VCB confirming as per I.S. for use on 11 kV, 3 phase, 50 Hz.
unearthed A.C. supply system having breaking rupturing capacity of 350 MVA
or Above complete with spring operated mechanism, mechanically & automatic
ON-OFF and spring mechanism charged, discharged indicators, ON-OFF
mechanical push button, operation counter necessary auxiliary switches, closing Rupees Thirteen Lakh Twenty
56 1 shunt trip, air insulated busbar chamber having heat shrinkable PVC sleeves, Ea. 1328836.8 Eight Thousand Eight Hundred
mechanical interlocks safety shutters, isolating plugs and a VCB trolley with Thirty Six and Paisa Eighty Only
three vacuum interrupters with epoxy support insulators and self aligning finger
type isolating contacts. The breaker shall be Manual cum motorised mechanism
& auto spring charge with TNC switch closing with following accessories. The
Standared Companies Switchgear shall be Used and Only Manufacutres as per
IEC 62271-200/201 for beneficial use.
1.flush mounting type digital multifunctional meter with communication facility -
2. Power Factor Meter One No
3. Double core current transformer cast resin type having ratio 200 to 50/1 core
for metering & second core for protection having required class of accuracy. -
4. Instantaneous under voltage relay,Over Voltage relay & Temperature rise
5. Electrical closing coil & short trip coil operating on 110V. D.C.- Three Sets
6. Auxiliary relay for anti pumping device
7. Three phase Three limb Drawout type feeder connected & output of 200 VA
cast resin insulated potential transformer having ratio 12000V./110V. and
VA Burdon with 0.5 accuracy. - One No.
8. Common Alarm bell operating on 110V A.C.- One No.
9. Digital KWH Meter - One No.
10. Cable boxes suitable up to 11 kV 3core 150 sq.mm XLPE cable. - Three
11. 230V. A.C. to 110V. D.C. power pack for closing & tripping circuit
12.Breaker ON-OFF, Auto trip and spring charged indicators. - Three Sets.
13.Phase indicating & panel illumination lamps with plug socket - Three Sets.
14.Numerical Communicable type non directional O/C & E/F Relay with
a setting of 5-250% both in O/C & E/F. -Three Set
complete with necessary interconnection with air insulated high grade copper
busbar {Breaker Testing scope include Closing Time, Opening Time, VCB Hi-
Pot test at Site}{ Relay Testing Scope Include testing of all protection by three
phase testing kit at site }(VCB Trolley is to be provided)
Providing and fixing printed instruction chart both in English and Gujarati and
duly framed with front glasses, for treatment of person suffering from Electric Rupees One Hundred Thirty and
shock with minimum 50" diagonally size. Paisa Twenty Nine Only
Supplying rubber matting of following thickness as per IS:15652/IEC
Rupees One Thousand Twenty
58 12 b)4mm Sq.Mtr 1027.17
Seven and Paisa Seventeen Only
Supplying stand first AID box with antiseptic cream, medicine for use on wounds
due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-
Rupees Two Hundred Ninety Nine
59 2 aid) adhesive tape for medicinal user, Scissors, anti-septic solution (Savlon or Ea. 299.97
and Paisa Ninety Seven Only
similar) etc. (All above contents shall be of standard makes)
Supplying FIRE bucket round bottom of 9 litres capacity made out of 24 gauge
G.I. sheet with extra handle at bottom duly painted white inside and Red out side Rupees Two Hundred Fourteen
with FIRE mark, filled with dry-sand and kept on existing stand provided or and Paisa Twelve Only
hung on wall hook.
Providing pair of rubber hand gloves suitable for working on 11 kV/22 kV
Rupees Two Hundred Fourteen
61 3 supply. Ea. 214.12
and Paisa Twelve Only
Supplying and erecting high tension cable end box outdoor type suitable. for 11 Rupees Three Thousand Eight
62 4 kV 150/185Sq.mm 3core H.T. cable complete with gland bushing and jointing Ea. 3853.15 Hundred Fifty Three and Paisa
material. Fifteen Only
Supplying & erecting D.C.P. type fire extinguisher for following capacity
cartridge type with gun metal cap 150 gram CO2 gas cartridge, powder and Rupees One Thousand Seven
63 5 brackets confirming to IS 2171 1985 and complete erected with necessary Ea. 1712.96 Hundred Twelve and Paisa Ninety
clamps made from 50 x 6 mm M S Flat with nuts and bolts grouted in wall Six Only
complete[A] For 5 Kg Capacity
Supplying & erecting D.C.P. type fire extinguisher for following capacity
cartridge type with gun metal cap 150 gram CO2 gas cartridge, powder and Rupees Two Thousand Two
64 5 brackets confirming to IS 2171 1985 and complete erected with necessary Ea. 2226.04 Hundred Twenty Six and Paisa
clamps made from 50 x 6 mm M S Flat with nuts and bolts grouted in wall Four Only
complete. [B] For 10 KG Capacity
Supplying & erecting carbon dioxide (CO2) fire extinguisher user of following Rupees Six Thousand Five
65 5 capacity with necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts Ea. 6591.26 Hundred Ninety One and Paisa
grouted in wall complete. [A] For 4.5 Kg Capacity Twenty Six Only
Supplying & erecting carbon dioxide (CO2) fire extinguisher user of following
Rupees Eight Thousand Six
capacity with necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts
66 5 Ea. 8671.86 Hundred Seventy One and Paisa
grouted in wall complete. [B] For 5.5 / 6.5 KG Capacity
Eighty Six Only
Supplying & fixing Steel Chequered Plate having 12 mm thickness, duly painted Rupees Five Thousand Seven
67 50 with two coats of black Japan colour. (Average Wt 200.3 kg / Sq.Mtr) Sq. Mtr. 5780.23 Hundred Eighty and Paisa Twenty
Supplying and erecting approved make panel mounting type Digital Voltmeter
Rupees One Thousand Two
having 3 digits LED display, 0 to 750 AC Volts range erected on existing panel
68 4 Ea. 1275.63 Hundred Seventy Five and Paisa
board with all connection, wiring etc .with manufacturers calibration certificate.
Sixty Three Only
Supplying and erecting approved make panel mounting type Digital Ammeter
having 3 digits LED display, external CT operated, calibrated for 0 to 1000 Rupees One Thousand Five
69 4 Amps suitable to operate on 500 Volt AC , erected on existing panel board with Ea. 1558.43 Hundred Fifty Eight and Paisa
all connection, wiring etc .with manufacturers calibration certificate. Forty Three Only
Supplying and erecting Ammeter / Voltmeter selector switch for 3 phase AC
Rupees Three Hundred Seventeen
70 8 Supply 500 V on existing panel board with necessary connections. Ea. 317.14
and Paisa Fourteen Only
Providing & erecting L.T. Current Transformer with bar primary 50/5 to 1000/5
Rupees Two Hundred Seventy
71 4 ratio 15 VA burden erected in existing CRCA box duly secured with insulating Ea. 274.72
Four and Paisa Seventy Two Only
materials connected to the meter
Supplying & erecting approved make Power Factor Meter 150mm dia
flush/projection type/ balanced & unbalanced load to work with appropriately Rupees Five Thousand One
72 4 provided CT’s 100/5A to 400/5A ratio & other accessories complete erected in Ea. 5102.52 Hundred Two and Paisa Fifty Two
M.S. box & connected to the circuit by means of PVC copper Core leads. Only
Supplying and erecting approved make suitable panel indicator LED type lamp, Rupees Forty Three and Paisa
lens cover, complete erected with necessary connections. Forty Three Only
Supplying & erecting directly operated single phasing preventer complete erected
Rupees One Thousand Seventy
74 4 and connected to supply up to 45 Amp. Range. Ea. 1078.68
Eight and Paisa Sixty Eight Only
providing and erecting Mains with ISI marked, 1.5KV grade electrolyte multi
stranded, annealed copper conductor with heat resistant PVC insulated conforms
to IS 694, IEC - 227 erected in existing pipe of following size (Specifically for
control panel, relays, power switchgears, motor starters & control wiring) with
required size of copper lugs, nuts and bolts if required.
(a) One wire 1.00 sq. mm Rupees Fifteen and Paisa Fifteen
(b) One wire 1.50 sq. mm Rupees Twenty One and Paisa
Twenty One Only
(c) One wire 2.50 sq. mm Rupees Thirty Four and Paisa
Thirty Four Only
(e) One wire 6.00 sq. mm Rupees Seventy and Paisa
(g) One wire 16.00 sq. mm
Rupees One Hundred Seventy
Seven and Paisa Seventy Six Only
(h) One wire 25.00 sq. mm
Rupees Two Hundred Ninety Five
and Paisa Ninety Three Only
(j) One wire 50.00 sq. mm
Rupees Five Hundred Eighty Eight
and Paisa Eighty Three Only
(l) One wire 95.00 sq. mm Rupees One Thousand One
10 Mtr. 1149.38 Hundred Forty Nine and Paisa
Thirty Eight Only
Providing and erecting following additional parts for panel mounting MCCBs
(A)Extended operating rotary handle with pad lock with three position trip,off,on Rupees Nine Hundred Sixty One
suitable for 25A to 250 A panel mounting cat-III and Paisa Fifty Two Only
Providing and erecting following additional parts for panel mounting MCCBs Rupees One Thousand Four
77 8 (B)Extended operating rotary handle with pad lock with three position trip,off,on Ea. 1442.28 Hundred Forty Two and Paisa
suitable for 400A to 630 A panel mounting cat-III Twenty Eight Only
Providing , erecting , fabricating the M.S. structure as per requirement on site
incorporating proper size of M.S. angles,square,round, flats, bars, channels,
sections complete with cutting, welding, grinding & finishing duly painted with Rupees Seventy Seven and Paisa
one coat of red oxide with erection on site as per direction of engineer in charge Seventy Seven Only
with necessary grouting, cementing, plastering & finishing complete.
Providing and fixing approved make Ladder type cable tray. Made from M.S
sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated of
double bended channel section longitudinal members with single bended Channel
section. Rungs of members welded to the base of the longitudinal members at
79 250 mm c/c spacing . as per IS and shall be coated with hot dip galvanizing as
per IS 2629/4759. with coupler plate / Fish plate and GI hardware like nut - bolt
and washers etc. erected on existing support as per Specification and as per
instruction of engineer in charge..
(3) 300 X 50 X 2.0 mm Thick Rupees Three Hundred Nine and
(6) 600 X 50 X 2.0 mm Thick
Rupees Four Hundred Seventy
One and Paisa Sixty Seven Only
Providing and fixing approved make 'T' Junction for ladder type cable tray.
Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
80 with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc.
erected on existing support as per Specification and as per instruction of
engineer in charge.. A - 'T' Junction
(3)300 X 50 X 2.0 mm Thick 'T' Junction
Rupees Two Hundred Sixty Five
and Paisa Sixty Three Only
(6) 600 X 50 X 2.0 mm Thick 'T' Junction
Rupees Four Hundred Seventy
One and Paisa Sixty Seven Only
Providing and fixing approved make '90° Elbow' for ladder type cable tray.
Made from M.S sheet steel. The Junction should be bended as per IS 2062/1079.
81 with coupler plate / Fish plate and GI hardware like nut - bolt and washers etc.
erected on existing support as per Specification and as per instruction of
engineer in charge..
(3) 300 X 50 X 2.0 mm Thick
Rupees Two Hundred Twenty
Seven and Paisa Twenty Five Only
(6) 600 X 50 X 2.0 mm Thick
Rupees Four Hundred Sixty Three
and Paisa Fifty Nine Only
INTERNAL POINT WIRING
Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm
(Green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multi strand
copper wires up to 10 mtr length , in below type of pipe erected with 6A
Modular type switch / bell push & accessories and earth continuity of following
Rupees Five Hundred Thirty Nine
82 30 type, erected on PVC / Metallic/Wooden box, single mounting base frame Ea. 539.34
and Paisa Thirty Four Only
covered with textured/metallic/white front plate modules erected on / in wall /
ceiling as per pipe erected, with necessary Lamp holder/ceiling rose /
H.D.Connector as directed.
(a) with medium class Rigid PVC pipe and accessories erected concealed in
wall/ceiling complete
Point wiring for FAN with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both
are of .ISI marked 1.1 KV Grade FRLS PVC insulated multi strand copper wires
up to 10 mtr length, in below type of pipe erected with 6A Modular type switch
and hum free EME step type electronic fan regulator mounted and accessories
with earth continuity of following type erected on PVC / Metallic/Wooden box, Rupees Eight Hundred Ten and
83 10 single mounting base frame covered with textured/metallic/white front plate PT. 810.02
modules erected on / in wall / ceiling as per pipe erected. with necessary ceiling
rose / H.D.Connector as directed.
(f) with medium class Rigid PVC pipe and accessories erected concealed in
wall/ceiling complete Cat. III
Providing following type of Modular Type Accessories mounted with PVC /
metallic/Wooden box, single mounting base frame covered with textured /
Rupees One Hundred Fifty One
84 40 metallic/white front plate , modules erected with necessary connections as per Ea. 151.5
and Paisa Fifty Only
site situation directed by Engineer In charge. (1)One No. SP 6 Amp. Cat. III
(2) One No 5 pin plug Cat.III Rupees One Hundred Fifty One
and Paisa Fifty Only
(9) 16 Amp. SP one way switch Cat.III Rupees One Hundred Eighty and
Paisa Seventy Nine Only
(10) 6/16Amp. Universal socket Cat.III
Rupees One Hundred Ninety Nine
and Paisa Ninety Eight Only
Providing and erecting ISI mark Medium class RIGID PVC PIPES of following
size complete to be erected on/in wall or ceiling erected with necessary PVC
Rupees Thirty Three and Paisa
88 100 fittings & Junction boxes fixed with adhesive solution & Clamps with following Mtr. 33.33
Thirty Three Only
dia of pipes, in approved manner as directed (b) 25 mm
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be erected
concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS Rupees Seventy Eight and Paisa
PVC insulated stranded wire of green colour for earth continuity of following Seventy Eight Only
size (A) With medium class Rigid PVC pipe and accessories (a) 2 wire 1.5 sq.
Providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be erected
concealed in /flushed on wall/ceiling, with 1.5 sq. mm copper conductor FRLS Rupees One Hundred Four and
PVC insulated stranded wire of green colour for earth continuity of following Paisa Three Only
size (A) With medium class Rigid PVC pipe and accessories (b) 2 wire 2.5 sq.
providing and erecting Mains with 1.1 KV grade FRLS PVC insulated ISI
marked stranded Copper conductor wire in following type of pipe to be erected in
/ on wall / ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated Rupees Three Hundred Twenty Six
stranded wire of green colour for earth continuity of following size (A) with and Paisa Twenty Three Only
medium class Rigid PVC pipe and accessories (h) 4 wire 6 sq. mm
providing and erecting Miniature circuit breaker single pole 6A to 25A suitable
to operate on 240 V A.C. system and having breaking capacity 10 KA to be Rupees One Hundred Twenty
erected in existing box. confirming to IS 8828/1996 with ISI Mark Cat.III Three and Paisa Twenty Two Only
Providing & erecting 240 V MCB double pole switch for motor & inductive load
(C Curve) having 10 KA breaking capacity & confirms to IS : 8828 in existing Rupees Three Hundred Thirty and
box having following capacity (A) 32 Amp. Cat.III Paisa Twenty Seven Only
Providing and erecting Sheet Steel powder coated MCB distribution board - flush
/ surface mounted fitted with busbar, neutral link, earth bar and DIN rail,
Conforms to IS 8623-1 & 3, IEC 61439-1 & 3 without MCB to house Rupees Three Thousand Four
94 1 appropriate nos. of MCBs.(The DBs should be used of same company of MCB to Ea. 3412.79 Hundred Twelve and Paisa
be used) suitable for (B) three phase incoming and single phase horizontal type Seventy Nine Only
outgoing Per phase isolation type (PPI) (b) sheet steel double door (iii)8 way
Supplying & erecting approved make RCCB + MCB (Electro magnetic type
only) working on residual current device having 10 KA short circuit breaking
capacity and 30 mAmp. Sensitivity & 30 mili sec. tripping time conforming to IS Rupees Three Thousand One
95 1 12640 test knob facility trip free mechanism operating for rated leakage at Ea. 3117.87 Hundred Seventeen and Paisa
nominal ten volt, complete erected including all materials lugs screws etc. Eighty Seven Only
completed.[f] 63A, 4 pole Three Phase
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to
Watt assembled on single MCPCB, with housing used as a heat sink shall be
made of thick sheet Steel conforming to IS: 513/CRCA/ aluminium die cast
powder coated and high U.V. & corrosion resistance with diffuser with
company mark/name 160V to 270V, Power Factor more than 0.95, THD < 15%,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt ,LED Rupees Five Hundred Thirty Five
LED driver efficiency > 85 % and Paisa Thirty Only
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have
shown ranges of Wattage capacity of LED fittings.The Engineer incharge may
select any wattage capacity between the ranges shown.) (A) Tube Light with
integral driver (v) 40 Watts, Surge-2 KV, IP-20, conventional 4 feet Cat.III
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to
Watt assembled on single MCPCB, with housing used as a heat sink shall be
made of thick sheet Steel conforming to IS: 513/CRCA/aluminium pressure die
cast powder coated and high U.V. & corrosion resistance with diffuser housed
in aluminium casted body with company mark/name
160V to 270V,Power Factor more than 0.95, THD < 15 %,
CCT 3000 K to 6500K,
Luminaire efficacy> 85 lumens/watt , Rupees Four Hundred Twenty
97 100 Ea. 427.23 Seven and Paisa Twenty Three
LED driver efficiency > 85 %
( fitting required LM-79 & LM-80 Certificates)(NOTE: Below description have
shown ranges of Wattage capacity of LED fittings.The Engineer incharge may
select any wattage capacity between the ranges shown.) (A) Square/ Circular
shaped Surface/Recessed Mount Downlight with provision for spring loaded
mounting clips complete.IP20 (ii) 15 watts, Surge-2 KV-cat-lll
Providing & erecting Approved make Power Saving 50 Watt Ceiling Fan with
double ball bearing ISI mark with Condenser 230 volt A.C. 50 Hz 1200 mm Rupees One Thousand Nine
98 10 sweep complete having 3blades with aluminium blades with , canopy & 30 cm. Ea. 1948.29 Hundred Forty Eight and Paisa
down rod erected with earthing.(Make shall be approved by Engineer in charge)) Twenty Nine Only
Supplying and erecting 19 / 20 mm. nominal bore Medium Class M.S. Pipe down
Rupees One Hundred Eight and
99 15 rod erected duly painted for fan complete with proper insulation without leakage Mtr. 108.07
Paisa Seven Only
Supplying & erecting Fan Hook of 10 mm M.S. Round bar grouted in RCC slab Rupees Forty Three and Paisa
with Making the site as original. Forty Three Only
Providing 2.5mm.thick laminated acrylic sheet to cover the fan hook or Fan box. Rupees Eighteen and Paisa
Supplying & erecting single phase approved make industrial exhaust fan suitable
for medium duty ring mounted low noise operation suitable for medium duty Rupees Two Thousand Fifty Four
having following dia size and maximum speed in RPM [A] 305 mm dia 900 and Paisa Thirty Four Only
Supplying and erecting approved make double ball bearing oscillating type
Heavy duty bracket fan with Aluminium Blades A.C. 23OV. 50cy/s wall
mounted with height adjustment and rotary tilting device complete with guard, Rupees Four Thousand Nine Hundred
wall bracket,mounting accessories as directed. (A) 450mm Fifty and Paisa One Only
Filling the necessary application to Supply Co,Following up and getting the
supplu filling the necessary Test report to the Supply Co.All Official/statutory Rupees Twenty Five Thousand Two
104 1 fess shall be paid by clients. (HT, Transformer, and all types of Electrical Ea. 25250
Hundred Fifty and Zero Paisa Only
Licening work including)
Total Amount A+B
Total Amount A+B
Deputy Executive Engineer (Civil) Executive Engineer (Civil)
PIU,-1, Ahmedabad PIU,-1, Ahmedabad
Asst. Engineer(Elect) Dy. Executive Engineer (Elect) Executive Engineer (Elect)
Piu Ahmedabad Piu Ahmedabad Piu Ahmedabad
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
TENDER NOTICE NO - 74.pdf
0.SBD Book_2023_Final_17_01_2024 (1).pdf
16. Standard Specification for Electrical Work (1).pdf
6372 Make List (1)_compressed.pdf
Devi Hostel -Schedule-B.pdf
PQ-2026.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].