Executive Engineer, Elect. Division PWD BandR Br., Karnal (0184-2265696)
Replacement of 315 KVA HT Transformer in Govt. Industrial Training Institute, Butana, Distt. Sonipat.
2023_HRY_265976_1
20234671B790 559B 495A B035 6E9DCD5A216D665BAR
Open Tender
Electrical Works
Works
90 days
BUTANA KUNDU
3 documents required · 3 mandatory
₹1,000
₹29,300
Yes
16 May 2023
16 Mar 2023
31 Mar 2023
16 Mar 2023
29 Mar 2023
16 Mar 2023
Amount
[24.3.4.1]HT CABLE 4.1. Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :70 to 120 sqmm
Supply, Installation, Testing and Commissioning of Oil filled 11/0.433 KV Copper Wound 3 Phase 50 Hz 315 KVA Transformer with OCTC, No load voltage ratio 11/0.433 KV, Vector Group Dyn 11 (HV-11KV-Delta and LV-0.433KV-Star), Tapping Range/Steps plus 5% to -10% in steps of 2.50%, Tap-Changer Off Circuit Tap switch, Temp. Rise (Oil/dg.) 40/45° C. Cooling ONAN- Outdoor Transformer, Termination HV/LV/Orientation Cable Box/Cable Box/180°, Impedance 4.5% (Sub to IS Tolerance) as per IS, Losses - 1.025 KW (Max) @50% Load and 3.1 KW (Max) @100% load as per Energy Efficiency Level 01, Fittings and Accessories - 1 No. Rating and Diagram Plate, 2 Nos. Earthing Terminals, 4 Nos. Lifting Lugs, 1 No. oil level indicator with minimum level marking, 2 Nos. Thermometer Pockets, 1 No. Conservator (Conventional without Air bag only) with oil filling hole with cap and drain plug, 1 No. Air release plug, 01 No. Silica gel breather, 01 No. off Circuit tap Switch, 04 No. BiDirectional Rollers, Jacking Pads, Radiators (epoxy painted only), First Filling of Oil (as per IS 335), Epoxy Paint shade #IS:631, Explosion vent, Bottom drain-cum Filter Valve, Top filter valve, Accessories:- 01 No. Marshalling Box, 01 No. WTI with Alarm and trip contacts, 01 No. OTI with alarm and trip contacts, 01 No. Buckholz Relay, Insulation Level - HV 75KVp/28 KVrms LV -/3 KVrms as per BIS 1180 Level 01. Make - Kirloskar/ ABB India/ Siemens/ Schneider/ Crompton/ Alstom/ Bharat Bijli/ NGEF/ Voltamp
Supply and erection of 11 kV HT aluminium conductor armoured cable as per IS:7098/(Part-2) 1985 with latest amendments on surface / Pipe with all labour and material as required : - 70 sqmm 3 core HT Cable Make- Havells/ Polycab /R.R. Kabel
Recovery Items Recovery of old Transformer Tank/Body Scrap
MS Sarwan Automation and Solution
S.S. Enterprises
Highlight Associates and Contractors
J.B.S.Electrical Co.
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .