Machineries/ Mechanical Engg Items
Turn-key
60 days
Samba
Please refer e-NIT
2 documents required · 2 mandatory
₹600
Executive Engineer Jal Shakti PHE Division Samba
₹12,000
5 Sept 2026
1 Aug 2026
18 Aug 2026
1 Aug 2026
18 Aug 2026
1 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Design, fabrication, installation, testing and commissioning of one no. LT control panel for 100hp HC pump at T/W no. 1 (Samba Town)
The panel should be equipped with following components / features: -
The panel should be fitted with 250 Amps MCCB and a set of RYB indicators at incoming side.
Star delta starter. - The panel should be fitted with starter comprising of 2 no. air brake contractors, 1 No. 185 Amps for main and 1 no. 185 Amps for delta supply and 1 no. 95 Amps for star operation, 1 no. timer for changing over the supply of motor from star to delta, 2 Nos. push buttons for start and stop operation of motor. 1 No. MCB 6 Amps. for the protection of internal control wiring. A neat and clean internal control wiring should be made with flexible, copper cables to complete the star delta circuit of outgoing supply.
Panel should be equipped with following devices and relays:
a) Thermal Overload Relay – MN12 (L&T)
b) Motor protection Relay: (MPD 192)
c) Voltage Protection Relay: (GIC/Multispan)
d) Single Phase Prevention Relay: (GIC)
e) Star-Delta Timer
Protection devices: - The panel should be equipped with relay which should be able to protect the motor from voltage and current related faults.
Voltage related faults: - Single phasing, under voltage, over-voltage, unbalanced voltage.
Current Related faults: - Over current / load, dry running, unbalanced current / load, earth leakage, short circuiting. | 1 | Job | - | - |
| 2 | Supply of Lauritz Knudsen (L&T) MU-G30 Three Phase Fully Automatic Star-Delta Submersible Pump Controller for T/W Chann Matlooni (Ghagwal section) and D/W Chal Katli (Sumb section)
Model : MU-G30 (MUG-30)
Motor Rating: 30 HP (22 kW)
Starter Type: Fully Automatic Star-Delta (FASD)
Rated Voltage: 415V ±10%, 50 Hz
Coil Voltage : Wideband (200V – 400V)
Overload Relay Range: (30 – 50) Amp
Protection: Overload + Single Phasing
Metering: Ammeter + Voltmeter (Analog)
Enclosure: Powder Coated MS Sheet
Mounting: Wall / Floor
Standard: IS/IEC 60947 | 2 | Jobs | - | - |
| 3 | Supply of Lauritz Knudsen (L&T) MU-G20H Three Phase Fully Automatic Star-Delta Submersible Pump Controller for T/W Odha, T/W Jatwal 1 (Ghagwal section), F/P Samba (Samba Town) and T/W Palth ( Nud section)
Model: MU-G20H (MUG-20)
Motor Rating: 20 HP (15 kW)
Starter Type: Fully Automatic Star-Delta (FASD)
Rated Voltage: 415V ±10%, 50 Hz
Coil Voltage : Wideband (200V – 400V)
Overload Relay Range: (28 – 42) Amp
Protection: Overload + Single Phasing
Metering: Ammeter + Voltmeter (Analog)
Enclosure: Powder Coated MS Sheet
Mounting: Wall / Floor
Standard: IS/IEC 60947 | 4 | Jobs | - | - |
| 4 | Supply of Lauritz Knudsen (L&T) MU-G10H Three Phase Fully Automatic Star-Delta Submersible Pump Controller for T/W no. 3 (Samba Town) and D/W Dabri (Sumb section).
Model: MU-G10H (MUG-10)
Motor Rating: 10 HP (7.5 kW)
Starter Type: Fully Automatic Star-Delta (FASD)
Rated Voltage: 415V ±10%, 50 Hz
Coil Voltage : Wideband (200V – 400V)
Overload Relay Range: (20 – 32) Amp
Protection: Overload + Single Phasing
Metering: Ammeter + Voltmeter (Analog)
Enclosure: Powder Coated MS Sheet
Mounting: Wall / Floor
Standard: IS/IEC 60947 | 2 | Jobs | - | - |
| 5 | Supply of Lauritz Knudsen (L&T) MU-G40H Three Phase Fully Automatic Star-Delta Submersible Pump Controller for T/W Sarien (Nud section).
Model: MU-G40H (MUG-40)
Motor Rating: 40 HP (30 kW)
Starter Type: Fully Automatic Star-Delta (FASD)
Rated Voltage: 415V ±10%, 50 Hz
Coil Voltage : Wideband (200V – 400V)
Overload Relay Range: (36 – 60) Amp
Protection: Overload + Single Phasing
Metering: Ammeter + Voltmeter (Analog)
Enclosure: Powder Coated MS Sheet
Mounting: Wall / Floor
Standard: IS/IEC 60947 | 1 | Job | - | - |
| 6 | Supply of Lauritz Knudsen (L&T) MU-G75H Three Phase Fully Automatic Star-Delta Submersible Pump Controller for B/W Kupri (Sumb section).
Model: MU-G75H (MUG-75)
Motor Rating: 75 HP (55 kW)
Starter Type: Fully Automatic Star-Delta (FASD)
Rated Voltage: 415V ±10%, 50 Hz
Coil Voltage : Wideband (200V – 400V)
Overload Relay Range: (66 – 110) Amp
Protection: Overload + Single Phasing
Metering: Ammeter + Voltmeter (Analog)
Enclosure: Powder Coated MS Sheet
Mounting: Wall / Floor
Standard: IS/IEC 60947 | 1 | Job | - | - |
| 7 | Supply of 400A, 4-Pole Main Switch / Isolator (Switch Disconnector), 415V, with operating handle for T/W no.1(Samba Town).
Rated Current :400 Amp
No. of Poles: 4 Pole (3 Phase + Neutral)
Rated Voltage: 415V AC
Type : Switch Disconnector / Isolator
Mounting: Wall Mounting
Operating Handle: Door Interlocked Rotary Handle
Standard :IS/IEC 60947-3 | 1 | Job | - | - |
| 8 | Supply and installation of 11 kV Polymer Drop Out (DO) Fuse Set (3 Phase) on Distribution Transformer structure including mounting, connections, and testing at D/W Ghagwal, B/W Ghagwal, T/W Nichla Badla, T/W Randwal,Jatwal II, T/W Chan Matlooni and T/W Odha (Ghagwal section).
Rated Voltage:11 kV
Type: Polymer (Silicone)
Base Rating: 100A
Fuse Link: 10A (K-Type)
Mounting: Horizontal on cross arm
Standard: IS 9385 | 7 | Jobs | - | - |
stage.html
html • 0.02 MB
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.63 MB
BOQ_1054382.xls
BOQ • 0.32 MB
CorrigendumemMLA23.pdf
PDF • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .