MANAGING DIRECTOR
KSDPLTD,KALAVOOR P.O,ALAPPZUH
SUPPLY INSTALLATION TESTING COMMISSIONING AND VALIDATION OF HVAC WORKS AS PER GMP STANDARD FOR NON BETA LACTUM PROJECT
2021_ksdp_453788_2
KSDP/PRJ/NB/HVAC/10/21-22/124
Open Tender
Miscellaneous Works
Supply and Service
90 days
KSDPLTD, KALAVOOR P.O, ALAPPZUHA
as per tender document
12 documents required · 12 mandatory
₹2,950
₹50,000
6 Apr 2022
16 Dec 2021
27 Dec 2021
16 Dec 2021
24 Dec 2021
16 Dec 2021
16 Dec 2021 - 24 Dec 2021
AIR HANDLING UNITS - (ISO - 7)
Commissioning of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, cooling coil section with 6 row deep chilled water cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirrel case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet. Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and Bypass damper for excess air. Service doors wherever applicable. provision Differential pressure gauge across 10,3micron filters. AHU is assembled and positioned. Missing items if any required for commissioning and validation should be considered in quote
AHU - 01 : 3000 CFM @ 125 MM WC static pressure (DISPENSING)
AHU - 02 : 3000 CFM @ 125 MM WC static pressure (SAMPLING)
AIR HANDLING UNITS - (ISO - 8)
commissioning Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, cooling coil section with 6 row deep chilled water cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirrel case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet. Inspection window, limit switch, light, Fine Filter section with 3micron filter in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and bypass damper for excess air. Service doors wherever applicable. provision Differential pressure gauge across 10,3 micron filters. AHU is assembled and positioned. Missing items if any required for commissioning and validation should be considered in quote
AHU - 03 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-1)
AHU - 04 : 4000 CFM @ 100 MM WC static pressure (LIQUID MFG-1)
AHU - 05 : 4800 CFM @ 100 MM WC static pressure (LIQUID MFG -2)
AHU - 06 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-2)
AHU - 08 : 13500 CFM @ 100 MM WC static pressure (RM STORE UNDER TEST)
AHU - 12 : 4500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 13 : 5500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 14 : 7500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 15 : 2600 CFM @ 100 MM WC static pressure (CAPSULE FILLING)
AHU - 16 : 2000 CFM @ 100 MM WC static pressure (CAPSULE MFG.)
AHU - 17 : 3500 CFM @ 100 MM WC static pressure (PASSAGE)
AHU - 18 : 2000 CFM @ 100 MM WC static pressure (DISPENSED MATERIAL & EHGC)
AHU - 19 : 7500 CFM @ 100 MM WC static pressure (GRANULATION-1)
AHU - 21 : 3000 CFM @ 100 MM WC static pressure (DISPENSED RM DAY STORE)
AHU - 22 : 5500 CFM @ 100 MM WC static pressure (INSPECTION)
AHU - 23 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR-1)
AHU - 24 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR.-2)
AHU - 25 : 4700 CFM @ 100 MM WC static pressure (COMPRESSION-1)
AHU - 26 : 4600 CFM @ 100 MM WC static pressure (COMPRESIION-2)
AHU - 27 : 5800 CFM @ 100 MM WC static pressure (COMPRESSION-3)
AHU - 28 : 4000 CFM @ 100 MM WC static pressure (AUTO COATER)
AHU : 5500 CFM @ 100 MM WC static pressure (ORS Area)
AHU: 7500 CFM @ 100 MM WC static pressure (RM Store)
AIR HANDLING UNITS DX-TYPE - (ISO - 8)
commissioning of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, DX cooling coil section with 6 row deep DX cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirrel case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet. Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and Bypass damper for excess air. Service doors wherever applicable. provision Differential pressure gauge across 10,3 filters.AHU is assembled and positioned. Missing items if any required for commissioning and validation should be considered in quote
Dx AHU - 01 : 1000 CFM @ 100 MM WC static pressure (QUARANTINE)
Dx AHU - 02 : 1500 CFM @ 100 MM WC static pressure (CAPSULE QUARANTINE)
Dx AHU - 03 : 1000 CFM @ 100 MM WC static pressure (TABLET QUARANTINE)
Dx AHU - 05 : 2000 CFM @ 100 MM WC static pressure (TABLET QUARANTINE)
CONDENSING UNIT
commissioning of Air cooled condensing units with scroll compressor , condenser coil , fan all housed in weather proof casing. The unit shall be complete with LP/ HP controls with cabling and control cabling for the condensing units
5.5 TR FOR DX
5.5 TR FOR DX
MANIFOLD
Supply ,filling and commissioning OF ECO FRIENDLY GAS
Refrigent Gas
AIR HANDLING UNITS DX-TYPE - (ISO - 8)
commissioning of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, DX cooling coil section with 6 row deep DX cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirrel case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet.Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air and Bypass damper for excess air. Service doors wherever applicable. provision Differential pressure gauge across 10,3 filters. Replacement of cooling coil. AHU is assembled and positioned. Missing items if any should be considered in quote
Dx AHU - 04 : 1200 CFM @ 100 MM WC static pressure (QUARANTINE)
AIR HANDLING UNITS - (3 MICRON)
commissioning of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 43 mm thick Puff insulation panel, with G4 fresh air filter, Prefilter section with G4 filters, cooling coil section with 6 row deep chilled water cooling coil , insulated SS 304 drain Pan,blower section with backward curve DIDW centrifugal fan along with KRUGER /NICOTRA make TEFC squirrel case induction motor (IE- 2) with IP 55 protection with base frame, Drive set consisting of taper lock pulleys & V-belts and complete with anti vibration mounts, Double skin rexin flexible connection for fan outlet. Inspection window, limit switch, light, Fine Filter section with 3micron filters in supply air discharge section. GI damper for Supply, Return, fresh & exhaust air. Service doors wherever applicable. provision Differential pressure gauge across 10,3 micron filters. Missing items if any should be considered in quote
AHU - 07 : 1500 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 09 : 1000 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 10 : 2000 CFM @ 75 MM WC static pressure (1.8 M WIDE PASSAGE)
AHU - 11 : 5500 CFM @ 75 MM WC static pressure (PACKING AREA)
VENTILATION UNITS
commissioning of Air Handling units with double skin construction fabricated from Al extruded section frame structure with internal coving and in non Thermal break construction, the inner skin 0.6MM thick Plain G.I & outer skin 0.6mm thick precoated GI construction with 25 mm thick puff insulation panel, consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW forward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inspection window, limit switch, bulk head lamp, fine filter section suitable for fixing 5 micron filters, Fresh air Louver at inlet, Inlet and outlet connections complete with service doors. Missing items if any should be considered in quote
VENT - 01(SUPPLY+RETURN): 8000 CFM @ 60 MM WC static pressure(CHANGE ROOM)
EXHAUST UNIT
commissioning on Single Skin type Exhaust Unit (EAU) made out of 18G GI powder coated consisting of Pre filter section for fixing 10micron filter, Fan section with DIDW forward curved Belt driven centrifugal fan (Kruger/Nicotra) driven by suitable NON Flame proof TEFC squirrel cage induction motor (CG/ABB/Kirloskar) with drive set consisting of Taper lock pulleys and V-Belts and complete with anti vibration mounts, Inlet and outlet connections complete with service doors. Missing items if any should be considered in quote
EXUT - 03 : 1000 CFM @ 40 MM WC static pressure(SUPPLY+ RETURN)
Dehumidifier
commissioning of Silica gel type dehumidifiers including heaters in regeneration air flow (without steam coil) required for achieving the RH conditions as specified & complete with Humidistat for auto operation and electrical panel with all controls, starters and accessories Missing items if any should be considered in quote.. (this should be done through OEM BRYAIR)
AHU - 12 : (TEMP-24 ± 2 , RH-50±5) (BLISTER)
AHU - 13 : (TEMP-22 ± 2 , RH-45±5) (BLISTER)
AHU - 14 : (TEMP-20 ± 2 , RH-40±5) (BLISTER)
AHU - 15 : (TEMP-22 ± 2 , RH-40±5) (CAPSULE FILLING)
AHU - 16 : (TEMP-22 ± 2 , RH-40±5) (CAPSULE MFG.)
AHU - 22 : (TEMP-24 ± 2 , RH-45±5) (INSPECTION)
AHU - 26 : (TEMP-24 ± 2 , RH-45±5) (COMPRESSION - 2)
AHU - 27 : ( TEMP-22 ± 2 , RH-40±5) (COMPRESSION - 3)
Positioning, commissioning of Silica gel type dehumidifiers including heaters in regeneration air flow (without steam coil) required for achieving the RH conditions as specified & complete with Humidistat for auto operation and electrical panel with all controls, starters and accessories Missing items if any should be considered in quote
AHU 2 5000 CFM (ORS Area)
interconnecting duct work between AHU , PCU , AND DEHUMIDIFIER
PRECOOLING UNIT - ( TREATED FRESH AIR - TFA )
commissioning of Double skin precooling Unit with 43 mm thick panel thermal break profile with 0.6mm precoated sheet outer side and 0.6mm thick plane sheet inside,compleat with 8 row deep cooling coil ,with G-4 filter at inlet and volume control damper at the out let Missing items if any should be considered in quote
AHU - 12,13,14,15,16,22,26,27 : 500 CFM
AHU 2 500 CFM (ORS)
Supply ,installation and commissioning - DUCTING (Make: Jindal)
Factory fabricated /Site fabricated GI sheet metal ducting in L section as per IS 635 standards with class VIII sheet MS duct frames,supports,suspended rods with complete paint with Silicon sealant for duct joints. ( Approximate Quantity )
24 G GI Sheet
22 G GI Sheet
20 G GI Sheet
18 G GI Sheet
Supply ,installation and commissioning - DUCT INSULATION
Duct insulation chemically Cross linked close cell Polyethyelve CLASS 1 insulation with metallic foil with tape and addicive. ( Approximate Quantity )
19 mm thick for supply air duct
13 mm thick for return air duct
Supply ,installation and commissioning - TERMINAL HEPA MODULE (ISO -7) AREA
Supply ,installation and commissioning False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes
610 x 610 x 115 mm (direct or L type)
457 X 457 X 115 mm (direct or L type
Supply ,installation and commissioning latest and advanced technology HEPA filters having efficiency of 99.99 down to 0.3 micron
Supply ,installation and commissioning SS 304 Perforated grill for the following HEPA Filters sizes
Supply ,installation and commissioning TERMINAL HEPA MODULE (ISO -8) AREA
Supply ,installation and commissioning False Ceiling type HEPA Filter housing with gear operated damper from room side, DOP port, pressure sensing port suitable for fixing gel seal type HEPA Filters of following sizes
610 x 305 x 115 mm (direct or L type )
305 x 305 x 115 mm (direct or L type )
Supply ,installation and commissioning latest and advanced technology GEL Seal HEPA filters having efficiency of 99.97 down to 0.3 micron.(during validation if replacement required)
610 x 610 x 150 mm (direct or L type )
305 x 305 x 150 mm (direct or L type )
457 X 457 X 115 mm (direct or L type )
610 x 610 x 115 mm (direct or L type )
610 x 305 x 115 mm (direct or L type )
305 x 305 x 115 mm (direct or L type )
Supply ,installation and commissioning SS 304 Perforated grill for the following HEPA Filters sizes
610 x 610 x 150 mm (direct or L type )
305 x 305 x 150 mm (direct or L type )
610 x 305 x 115 mm (direct or L type )
457 X 457 X 115 mm (direct or L type )
610 x 305 x 115 mm (direct or L type )
305 x 305 x 115 mm (direct or L type )
SUPPLY AND ERECTION - SUPPLY & RETURN AIR GRILL / DIFFUSER ( 3 MICRON & VENTILATION AREAS)
Supply ,installation and commissioning - Slab / false ceiling Grill module made out of 18G GI with powder coated finish suitable to fix collar damper and AL perforated grill
AL linear bar grill with VCD suitable to fix in Grill modules
Supply ,installation and commissioning GRILL MODULE FOR RETURN
Supply ,installation and commissioning of slab / false ceiling Grill module made out of 18G GI with powder coated finish with collar damper and suitable for AL perforated grill and 10 micron filter
RAGM1 (665 X 665 mm )
RAGM2 (512 X 512 mm )
RAGM3 (360 X 360 mm )
Supply ,installation and commissioning - 10 micron filter
Supply ,installation and commissioning - SS perforated grill for the above grill module.
Supply ,installation and commissioning - RISERS GRILL
Grill module made out of 18G GI with powder coated finish suitable to fix collar damper and grill.
SS 304 perforated grill suitable to fix in the panel riser
GI powder coated coller damper to be fixed inside the partition raiser
EU-4 filter washable filter for return air raiser (10 micron)
Supply ,installation and commissioning - DAMPERS
AL low leakage volume control damper suitable for supply and return ducts
18 G GI fire dampers with Fusible Link type for fire rating of 90 minutes
Supply ,installation and commissioning - LOUVERS FOR SERVICE AREA
Exhaust Air Louvers: Supply & Installation of Exhaust air intake louvers made from 3" wide (Minimum 3 MM thk) powder coated extruded aluminium @ 1" pitch with proper stiffeners complete with 20 micron filter and HDPE insect mesh fixed in a removable frame as per approved design
Supply ,installation and commissioning of cabinet type inline exhaust fans with 20 micron filter for service area
Service Floor : 2000 cfm @ 40 mmstpr
Second Floor : 2000 cfm @ 40 mmstpr
First Floor : 2000 cfm @ 40 mmstpr
Supply ,installation and commissioning- Differential Pressure Gauges
Differential pressure gauges for rooms with 18G GI powder coated box with 18G SS 304 flush cover, nozzles and tubing. ( Range - 0-10mm wc )
Differential Pressure gauges for AHUs and ventilation across the pre / fine / semi HEPA filter ( Range 0-100mm wc )
CHILLED WATER MANIFOLD FOR AHUs
commissioning of Chilled Water Manifold size suitable to AHU includes 5 Nos. Butterfly / Ball Valves, 1 No. Balancing valve, 1 No. Y-strainer, 1 No. 3 Way modulating mixing Valve with thermostat (with interconnected wiring between thermostat & mixing valve), 2 Nos. dial type Pressure gauges, 2 Nos. temperature Gauges, 1 No drain valve with MS 'C' class 6 m pipe for interconnection with insulation. Missing items if any should be considered in quote
AHU - 03 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-1)
AHU - 04 : 4000 CFM @ 100 MM WC static pressure (LIQUID MFG-1)
AHU - 05 : 4800 CFM @ 100 MM WC static pressure (LIQUID MFG -2)
AHU - 06 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-2)
AHU - 08 : 13500 CFM @ 100 MM WC static pressure (RM STORE UNDER TEST)
AHU - 12 : 4500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 13 : 5500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 14 : 7500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 15 : 2600 CFM @ 100 MM WC static pressure (CAPSULE FILLING)
AHU - 16 : 2000 CFM @ 100 MM WC static pressure (CAPSULE MFG.)
AHU - 17 : 3500 CFM @ 100 MM WC static pressure (PASSAGE)
AHU - 18 : 2000 CFM @ 100 MM WC static pressure (DISPENSED MATERIAL & EHGC)
AHU - 19 : 7500 CFM @ 100 MM WC static pressure (GRANULATION-1)
AHU - 21 : 3000 CFM @ 100 MM WC static pressure (DISPENSED RM DAY STORE)
AHU - 22 : 5500 CFM @ 100 MM WC static pressure (INSPECTION)
AHU - 23 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR-1)
AHU - 24 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR.-2)
AHU - 25 : 4700 CFM @ 100 MM WC static pressure (COMPRESSION-1)
AHU - 26 : 4600 CFM @ 100 MM WC static pressure (COMPRESIION-2)
AHU - 27 : 5800 CFM @ 100 MM WC static pressure (COMPRESSION-3)
AHU - 28 : 4000 CFM @ 100 MM WC static pressure (AUTO COATER)
AHU 2 5000 CFM (ORS Area)
AHU 1 7500 CFM (RM Store)
AHU - 07 : 1500 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 09 : 1000 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 10 : 2000 CFM @ 75 MM WC static pressure (1.8 M WIDE PASSAGE)
AHU - 11 : 5500 CFM @ 75 MM WC static pressure (PACKING AREA)
commissioning of CHILLED WATER MANIFOLD FOR PRECOOLING UNIT ( TFA ) Missing items if any should be considered in quote
PCU - 25 MM
PCU - 20 MM
PCU 14,15,22 &26 - 40/50 MM
PCU 12,13 &16 - 32 MM
SUPPLY AND LAYING OF PVC drain piping with 9 mm nitrile rubber insulation for AHU'S drain
SUPPLY AND FABRICATION OF STEEL STRUCTURE
MS Supports for AHU s and Condensing units ,with chequered plate and ISMB beams
VRV SYSTEMS commissioning
OUTDOOR UNITS
Rectification of defects in VRV Outdoor unit ( including all materials/spares for rectification of defect)
commissioning of VRV system including top up of refrigerant GAS
Y Branch
Supply and installation of DRAIN PIPING
Rigid PVC piping complete with fittings, supports and duly insulated with 6 mm thick closed cell nitrile rubber insulation
ELECTRICAL PANEL FOR VRV SYSTEM
Rectification of defects in VRV Outdoor unit ( including all materials/spares for rectification of defect)
LEAK TEST. ANY LEAKE OBSERVED DURING TESTING SHOULD BE ARRESTED. (Supply and Return duct)
AHU - 03 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-1)
AHU - 04 : 4000 CFM @ 100 MM WC static pressure (LIQUID MFG-1)
AHU - 05 : 4800 CFM @ 100 MM WC static pressure (LIQUID MFG -2)
AHU - 06 : 1500 CFM @100 MM WC static pressure (FILL/SEAL-2)
AHU - 08 : 13500 CFM @ 100 MM WC static pressure (RM STORE UNDER TEST)
AHU - 12 : 4500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 13 : 5500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 14 : 7500 CFM @ 100 MM WC static pressure (BLISTER)
AHU - 15 : 2600 CFM @ 100 MM WC static pressure (CAPSULE FILLING)
AHU - 16 : 2000 CFM @ 100 MM WC static pressure (CAPSULE MFG.)
AHU - 17 : 3500 CFM @ 100 MM WC static pressure (PASSAGE)
AHU - 18 : 2000 CFM @ 100 MM WC static pressure (DISPENSED MATERIAL & EHGC)
AHU - 19 : 7500 CFM @ 100 MM WC static pressure (GRANULATION-1)
AHU - 21 : 3000 CFM @ 100 MM WC static pressure (DISPENSED RM DAY STORE)
AHU - 22 : 5500 CFM @ 100 MM WC static pressure (INSPECTION)
AHU - 23 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR-1)
AHU - 24 : 2000 CFM @ 100 MM WC static pressure (GRANULES QTR.-2)
AHU - 25 : 4700 CFM @ 100 MM WC static pressure (COMPRESSION-1)
AHU - 26 : 4600 CFM @ 100 MM WC static pressure (COMPRESIION-2)
AHU - 27 : 5800 CFM @ 100 MM WC static pressure (COMPRESSION-3)
AHU - 28 : 4000 CFM @ 100 MM WC static pressure (AUTO COATER)
AHU 2 5000 CFM (ORS Area)
AHU 1 7500 CFM (RM Store)
AHU - 07 : 1500 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 09 : 1000 CFM @ 75 MM WC static pressure (BOTTLE WASHING)
AHU - 10 : 2000 CFM @ 75 MM WC static pressure (1.8 M WIDE PASSAGE)
AHU - 11 : 5500 CFM @ 75 MM WC static pressure (PACKING AREA)
Dx AHU - 01 : 1000 CFM @ 100 MM WC static pressure (QUARANTINE)
Dx AHU - 02 : 1500 CFM @ 100 MM WC static pressure (CAPSULE QUARANTINE)
Dx AHU - 03 : 1000 CFM @ 100 MM WC static pressure (TABLET QUARANTINE)
Dx AHU - 04 : 1200 CFM @ 100 MM WC static pressure (QUARANTINE)
Dx AHU - 05 : 2000 CFM @ 100 MM WC static pressure (TABLET QUARANTINE)
Rectification of defects in electrical started panels of all AHUS/DEHUMIDIFIER including change of breaker ,change in cables from starter panel to AHU s /Dehumidifier
VALIDATION & DOCUMENTATION
DQ/OQ documents, Maintenance manual, Test certificate for equipment ( IQ format shall be provided by us but filling will be done later). 1) Smoke Test 2) Air balancing and velocity profile test 3) Pressure balancing test 4) Temperature & RH test 5) Filter integrity test 6) Air Flow Pattern
Blue Star Limited
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .