Loading…
Loading…
Tender Value
₹1.0 Cr
EMD Value
₹2.1 L
Closing Date
9 Oct 2026, 1:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
ELECT.G
17 conditions · 5 needing a document upload
Financial Eligibility Criteria: (Ref: RB letter No. 2022/CE- I/CT/GCC2022/POLICY : Advance Correction Slip No.-1 dt 14.07.2022) The tenderer must have minimum average annual contractual turnover of V/N or 'V' whichever is less; where V= Advertised value of the tender in crores of Rupees N= Number of years prescribed for completion of work for which bids have been invited. The average annual contractual turnover shall be calculated as an average of "total contractual payments" in the previous three financial years, as per the audited balance sheet. However, in case balance sheet of the previous year is yet to be prepared/ audited, the audited balance sheet of the fourth previous year shall be considered for calculating average annual contractual turnover. The tenderers shall submit requisite information as per Annexure-VIIB, along with copies of Audited Balance Sheets duly certified by the Chartered Accountant/ Certificate from Chartered Accountant duly supported by Audited Balance Sheet.
The intending tenderers should possess a valid electrical contractor license at the time of opening of tender, issued by any state government & same should be submitted along with tender documents by all bidders including working contractors of this unit otherwise offer shall be summarily rejected....... IT SHOULD BE NOTED BY THE TENDERER THAT ELECTRICAL LICENSE UNDER RENEWAL AT THE TIME OF TENDER OPENING WILL NOT BE CONSIDERED AND OFFER WILL BE SUMMARILY REJECTED. IT IS THE RESPONSIBILITY OF TENDERER TO UPLOAD VALID ELECTRICAL CONTRACTOR LICENSE ON THE DATE OF TENDER OPENING.
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
41 conditions · 4 needing a document upload
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. THE TENDERER SHOULD UPLOAD VALID GST REGISTRATION CERTIFICATE ALONG WITH THE OFFER.
The tender shall comply with General Condition of contract (GCC),2022 of Indian Railways (file attached). and its latest amendment, if any. The tenderer shall submit the offer after duly satisfying himself/herself with the GCC,2022 in general.
Tenderers are required to upload the Bank details as per Annexure-XII (Real Time Gross Saving (RTGS)/National Electronic Fund Transfer (NEFT) Model Mandate Form)of tender document.
Tenderers are required to upload requisite details as per Annexure-VIIB (DETAILS OF CONTRACTUAL PAYMENT RECEIVED IN LAST THREE FINANCIAL YEARS AND CURRENT FINANCIAL YEAR) without which the offer is liable to be rejected.
Tenderers are compulsorily required to upload Affidavit as per Annexure-XXIV along with tender document, without which the offer will be considered incomplete and will be rejected summarily.
All requisite documents/credentials mentioned in clause 3.5 of the tender document attached pertaining to his/their technical and financial eligibility. (As applicable).
All requisite documents mentioned in clause 3.7 of the tender document attached pertaining to constitution of firm/concern. (As applicable).
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
No post tender correspondence for submission of additional documents shall be entertained after opening of the Technical & Commercial offers. Even suo-moto post tender letters of the tenderer/s shall be treated as Null & Void.
This tender complies with Public Procurement Policy (Make in India) Order 2017, dated 15/06/2017, issued by Department of Industrial Promotion and Policy, Ministry of Commerce, circulated vide Railway Board letter no. 2015/RS(G)/779/5 dated 03/08/2017 and 27/12/2017.
IF ANY DISCREPANCY IS FOUND IN THE TENDER DOCUMENT, NAMELY SOR ITEM DESCRIPTION, SPECIAL TENDER CONDITION ETC., CLARIFICATION CAN BE SOUGHT FROM THE OFFICE OF SRDEE/G/DLI, DRM OFFICE, STATE ENTRY ROAD, NEW DELHI.
This tender complies with Railway Board instructions for Startups (recognized by Department of Industrial Policy and Promotion, Ministry of Commerce and Industry) for exemption from payment of Bid Security as detailed in GCC 2022 as amended from time to time. Such Startup firms may note that no other exemption is applicable to them in this particular tender.
On account payment, contractor shall submitted indemnity bond with validity up to the completion/extended period in the prescribed format (please refer Annexure-XXVIII) at the contractor's cost, vesting the ownership of such material with the railways.
This tender shall also complies with "Indian Railways Standard General Conditions of Contract, April 2022 (Advance Correction Slip No. 11)" vide Railway Board letter No. 2022/CE-I/CT/GCC- 2022/POLICY/Pt.I (E-3320424), dated: 13.03.2026 (attached)
The rate to be quoted by tenderer shall be inclusive of all state/central taxes including GST. tenderer shall submit GST certificate along with the offer.
All disputes or differences of any kind whatsoever arising out of or in connection with this contract, whether during its execution or after completion, termination, or breach thereof, shall be subject to the exclusive jurisdiction of the competent courts at New Delhi only.
The issues not covered under the tender document shall be governed by General conditions of Contract (GCC) 2022 or its latest amendments if any during entire period of contract. If any contradiction in Tender Document and GCC is observed then GCC shall prevail.
Defective parts shall only be replaced with OEM's spares. Proper invoices/delivery challan /warranty certificate etc. shall be provided by the firm to prove genuineness of spare parts.
The Contractor shall comply with all applicable provisions of IS 732:2019 (Code of Practice for Electrical Wiring Installations) for every relevant item mentioned in the NIT Schedule.
This tender shall also complies with "Indian Railways Standard General Conditions of Contract, April 2022 (Advance Correction Slip No. 12)" vide Railway Board letter No. 2022/CE-I/CT/GCC- 2022/POLICY (3389822), dated: 12.08.2026 (attached)
Before energization /commissioning, the contractor shall carry out all pre-commissioning tests (like, Continuity resistance of conductors, Insulation resistance test, Polarity test, Verification of automatic disconnection of supply (ADS), Phase sequence test, Functional tests, Voltage drop verification, Earth electrode resistance test, Earth Continuity test, Load test, Verification of additional protection (RCDs/RCCBs/RCBOs) etc.) and submit the corresponding test reports as specified in the Chapter 16 (Verification of Installation) of CPWD General Specifications for Electrical Works, Part-I (Internal), 2023 or latest. The rates quoted in the NIT schedule are inclusive of all the aforementioned tests and no additional payment will be made and contractor shall submit the required test report for the same
All test instruments used for carrying out the pre-commissioning tests shall be of reputed make (like Megger, Fluke etc. ) and shall be properly calibrated, with valid calibration certificates available for verification whenever required.
Provision of 48 V pit light and catwalk light with other allied works in washing cum pit line (03 Nos.) at Old Delhi Station.
112-SRDEE-G-DLI-2026-27~NR
112-SRDEE-G-DLI-2026-27
Open
Works - General
5 Months
Delhi, Delhi
₹0
₹2.1 L
17 Sept 2026
17 Sept 2026
25 Sept 2026
27 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ 10445600.00 Below/P | ||
| — | 633.00 | — | — | ||
| Supply, fixing, testing and commissioning of 48V, 50 Hz LED based pit light luminary with IP-66 protection, impact resistance IK10 having system wattage less than or equal to 22 watt complete with anti theft mounting arrangement as per site requirement of make Phillips, Bajaj, Havells or similar conforming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121-Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per explanatory note. | — | — | — | 26,11,125 | |
| — | 30.00 | — | — | ||
| Supply, fixing, testing & commissioning of Step down single Phase Isolation transformer 230V/110V or 48 V AC of 5KVA capacity (transformer shall be double wounded type copper wounded, voltage regulation of t/f shall be 95 % or more and insulation class II or better), input -output voltage meter, MCB complete with fixing arrangement and anti-theft arrangement as per site requirement and conforming to latest relevant IS, IEC 61558 or latest. The design of anti theft arrangement and stand shall be as per site requirements and prior approval of Railway Engineer & as per explanatory note. | — | — | — | 9,91,200 | |
| — | 633.00 | — | — | ||
| Supply, fixing, testing & commissioning of weatherproof cable junction box (Make: Hensel KF 1616 B or equivalent) dimensions H x W x D: 155 x 210 x 92 mm (approx.), conforming to IEC 60670-1/-22 and IEC 60670-22, complete with built-in 5/6-pole branch terminal as per site requirement, screw connection terminals having 2 clamping units per pole, rated conductor size 6- 16 sq.mm Cu/Al, suitable for solid, stranded and flexible copper conductors. Junction box shall be manufactured from UV resistant polycarbonate (PC) thermoplastic, halogen-free, silicone-free, weatherproof and corrosion resistant, with glow wire test 960°C as per IEC 60695-2-11 and UL94 V-0 flammability rating. Rated insulation voltage shall be 690 V and rated current 102 A. The enclosure shall be suitable for indoor and outdoor installation with ambient temperature range -25°C to +70°C, impact strength IK09, and degree of protection IP66/IP67/IP69. The box shall be provided with quick- locking transparent/solid lid arrangement, sealable without accessories, external wall mounting brackets and sealing plugs. Cable entry arrangement shall consist of 10 metric knockouts (M25/M32/M40) distributed on enclosure walls as per manufacturer design. Colour: Black (RAL 9011) complete as required at site including all fixing accessories like lock nuts, glands, termination etc. & as per explanatory note. Note: The junction box shall have entry arrangement for 4x16 sq.mm XLPE cable and 6 sq.mm copper PVC wire outgoing. The glands/locknuts are included in this item only. | — | — | — | 19,93,950 | |
| — | 385.00 | — | — | ||
| Supply, fixing, testing and commissioning of 48V, 50 Hz LED based bulk head/ Catwalk/ Pathway light luminary with IP-66 protection, impact resistance IK10 having system wattage less than or equal to 22 watt complete with anti-theft mounting arrangement as per site requirement of make Phillips, Bajaj, Havells or similar conforming to CEE/NR's spec. No. CEE/NR/121- Elect/PS/2018 (Rev- '3') or latest at Tech Spec-I attached & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') at Tech Spec-II attached or latest & as per explanatory note. | — | — | — | 16,23,160 | |
| — | 300.00 | — | — | ||
| Supply and recessing/fixing of PVC conduit pipe of size 25 mm conforming to IS. 9537 Part-III (or Latest version) with accessories junction box, bends etc. including making chase, plastering/clamping etc. as per site requirement & as per explanatory note. | — | — | — | 9,900 | |
| — | 1000.00 | — | — | ||
| Supply, Fixing, testing & commissioning of following sizes FRLSH PVC insulated multi stranded copper (annealed) conductor single core cable conforming to IS 694 (or Latest Version), IS 732:2019 or latest and drawing in Laid (recessed /surface) PVC conduit pipe for wiring of point wiring / circuit wiring / sub main / main as required including connections, testing and commissioning & as per explanatory note. Size 1x6.0 sq.mm | — | — | — | 95,000 | |
| — | 15.00 | — | — | ||
| Earthing with 40 mm dia. GI pipe class 'B' 4.5 meter long earth electrode as per IS:3043 (latest version) to achieve earth resistance less than 5 ohms including construction of masonry enclosures with hinged cover plate of cast iron with locking arrangement (approx. size 400 mm x 400 mm) on top, provision of earth plate, connections from earth electrode to switch gear/pole as per drawing & as per explanatory note. | — | — | — | 89,160 | |
| — | 75.00 | — | — | ||
| Supplying and laying 25 mm X 5 mm G.I strip confirming to relevant IS as per IS:3043 (Latest version), fixing on surface or as per site condition, clamping or fixing with suitable arrangement as per site requirement, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required & as per explanatory note. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50 mm) | — | — | — | 11,625 | |
| — | 2700.00 | — | — | ||
| Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required conforming to IS/IEC 61537:2006 & as per explanatory note. 150 mm width X 50 mm depth X 1.6 mm thickness | — | — | — | 21,03,300 | |
| — | 660.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Upto 35 sq. mm | — | — | — | 2,32,320 | |
| — | 200.00 | — | — | ||
| Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest including excavation, sand cushioning, protective covering and refilling the trench [size width not less than 35 cm and depth- 75 to 100 cm] etc. as required as per detail drawing approved by competent authority. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Above 35 sq. mm and upto 95 sq. mm | — | — | — | 84,200 | |
| — | 5940.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Upto 35 sq. mm (clamped with 1mm thick saddle) | — | — | — | 3,50,460 | |
| — | 1800.00 | — | — | ||
| Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required as per IS 1255 (reviewed 2016) or latest, IS 732:2019 or latest. In case of any demolition of PCC, RCC, road, wall surface etc. the contractor should ensure repairing of the same on own expenses as per site requirement and satisfaction of railway representative and conforming to CPWD General Specifications for Electrical Works Part-II External -2023 and CPWD DSR (E&M) 2025 & as per explanatory note. Above 35 sq. mm and upto 95 sq.mm (clamped with 25x3mm MS flat clamp) | — | — | — | 2,50,200 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
GCC-2022-ACS-12compressed.pdf
ATTACHMENT
16CPWDGeneralSpecforElectWorkPart-
ATTACHMENT
TECHSPEC-IRev-3.pdf
ATTACHMENT
TECHSPEC-IIRev-4.pdf
ATTACHMENT
ExplanatoryNote.pdf
ATTACHMENT
TenderDocument.pdf
ATTACHMENT
GCC-2022-ACS10_merged.pdf
ATTACHMENT
GCCAdvanceCorrectionSlipNo.11.pdf
ATTACHMENT
ModifiedSpecialConditionsofContract_1.pdf SPECIAL CONDITIONS
ATTACHMENT
Chapter-16CPWDGeneralSpecforElectWorkPart-IInternal2023.pdf
ATTACHMENT
ModifiedSpecialConditionsofContract_1.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .