| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹10.6 LAccepted-AOC | 1 | Accepted-AOC L1 | |
| 2 | 2₹10.7 L+₹11,611 (1.09%)Rejected-AOC | 2 | Rejected-AOC L2 | |
| 3 | Rejected-Technical | - | Rejected-Technical EMD RELEASE | |
| 4 | Not Admitted-Fee/PreQual/Technical/Finance | - | Not Admitted-Fee/PreQual/Technical/Finance Not qualified for AOC | |
| 5 | Rejected-Technical KARUKAPPILLY THATTATHUKUDIYIL BUILDING KOLENCHERY 682311 | KOLENCHERY | ERNAKULAM | KERALA | 682311 | - | Rejected-Technical EMD RELEASE |
Tender Value
₹12.9 L
EMD Value
₹35,000
Closing Date
17 Oct 2022, 5:00 pmClosed
CHIEF ENGINEER, KSCADC
CHIEF ENGINEER KSCADC 1st Floor, Chalachithra Kalabhavan Building, Vazhuthacaud, Jagathy P.O. Thiruvananthapuram Pin-695014
PMMSY Construction of Aquatic Referral Lab for KUFOS in Ernakulam district- Electrical Works
2022_SCADC_513872_1
ET-24/2022-23
Open Tender
Electrical Works
Item Rate
120 days
Panangadu
Please refer Tender documents.
6 documents required · 6 mandatory
₹2,950
₹35,000
22 Mar 2023
7 Oct 2022
19 Oct 2022
7 Oct 2022
17 Oct 2022
7 Oct 2022
Amount
Electrical Work
1.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.5 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.50 mm
1.24.7 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet
1.26 : Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.53.1 : Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
1.56 : Supplying and fixing suitable size Gl box with modular plate and cover in front on surface or in recess, including providng and fixing 2 Nos. 3 pin 5/6 A modular socket outlets and 2 Nos. 5/6 A modular switches, connection etc. as required. (For light plugs to be used in non residential buildings).
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.13.1 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.13.2 : Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.15.2 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.15.3 : Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required.63 amps
2.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
2.18 : Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
5.4 : Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
5.14 : Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
90.4.1 : Supply and installation of suitable size MS rod type fan clamp in the RCC slab as per IS 732 as required.
90.10.3.14 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant )25A SP switch with indicator
90.10.3.33 : Supply and Fixing the following modular switches & accessories in the existing front plates and giving necessary connections as required (RoHS compliant ) 25A 3pin shuttered socket
90.11.1.11 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 6 way (8+18)- three phase double cover (IP 42/43)
90.12.7.40 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 10 sq mm with factory made clamp
90.12.7.41 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 16 sq mm with factory made clamp
90.15.4.2 : Supply Conveyance, installation, testing and commissioning of 36/40W LED street light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing,acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
od38618/2021_2022 : LIGHT FITTINGS Supply, Installation, Testing & Commissioning of batten type1x20 / 1x21W LED Type Tube Light ALUMINIUM Body BN021 4 FEET design channel light out put on ceiling / wall including connection with 1sq.mm FRLS PVC insulated copper conductor multi stranded three core cable etc.(including lamp) as required (Make Philips,Crompton Greeves.)
od38621/2021_2022 : GENERAL PURPOSE LUMINAIRES. Supplying and fixing following SLEEK RD- surface mounted or recessed Round or Square Down light 112545 BGSLO Sleek surface 18W WH RD cool white LED down light fo soft diffused lighting complete light out put on ceiling / wall including connection with 1sq.mm FRLS PVC insulated copper conductor multi stranded three core cable etc as required (Make Philips,Crompton Greeves.)testing and commissioning
od38622/2021_2022 : Supply, installation, testing and commissioning of following exhaust fan in the exisitng opening, including making the hole to suit the size of the above fan, making good damage, connection, testing, commisioning etc. as required. (a) 230 mm metal body (Make:- Almonard - light duty)<br>
od38624/2021_2022 : Supply and fixing of Angle holder or pendent type with 9w LED lamp.Including Lamp Shade.<br>
od38625/2021_2022 : Supply, installation, testing and commisioning of following sweep ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FR PVC insulated, copper condutor, single core cable etc. as required. (a) 1200 mm sweep ceiling fan white shade with stepped type electronic fan regulator (Usha (Striker)/,Crompton(High breeze)/ Havells (Velocity))<br>
od38627/2021_2022 : Providing, Fixing, Laying & Clamping at site of Copper earthing conductors<br>inclusive of providing earthing terminations and bracing of the terminations<br>etc.<br>10 SWG Copper wire.
od51807/2021_2022 : Supply, fabrication, errection testing and commissioning of 16 SWG electrical panel board with 160A FP isolater as incomer and 200A onload changover for the generator connection with 3 numbers of 40A FP MCB and 5 numbrs of 63A FP SFU with sufficient HRC fuse as outgoings ( include voltmter, ammeter and indication lights)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
od68120/2021_2022 : Supplying and fixing following size/ modules, GI box /Plastic surface/recessed box along with modular base & cover plate for modular switches in recess /Surface /Furniture etc as required(C)Information out let RJ 45 Cat 6
90.12.7.1 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 2 core 4 sq mm with factory made clamp
od336162/2021_2022 : Supply, installation, testing and commissioning of Bulk head light including 9W LED light fixtures
od336165/2021_2022 : Supply, Erection,Testing and Commissioning of Hot press moulded weather proof meter box including HRC fuse link, 125A SFU and provision for fixing CT and three phase meter box handle for the operation and other necessary accessories and connecting items 125A HRC fuse 3 numbers
od336185/2021_2022 : Supply and installation of 4 sqmm to 16 sqmm. 60 mm long x 12 mm wide x 1 mm thick Copper earthing clips for single compression glands and giving all connections.<br>
90.12.7.44 : Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 50 sq mm
9.1.36 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 50 sq. mm (35mm)
90.11.1.20 : Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required. 8 way (8+24)- double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/TP MCB as outgoing (IP 42/43)
2.2.2 : Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required125 Amp,16 KA,TPMCCB
GK INDUSTRIES
Power Care Electrical
Delstar a Grade Electrical contractors
poweron electrical designers and contractors
Bidder Name
Delstar a Grade Electrical contractors
Power Care Electrical
GK INDUSTRIES
Pattarumadathil Electricals
poweron electrical designers and contractors
stage.html
html • 0.05 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_736603.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .