| Sl No | Description | Qty | Unit | M/S MANAB ENTERPRISE L3 | M/s. Kar Electric Works L2 | PHINIX L1 |
|---|---|---|---|---|---|---|
| 1.00 | Servicing, Checking, Testing & Repairing of Dry-Type Transformer
Carrying out overall servicing, inspection, checking, testing of 11/0.433 kV dry-type transformer, including isolation, discharge and making the transformer safe for maintenance; thorough cleaning of HV/LV windings, core, insulation and enclosure; inspection for dust, moisture, overheating, cracks, tracking, loose connections and other abnormalities; checking and tightening of all HV/LV terminals, earthing connections, tap links and mounting arrangements; checking and functional testing of temperature sensors, temperature controller, alarm/trip circuits and other protection/indication devices; carrying out insulation resistance, winding resistance, and other applicable electrical tests; attending to and rectifying minor defects, loose connections, damaged hardware and other necessary minor repairs; replacement of minor consumables and hardware wherever required; complete reassembly, final testing and commissioning of the transformer after servicing, including submission of detailed service and test report, complete in all respects as per manufacturer's recommendations, applicable IEC/IS standards and instructions of Engineer-in-Charge.
Rate shall include: Skilled manpower, supervision, tools and tackles, calibrated testing instruments, cleaning materials, minor consumables, minor repair works, dismantling/reassembly, testing, commissioning and submission of service/test report, complete in all respects.
1000 KVA; 11/0.433 KV Dry Type Transformer | 4 | Job | 32,300 ₹1,29,200 Lowest | 33,450 ₹1,33,800 | 90,183 ₹3,60,732 |
| 1.01 | 750 KVA; 11/0.433 KV Dry Type Transformer | 2 | Job | 29,000 ₹58,000 Lowest | 32,980 ₹65,960 | 71,183 ₹1,42,366 |
| 1.02 | 500 KVA; 11/0.433 KV Dry Type Transformer | 4 | job | 2,000 ₹8,000 Lowest | 25,930 ₹1,03,720 | 43,800 ₹1,75,200 |
| 2.00 | Throughly servicing and overhauling of 800 amp HT VCB Panel Bus Bar and dismentling all components of electrical and mechnical portion incl. cleaning the dities, moisture of the BBC, HT bushing Spout, incl. V- contract, fingure contract by CTC oil and petrolium jelly , mechanical spring allied checking & testing of HT gear and reassembling of the components with all necessary works and testing of IR Value by 5000 Volt Insulating testing megger. | 23 | Job | 2,300 ₹52,900 Lowest | 2,300 ₹52,900 Lowest | 9,875 ₹2,27,125 |
| 3.00 | Checking the coils and contacts incl. calibration of different type relay (Overcurrent, Over voltage and earth fault relay) incl. submission of test report incl. transportation charges. | 23 | Job | 1,500 ₹34,500 Lowest | 1,500 ₹34,500 Lowest | 12,587 ₹2,89,501 |
| 4.00 | Supplying & fixing of 14 window Anunciator within the existing HT 3 panel including making necessary interconntion as per direction of EIC. | 4 | Job | 12,430 ₹49,720 | 12,430 ₹49,720 | 11,145 ₹44,580 Lowest |
| 5.00 | Supplying & fixing 8-channel temparature scanner display of 500 KVA TR including making necessary interconntion as per direction of EIC. | 6 | Sets | 27,300 ₹1,63,800 | 27,300 ₹1,63,800 | 11,136 ₹66,816 Lowest |
| 6.00 | SITC of multi-functional communicable protection relay. (Make: Schneider Electric, P3U30-6AAA 1BBAA/ eqv) having minimum following specifications -
A) Protection: Phase overcurrent (50/51) and Earth fault overcurrent (50N/51N) Directional Elements: Directional phase overcurrent (67) and Directional earth fault (67N), Transient earth fault 67NI, Voltage & Frequency: Undervoltage (27), Overvoltage (59), Residual overvoltage (59N), and Frequency protection (81/81R/81N), Thermal overload (49), Negative phase sequence /unbalance (46/46BC), Breaker failure (50BF), and Auto-reclose (79) Breaker failure 50 BF, Directional active under power 37P, capacitor overvoltage 59C etc.,
B) Measurement: 3Phase Current, Positive, negetive and zero sequence current, Phase & Line voltage, Fault location current, Frequency, Active Power, Reactive Power & Apparent Power, Active & Reactive Energy, Cos φ, Tan φ, Voltage & Current Phasor Diagram View, THD etc
C) Monitoring: Trip circuit supervision 74, Condition monitoring of CB, Relay self Monitoring
D)Logs and records: Event recording, Disturbance Recording & Tripping context
E)Communication: Remote monitoring over Modbus RTU having compliance as per IEC 60870-5-103 / 60870-5-101, Password protection
F) General: compatible with both 1 A and 5 A CT secondary ratings.Voltage Inputs: Standard PT inputs covering ranges 100/110V VT voltage, Embedded HTTP server
G) Environment: Ambient Temp: -10 to 55 °C, RH - 90%, IP 54 | 4 | Sets | 85,000 ₹3,40,000 | 85,000 ₹3,40,000 | 38,456 ₹1,53,824 Lowest |
| 7.00 | Supply and Pouring of silica gel in ducting breather. | 2 | Kg | 1,500 ₹3,000 | 1,300 ₹2,600 Lowest | 3,434 ₹6,868 |
| 8.00 | Supply & Fixing 110V DC pilot lamp (Red, green, white, yellow & Blue) after dismelting the burnt out pilot lamp as per direction of EIC. | 70 | Nos. | 250 ₹17,500 | 150 ₹10,500 Lowest | 150 ₹10,500 Lowest |
Tender Value
Refer Docs
EMD Value
₹47,951
Closing Date
28 Aug 2026, 4:00 pmClosed
Room No. 108, Purta Bhawan, Salt Lake
Room No. 108, Purta Bhawan, Salt Lake
Infrastructural work at VYBK In Connection with International Football Match to be held between India Vs Brazil-------Repair and Renovation of HT gear of 5 nos. Sub-Station
2026_WBPWD_5019368_1
WBPWD/EE/BED/e-NIQ-93/2026-27
Open Tender
ELECTRICAL WORKS ORG
Item Rate
15 days
VYBK
Please refer Tender documents.
6 documents required · 6 mandatory
₹47,951
Room No. 108, Purta Bhawan, Salt Lake
13 Oct 2026
21 Aug 2026
31 Aug 2026
21 Aug 2026
28 Aug 2026
21 Aug 2026
21 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SIT&C of Letter sign on existing round sign board.
Dismentaling, Installation, Testing & Commissioning of New Glow Sign Board of approved make having guarantee of minimum 3 years on new glow sign board/ frame etc. all complete using scaffolding and reinstalling it in position with following technical specifications: i) MS structure with approved file from dept . side , base & back side 4 mm ACP orange colour, signage 20 ft dia, maximum 10 inch depth. | 400 | Sq Ft | - | - |
| 2 | Supply and Delivery of LED 3D letters 2 ft height Maximum • Lettering/Faces: 3D LED illuminated letters with 4 mm acrylic • Backing/Cladding: Exterior-grade Aluminium Composite Panel (ACP) minimum 3mm to 4mm thick with PVDF coating for weather and UV resistance.
• Trims & Fasteners: Stainless steel (SS 304 grade) screws, nuts, and waterproof rubber beading/silicon sealant to prevent water ingress into letters or electrical housings. Letter depth 100 mm , side & base COPPER COLOUR , FRONT WHITE ACP FOR DAY TIME. | 45 | Nos | - | - |
| 3 | Supply and Delivery of LOGO - 3D LED illuminated letters with 4 mm acrylic 6 FT HEIGHT• Backing/Cladding: Exterior-grade Aluminium Composite Panel (ACP) minimum 3mm to 4mm thick with PVDF coating for weather and UV resistance.
• Trims & Fasteners: Stainless steel (SS 304 grade) screws, nuts, and waterproof rubber beading/silicon sealant to prevent water ingress into letters or electrical housings. Letter depth 100 mm , side & base COPPER COLOUR , high-translucency vinyl PRINT , UV PROTECTED PASTE ON LOGO AS PER APPROVED DESIGN. | 1 | Nos | - | - |
| 4 | Supply and Delivery of Illumination: Branded water-resistant (IP67 rated) LED modules SAMSUNG/GOQ/NINJA/OSRAM/BNZ. ORANGE CLOUR/ WHITE , BIS REQUIRED FOR APPROVAL. 1.2 WATT TO 1.8 WATT | 3,250 | Nos | - | - |
| 5 | Supply and Delivery of Wiring: ISI-marked copper conductor (Make-RR/Polycab/Finolex) flexible multi-strand wires (minimum 1.5 sq mm) pulled through protective PVC conduits. | 1 | Item | - | - |
| 6 | Supply and Delivery of AC To DC POWER SUPPLY – MEANWELL MAKE 350WATT -12 V OUT PUT NON WATER PROOF WITH IP 66 RATED BOX | 20 | Nos | - | - |
| 7 | SIT&C of Letter sign of ''VIVEKANANDA YUBA BHARATI KRIRANGAN" near VIP bypass Road and main Entry gate
Removal of existing letters, existing material with structure, all complete using scaffolding and reinstalling it in position with following technical specifications:
i) structure with approved file from dept . side , base & back side 4 mm ACP orange colour, letters 2ft length and 10 mm depth. | 62 | Nos | - | - |
| 8 | Supply and Delivery of LED 3D letters 2 ft height Maximum • Lettering/Faces: 3D LED illuminated letters with 4 mm acrylic • Backing/Cladding: Exterior-grade Aluminium Composite Panel (ACP) minimum 3mm to 4mm thick with PVDF coating for weather and UV resistance.
• Trims & Fasteners: Stainless steel (SS 304 grade) screws, nuts, and waterproof rubber beading/silicon sealant to prevent water ingress into letters or electrical housings. Letter depth 100 mm , side & base COPPER COLOUR , FRONT WHITE ACP FOR DAY TIME. Two nos. ''VIVEKANANDA YUBA BHARATI KRIRANGAN"=31 letters X 2 nos.= 62 nos. | 62 | Nos | - | - |
| 9 | Supply and Delivery of Illumination: Branded water-resistant (IP67 rated) LED modules SAMSUNG/GOQ/NINJA/OSRAM/BNZ. ORANGE CLOUR/ WHITE , BIS REQUIRED FOR APPROVAL. 1.2 WATT TO 1.8 WATT | 5,500 | Nos | - | - |
| 10 | Supply and Delivery of Wiring: ISI-marked copper conductor (Make-RR/Polycab/Finolex) flexible multi-strand wires (minimum 1.5 sq mm) pulled through protective PVC conduits. | 1 | Item | - | - |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.91 MB
2911_ii.pdf
Tender Documents • 0.50 MB
BOQ_5091608.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .