Loading…
Loading…
Tender Value
₹50.0 L
EMD Value
₹49,969
Closing Date
23 Oct 2026, 6:00 pm
executive engineer
SR to Providing and erecting Electrical installation work at outside barracks, hospital and caballing work at inside jail barrack and Supply, Installation, Testing & Commissioning of 100 KVA DG set and Related Items at Mahila Jail at central jail at Vadodara Dist: Vadodara [1st Attempt]
351847
NIT No 12 [2026-27] Sr No 5
Open
Electrical Works
Works
Vadodara
13 documents required · 12 mandatory · 1 optional
₹1,500
GUJARAT STATE POLICE HOUSING CORPORATION LIMITED
₹49,969
3 Oct 2026
3 Oct 2026
3 Oct 2026
23 Oct 2026
3 Oct 2026
No. InFigure In Words Rs.
Providing & erecting Point wiring with 1.1 KV grade ISI marked 2 X 1.5 sq.
mm copper PVC insulted FRLSH wire with 1.5 sq. mm (green) copper PVC
insulated FRLSH wire for earth continuity in FIA approved ISI mark medium
class white colour 20/25 mm dia. embossed rigid PVC pipe with PVC fitting
fixed with adhesive solution erected on Brick Wall / slab along with
continuous G.I. fish wire to draw wires and laid in approved manner zari for
PVC pipe and boxes shall be filled with cement mortar and finishing the RS: Five
1a surface to match the wall / ceiling complete with approved make 5/6 Amp. 290.00 Point 535.00 Hundred Eighty
ISI make modular type switch and accessories mounted in 20 G. G.I. company only
fabricated metallic box covered with appropriate front plate modules erected
flushed with wall / ceiling with necessary modular lamp holder / modular
ceiling rose / HD Connector as directed.(Make & Model approved by EIC and
matching colour with switch and accessories) for OPEN Wiring . Light point.
Necessary sheet / tape / polythene / sand must be erected or filled in all box
to prevent mortar going into the box. Length of point wiring must not increase
than 10 mtr. For that necessary switch boards and their locations must be
finalised before execution by agency otherwise payment will not be done for
extra long point. (For future extention, if required, agency has to erect one
higher size metal box and modular plate as per instruction of EIC. Cost of
blank plate shall be paid as per tender item) (Conductor resistance should be
as per IS:8130/1984)
For Fan Point (with 6 A. Modular type switch and two module hum free EME RS: Eight
1b Five step type Electronic fan regulator both are with ISI Mark)) Cat.-II 150.00 Point 770.00 Hundred Sixteen
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
For separate Point (with 6 Amp. Switch & 3 pin socket both having ISI mark) RS: Six
1c Cat.-II 30.00 Point 573.00 Hundred Sixteen
For Looped on switch board (with 6 Amp. Switch & 3 pin socket both are with RS: Two
1d ISI Mark) Cat.-II 45.00 Point 281.00 Hundred Ninty Five
Providing and erecting ISI mark Medium class white RIGID PVC PIPES of
following size complete to be erected on/in wall or ceiling erected with
RS: Twenty
3-a necessary PVC fittings & Junction boxes fixed with adhesive solution & 1000.00 Mtr. 24.00
Four only
Clamps with following dia of pipes, in approved manner as directed For
For 25MM Dia RS: Thirty
Three only
Providing & Erecting Mains with FRLS PVC Insulated wire ISI marked 1.1 KV
grade In Existing FIA approved ISI mark medium class 20/25 mm dia.
embossed rigid white PVC pipe with PVC fitting fixed with adhesive solution
to be erected on/in brick wall / slab along with continuous G. I. fish wire to
draw mains laid in approved manner with plastering by cement mortar &
RS: Fifty Eight
4-a finishing the surface to match the wall / ceiling complete with FRLS PVC 1200.00 Mtr. 58.00
insulated wire for earth continuity. (Approved ISI make only) [a] 2 x 1.5 only
sq.mm. FRLS copper multi stranded conductor mains with 1.5 sq.mm. FRLS
copper multi stranded conductor for earthing as per standard colour code.(In
Existing 20/25mm Pipe) [Wire must be having box packing]
For 2 X 6.0 sq.mm. copper multi stranded conductor mains with 2.5 sq. mm
copper multi stranded conductor earthing as per standard colour code ---(In
4-b 600.00 Mtr. 150.00 Hundred Fifty
Existing 20/25mm Pipe)[Wire must be having box packing]
Providing & fixing 25 mm. dia. PVC insulated G.I. corrugated Flexible pipe
with necessary socket, PVC bushes saddle, Check-nuts etc. complete of RS: Thirty
following sizes. Seven only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Providing and fixing Plug Point wiring with 1.1 KV grade ISI marked
approved make 2 x 2.5 sq.mm copper PVC insulated FRLSH wire with
sq.mm (green) copper PVC insulated FRLSH wire for earth continuity in FIA
approved ISI mark white colour medium class 20/25 mm dia. embossed
rigid PVC pipe with PVC fitting fixed with adhesive solution erected in
wall/slab along with continuous G. I. fish wire to draw wires and laid in
approved manner zari for PVC pipe & boxes shall be filled with cement RS: Eight
6 mortar & finishing the surface to match the wall / ceiling complete with 16 10.00 Point 896.00 Hundred Ninty Six
Amp Modular type Swich and accessories mounted in 20 G. GI company only
fabricated metallic box covered with appropriate front plate modules erected
flushed with wall. (a) 16 Amp. Indicator switch & 1 No. 6/16 A universal
socket white colour suitable for 3 pin top duly both having ISI mark.
(Necessary sheet / tape / polythene / sand must be erected or filled in all box
To Prevent Mortor Going In To The Box) Cat.-II
Supplying and Erecting LED indoor fitting of approximately 4feet long with
LED of wattage 0.2W to 0.5W assemble on single MCPCB with housing use as
a heat sink shall be made from Aluminum extrusion having enough strength
(sample must be approved by EIC)with polycarbonate diffuser with following
specification:
(A) Company mark/name on the fitting.
(B) Rated input voltage and frequency: 220V to 240 VAC ; 50Hz.
(C) Rated input wattage: max. 24w
(D) Rated input current : 0.2 Amp RS: Three
7 (E) Power Factor : Min. 0.90 250.00 Each 370.00 Hundred Seventy
(F) ATHD :Max. 15% only
(G) Rated Luminous flux: Min. 2420 lm
(H) CCT: 6500K
(I) CRI: Min. 80Ra
(J) Driver Efficiency: Min. 80%
(K) LED life span: Min. 50000 Hrs @ L70
(L) Over Voltage protection: Withstand up to 440V/AC for 4 Hrs.
(M) Surge protection : Min. 2KV
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
(N) IP rating: IP
(O) IK rating : IK
(P) Short circuit , Open circuit & Reverse Polarity Protection must be provided
(Q) Fixing Clamp min.12mm wide heavy duty design & strength should be
sufficient to hold the fitting erected on wall or ceiling & Fitting lenght should
be min.1100mm.
(R) 3 core x 1.0 Sqmm copper wire with min. 1ft (300mm) earthing connector,
Diffuser shape must be OMEGA/Mashroom & Al.base must be powder
(Note:-The manufacturer/ authorized Channel partner of the manufacturer
has to submit 5 yrs free replacement Guarantee for complete Fixture)
[Approval will be given strictly subject to item specification]
SITC of 8 W LED Lamps integral type, cool white with PC diffuser suitable for RS: One
8 B22 Lamp holder having 800 Lumes & p.f.>0.9.. 50.00 Each 111.00 Hundred Eleven
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Providing & Erecting 2.0 mtr. long Earthing system by making minimum bore
of 225 mm dia. in soft soil. Suitable for doing pipe-in-pipe technology earthing.
Earthing electric rod must be made from Corrosion free hot dip galvanizing
pipes having following specification.
(A) Earthing Electrode: outer Pipe: - 88 mm minimum O.D., 'B ' Class ISI mark
of Reputed Brand, Inner pipe: - 42 mm minimum O.D., Pipe B Class ISI mark
reputed Brand. Terminal Size: 70 mm X 100 mm length, Terminal should be
made from inner pipe for that pipe must be pressed and gave rectangular
shape so its work as a terminal. The hot deep galvanising must be done after
above process. Galvanised thickness must be minimum 75 micron anywhere. RS: Seven
9-a SS Nut bolt:- 2 nos. with washer suitable for 14 mm dia. hole must be provided 12.00 Each 7025.00 Thousand Twenty
at terminal. Total minimum Weight (approx.) of earth electrode with inside Five only
conductive material be 26 kg.
(B) Inner chemical (CCM Compound):- Resistivity:- 0.2 ohm/ meter testing as
per IEC 62561-2017, Voltage drop:- < 1 volt at no load & dry form, Sulphur
content:- <2%
(C) Back fill Compound:- Earthing compound should be capable to retain
moisture for long time. Back Filling Compound weight is 25 Kg.
(D) Chamber and cover:- Earthing chamber should be size of 400 mm X
mm X 400 mm depth and Cover should be heavy duty cast iron with required
size of 300 mm X 300 mm X 4 mm thick.
Necessary test report must be submitted.
1. Short circuit test by ERDA/ CPRI for 25KA
2. Resistivity test of conducting material from NABL accredited lab.
3. Hot dip galvanised / zinc coating micro test from reputed laboratory.
4. General test report from OEM regarding specification of earthing.
[Make and model approved by EIC Strictly subject to item specification only]
[OEM has to submit all detail & sample for approved before supplying]
[Water must be poured in bore before starting earthing. Earthing value must
be measured with earth tester. Agency has to bring the earth resistance to at
least 02 ohms & voltage between neutral & Earthing upto 02 volt. Agency has
to maintain earthing & its value for one year. Earthing must be done in the
presence of A.E. (GSPHCL)]
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Add Extra for excavation in Hard rock by dry and wet blasting and chiselling RS: Two
9-b for pipe type earthing. 8.00 Each 276.00 Hundred Seventy
Providing & Erecting Mains with ISI marked, 1.1 KV grade electrolyte multi
stranded, annealed copper conductor with heat resistant PVC insulated
conforms to IS:694, IEC - 227 erected in existing pipe of following size
RS: Seventy
10-a (Specifically for control panel, relays, power switchgears, motor starters & 50.00 Mtr. 70.00
control wiring) with required size of copper lugs, nuts and bolts if required. [f]
One wire 6.00 sq. mm
For One wire 16.00 sq. mm RS: One
10-b 20.00 Mtr. 176.00 Hundred Seventy
One wire 70.00 sq. mm RS: Eight
10-c 20.00 Mtr 829.00 Hundred Twenty
Nine only
Providing and erecting METALIC DANGER NOTICE BOARD for medium
RS: Sixty Nine
11 voltage installation to be erected as per IS. 10.00 Each 69.00
Providing, erecting, testing ceiling Fan confirming to IS: 374/1979 AMDT No.
1 to 6 Class-I, 50 Hz. Specification of Ceiling Fan must be as per below. (1)
Sweep: 1200 mm, (2) Operating Voltage: 180 to 230 V, (3) Power Factor: > 0.9,
(4) Power Consumption: maximum 53W, (5) RPM: minimum 330, (6)Service
value:min 4.3 m3/mtr, (7) Class of insulation: 'B', (8) No. of heavy duty
premium quality Ball bearing: Two, (9) Total Body: Top & Bottom should be
alluminium, (10) Blade: Aluminium approx 1.1 mm thick, (11) Colour: White RS: One
high grade powder coating, (12) Canopy: Two Nos. Heavy duty, (13) Thousand Nine
Condenser: Min. 1.5 MFD (15% tolerance) as per IS 1709-1984 Branded Hundred Twenty
make,(14) Down road: up to 1.0 mtr as per site tequirment, (15) Required Nine only
fixing accessories, (16) 3 core 0.75sq.mm wire as per site requirment,(17) no
vibration and noise due to mechanical parts.(18) Necessary saftey wire should
be erected with fan for safety & checked with EIC (OEM has to approved
model as per tender specification and tested at ERDA)
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying & Erecting Fan Clamp of 30 x5 mm flat of required length & 10mm
RS: Ninty
13 MS Bolt & Nuts erected with necessary hook of 10mm M.S. Round Bar 50.00 Each 98.00
Eight only
Providing ad erecting approved make single phase Double Door metal clad
D.B. as per relevant indian standards ammended upto date.
Supplying and fixing following way single phase MCB distrubution board of
company fabricated MCBDB Door Back Side &body Must Be Made OF
MM Thick CRCA Sheet sheet with sheet box with powder coated inside and
outside after apply seven tank chemical process of cover complete with
suitable integral single piece construction tinned copper busbar and link with
all necessary interconnection and with necessary size MS frame for mounting
MCBDB. Manufacturer must be provided (1) IP 43 and as per IS:8623-1 &
IEC 61439-1 & 3 having D type PU gasket. (2) Seven tank Powder coating
Certificate (3) Tinned Copper/Brass make neutral & Earthing link with
isolation & Protecting Cover for 240 Volts on surface / recess complete with Rs.six thousand two
14 loose wire box, terminal connectors for all incoming and outgoing circuits, 10.00 Each 6254.00 hundred fifty four
with suitable size FRLS PVC insulated copper conductor up to terminal blocks only.
and internal connection, tinned coppper bus bar, 1 no. tinned copper neutral
link, tinned copper earth bar, din bar, detachable gland plate, interconnections,
powder painted including earthing etc.
Single phase incoming and horizontal single phase outgoing. For 16 Way
MCBDB: Including 40 Amp. 30 mA double pole ELCB (ELCB confirming to
IS:12640/1988 having sensitivity of 30 mA and breaking capacity of 10 KA),
MCB 40 Amp. double pole switch (C curve confirms to IS:8828 having
breaking capacity of 10 KA) and S.P. MCB of rating 6 to 32 Amp. with NL
suitable to operate on 240 Volt A.C. power. (6 Amp:- 4 Nos., 16 Amp:- 4 Nos.
& 25 Amp: 4 Nos.)
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
(The DBs should be used of same company of MCB / ELCB to be used)
(MCBDB must be erected in line & level with spirit level and finish the
external edge with box cutting plaster) (Same colour MCB(SP/DP) should be
used as same as MCBDB) [Including Necessary numbering / marking on box
done with red colour radium sticker as per site requirement and instructions
given by EIC on site. Font / number size given by EIC on site as per
requirement]
Providing & erecting 415V MCB Four Pole Switch for Lighting Load (C curve)
having 10KA breaking capacity & confirms to IS :8828 in existing box having
15 10.00 Each 662.00 Hundred Sixty Two
following capacity(b)40 Amp.
Supplying & erecting approved make SMC press moulded composite FRP.
loop-in, loop-out approx. 2mm thick box complete with Bakelite connector
strip 5way(3P+N+E),DIN rail for mounting mob & hinged doors as per RS: Eight
16 requirement having locking arrangements with mounting clamp with nuts, 10.00 Each 890.00 Hundred Ninty
bolts & washers suitable for erection on pole with cable clamps& earth bolt of only
following size of box(A) 300mm x 200mm x 100mm [deep]
Supplying & erecting 12 mm thick backelite sheet of approved make and
grade on25x25x3mm red oxide painted angle iron frame suitable for fixing RS: Two
ICDP SWITCH and energy meter (contractor shall make approved drawing of Thousand Two
17 5.00 Sq.Mtr. 2289.00
Bakelite sheet To arrange required NO of Energy meter& ICDPswitch -busbar Hundred Eighty
etc as per Actual space available in electrical room at site) Nine only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
18 Desiging,fabricating,testing electrical panel (switch board) at
manufacuturer's workshop and Providing & erecting at site. Panel should be
weather proof, dust & vermin proof, floor mounted front operated cubical
panel board having IP-54 made from 2 mm. thick CRCA M.S. sheet for outer
body,gland plate & doors, 1.6 mm. thick CRCA M.S. sheet for internal
partitions with necessary supporting angles, flats including skirting,
bending, drilling, welding, riveting with internal partitions & cable
alley,rubber gromets, rib, control wires, backelite control fuses as per
requirements,sufficient nos. of hinges for doors, door locking arrangement, RS: Twenty One
rubber gasket complete with Required Nos. heavy Duty Connector with Thousand Two
2.00 Sq.Mtr. 21275.00
Cadmium plated nut and bolt for Anti rusting and Al.busbar for earth, Hundred Seventy
nuts/bolts,washer etc as per instruction of engineer-In-Charge. Cost of Five only
supplied item like switchgears, LED indicator ,CTs , busbars and PVC FRLS
copper wire with suitable size for power interconnection,measuring
instruments, foundation flange-bolts-base plates, cost of C channel/angle
iron stand (1ft to 2ft height as per cable size)shall be excluded of panel
fabrication.Specification of suppiled items is attached seperatly.
The panel shall be supplied with Seven Tank chemical process. which shall be
carried out before applying painting, painted with powder coating. (The rates
excludes the cost of switchgears, busbars, interconnecting mains & Copper /
Aluminium strip, fuse, meters etc. The dimension shall be measured excluding
base beams.switchgear of approved brand and specification shall be used and
erected at CPRI approved panel manufacturers only. Busbar compartment
must be separate for easy termination of tails/cables and to avoid least
distance of punching holes in busbar. Panel depth shall be 350 mm.
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Panel manufacturer have to give 4 years service support if in case of
breakdown or fault. Panel manufacturer have to submit electrical meter
calibration report. Agency should design the panel in such a way that there
should not be any excess in panel area (sq.mtr) & length of bus-bar (mtr), if
any excess is need to be done agnecy has to draw attention to GSPHCL at the
time of approval of G.A. drawing.
Loading and unloading of above item shall be done by hydra and skill work
force under supervision of electrical engineer and guidelines given by
manufacturer to avoid damage to the item.
Size of door and Ele. room / Pump room shall be measure and provide to
panel manufacturer to prepare GA drawing considering the size of electrical
room/pump room door and also inside size of it. Agnecy has to co-ordinate
with civil agency for giving proper dimenssion of electrical room/pump room
to accomodeted panel easily.[Including Necessary numbering / marking on
PANEL done with red colour radium sticker as per site requirement and
instructions given by EIC on site. Font / number size given by EIC on site as
per requirement] (See attached details specification of panel & manufacture
also while quoting rate. [Manufacturer must be of Gujarat state so three
stage inspection can be done if required and service support]
Supplying and erecting tripple pole & neutral 440V / 500 V Panel mounting
Copper Busbars with four equal Nos. of electrolyte bus having current density
not more than 1.6 Amp. / sq.mm (Rated current / cross section area) duly RS: Three
wraped with colour insulating tape for phase sequence of following current Thousand One
19-a carrying capacity, erected with necessary bus bar supports / insulators, main 1.00 Rn. Mtr. 3171.00
Hundred Seventy
cable socket to each bar, erected in existing cubical panel with necessary One only
connections.For electrolyte copper busbars Suitable for 200 Amp. capacity
Suitable for 300 Amp. Capacity RS: Four
Thousand Eight
19-b 1.00 Rn. Mtr. 4861.00
Hundred Sixty One
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Suitable for 400 Amp. capacity RS: Seven
Thousand Two
19-c 1.00 Rn. Mtr. 7247.00
Hundred Forty
Seven only
Suitable for 630 Amp. capacity RS: Ten
Thousand Four
19-d 2.00 Rn. Mtr. 10455.00
Hundred Fifty Five
Supplying and Erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 50 K.A. at 415 V. having normal RS: Twenty
current rating 400 A. with Variable thermal & magnetic release suitable to Seven Thousand
20 work on A.C.supply 50 c/s. with all internal connections spreader tinned 2.00 Each 27477.00 Four Hundred
copper & complete erected in existing 16 G.M.S. housing. housing. ICS=100% Seventy Seven
of ICU only Cat. III only
Supplying and Erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 K.A. at 415 V. having normal
current rating 250 A. with Variable thermal & magnetic release suitable to RS: Twenty Two
work on A.C.supply 50 c/s. with all internal connections spreader tinned Thousand Eight
copper & complete erected in existing 16 G.M.S. housing. housing. ICS=100% Hundred Thirteen
of ICU only Cat. III (Use as per requirement) only
Supplying and Erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 K.A. at 415 V. having normal
current rating 200 A. with Variable thermal & magnetic release suitable to RS: Seventeen
work on A.C.supply 50 c/s. with all internal connections spreader tinned Thousand Six
copper & complete erected in existing 16 G.M.S. housing. housing. ICS=100% Hundred Sixty
of ICU only Cat. III (Use as per requirement Seven only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying and Erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 35 K.A. at 415 V. having normal
current rating 125 A. with Variable thermal & magnetic release suitable to RS: Eight
work on A.C.supply 50 c/s. with all internal connections spreader tinned Thousand Seven
copper & complete erected in existing 16 G.M.S. housing. housing. ICS=100% Hundred Seventy
of ICU only Cat. III Four only
Supplying and Erecting Approved make Four pole moulded case circuit
breaker having breaking capacity ICU of 25 K.A. at 415 V, having normal
current rating 25 A to 100 A. with Fixed thermal & magnetic release suitable RS: Six
to work on A.C. supply 50 c/s. with all internal connections spreader tinned Thousand Seven
copper & complete erected in existing 16 G.M.S. housing. ICS=100% of ICU Hundred Twenty
only. Three only
Providing & Erecting (A) Extended operating rotary handle with pad lock
with three position trip,off,on suitable for 25A to 250 A panel mounting cat- RS: Nine
25 III. 19.00 Each 952.00 Hundred Fifty Two
Providing & Erecting (B)Extended operating rotary handle with pad lock RS: One
with three position trip,off,on suitable for 400A to 630 A panel mounting cat- Thousand Four
26 III 2.00 Each 1428.00
Hundred Twenty
Eight only
Supplying and erecting Approved make Earth fault Relay suitable to mount
with inter connection to moulded case circuit breaker having CT ratio & RS: Five
MCCB rating as following along with shunt trip 220 V AC with all internal Thousand Eight
27 connections & complete erected in existing M.S.housing.250-400 A., CT Ratio 1.00 Each 5898.00
Hundred Ninty
1/400 Eight only
Supplying & erecting approved make Four Pole 415 V change over switch
RS: Twenty Two
interior for panel mounting with operating mechanism A.C.23 duty
28 1.00 Each 22035.00 Thousand Thirty
confirming to I.S.S. for 400 Amp. Cat.-III,
Five only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Miniature circuit breaker single pole 6 Amp. to 25 Amp. suitable to operate
on 240 V A.C. system and having breaking capacity 10 KA to be erected in RS: One
29 existing box. confirming to IS 8828/1996 with ISI Mark. Cat.III. 10.00 Each 122.00 Hundred Twenty
Providing & erecting 240 V MCB Double pole switch for Motor & Inductive
RS: Three
Load (c curve) having 10 KA breaking capacity & confirms to IS:8828 in
30 10.00 Each 360.00 Hundred Sixty
Existing M.S. box having following capacity. For 40 Amp. Cat:-III
Providing & erecting 240 V MCB Double pole switch for Motor & Inductive
RS: Three
Load (c curve) having 10 KA breaking capacity & confirms to IS:8828 in
31 10.00 Each 327.00 Hundred Twenty
Existing M.S. box having following capacity. For 6-32 Amp. Cat:-III
Seven only
Providing & erecting 415 V MCB Four Pole for Motor & Inductive Load (C
RS: Eight
Curve) having 10KA breaking capacity & confirms to IS :8828 in existing box
32 30.00 Each 803.00 Hundred Three
having following capacity [c] 63 Amp. Cat.-III
Providing and erecting metalic danger notice board for MEDIUM VOLTAGE
RS: Sixty Nine
33 installation to be erected as per I.S. 10.00 Each 69.00
Providing and erecting multifunctional meter suitable for application of Power
monitoring and showing measurement of following Voltage, Frequency,
Apparent energy, Apparent power, Active and reactive energy, Active and
reactive power, Average voltage Vavg, Peak demand power PM, QM, SM,
Demand power P, Q, S, Apparent power S, S1, S2, S3, Unbalance current,
Power factor and displacement PF (signed, four quadrant), Calculated neutral RS: Thirteen
current, Active, reactive, apparent energy (signed, four quadrant), Active Thousand Nine
34 power P, P1, P2, P3, Voltage U21, U32, U13, V1, V2, V3, Phase currents, 1.00 Each 13984.00
Hundred Eighty
Average current Iag, Peak demand currents, Reactive power Q, Q1, Q2, Q3, Four only
Demand current I1, I2, I3, [Us] rated supply voltage 40...300 V AC 45...65 Hz,
40...300 V DC, Network frequency 50 Hz, Type of network 3P, Display type
segments LED, Display colour Red, Messages display capacity 3 fields of
characters, Display digits 12 digit(s) - 14.2 mm in height
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying and erecting approved make set of indicator lamps of LED type
lamp, lense cover, Bakelite holder complete erected with necessary RS: Forty
connections. Three only
Providing & erecting L.T. Current Transformer with bar primary 50/5 to
1000/5 ratio 15 VA burden erected in existing CRCA box duly secured with
36 6.00 Each 272.00 Hundred Seventy
insulating materials connected to the meter
Supply, Installation, Testing & Commissioning of Three Phase, 440 V Surge
Suppressor protection Device (SPD) & 40 Amp. TPN MCB (or as per SPD
OEM guideline for the protection of SPD which is erected such a way that it
can be operated easily) with MS Enclosure & necessary required 5 Core x 6.0 RS: Six
Sq.mm. size flexible copper cable for Connection. SPD Must be Capable to Thousand Three
Protect all electrical and electronic equipments. If SPD Blast or Fuse then the Hundred Ninteen
panel Builder must have replace it soon during defect liability period. The only
Detail Specification are As per Attached sheet with Annexture-A(E)
(Hakel,OBO, Iskira make) (With Three year Gaurantee / Warranty)
Providing and fixing approved make Ladder type cable tray. Made from M.S
sheet. The cable tray should be bended as per IS 2062/1079 shall be fabricated
of double bended channel section longitudinal members with single bended
Channel section. Rungs of members welded to the base of the longitudinal
RS: Three
members at 250 mm c/c spacing . as per IS and shall be coated with hot dip
38 50.00 Mtr 306.00 Hundred Six
galvanizing as per IS 2629/4759. with coupler plate / Fish plate and GI
hardware like nut - bolt and washers etc. erected on existing support as per
Specification and as per instruction of engineer in charge.. 300 X 50 X 2.0 mm
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Providing & erecting FRLS XLPE (IS : 7098) (I)-88 ISI marked armoured
Aluminium conductor cable for 1100 volt to be laid 90 cms. Under ground or
to be laid on wall with 1.6 m.m thick G.I. heavy guage cable clamp or in RS: One
39-a existing DWC pipe underground or road crossing or floor .(H) 3 1/2 core 185 600.00 Mtr 1075.00 Thousand seventy
Sq. mm ( 95 Sq. mm 1/2 core) (FOr Jail Ele room to Inside barrack panel five only
3 1/2 core 95 Sq. mm ( 50 Sq. mm 1/2 core) (For Main ele room to outside RS: Five
39-b barrack) 500.00 Mtr 583.00 Hundred Eighty
Three only
Providing and erecting FRLS XLPE (IS:7098)(I)-88 ISI armoured cable
multistrand Aluminium conductor for 1.1 KV. to be laid on wall with RS: One
40 necessary clamps or in existing trench / pipe of following size of cables(A) 4 1900.00 Mtr 182.00 Hundred Eighty
core 16 Sq. mm Two only
Providing & laying. R.C.C. Hume pipe for cable to be laid 90 cm. below
RS: Three
ground across the road crossing or on floor with necessary material in an
41 200.00 Mtr 340.00 Hundred Forty
approved manner and making the ground as per original.(C) 300 mm dia
Providing & laying. R.C.C. Hume pipe for cable to be laid 90 cm. below
ground across the road crossing or on floor with necessary material in an
42 200.00 Mtr 261.00 Hundred Sixty One
approved manner and making the ground as per original.(E)150 mm dia
Providing & laying HDPE Double walled corrugated pipes (DWC)
(conforming to IS: 16205 (part 24) 2018)) with minimum load required of 450N
capacity with anti rodent and ultra violet material properties with necessary
connecting accessories of same material at required depth to be laid 90 cms. RS: One
43-a under ground for laying of cable below ground / road surface for enclosing 2000.00 Mtr 117.00 Hundred Seventeen
cable and back filling the same to make ground as per original. (A) For Outer only
dia. 50 mm and Inner dia. 38 mm. (Test Certificate to be Submitted)
For Outer dia. 90 mm and Inner dia. 75 mm. (Test Certificate to be Submitted) RS: One
43-b 100.00 Mtr 150.00 Hundred Fifty
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
For Outer dia. 120 mm and Inner dia. 90 mm. (Test Certificate to be RS: One
43-c Submitted) 100.00 Mtr 191.00 Hundred Ninty One
Providing & fixing Double compressed heavy duty flange type brass cable
gland with rubber ring for P V C insulated armoured cable complete with RS: Two
44-a outgoing tails, insulating tape etc. For following size cables. For 3*1/2 core X 10.00 Each 236.00 Hundred Thirty Six
185 Sq. mm (Sigma, MCI, Comet Make Only) only
3 1/2 core 120 Sq. mm ( 70 Sq. mm 1/2 core) RS: Six
44-b 15.00 Mtr 642.00 Hundred Forty Two
3 & 1/2 core 95 Sq. mm RS: One
44-c 10.00 Each 130.00 Hundred Thirty
Providing & fixing Double compressed heavy duty flange type brass cable
gland with rubber ring for P V C insulated armoured cable complete with
RS: Sixty Six
45 outgoing tails, insulating tape etc. For following size cables. For 4 core x 16.0 50.00 Each 66.00
Sq. mm (Sigma, MCI, Comet Make Only)
Providing & fixing Solderless crimping type Aluminium lugs conforming to IS
suitable for cable of following size evenly crimped with high pressure tool &
RS: Fifteen
46 connected to switchgear terminals with brass/cadmium plated nut bolts in an 100.00 Each 15.00
approved manner. For 16/25 Sq.mm. Allumium Cable
Providing & fixing Solderless crimping type Aluminium lugs conforming to IS
suitable for cable of following size evenly crimped with high pressure tool &
RS: Eighty
47-a connected to switchgear terminals with brass/cadmium plated nut bolts in an 20.00 Each 80.00
approved manner. For 185.00 Sq.mm. Allumium Cable
95 Sq.mm RS: Forty
47-b 30.00 Each 40.00
35/50 Sq.mm. RS: Twenty
47-c 10.00 Each 20.00
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Providing, erecting, fabricating the M.S. structure as per requirement of site as
per structure design Including proper size approved by EIC of M.S. angles,
flats, bars, square pipe, channels, sections (Tata, Jindal, Asian, JSI Make)
complete with cutting, welding, grinding and finishing duly painted with
RS: Seventy
Asian/Nerolac make premium quality oil paint and true care red oxide metal
48 150.00 Kg. 75.02 Five and Paise Two
primer,asian paint make with erection on site as per direction of engineer in
charge with necessary grouting cementing, plastering and finishing complete.
All hole opening of square pipe end must be closed with M.S plate welding.
Payment will be done on KG as per Actual weight.
Providing & erecting FRLS XLPE (IS : 7098) (I)-88 ISI marked armoured
Copper cable for 1100 volt to be laid 90 cms. Under ground or to be laid on RS: Four
49 wall with suitable G.I. heavy guage 1.0 mm thick cable clamp or in existing 80.00 Mtr. 451.00 Hundred Fifty One
DWC pipe underground or road crossing or floor..For 4 core x 4 sq.mm. only
Dismantling the existing light, fan, bell, independent plug point, wiring with
mains of all types along with accessories etc. complete and handed over to RS: One
50 188.00 point 1.00
dept. only
Dismantling the existing switchgears, DB and Busbar of any size complete
RS: Seven
51 with / without board or angle iron frame. 10.00 Each 7.00
Dismantling the existing any type of indoor light fittings RS: Five
Dismantling the existing ceiling fan / exhaust fan / cabin fan / bracket fan
53 complete with accessories, G.I. down rod, frame etc. and making the site clear. 100.00 Each 9.00
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Constructing brick masonry chamber for under ground C.I. inspection
chamber and bends with brick having crushing strength not less than
kg./cm2 in C.M. 1.5 precast R.C.C. cover 1:1.5:3 of size 455 x 610 mm internal
dimenslons. R.C.C. top slab with C.C. 1:1.5:3 mix (1 Cement : 1.5 coarse sand :3 RS: Three
graded stone aggregate 20mm size) foundation concrete 1:5:10 inside plaster Thousand Seven
54 15mm thick with cement mortar 1:3 finished smooth with a floating coat of 10.00 Nos. 3793.18 Hundred Ninty
neat cment walls & bed connect etc. complete rate inclusive of outside plaster Three and Paise
of 15mm thick in cm 1:3 form top of chamber and all side up to 15 cm deep Eighteen only
below ground level. rate also inclusive of providing and fixing precast cover of
size 0.7 m x 0.5 x .07 m with 2 no of m.s. flat handle in cement concrete 1:1.5:3.
Providing and fixing pre-cast Rubber Dye/ Steel Dye inter locking concrete
block 60mm thick grade of concrete M300 pnumatic compressed/vibrated RS: Six
mechanically and as per approved design Conforming to IS 15658:2006 Hundred Ninty
55 15.00 sq.mtr 697.10
including 35mm sand layer for levelling and filling the joint with sand in Seven and Paise
proper line and level as per guidelines of IRC: SP 63-2018 etc. complete. Ten only
Supplying & erecting approved make SMC press moulded composite FRP.
loop-in, loop-out approx. 2mm thick box complete with bakelite connector
strip 4way & hinged doors having locking arrangements with mounting clamp RS: Eight
56 with nuts, bolts & washers suitable for erection on pole with cable clamps& 20.00 Each 890 Hundred Ninty
earth bolt of following size of box.For ( c) 300mm x 200mm x 100mm [deep] ( only
For All Barrack Incoming supply)
Providing & Erecting following Shockproof tissino type accessories erected on
3 mm thick PC (Polycarbonate) sheet in PVC/ Metal/Wooden Box. erected RS: Thirty One
57-a 20.00 Each 31.00
on wall/ ceiling. : One no 3/5 pin 6 A Socket only
One no Single pole 16 A Switch RS: Forty
57-b 100.00 Each 47.00
Seven only
One no 6/16 A Universal Socket RS: Forty
57-c 50.00 Each 47.00
Seven only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
One no Single pole 16 A Switch & One no 6A/16A Universal Socket combined RS: One
57-d with indicator & fuse 70.00 Each 124.00 Hundred Twenty
Four only
Bakelite ceiling, rose RS: Eighteen
57-e 324.00 Each 18.00
Bakelite lamp holder RS: Twenty
57-f 576.00 Each 22.00
Providing & Erecting 3mm thick White Color ISI Mark laminated acrylic Sheet
RS: Three
58 with grooving as directed by EIC(Make:Sundek) 1000.00 Sq.inch 3.00
Providing & Erecting Cable Terminal ( ‘Z" Type) Set of Two for (i)200 / 250 RS: Five
59 Amps 10.00 Each 501.00 Hundred One
Providing & Erecting Cable Terminal ( ‘Plain" Type)Set of Four for (ii) 125 / RS: Eight
60 200 Amps 10.00 Each 806.00 Hundred Six
Providing & Erecting Cable Terminal ( ‘Plain" Type)Set of Four for (ii) (iii) 250 RS: One
/ 320 Amps Thousand Three
Hundred Twenty
Three only
Supplying & erecting single phase approved make industrial exhaust fan
suitable for medium duty ring mounted low noise operation suitable for RS: Two
62 medium duty having metallic grill and following dia size and maximum 20.00 Each 2034.00 Thousand Thirty
speed in RPM [A] 305 mm dia 900 RPM Four only
Supplying installing testing and commissioning of . submersible pump set
RS: Thirty Six
suitable for bore of 150 mm. dia. or more having three phase motor capacity
Thousand Five
63 not more than 7.5 H.P. with following capacity ..(B) ( 8 stage) 390 to 350 LPM 1.00 Each 36548.00
Hundred Forty
discharge at 62 to 70 mtrs. head respectively suitable for 50mm dia. delivery
Eight only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying & erecting approved make motor control cubical panel (Direct -
on - line) made from 16 G. CRCA sheet duly epoxy powder painted inside and
outside with hinged doors and locking, arrangement consisting of suitable size
of ON- OFF isolator (AC - 3/23duty) main fuses, single phasing preventer,
indicating lamps for R- Y - B phases, overload relay, Automatic water level RS: Eight
wires duly socket crimped, main contactor & overload relay, start - stop push Hundred Twenty
buttons, to be erected on angle iron frame grouted on wall as directed. The Four only
isolator, overload relay & contactors will be of L & T, Siemens or BCH make
only. (B) DOL for 7.5 H.P.
Lifting of submersible motor pump set complete with required No .& size of
casing pipes by means of proper chain pulley block and pipe. wrenches. Job
Thousand Six
65 includes stacking of pipes chronologically after due checking of threads.(A) 1.00 Per job 1695.00
Hundred Ninty Five
Up to 60 mtrs.
Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible RS: One
66 Submersible copper cable approved make of following Size. (C) 3 Core x 4 Sq. 100.00 Mtr 145.00 Hundred Forty Five
Supplying ISI Marked (Embossed) following size of Heavy duty “C” Class G.I RS: Three
67 . Pipe & erecting as directed by Engineer-in-charge with necessary plumbing 20.00 mtr 352.00 Hundred Fifty Two
as desired.(D) 50 mm dia only
eavy duty clamp made from 4" x 1.5" iron strip suitable for column pipe 1.5" to RS: One
68 2" length. (B) 50mm(2") dia pipe 1.00 Each 178.00 Hundred Seventy
Eight only
Supplying & erecting G.l. bend for pipe connections suitable for (D) 50 mm(2") RS: One
69 1.00 Each 114.00 Hundred Fourteen
Supplying & erecting UPVC heavy duty Flanges with rubber packing and RS: One
70 hardware materials for pipe connections suitable for (A) 50 mm (2") 2.00 Each 157.00 Hundred Fifty
Seven only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying & erecting approved make by EIC Hi–Tech, Hi-Tensile submersible
pump column pipes UPVC white colour- 3 meter height one end male
71 30.00 Each 1068.00 Thousand sixty
threaded & other end female threaded PVC Joint system with coupler & S.S.
eight only.
wire lock (heavy type)50 mm (27 kgf/cm²)
Supply of following size of TOP & BOTTOM accessories i.e. Adaptor set (CI) RS: One
long, pump guard set, starter pipe Rubber ring for submersible pump & Thousand Four
72 2.00 Per set 1475.00
UPVC column pipe as directed by Engineer - in - charge with necessary Hundred Seventy
plumbing as desired.50 mm Five only
Providing and erecting open well type horizontal submersible mono block
pump set with cast iron body having following specification [b] For 3 phase
open well horizontal mono block pump set suitable for 1350 LPM to 310 LPM
@ 10 to 42 Mtr head suitable for 80 mm dia delivery pipe with 10 mtr.
necessary Size 3 Core Flat copper flexible cable. (Body: Cast iron / Winding :
Copper / stator : Copper / rotor : Copper / shaft : SS 304 material test
certificate from manufacture shall be submitted).
For ____5.0____ HP 3 phase open well pump single/multi stage as per actual RS: Twenty
head requirement as per site situation. Thousand Four
73 The model of the pump with respect to head and discharge will be approved 2.00 Each 20417
Hundred Seventeen
by EIC. only
Pump should have following specifications:
(1) Minimum 10 mtr. Cu. flat cable of suitable size must be provided with
(2) Pump shall be installed as per manufacturer foundation/erection drawing
or as per IS specification.
(Body full C.I., stator winding- copper, rotor- copper, shaft- SS 304, motor-
Energy efficiency)
Lowering of existing submercible motor pump set complete with required No. RS: Eight
74 and size of pipes by means of proper chain pulley block and pipe wrenches. 2.00 Each 848 Hundred Forty
Job includes stacking of pipes cronolo1.00 HP to 5.0 HP. Eight only
Providing & erecting ISI make medium duty (B class) galvanized MS pipe RS: Two
75 with coupling, bend, union, reducer, tee, MS flange etc. with plumbing 30.00 Mtr. 260 Hundred Sixty
charges. [d] 50 mm dia only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Supplying and erecting C.I. Swing check type non-return (reflux) valve ISI RS: One
76 marked with packing, flange, nuts and bolts etc.suitable for following pipe 3.00 Each 1010 Thousand Ten
size. [a] For 50 mm dia. only
Supplying and erecting approved make 3 HP DOL type motor control cubical
panel made from 16 G. CRCA sheet duly epoxy powder painted inside and
outside with hinged doors and locking arrangement Floor Mounting On
mm Height with MS Stand Angle & CC Foundation. Size 35 mm (H) x 35 mm
(W) x 05 mm (D). Panel must be with Minilec Relay for automatic changeover
of pump 1 & 2 logically without using manually changeover switch. The detail
specification & quantity of material used are as under. (Minimum Panel Size:
1.10 meter (H) x 1.10 meter (W) x 0.25 meter (D).
INCOMMER SECTION: (1) MCCB-30 KA-TP (DU-100H), Rating: 63 Amp., RS: Forty Six
Make: L&T, Qty: 01 No. (2) Digital Ammeter (SR-65), Rating: 0-60 Amp., Thousand Seven
Make: Salzer, Qty: 01 No. (4) Digital Voltmeter (SR-65), Rating: 0-500 V, Make: only
Salzer, Qty: 01 No. (6) C.T.- Current Transformer, Rating: 60/5 Amp., Make:
Virat, Qty: 03 Nos. (7) Indicating Lamps (R,Y,B), Rating: 22.5 mm LED, Make:
Airon, Qty:03 Nos. (8) SP MCB , Rating: 20 Amp., Make: L&T , Qty: 03 Nos. (9)
Control Wiring, Rating: 1.0 Sq.mm, Make: Any ISI, Qty: Lot (10) Copper
Busbar, Rating: 63A/100 Amp., Qty: Lot11) Numeric logical relay, Qty:
No.Make:Minilec
Outgoing Feeder (5 HP DOL Feeder): Qty: 02 Nos. (1) MCB-TP-10 KA, Rating:
20 Amp., Make: L&T, Qty: 02 Nos. (2) Power Contactor (415 V) Main, Rating:
12 Amp., Make: L&T, Qty: 02 Nos. (3) Over Load Relay, Rating: 9-15 Amp.,
Make: L&T, Qty: 02 Nos. (4) Digital Ameter (SR-65), Rating: 0-20 Amp., Make:
Meco, Qty: 02 Nos., (5) Digital Voltmeter (SR-65), Rating: 0-500 V, Make: Meco,
Qty: 02 Nos. (6) Indicating Lamps (Start,Run,Trip), Rating: 22.5 mm LED,
Make: Airon, Qty: 04 Nos. (7) Push Button (Start,Stop), Rating: 22.5 mm, Make:
Airon, Qty: 04 Nos. (8) SPP, Rating: 415 V, Make: Space, Qty: 02 Nos. (9)
Terminal, Rating: As per Amp., Make: Airon, Qty: 04 Nos. (10) Control Wiring,
Rating: 1.0 Sq.mm., Make: Any ISI, Qty: Lot (11) Power Wiring, Rating: As Per
Amp., Make: Any ISI, Qty: Lot
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Outgoing Feeder (6 Amp. - 01 No.) For Capacitor (1) MCB-TP-10 KA, Rating:
Amp., Make: L&T, Qty: 01 No. (2) Capacitor- MPP Type, Rating: 2 KVAr,
Make: Concap, Qty: 02 No., (3) Power wiring, Rating: As Per Amp., Make: Any
ISI, Qty:Lot
Outgoing Feeder (32 Amp. - 01No.) For Lighting (1) MCB-TP-10 KA, Rating:
Amp., Make: L&T, Qty: 01 No. (2) Power wiring, Rating: As Per Amp. (3)
Earthing Strip: 25 x 6;A.L.Strip, Qty: 01 No.(4) MCB-DP-10KA , Rating: 20A,
Make: L&T, Qty.:01 Nos.
Providing and erecting ISI marked PVC insulated PVC Sheathed Flat flexible RS: One
78 Submersible copper cable approved make of following Size. [d] 3 Core x 6.00 60.00 Mtr. 171 Hundred Seventy
Sq. mm One only
Providing water proof straight joint in PVC insulated flat flexible copper cable RS: One
79 by using insulated material water proofing material and making the joint 2.00 Each 188 Hundred Eighty
complete. UP to 10 Sq.mm Eight only
Supplying and erecting, commissioning and testing 100 KVA Diesel
Generating set per the CPCBIV+ norms or latest norms having continuous
rating, 3 phase, 415 volts, 50 cycles A.C. supply comprising of a totally
enclosed Water cooled diesel engine with multi-cylinders developing suitable
BHP not less than following capacity at 1500 RPM with 10% overload for one
hour in 24 hours Cost including Legal fee & liaison work i.e. Preparation of RS: Eleven lac
site plan tracing & its prints, Site plan approval from Energy & Petro. div., Fifty Thousand
80 KWH Meter & CT testing for D.G. Set, Site test report . Pre NOC & Final 1.00 Each 1150179 One Hundred
NOC Certificate from Elect. Inspector, Registration at Elect. Duty wing. Cost Seventy Nine
inclusive of Testing:- Testing means full load & 10% over load testing of only
D.G.Set at Company / Dealer work shop. Cost inclusive of Diesel, to & fro
Fair, Lodging boarding etc. of two engineer of corporation. Agency has to fill
the diesel to full the tank at the time of handing over the DG set to
beneficiaries.
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
(ADiesel Engine: Multi Cylinder in line configuration, water coolded,
Turbocharged after cooled, Naturally Aspirated, Heavy duty suitable for
generating set application, developing Suitable BHP @ 1500 RPM, under NTP
conditions with an overload capacity of 10% for any one hour in any 12 hours,
Deisel Engine will be as per the CPCBIV+ norms or latest norms. Vertical
totally enclosed, electric start, compression ignition, 4 stroke, designed to run
continuously at 1500 RPM Standard Complete with Radiator with fan, Fuel
Pump, Electronics Governor -G3 as per ISO 8528 Part V class , Lube Oil & fuel
Filter, Diesel Filter, Dry type Air cleaner with service indicator, Flywheel
Housing and Flywheel to suit single bearing Alternator, Residential type
Silencer, Electrical Starter Motor - 12/24 V ( as per Company Design ) with soft
starting system, CRDI System, DOC, SCR, IOT Remote Monitoring System,
Engine control panel , Battery charging Alternator, first fill of lube oil &
coolant having safety of Low lube oil pressure, High water Temperature. (
Diesel Engine make:- Cummins/ KOEL/ Cater pillar/ Mahindra)
Alternator:- suitable for continuous operation rated at 1500 rpm, 415 V, 0.8 PF,
50 HZ, 3Ph, Class H insulation, IP 23 SPDP Enclosure, self-excited & self-
regulated Brush less with voltage regulation of +1 % of rated load from no
load. confirming IS:4722, BS EN 60034-1 & will be suitable for tropical
condition. ( Alternator Make:- Stamford/ Crompton/ Leroy- somer)
Standard Control Panel:- Cubicle type set mounted standard logical auto on
/off facility control panel consists of Microprocessor based genset controller &
AMF logic wiring & necessary relay, contactor , MCB etc with hinged doors,
bottom gland plate manufactured with 16/18 SWG CRCA sheet provides:-
MCCB of suitable rating & shall be ICS = 100% ICU , Current Transformer,
Aluminum/ Copper bus bars of suitable capacity with incoming & Outgoing
terminations, LED Indication lamps for DG ON & LOAD ON, battery
charging alternator fail indication, Set of Instrument fuces, Emergency Stop-
Push button. The controleer has all the basic safeties and protections.
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Base Frame:- Sturdy, fabricated, welded construction, channel iron base frame
for mounting the above Engine & Alternator & Acoustic Enclosure. Set will
have 4 nos. AVM of suitable capacity.
FUEL TANK:- 8 Hrs Capacity , with Inlet & Outlet arrangement with air vent
& drain plug arrangement.
Batteries:- As per manufacture starter Design voltage requirement , Dry
Uncharged batteries with leads, terminals & Battery Charger.( Make:- Exide &
Model Approved by EIC)
Accoustic Enclosure Canopy:- Providing, fitting & testing Sound Attenuated
Container acoustic modular enclosure as per latest CPCB norms are insulated
with the fire- retardant & noise absorbent foam/ rockwool so as to comply
with noice level of 75 db (A) at 1 meters distance in OPEN free field
environment as per ISO 8528 part 10 Specified by ministry of Environment &
Forest with accessories i.e. Anti-vibration Mounts, protected by LLOP & HCT
/ HWT, Residential silencer in lieu of industrial silencer
,Exhaust piping from exhaust manifold to residential silencer fitted on top /
inside the container. If required exhaust piping extension is to be taken from
the residential silencer, Fuel piping from fuel tank to engine & return line from
engine to fuel tank, Doors with locking arrangement, Weather proof and can
be placed in open sky,.Agency has to submit service report which is done
during defect liability period and submit it to with final Security deposit.
(A) Agency has to provide DG set 100 KVA ,BHP not less than 126 BHP with
diesel of 80% of fuel tank capacity , Heavy Duty standard oil M.S./ PVC
Barrel & Diesel Filling hand Pump of required capacity at the time of Handing
over. ( (Diesel Engine- cummins, Mahindra, koel, caterpiller) (Alternator-
crompton, stamford, Leroy- Somer)
Providing & erecting approved make ATS panel suitable for following size of
3 phase, 415 V., 50 Hz, A.C. diesel generating set complete of scope as detailed
RS: Seventy Two
1) Power module: Motorised Changeover switch with ATS controller,
81 1.00 Each 72035 Thousand Thirty
Auxiliary contactor with NO & NC contacts with Automatic Battery Charger,
Five only
indicating lamps for Generator ON, Mains ON, Load and suitable control
terminals and power terminals with neutral earthing studs.(E) ATS Panel for
100/ 125 kVA 3 phase DG Set
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Excavation for foundation in loose or soft soil upto 1.5 m. depth including RS: One
82 sorting out and stacking of useful materials and disposing of the excavated 4.00 Cum. 118 Hundred Eighteen
stuff upto any Lead and Lift. only
Providing & laying Cement Concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 RS: Three
graded stone aggregates of 20 mm nominal size) and curing complete Thousand Six
including cost of formwork in FOUNDATION AND PLINTH.For DG set Hundred Ninteen
Foundation. only
BRICK WORK using common burnt clay building bricks having crushing RS: Four
84 strength not less than 35 Kg./Sq. cm. In Foundation & Plinth in cement mortar 5.00 Cum. 4080 Thousand Eighty
1 : 6 ( 1 cement : 6 coarse sand ( Conventional Bricks) for Foundation & Plinth. only
Filling available excavated earth (excluding rock) in trenches. plinth, RS: One
85 sides of foundations etc. in layers not exceeding 20 cm. in depth consolidating 6.00 Cum. 132 Hundred Thirty
each disposited layer by ramming and watering. Two only
FILLING in plinth with SAND under floors including watering, raming RS: Four
86 consolidating and dressing etc. complete. 1.00 Cum. 467 Hundred Sixty
Seven only
Providing and laying cement concrete 1:5:10 (1- Cement : 5- coarse sand : 10- RS: Two
hand broken stone aggregates 40 mm nominal size) and curing complete Thousand Five
excluding the cost of formwork of Plywood only with fair finish & Proping Hundred Fifty Four
must be of steel only so as to give fair finish in (A) Foundation and Plinth . only
Providing 20mm thick SAND FACED cement plaster on walls above ground
RS: Three
level consisting 12mm thick backing coat of C:M 1:3 (1 cement; 3 sand) and
88 13.00 Sqm. 334 Hundred Thirty
8mm thick finishing coat of C:M 1:1 (1 cement; 1 sand) etc. complete for any
Four only
providing and corrogulated JSW pre coated sheet roofing fixed withh RS: One
galvanised iron J or L hooks, bolts and Nuts 8 mm dia with bitumin and G.I. Thousand Ten
Limpet washer or G.I. limpet washer with white lead complete excluding the Hundred Twenty
cost of Purlines , rafters and trusses(0.60mm thick) Two only
Item Estimated Rate [Rs. Ps.] Amount
Description of Item Qty. Unit
No. InFigure In Words Rs.
Providing , Fabricating and fixing M.S. GRILL/GATE of approved
pattern fabricated from Structural Steel M.S. flat,square bars, round bars,c-
channel, box pipe as per detail Drawings. Rate is including welding. Rate is
also including two coats of Oil paint and one coat of yellow Zinc cromium RS: Seventy
90 primer coat of approved brand only oil paint shall be Luxol Enamel 400.00 KG 75.02 Five and Paise Two
paint of Berger Paint india limited. or asian paint apcolite premium gloss only
Enamel of asian paint or Dulux premium gloss enamel of dulux paint only.
used as per approved materials list of GSPHC steel must be used ISI marks.
Providing TMT Bars Fe-500D reinforcement of any other approved RS: Seventy
91 brand of GSPHC ONLY for RCC work including cutting, bending, binding 190.00 KG 76.5 Six and Paise Fifty
and placing in position etc.complete for all floors. only
(B) Total Amount of Electrical Work Rs.
(B) Total Amount of Electrical Work Rs.
Signature of Contractor Executive Engineer
G S P H C Ltd
Gandhinagar
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
Volume-1.pdf
Volume-2.pdf
Volume-3.pdf
Volume-4.pdf
Comon Condition.pdf
Electric condition.pdf
Market List.pdf
Schedule B.pdf
speciial condition.pdf
NIT No 12 (2026-27).pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .