Er. Rahul Dhiman E.E.
JSV Division Nagrota Bagwan
Source Strengthening WSS Sadarpur Thanpuri Rajiana and WSS Jandrah JJM SH Drilling lowering of assembly Tube well Construction of Trench weir WTP Construction of various UG Reservoir Construction of Pump House Supply and errection of pumping mac
2022_HPIPH_60191_1
NGB-KNG01-773
Open Tender
Civil Works
730 days
Nagrota Bagwan
Please refer Tender documents.
14 documents required · 14 mandatory
₹2,500
EE JSV Nagrota Bagwan
₹16.8 L
4 Aug 2022
30 Apr 2022
17 May 2022
30 Apr 2022
17 May 2022
30 Apr 2022
Amount
Transportation of Rig along-with allied accessories etc.complete including erection and levelling at site through all kind of roads,approaches field etc.in all leads and lifts upto site of work complete in all respect.
Drilling of bore as per specifications laid down in IS-2800-1991(Part-I) with uptodate ammendments,if any;with Percussion Rig or combination drilling Rig starting with 650-600mm.dia M.S.Pipe reduced to 450-400mm.dia M.S.pipe confirming to IS-4270-2001 with uptodate ammendments,if any in all kinds of soils,boulders,rocks, collapsible strata,saturated soil, artesian conditions including the cost of all consumables,stores, water, fuel, lubricants and other accessories etc.complete in all respect.
Drilling and lowering of M.S.casing pipes 650-600mm.dia confirming to IS-4270-2001 with uptodate ammendments, if any of suitable sizes as mentioned above from 0 to 30 Metres below ground level.
Drilling and lowering of M.S.casing pipes 600-550mm.dia confirming to IS-4270-2001 with uptodate ammendments, if any of suitable sizes as mentioned above from 30 Metres to 60 Metres below ground level.
Drilling and lowering of M.S.casing pipes 550-500mm. Dia confirming to IS-4270-2001 with uptodate ammendments, if any of suitable sizes as mentioned above from 60 Metres to 90 Metres below ground level.
Collection,preservations and display of suitable size sample box with top lid and locking arrangem,ent till handing over of the Tube-Well to the Department complete in all respect.
Supply and lowering of IS-Marked Electric Resistance Welded Mild Blind Steel pipe 200mm.dia nominal size housing, 6.4mm.thick having outside diametre 219.1mm.screwed and socketted confirming to IS-4270-2001 with uptodate ammendments, if any, about 4.00 Metres to 7.00 Metres in length, welded without any circumferential joints into bore hole in vertical position including cost of all scaffolding derricks, poles, clamps embedded in foundation etc. including cost of all cuttings, threadings aqnd welding of pipes etc.
Supply ands lowering of IS-Marked Electric Resistance Welded Mild Steel slotted pipe 200mm.dia nominal size housing, 6.4mm.thick having outside diametre 219.10mm.screwed and socketted confirming to IS-4270-2001 with uptodate ammendments, if any, about 4.00 Metres to 7.00 Metres in length pipe should have 1040 slots per metre as per IS-8110:1985 of 75x1.57mm.slot size, welded without any circumferential joints into bore hole in vertical position including cost of all scaffolding derricks, poles clamps embedded in foundation etc.including cost of all cuttings, threading and welding of pipes etc.complete in all respect.
Providing and fixing of M.S.centralized guides at suitable spacing for each Tube-Well as per IS-226-1991 with uptodate ammendments, if any complete in all respect.
Supply,lowering,fixing and lowering in position IS-Marked Mild Steel bail plug of 200mm. Diametres with 'U' hooks as per IS-2800-1991 with uptodate ammendments,if any complete in all respect.
Providing,fixing and lowering in position threaded iron cap with locking arrangements of approved design to prevent foreign matter from getting into bore hole as required complete in all respect.
Supply and packing of gravel consisting of hard quartz or other suitable material with an average specific gravity of not less than 2.5, not containing more than 2% by weight of thin flat or stangated pieces shall be of sub rounded grains with minimum anuglar features of size 2-3.35mm.shall be free from impurities such as; shafe,shale mica, felspar, clay, sand, dit loam haematite and organic materials as per IS-4097-1967 with uptodate ammendments, if any arround intake of Tube-Well with minimum thickness of shroud around screen generally 100mm. to the entire depth of the bore as per IS-2800(Part-I):1991 with uptodate ammendments, if any, complete in all respect.
Development of Tube-Well by backwashing method with Air Compressor of minimum 750CFM capacity Pumping pipe of 200mm. Size and Air line of minimum 65mm size or with other suitable method, till the Well is thoroughly developed as per Clause-4.2 of IS-11189:1985, with upto date ammendments, if any; complete in all respect.
Development of Tube-Well by continuous over Pumping method with V.T.Pumps/Submersible Pumps of suitable capacity not less than double the discharge established by the Compressor method/design discharge, untill the well sand free as per IS-11189:1985 with uptodate ammendments, if any; complete in all respect as per the directions of the Engineer-in-Charge. The draw-down and discharge to be established by running the VT/Submersible pump continuously for 8 Hours in the presence of the officer not less than the rank of the Assistant Engineer.
Testing the vertcality of the Tube-Well as per Clause-4.3 of IS-2800(Part-II)-1979 with uptodate ammendments, if any, using plumb or plunger 6mm.smaller in dia within the inside diameter of the Well casing. The result of the verticality test shll be recorded on proforma shown in Appendix-A of IS:2800(Part-II)-1979 with uptodate ammendments, if any.
Dismentalling of Rig or other allied, accessories after completion of job complete in all respect.
Design and Construction of Pump House cum Chowkidar quarter having 63.00 Sqmt Plinth area and 3.30 Mtrs. height complete in all respect. The pump house shall be aesthetically designed (to be approved by the competent authority). The work shall include all internal and external electrical wiring, water supply and sanitary fitting, painting and distempering, precast terrazo tile flooring, wooden frames and panelled & glazed shutter for doors & window and other allied items. The doors & window shall be in double shutters and M.S grills for window and internal wiring shall be in PVC conduit. All work shall be conforming to relevent IS code and to the entire satisfaction of Engineer-in- Charge. (For detailed specification refer as per chapter No. 1 & data sheet No. 3.)
C/o Pump house (For Phase-1st)
C/o Pump house (For Phase-4th)
Designing, Constructing, Testing & Commissioning of Trench weir at source for tapping water from Banner Khad consisting of including all allied Civil Works, Site development, cutting/excavation in all kinds of soils, C/o PCC/RCC Retaining walls, Breast walls, crate work, dewatering etc complete as directed by engineer in charge to provide silt free water as per ultimate requirement. The rates quoted by the contractor shall be for the complete work. All ancilliary works and accessories required to make the intake system fully functional shall be included in the cost of work. Nothing extra shall be paid on this account within all leads & lifts. (For detailed specification refer as per chapter No. 1 & data sheet No. 1.1.)
Design, construction, testing and commissioning of 0.88 MLD Water purification Treatment Plant in shape of rapid sand filters at village Kaisthwari including cost of site development to adjust hydraulic levels as per contour plan and structural requirement cost of construction of civil works, hoisting and errection of all steel works, installation of mechanical, electrical accessories equipment/ machinery, laying of all interconnecting G.I./ MSERW pipe and scouring arrangement from all units with disposal of the same to appropriate place i.e. near by Nallah/ Khad/ Natrual drainage, valve,fitting and all other contingent works at village Kaisthwari capable of taking input and giving output as laid down in chapter-I of CPHEEO manual underl all climatic conditions specified therein. The treatment plant includes construction of RCC Mix M-30 of inlet chamber, Raw Water Tank , clear Water Tank, Pre-sedimentation tank, tappered floculator, flush Mixing, secondary settling tank, Parshal flume, Rapid sand filter beds and pipe gallery, wash lime solution tank, Alum solution tank and Dozer kuhl inter connecting path, (1.20 metre wide) Chamical house chemicals handling and feeding arrangement, Auto geseous chlorination unit, backwash unit with pumping set and Air compressor including arrangement for disposal of waste from water treatment process, plant building compring office, C/o Pump house, C/o Boundary wall, P/F lightening arrangement(sodium vapour lamps 150 watt) made in the boundary unit in the plant area, C/o PCC Retaining walls, P/F electoral mechanical equipment, proper walk way for inspection/operation of various units. Providing and setup of all laboratory equipment and sizes shall be based on manual of water supply and treatment published by CPHEEO, Ministry of Urban development, Govt of india new Delhi. The design of various units shall confirm to the relevant BIS codes. All the hydraulic structure shall be designed and constructed in RCC M-30 design shall be carried out as per design shall be carried out as per design parametre included in the No.3.1. (For detailed specification refer as per chapter No. 1 & data sheet No. 1.)
All structure shall be designed for up lift pressure and encounted at footing as per contour plan up loaded suitable protection structure shall be designed and provide to avoid direct entry of HFL water with treatment premises. The scope of work shall be as per common design parameters technical specification and special condition appended in the DNIT. This further includes combination of various treatment units based on flow diagram given in the above manual for consideration of alternative proposals or any other low cost treatment methods based on existing plants working under similar conditions with necessary performance certifications. The firm should quote its rates for its offered proposal with cogent reason/justification for adopting the particular method of treatment of water and design of relevant units which should be based in recommendations of latest relevant codes/manuals on water supply and treatment published by CPHEEO, Ministry of Urban Development, Govt of india, New Delhi.
Designing, Constructing, Testing & Commissioning R.C.C. Circular partially underground/Elevated storage tanks as per capacity given below at various stages/sites including excavation in all kinds and types of strata, soil strata including dewatering in M30 design mix in foundation, walls, bottom slab , roof slab/dome with smooth finishing in 1:3 inside the tank, all alied Civil Works, Site development, cutting/excavation in all kinds of soils, C/o PCC/RCC Retaining walls, Breast walls, refilling and disposing of surplus stuff with in all leads and lifts, labour and material charges. The job also includes providing lowering, laying, erecting, hoisting and jointing of pipe assembly for inlet, outlet, overflow and scour pipe ,proper manifiold at outlet including all fittings, bye pass arrangement consisting of GI / MS pipes special and valves of required classes and dia and all other accessories required such as MS ladders inside and outside ventilator with mosquito proof wire mesh,lightening arrester complete ,SFRC manhole covers including frames and covers (medium duty) with proper locking arrangement water level indicator, RCC frames for all valves ventilating shafts shall also be provided including all leads and lifts as per entire satisfaction of Engineer-in-Charge. The tanks shall be hydraulically tested for water tightness all works shall be conforming to relevant IS code. The cost of valves & other accessories shall be included in the rates of tanks . Battery Limit shall be considered as 3.00 m from the edge of the structure or the boundary of the land whichever is less.The rates quoted by the contractor shall be for the complete work. All ancilliary works and accessories required to make the system fully functional shall be included in the cost of work. Nothing extra shall be paid on this account.The work shall include supplying of Five sets of structural design after testing the bearing capcity of soil and drawings, etc complete as directed by engineer in charge as per relevent data sheet and scope of work. (For detailed specification refer as per chapter No. 1 & data sheet No. 2.)
C/O MBR 50,000 Ltrs Capcity @ 15 mtr staging (Village Hatwas)
C/O MBR 1,20,000 Ltrs Capcity @ 10 mtr staging (Village Jassour)
C/O Underground MBR 3,70,000 Ltrs Capcity (Village Bharobar)
C/O SR 50,000 Ltrs Capcity @ 15 mtr staging
C/O SR 20,000 Ltrs Capcity @ 15 mtr staging
C/O SR 30,000 Ltrs Capcity @ 10 mtr staging
C/O Underground Collection tank 3,40,000 Ltrs Capcity
C/O Underground MBR 3,40,000 Ltrs Capcity
For Phase-1st (WSS Ghorab, Bhunehar, Hatwas) Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 235.56
Discharge required from each pump. = 2.34 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from T/Well
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Static head in Mrs = 200.00 mtrs.
Length of R/Main = 1515 mtrs.
Dia of Rising main = 65 mm (M)
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system (1 No.)
SMPS 4.5 Amps to energise PLC system (1 No.)
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon. (1 No.)
Control MCB for Automation System (1 No.)
Level Sensor to indicate the water level of tank remotely (1 No.)
Shielded Data Cable for Communication of Level Sensor with PLC (1 No.)
Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/ Rockwell Automation. (1 No.)
Cloud GateWay for Data Clouding to Server (1 No.)
SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/ Backoff Automation (1 No.)
Cloud Space for data storage at cloud/server (1 No.)
Installation, Commissioning and Software Development (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For Phase-2nd & 3rd (WSS Sadarpur, Thanpuri, Rajiana,Kalaid & WSS Upperli Kothian and Sunhi Satori ) Stage - 1st Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 26.92
Discharge required from each pump. = 30.40 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from T/Well
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of Tube Well = 90 mtrs
Static head in Mrs = 22.00 mtrs.
Length of R/Main = 160 mtrs.
Dia of Rising main = 200 mm MSERW
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For Phase-2nd (WSS Sadarpur, Thanpuri, Rajiana,Kalaid ) Stage - 2nd Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. (For detailed specification refer as per chapter No. 3 & data sheet No. 5.) The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 262.01
Discharge required from each pump. = 6.97 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from WTP
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Static head in Mrs = 202.00 mtrs.
Length of R/Main = 3400 mtrs.
Dia of Rising main = 100 mm G.I (M)
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system (1 No.)
SMPS 4.5 Amps to energise PLC system (1 No.)
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon. (1 No.)
Control MCB for Automation System (1 No.)
Level Sensor to indicate the water level of tank remotely (1 No.)
Shielded Data Cable for Communication of Level Sensor with PLC (1 No.)
Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/ Rockwell Automation. (1 No.)
Cloud GateWay for Data Clouding to Server (1 No.)
SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/ Backoff Automation (1 No.)
Cloud Space for data storage at cloud/server (1 No.)
Installation, Commissioning and Software Development (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For Phase- 3rd (WSS Upperli Kothian and Sunhi Satori ) Stage - 2nd Supply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. (For detailed specification refer as per chapter No. 3 & data sheet No. 5.) The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 223.94
Discharge required from each pump. = 22.24 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from WTP
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Static head in Mrs = 202.00 mtrs.
Length of R/Main = 5250 mtrs.
Dia of Rising main = 200 mm MSREW
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge. (1 Nos Job)
For Phase-4th (WSS Jandrah ) Stage - 1st Supply of submersible pumping set of (KSB / Kalama/ Kirloskar/ Johnston/ Cromption/ BS) make conforming to BIS; 8034-1976 latest suitable for lifting clear water (latest with uptodate ammendments) fitted with bronze impellers/ suitable alloy directly coupled to squirrell case electric induction motor of same make as (manufacurer standard) conforming to BIS; 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearings & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard,errection clamps,cable clips & depth gauge etc. The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 27.38
Discharge required from each pump. = 16.57LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from P/Well
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Depth of P/ Well = 8 mtrs
Static head in Mrs = 23.00 mtrs.
Length of R/Main = 90 mtrs.
Dia of Rising main = 150 mm MSERW
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-150 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-150 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
For Phase-4th (WSS Jandrah ) Stage - 2ndSupply of horizontal spindle,horizontal/radial split casing and suction (backpull out arrangement) single/ double / multistage centrifugal pumps or combination of pumps in series /parallel of KSB / Mather & Platt/ Jyoti /Kirloskar /BE /Maxflow/ Beaconweir Sabar make conforming to BIS: 1520-1980 (latestwith upto date ammendments) read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned charactristics with impellers of bronze/suitable alloy, priming funnels,casing ring & shaft sleeves of bronze/ suitable alloy, shaft of sutable steel grade with cast iron casing coupled directly through a flexible coupling on a common C.I. / Cast steel base plate (base plate to be from the principle manufacturer of pumping set) to slippering/squirrel cage screen protected drip proof electric induction motor of Kirlokar /NGEF/Crompton / Siemen /Jyoti /BHEL /GEC /ABB conforming to BIS: 325-1978 read read with BIS: 900-1968 (latest with upto date ammendments) It should include the cost of bearings, nuts & bolts,painting etc. (For detailed specification refer as per chapter No. 3 & data sheet No. 5.) The pump shall be suitable for operation on data given below:- (For detailed specification refer as per chapter No. 3 & data sheet No. 5.)
Total Head = 366.09
Discharge required from each pump. = 16.57 LPS
No. of pump required = 2.00 Nos. One act as stand by
Location of the site of installation of machinery. = The site is located at a distance of 20 Kmts from Palampur
The Altitude of installation. = The altitude of place is 955.00 mtrs above MSL
Type of current. = AC Three phase supply with
Rate Voltage = 400± 10%
Type of water and its source = Clear water from Collection Tank
Charactristics of water. = -
a) Ambient Temperature dig.c = 20° C
b) Turbidity NTU = 2 NTU (<50PPM)
c) Hardness260Mg/Ltrs(as CaCO3) = -
d) pH Value = 6.5 - 8.5
e) total solid Mg /Ltrs = -
f) Other = Depth of water during HFL in Pond 12 m (Max. Draw Down 6m)
Static head in Mrs = 299.50 mtrs.
Length of R/Main = 5500 mtrs.
Dia of Rising main = 150 mm MSERW
No of working hours per day = 8 Hours
Limit of pump operation. = (-) 15 % (+) 10% of total head
R.P.M. of pumping set. = 2900 RPM ( or to be specified by the tenderer)
Test run. = 16 Hours continueously for 7 days
Supply , Installation, Testing and Commissioning of Fully Automatic LT Panel for pump made out of 16 Gauge sheet powder coated dust and veremin proof wall mounted and front opering door type switch board with copper insulated wiring suitable to operate 1 nos. pump of rating required HP automatically through Variable Frequency Drive Starter. Starter should be capable to handle all the faults like short circuit, over current, under current, over voltage, under voltage, dry pump protection. It should get on and off command automatically from PLC and HMI. Monitoring and controlling of Pump running and tripping status should be monitored and controlled remotely through IOT enabled device. Access should be given to 3 users. Make: Aarmation Electric Private Limited/MAS/ELLES
Variable frequency drive starter of required HP Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to control the frequecy of pumps through out the operation and also should be capable to maintain the power factor of the system within acceptable limits. It should have ambient temperature 50 Degree without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: Aarmation Electric Private Limited/MAS/ELLES (1 No.)
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc with RS 485 communication Make L&T/Conserve/Siemens (1 No.)
Main incomer MCCB suitable capacity of L&T / Standard make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition) with neutral linked under voltage release. (1 No.)
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments. (1 Set)
LED On / Off indicator and push button, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Buss Bar, i.e.Bolt, insulator, etc. (1 Set)
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions. (2 Nos.)
Control Transformer to safegaurd the control circuit of all the components from the voltage surges and spikes. (1 No.)
Power and Control wiring and Busbar (1 No.)
Installation, Commissioning and Software Development (1 No.)
Surge suppressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges. (1 No.)
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements (1 No.)
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KitKat fuses of HPSEB Make: Aarmation/Siemens/Schneider/L&T (1 No.)
Programmable logic controller with appropriate digital and analog inputs and outputs to give automatic command to star delta and also will get data from Multi function Meter for Current, Voltage, KWH, PF and THD. Make Mitsubishi/L&T/Delta
Electronic relay card 8 channel for PLC system (1 No.)
SMPS 4.5 Amps to energise PLC system (1 No.)
HMI 7" display with IOT to give on and off command manually and also to show pump running and breakdown status at pump station Make Wientek/Exor/Mitsubishi/Mecon. (1 No.)
Control MCB for Automation System (1 No.)
Level Sensor to indicate the water level of tank remotely (1 No.)
Shielded Data Cable for Communication of Level Sensor with PLC (1 No.)
Supply of Mobile App (Android/IOS) with User ID and Password to monitor and control the pumping operation from Mobile for 3 users. Make: Aarmation Electric/Bechoff Automation/ Rockwell Automation. (1 No.)
Cloud GateWay for Data Clouding to Server (1 No.)
SCADA software to be installed in Laptop/PC to remotely monitor and control the operation of pumps and also to analysis the pump start and stop history logging, fault status, fault history, Power Quality Parameters like PF, Current, Voltage, KWH, THD etc Make Aarmation Electric/Rockwell Automation/ Backoff Automation (1 No.)
Cloud Space for data storage at cloud/server (1 No.)
Installation, Commissioning and Software Development (1 No.)
Providing & Fixing of Kirloskar/Kilburn /IVC/Fouress/Gled/BHEL/ Leader make Cast steel double flanged sluice valve of Class ASA-300 confirming to BIS-1414 (API-600) (to be provided on delivery side) of equal size to one dia more than the dia of delivery of pump and capable of with standing nominal seat test pressure of 21 kg/cm².
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of Class ASA-300 confirming to BS 1868 (API-600) (latest edition) to be provided on delivery side) of size one step higher than the delivery size of pump and shall be suitable for withstanding nominal seat pressure of 21kg/cm².
Providing & laying PVC insulated jointless, flat water proof copper cable of Siemens/ Finolex/ Grandlay/ Gloster make conforming to BIS:1554 (Part I) -1988 or latest with up to date ammendments of suitable size for the pump sets offered(one cable carrying all three phases) including all other electrical equipment /accessories such as thimbles ,flexible pipe, solder, nuts & bolts cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
On supply side of 3½ core coper cable 10.00 mm^2 ( From HPSEB Meter to Switch & Starter).
On motor side 3 core flat joint less copper cable of size 4.00 mm^2 ( From Switch & Starter to Motor) pump installed in the bore.
Providing and Laying column aseembly of G.I./MSERW pipe considering site requirements and having appropriate size in accordance with the delivery size of pumping set . The pipe shall conform to relevant BIS codes & capable of with standing the feild test pressure equal to 1.5 times the operating pressure including all type of fittings such as bends, tapers/ reducers, flanges, rubber gaskets 3mmthick, nuts & bolts and any other fitting required at site and work shall be to the entire satisfaction of Engineer-in-Charge. The pipe material shall conform to relevant BIS Code and capable of with standing FTP equal to 1.5 times the operating pressure the complete arrangement shall compromise of
Suction Pipe = 125 mm dia
Delivery pipe = 100 mm dia
NOTE:- Actual laying to be done as per final drawings to be approved by the Engineer in charge Errection of all equipments of Pumping Machinery including cost of tees, bends, tapers & any other fittings required as per site conditions & as per directions of Engineer-in-Charge.
Excavation in foundation trenches etc. (in pipes and pits) in all kinds of soil such as pick work, jumper work, blasting work soft /hard rock, chiesling soft /hard rock where blasting is prohibited, slushy, daldal and saturated soil I/c pumping or bailling out water with in all heights stacking the excavated soil with 15cm layer when required into plinth ,sides of foundations etc. consolidating each deposited layer by ramming and watering and then disposing of all surplus earth as per direction of Engineer-in-Charge with in all leads and lifts .
Providing, laying, jointing & testing of bevelled ended GI pipe Medium Class with MS Flange of following Table (6%) flange joint & other Pipe (94%) circumfrential butt welded joints by electrical arc welding (welding thickness shall be equal to pipe wall thickness) and testing of GI pipe of following dia meters conforming to IS 1239-2004 (Part-II), having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers , all short pieces, bends etc. as per site requirement made from parent tubes. The laying of pipe shall include all operations such as cutting, welding, jointing, fabrication of bends, tees, making bevelled pipe ends suitable for butt welding , lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (Earth work in trenches and cost of providing flanges i/c nuts & bolts, welding of flanges, gasket will be measured and paid for separately) . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes ( If damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (For detailed specification refer as per chapter No. 2 & data sheet No. 4)
65 mm dia (For Phase-1st WSS Ghorab, Bhunehar, Hatwas)
100 mm dia (For Phase-2nd WTP to MBR Jassour)
Providing,laying, jointing & testing of bevelled ended MSERW pipe (Zinc Coated) 4.80mm thick with MS Flange (6%) and other pipe (94%) with circumfrential butt welded joints by electrical arc welding ( welding thickness shall be equal to pipe wall thickness) and testing of pipe of Jindal /Surya Roshni / Tata/AST make of following dia meters conforming to IS/ISO 3183:2007 with steel grade L-290 or X-42, having wall thickness as specified below capable of withstanding required test pressure, including manufacturing and febrication of reducers/ tapers , all short pieces, bends etc. as per site requirement made from parent tubes . The laying of pipe shall include all operations such as cutting, welding, jointing, fabrication of bends, tees, making bevelled pipe ends suitable for butt welding , lowering & laying in excavated trenches to ensure required level complete in all respects to the best satisfaction of the Engineer-in-charge (Earth work in trenches and the cost of providing and welding flanges i/c nut & bolts, gasket will be measured and paid for separately) . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The damaged portion of the pipes ( If damaged during laying & jointing operation of pipe) and all other specials made from the parent tube shall be provided with anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing of pipes, D.P. test of butt welded joints complete in all respect and to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (For detailed specification refer as per chapter No. 2 & data sheet No. 4)
200 mm dia (For Phase-2nd & 3rd Trench weir to WTP)
200 mm dia (For Phase-3rd WTP to MBR Kothian)
150 mm dia (For Phase-4th P/well to MBR)
Providing & Fixing of Kirloskar/ Kilburn/IVC/Fouress /Gled/BHEL/Leader make Cast steel double flanged swing check type reflux valve having bypass arrangement of class ASA-300 confirming to BS 1868 (API-600) (latest edition) and shall be suitable for with standing nominal seat pressure of 52 kg/cm² complete in all respect as per the direction and to be entire of Engineer-in-Charge within all leads and lifts.
200 mm dia (For Phase-2nd & 3rd )
150 mm dia (For Phase-4th)
100 mm dia (For Phase-1st)
65 mm dia (For Phase-1st)
Providing , laying, jointing & testing of screw and socket Galvanised Mild steel tube medium class of approved make of Jindal/Surya/Roshni/Tata including all tube fitting are required as per actual site within all leads and lifts including cost of G.I fitting & Valve as per the direction of Engineer-in Charge. (Cost of excavation with be measured and paid separately.) (For detailed specification refer as per chapter No. 2 & data sheet No. 4)
65 mm dia (For Phase-1st)
80 mm dia (For Phase-1st)
65 mm dia (For Phase-2nd)
80 mm dia (For Phase-2nd)
65 mm dia (For Phase-3rd)
80 mm dia (For Phase-4th)
Providing and welding of MS flanges (In pairs) for the joints of GI / MSERW pipes mentioned as below and same shall conform to BIS 6392-1971 ( latest with up to date amendments) including the cost of nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets conforming to relevant BIS standards and it shall also include carriage of materials within all leads and lifts complete in all respect to the best satisfaction and direction of Engineer in charge, The welding of MS flanges with plain ended MSERW/G.I. pipe by two layer or outer face make joint leak proof.
65 mm dia MS Flange of Table - 5 (For Phase-1st)
65 mm dia MS Flange of Table - 17 (For Phase-1st)
65 mm dia MS Flange of Table - 28 (For Phase-1st)
100 mm dia MS Flange of Table - 17 (For Phase-2nd)
100 mm dia MS Flange of Table - 28 (For Phase-2nd)
200 mm dia MS Flange of Table - 5 (For Phase-3rd)
200 mm dia MS Flange of Table - 11 (For Phase-3rd)
200 mm dia MS Flange of Table - 17 (For Phase-3rd)
200 mm dia MS Flange of Table - 23 (For Phase-3rd)
150 mm dia MS Flange of Table - 5 (For Phase-4th)
150 mm dia MS Flange of Table - 17 (For Phase-4th)
150 mm dia MS Flange of Table - 28 (For Phase-4th)
Unipro Techno Infrastructure Pvt Ltd
HARJEET SINGH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid