| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹36.2 LAccepted-Finance | ₹36.2 L | L1 | Accepted-Finance L1 Bidder |
| 2 | L2₹40.7 LRejected-Finance 306 THE LENORA OPP ST THOMAS SCHOOL NEW CITY LIGHT ROAD SURAT GUJARAT 395007 UDYAM GJ 22 0052777 24AABCE7473M1ZB R 24AABCE7473M1ZB M MSME STATUS AS VERIFIED | SURAT | GUJARAT | 395007 | ₹40.7 L | L2 | Rejected-Finance L2 Bidder |
| 3 | L3₹41.0 LRejected-Finance 121 GOLDEN PLAZA TAGORE ROAD RAJKOT RAJKOT GUJARAT 360002 UDYAM MH 26 0107568 09AAACU9454F1Z2 B 24AAACU9454F1ZA R 27AAACU9454F1Z4 M 10AAACU9454F1ZJ G MSME STATUS AS VERIFIED | RAJKOT | GUJARAT | 360002 | ₹41.0 L | L3 | Rejected-Finance L3 Bidder |
| 4 | Rejected-Technical | - | - | Rejected-Technical Not Qualified |
| 5 | Rejected-Technical | - | - | Rejected-Technical Not Qualified |
| Sl No | Description | Qty | Unit | ENPRO Enviro Tech and Engineers Pvt. Ltd. L2 | FLOW DYNAMICS INDIA L1 | Unicare Technologies pvt ltd L3 |
|---|---|---|---|---|---|---|
| 1.00 | Providing and Running Operation, Maintenance and Servicing of 100KLD MBBR Sewage Treatment Plant at IPR Campus, Bhat, Gandhinagar. The rate is inclusive of Plant Operators (1nos ), 24 X 7 (in Three Shifts) for Operations & maintenance, & Providing Superviser (1No), all materials, maintenance of plants parts, i.e. Pumps, Motors, blowers, belts, pipes, all electricals parts & equipments, oiling, Greasing, other equipments (if any), wiring, equipments Plumbing lines, primer & painting of MS structure pipes & tanks, cabling, valves, (Civil, Electrical, Plumbing works)etc, as required during operation for achieving specified parameters of treated sewage water. (All Spares and replacement of any defective part shall be included in the service contract including consumable & keeping near by area clean & Green.)
The treated water should conform to the following parameters:
(1) pH Value: 6.5-8.8, (2) BOD: <5 mg/ltr, (3) COD: <30 mg/ltr, (4) TSS : < 10 mg/ltr, (5) Oil & Grease: 10 mg/ Ltr, (6) Residual Chlorine: < 1-3 mg/ltr, (7) Fecal Coliform (MPN/100 ml): <100, (8) NH3-N: 5 mg/ltr, (9)Total Phosphorous: 2mg/ltr, (10) N-Total: < 10 mg/ltr, (11) E-Coli (MPN/100 ml): NDL
Note:- 1.The cost shall include all Chemicals , Plant parts as per need & in required quantity for Maintenance of STP including but not limited to chemicals for poly dosing system, Sodium Hypo Chloride for Dis-infection, including reparing and replacement of defective parts (if any ) during the entire period of Maintenance of Two Years.
2. All maintenance shall be strictly followed as per the Original Equipment Manufacturer (OEM’s) operation and Maintenance Manual. | 24 | Month | 1,68,740 ₹40.5 L | 1,45,140 ₹34.8 L | 1,66,920 ₹40.1 L |
| 2.00 | Testing of Samples
Testing samples & Submitting the testing report to Institute of Raw sewage (Raw water) at bar screen chamber inlet (01 sample) and Treated sewage (Treated water) from STP (01 sample). Sample testing includes the parameters like PH, COD, BOD, TSS, Oil & Grease, residual chloride, fecal coilform, NH3-N, N-total, Total Phosphorous, E-coil, etc. Sample should be tested from approved lab NABL / NABET Accredited, MOEF, SPCB or govt approved lab as per instruction or as directed by Engineer-in-charge (EIC).
Note : One Sample for Raw sewage & One Sample for treated sewage will be counted as a One Set. | 24 | Set | 767 ₹18,408 | 5,900 ₹1.4 L | 4,000 ₹96,000 |
Updated dates
Tender Value
₹37.0 L
EMD Value
₹74,033
Closing Date
10 Feb 2026, 3:00 pmClosed
Dean (Admin)
Institute for Plasma Research (IPR), Near Indira Bridge, Bhat, Gandhinagar-382428
Operation, Maintenance, Testing and servicing of 100 KLD MBBR (STP) Sewage Treatment Plant at IPR Campus, Bhat, Gandhinagar, Gujarat.
2026_IPR_892671_1
IPR/TN/CIVIL-PR/01/2026
Open Tender
Civil Works - Others
730 days
IPR Campus, Bhat, Gandhinagar
As per Tender Documents
8 documents required · 8 mandatory
₹0
₹74,033
29 Apr 2026
7 Jan 2026
12 Feb 2026
7 Jan 2026
10 Feb 2026
24 Jan 2026
7 Jan 2026 - 15 Jan 2026
Providing and Running Operation, Maintenance and Servicing of 100KLD MBBR Sewage Treatment Plant at IPR Campus, Bhat, Gandhinagar. The rate is inclusive of Plant Operators (1nos ), 24 X 7 (in Three Shifts) for Operations & maintenance, & Providing Superviser (1No), all materials, maintenance of plants parts, i.e. Pumps, Motors, blowers, belts, pipes, all electricals parts & equipments, oiling, Greasing, other equipments (if any), wiring, equipments Plumbing lines, primer & painting of MS structure pipes & tanks, cabling, valves, (Civil, Electrical, Plumbing works)etc, as required during operation for achieving specified parameters of treated sewage water. (All Spares and replacement of any defective part shall be included in the service contract including consumable & keeping near by area clean & Green.) The treated water should conform to the following parameters: (1) pH Value: 6.5-8.8, (2) BOD: <5 mg/ltr, (3) COD: <30 mg/ltr, (4) TSS : < 10 mg/ltr, (5) Oil & Grease: 10 mg/ Ltr, (6) Residual Chlorine: < 1-3 mg/ltr, (7) Fecal Coliform (MPN/100 ml): <100, (8) NH3-N: 5 mg/ltr, (9)Total Phosphorous: 2mg/ltr, (10) N-Total: < 10 mg/ltr, (11) E-Coli (MPN/100 ml): NDL Note:- 1.The cost shall include all Chemicals , Plant parts as per need & in required quantity for Maintenance of STP including but not limited to chemicals for poly dosing system, Sodium Hypo Chloride for Dis-infection, including reparing and replacement of defective parts (if any ) during the entire period of Maintenance of Two Years. 2. All maintenance shall be strictly followed as per the Original Equipment Manufacturer (OEM’s) operation and Maintenance Manual.
Testing of Samples Testing samples & Submitting the testing report to Institute of Raw sewage (Raw water) at bar screen chamber inlet (01 sample) and Treated sewage (Treated water) from STP (01 sample). Sample testing includes the parameters like PH, COD, BOD, TSS, Oil & Grease, residual chloride, fecal coilform, NH3-N, N-total, Total Phosphorous, E-coil, etc. Sample should be tested from approved lab NABL / NABET Accredited, MOEF, SPCB or govt approved lab as per instruction or as directed by Engineer-in-charge (EIC). Note : One Sample for Raw sewage & One Sample for treated sewage will be counted as a One Set.
Please Enable Macros to View BoQ information
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 3.35 MB
BOQ_938284.xls
BOQ • 0.32 MB
TechnicalBidIPRTNCIVILPR012026.pdf
Tender Documents • 4.88 MB
Download all tender documents and submit your bid