Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
25 Nov 2026, 6:00 pm2d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Superintending Engineer, Project Implementation Unit, Health & Family Welfare Department.
Empanelment of Contractor for Annual Rate Contract for Maintenance of Operation Theatre Across the State of Gujarat.
362147
2026-27/90/04
Open
Civil Works
Works
Gandhinagar
1 document required · 1 mandatory
₹2,400
PIU-General Fund A/c 11-114
₹1 L
4 Nov 2026
4 Nov 2026
4 Nov 2026
25 Nov 2026
4 Nov 2026
120 days
Name of work : Empanelment of Contractor for Annual Rate Contract for Maintenance of Operation Theatre Across
the State of Gujarat.
Item Description Unit Qty Rate
Repair / Replacement / New item of OT ( PART - A )
Repair / Replacement of damaged / non functional element of OT ( PART - A ) ::
Automatic Sliding Doors -
Replacing of Foot Switch for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing foot Switch make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of Touchless Sensor for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Touchless Sensor make or equivalent & compitible with door )
Automatic Sliding Doors -
3 Replacing of Transformer for automatic sliding door to make it operational as per technical specification or as nos. 1
directed by Engineer Incharge . ( make:- existing Transformer make or equivalent & compitible with door )
Automatic Sliding Doors -
4 Replacing of Supply Card for automatic sliding door to make it operational as per technical specification or as nos. 1
directed by Engineer Incharge . ( make:- existing Supply Card make or equivalent & compitible with door )
Automatic Sliding Doors -
5 Replacing of Door PCB for automatic sliding door to make it operational as per technical specification or as directed nos. 1
by Engineer Incharge . ( make:- existing Door PCB make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of Bim Sensor for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Bim Sensor make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of Thortle Pully for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Thortle Pully make or equivalent & compitible with door )
Automatic Sliding Doors -
8 Replacing of Belt for automatic sliding door to make it operational as per technical specification or as directed by nos. 1
Engineer Incharge . ( make:- existing Belt make or equivalent & compitible with door )
Item Description Unit Qty Rate
Automatic Sliding Doors -
Replacing of Guide Roler for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Guide Roler make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of Door gasket for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Door gasket make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of View window for automatic sliding door to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing View window make or equivalent & compitible with door )
Automatic Sliding Doors -
Replacing of DC brushless motor for automatic sliding door to make it operational as per technical specification or
as directed by Engineer Incharge . ( make:- existing DC brushless motor make or equivalent & compitible with door )
Automatic Sliding Doors -
13 Replacing of Battery for automatic sliding door to make it operational as per technical specification or as directed by nos. 1
Engineer Incharge . ( make:- existing Battery make or equivalent & compitible with door )
Wall mounted Surgeon Control panel -
Replacing of Power supply/ tramsformer for Surgeon Control panel to make it operational as per technical
specification or as directed by Engineer Incharge . ( make:- existing Power supply/ tramsformer make or equivalent &
compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of Pi card for Surgeon Control panel to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Pi card make or equivalent & compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of SCP Pcb Card for Surgeon Control panel to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing SCP Pcb Card make or equivalent & compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of Telephone card for Surgeon Control panel to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Telephone card make or equivalent & compitible with Control Panel
Wall mounted Surgeon Control panel -
Replacing of H/T Sensor for Surgeon Control panel to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing H/T Sensor make or equivalent & compitible with Control Panel )
Item Description Unit Qty Rate
Wall mounted Surgeon Control panel -
Replacing of Differential Pressure Sensor for Surgeon Control panel to make it operational as per technical
specification or as directed by Engineer Incharge . ( make:- existing Differential Pressure Sensor make or equivalent
& compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of Touch for Surgeon Control panel to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Touch make or equivalent & compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of Monitor for Surgeon Control panel to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Monitor make or equivalent & compitible with Control Panel )
Wall mounted Surgeon Control panel -
Replacing of On/Off Switch for Surgeon Control panel to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing On/Off Switch make or equivalent & compitible with Control Panel )
LED Dimmable X-Ray -
23 Replacing of X-Ray led light for X-Ray to make it operational as per technical specification or as directed by nos. 1
Engineer Incharge . ( make:- existing X-Ray led light make or equivalent & compitible with X-Ray )
LED Dimmable X-Ray -
Replacing of Blast/ Power Supply for X-Ray to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Blast/ Power Supply make or equivalent & compitible with X-Ray )
LED Dimmable X-Ray -
Replacing of Dimmer/realy Card for X-Ray to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Dimmer/realy Card make or equivalent & compitible with X-Ray )
LED Dimmable X-Ray -
26 Replacing of On/ off Switch for X-Ray to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing On/ off Switch make or equivalent & compitible with X-Ray )
Hatch/ Pass Box -
Replacing of Power Supply for Hatch Box to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Power Supply make or equivalent & compitible with Hatch Box )
Hatch/ Pass Box -
Replacing of Control Card for Hatch Box to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Control Card make or equivalent & compitible with Hatch Box )
Item Description Unit Qty Rate
Hatch/ Pass Box -
29 Replacing of LED Light for Hatch Box to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing LED Light make or equivalent & compitible with Hatch Box )
Hatch/ Pass Box -
30 Replacing of UV Light for Hatch Box to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing UV Light make or equivalent & compitible with Hatch Box )
Hatch/ Pass Box -
Replacing of H/B controll on/off switch for Hatch Box to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing H/B controll on/off switch make or equivalent & compitible with
Hatch/ Pass Box -
Replacing of Magnet controol Card for Hatch Box to make it operational as per technical specification or as directed
by Engineer Incharge . ( make:- existing Magnet controol Card make or equivalent & compitible with Hatch Box )
Dimmable Peripheral Lights -
Replacing of PFL Light Strip for Peripheral Lights to make it operational as per technical specification or as directed
by Engineer Incharge . ( make:- existing PFL Light Strip make or equivalent & compitible with Peripheral Lights )
Dimmable Peripheral Lights -
34 Replacing of Blast for Peripheral Lights to make it operational as per technical specification or as directed by nos. 1
Engineer Incharge . ( make:- existing Blast make or equivalent & compitible with Peripheral Lights )
Single/ Double Arm Moveable Pendant -
35 Replacing of Moter for Pendant to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing Moter make or equivalent & compitible with Pendant )
Single/ Double Arm Moveable Pendant -
36 Replacing of Power Supply for Pendant to make it operational as per technical specification or as directed by nos. 1
Engineer Incharge . ( make:- existing Power Supply make or equivalent & compitible with Pendant )
Single/ Double Arm Moveable Pendant -
Replacing of UP / Down Switch for Pendant to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing UP / Down Switch make or equivalent & compitible with Pendant )
Single/ Double Arm Moveable Pendant -
Replacing of Switch And Socket for Pendant to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Switch And Socket make or equivalent & compitible with Pendant )
Single/ Double Arm Moveable Pendant -
39 Replacing of Gas Outlets for Pendant to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing Gas Outlets make or equivalent & compitible with Pendant )
Item Description Unit Qty Rate
Single/ Double Arm Moveable Pendant -
Replacing of Matching probe/ adapter to make it operational as per technical specification or as directed by Engineer
Incharge . ( make:- existing Matching probe/ adapter make or equivalent & compitible with Pendant )
Single/ Double Arm Moveable Pendant -
41 Replacing of Braking Gas Pipe to make it operational as per technical specification or as directed by Engineer rmt 1
Incharge . ( make:- existing Gas Pipe make or equivalent & compitible with MGPS System )
Single/ Double Arm Moveable Pendant -
42 Replacing of Tray to make it operational as per technical specification or as directed by Engineer Incharge . ( make:- nos. 1
existing Tray make or equivalent & compitible with Pendant )
Ceiling Mounted LED OT Light -
43 Replacing of Power Supply to make it operational as per technical specification or as directed by Engineer Incharge . nos. 2
( make:- existing Power Supply make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
44 Replacing of dome to make it operational as per technical specification or as directed by Engineer Incharge . ( make:- nos. 1
existing dome make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
45 Replacing of Wall Control Unit to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing Wall Control Unit make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
Replacing of Wall Control Unit Power Supply to make it operational as per technical specification or as directed by
Engineer Incharge . ( make:- existing Wall Control Unit Power Supply make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
Replacing of Camera And All things to make it operational as per technical specification or as directed by Engineer
Incharge . ( make:- existing Camera And All things make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
Replacing of Camera HDMI Converter to make it operational as per technical specification or as directed by Engineer
Incharge . ( make:- existing Camera HDMI Converter make or equivalent & compitible with OT Light )
Ceiling Mounted LED OT Light -
49 Replacing of NDS Moniter to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing NDS Moniter make or equivalent & compitible with OT Light )
HEPA Filter for Laminar Air flow -
Replacing of Pressure Relief Dampers for Laminar Air flow to make it operational as per technical specification or as
directed by Engineer Incharge . ( make:- existing Dampers for Laminar Air flow make or equivalent & compitible with
Laminar Air Flow and applicable standards )
Item Description Unit Qty Rate
HEPA Filter for Laminar Air flow -
Replacing of all Hepa Filters in planum size 2400mm x 2400mm for Laminar Air flow to make it operational as per
technical specification or as directed by Engineer Incharge . ( make:- existing HEPA Filter make or equivalent &
compitible with Laminar Air Flow and applicable standards )
Scrub Station -
52 Replacing of Sensor to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing Sensor make or equivalent & compitible with Scrub Station )
Item Description Unit Qty Rate
Scrub Station -
Replacing of Foot Switch/ paddle to make it operational as per technical specification or as directed by Engineer
Incharge . ( make:- existing Foot Switch/ paddle make or equivalent & compitible with Scrub Station )
Scrub Station -
54 Replacing of transformer to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing transformer make or equivalent & compitible with Scrub Station )
Scrub Station -
55 Replacing of mixer valve to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing mixer valve make or equivalent & compitible with Scrub Station )
Scrub Station -
56 Replacing of Connection pipe to make it operational as per technical specification or as directed by Engineer nos. 1
Incharge . ( make:- existing Connection pipe make or equivalent & compitible with Scrub Station )
Scrub Station -
57 Replacing of t -joint to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing t -joint make or equivalent & compitible with Scrub Station )
Anti bacterial and anti fungal paint -
Providing and applying anti bacterial and anti fungal paint on existing painted surface as per specification.
Anti static Flooring -
59 Removing of Old Anti Static Flooring and clean the surface as per manufacturer recommendation and Providing and sqmt 1
Laying Anti static Flooring as per specification.
Integrated Storage Unit-
60 Replacing of Lock to make it operational as per technical specification or as directed by Engineer Incharge . ( make:- nos. 1
existing Lock make or equivalent & compitible with Storage Unit )
Integrated Storage Unit-
61 Replacing of Handle to make it operational as per technical specification or as directed by Engineer Incharge . ( nos. 1
make:- existing Handle make or equivalent & compitible with Storage Unit )
Integrated Storage Unit-
62 Replacing of Glass to make it operational as per technical specification or as directed by Engineer Incharge . ( make:- nos. 1
existing Glass make or equivalent & compitible with Storage Unit )
Supply, Installation, Testing, and Commissioning wall and Ceiling System - 3 mm thick Solid Mineral Composite
Sheet (SMS) panels for wall and ceiling system.It shall consist of 3 mm thick solid mineral composite sheet (SMS)
with aluminium backing structural panel (minimum 15 mm thick, consisting of a trapezoidal/honeycomb aluminium
corrugated core glued between two flats of aluminium sheets, with suitable substructure frame). Total panel
63 thickness shall not be less than 18 mm (3 mm thick SMS + 15 mm thick aluminium back). SMS panel shall be of Sq.mtrs 1
bacteriostatic, dense, non-porous and non-flammable (Reaction to fire class 1 norm) material. Anti-bacterial paint
should not be applied and as per detailed item specification.
Item Description Unit Qty Rate
Supply, Installation, Testing, and Commissioning (SITC) of 40 mm thick prefabricated modular operation theater
(OT) panels for wall and ceiling system. Panel Core consists of high-pressure injected rigid Polyurethane Foam
(PUF) with a density of 40 Kg/m³ (±2 Kg/m³). Front Skin: 0.8 mm thick Electro Galvanized Plain (EGP) for durability
and impact resistance. Back Skin: 0.8 mm thick Pre-Painted Galvanized Iron (PPGI) sheet. Panels are fixed to
existing brick walls using an SS or GI U-channel substructure. A variable cavity/gap is maintained between the brick
wall and the steel panel to allow for flush mounting of conduits and equipment like X-ray viewers and surgeon control
panels. The panel surface must be coated with 300 microns Dry Film Thickness (D.F.T.) of anti-bacterial paint. The
paint must be free from toxic agents like formaldehyde, toluene, xylene, and paradichlorobenzene and as per
detailed item specification.
Factory Finished Wall System - Truly Modular Anti Microbial Stainless Steel Panels (SS 304 Grade ) : The primary
material for the panel's exposed surface is high-grade stainless steel of Grade: SS 304 (also known as DIN 1.4301,
UNS S30400, or SUS304) with minimum 0.8mm to 1mm thick SS sheet for the front surface. The stainless steel
typically has a smooth finish (e.g., 2B, BA, No. 4, or super mirror) which inherently provides a hygienic, non-porous
surface that resists bacterial growth. An additional antimicrobial powder coating is required, as specified.The panels
are part of a modular system designed for a complete, factory-finished installation. The SS panel is backed with
16.0mm high-quality plasterboard (gypsum board). A complete and appropriate substructure for installation is
required to transfer the load and ensure stability. The system requires medical-grade gaskets or the capacity for hot
welding to ensure a tight seal, preventing leakage and contamination between panels. No other material other than
Stainless steel 304 (grade specified) shall be used for the primary panel construction itself, ensuring material
consistency and performance. The system must meet specific performance criteria for safety and application
suitability. The combination of the SS 304 material and the specified coating ensures an anti-bacterial/antimicrobial
surface suitable for sterile environments, Including anti bacterial paint on S.S.wall. The internal surfaces of the
corridor walls should be sprayed with water based non – reflective liquid plastic paint with a minimum dry film
65 thickness of 300microns. The sterile coating should remain unaffected by radiation and other ionizing radiation at Sq.mtrs 1
levels in excess of 1000 mrad and is classified to class I when tested in accordance with the requirements specified
under BS.476: Part 7 1971,Surface spread flame Test for Materials. The wall panel system should have a fire
resistance rating of a minimum of 25 minutes, as per technical specifications.The sterile coating should remain
unaffected by radiation at levels in excess of 1000mrad and is classified to class I when tested in accordance with
the requirements specified under BS 476: Part 7 1971 Surface spread of flame test for materials., its anti-microbial
system should not leach out & its anti-microbial properties should last for a minimum of 10 years. This is a critical
safety feature achieved through the use of fire-retardant core materials like the specified plasterboard.Modularity:
The system is pre-fabricated and modular, allowing for integration with other cleanroom components such as flush
doors, view panels, and utility provisions (e.g., for cables, medical gases).
Item Description Unit Qty Rate
Supply, Installation, Testing and Commissioning of Hermetically sealed doors the door to the should be a
hermetically sealed, single sliding door measuring 2.1 meters in height and 1.5 meters in width , CE marked or BIS
certified products or FDA or EN certificate or IEC compliance wherever applicable and as per detailed item
Supply, Installation, Testing and Commissioning of Touch screen control panel the 20" or more. This control panel
shall work as the central control panel for the HVAC controls, instruction board, touch screen and ON/OFF of MOT
69 light. It shall be CE/US FDA/ETL/UL/BIS certified/ listed.The Control Panel shall be able to display the Isolation Panel Nos. 1
Alarm Conditions along with MGPS Alarms and as per detailed item specification.
Supply, Installation, Testing and Commissioning of Pressure relief dampers - Pressure relief dampers or over flow
ports shall be provided in each room to prevent contamination of air from clean and dirty areas. The frame, body and
blade shall be of grade SS 304 stainless steel and as per detailed item specification.
Supply, Installation, Testing and Commissioning of Hatch boxes should be equipped with two doors and the doors
shall be operated electrically/motorised.The hatch shall be designed in such a way that only one door shall be
openable at one time.Hatch Box material shall be SS 304 grade. Length and width of the hatch box shall be
minimum 600mm by 600mm and as per detailed item specification.
Supply, Installation, Testing and Commissioning of LED type flat panel X-Ray Viewing panel of miniumum 14" x 17"
72 size . The body shall be of extruded aluminum powder coated with bacteria resistant and disinfectant resistant finish Nos. 1
and as per detailed item specification.
Supply, Installation, Testing and Commissioning of LED type Double Film flat panel X-Ray Viewing panel of
73 miniumum 28" x 17" size. The body shall be of extruded aluminum powder coated with bacteria resistant and Nos. 1
disinfectant resistant finish and as per detailed item specification.
Supply, Installation, Testing and Commissioning of double arm moveable pendant for anesthetist and surgeon. It
shall have double moveable arms (any combination) with total coverage of minimum 1800 mm and minimum
degree. Each arm shall have ability of horizontal movement. Vertical movement shall be motorized and the arm
74 height shall remain at a height greater than 6.5 feet above floor level. The pendant shall be European CE Certified Nos. 1
with 4 digit notified body number/US FDA/ETL/UL/BIS certified/listed. Weight carrying capacity of the arm shall not
be less than 180 kg and it shall have electromagnetic/pneumatic brakes and as per detailed item specification.
Item Description Unit Qty Rate
Supply, Installation, Testing and Commissioning of LED OT Light, HD Camera, HD Flat Head Panel Monitor. MOT
light – LED : Number of light heads: Two, Colour temperature range: 3800°K to 5000°K (±10%)-Variable colour
temperature , Field size diameter: 20cm to 28cm (+/- 10%), Working range: 750mm to 1100mm (+/- 10%),
Illumination level: minimum 160,000 lux (both for major dome and minor dome separately). HD Camera System –
1080 p/i : Signal to noise ratio (S/N Ratio): >50 dB, Optical zoom: 10X, Digital zoom: 12-15X, White balance and
75 gain: Automatic/Manual. HD LED Flat Panel Monitor : It shall be 30”-32” medical grade high definition progressive Nos. 1
scan flat-panel monitors withceiling mounted spring arm suspension to support high definition/HDTV progressive
scan images and shall be able to support and display DVI/HDTV, RGBHV, S-video, composite video signals and as
per detailed item specification.
Supply, Installation, Testing and Commissioning of Recording System shall be full HD medical grade monitor LED
76 minimum 19 inch touch screen and having one TB storage space and as per detailed item specification. Nos. 1
Supply, Installation, Testing and Commissioning of View Window (with Motorised Blinds) and as per detailed item
Supply, Installation, Testing and Commissioning of Double Dome OT Light with Ceiling mounted having following
78 features and enclosed technical specifications, CE marked or BIS certified products or FDA or EN certificate or IEC nos. 1
compliance wherever applicable and as per detailed item specification.
Total of PART - A
Item Description Unit Qty Rate
Comprehensive maintenance of Modular OT (PART - B)
Comprehensive maintenance of OT as per prevailing standards and specifications as directed by Engineer In Charge
1 For : Modular OT for 1st year nos. 1
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Modular OT for 2nd year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Modular OT for 3rd year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge For Modular
OT for 4th year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Modular OT for 5th year
Total of PART - B
Comprehensive maintenance of Non Modular OT (PART - C)
Comprehensive maintenance of OT as per prevailing standards and specifications as directed by Engineer In Charge
1 For : Non Modular OT for 1st year nos. 1
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Non Modular OT for 2nd year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Non Modular OT for 3rd year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Non Modular OT for 4th year
Comprehensive maintenance of OT as per prevailing standards and as directed by Engineer In Charge
For : Non Modular OT for 5th year
Total of PART - C
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
20-Special Conditions-27-05-2026.pdf
SBD_ARC_OT 26-27.pdf
Schedule-B OT Final.pdf
Tender Details-90-04.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .