Municipal Commissioner, Ahmedabad.
Augmentation work for Electrical, Mechanical & Instrumentation works with 3 years Comprehensive O&M for Existing W-5 Sewage Pumping Station (SPS) at Usmanpura, Sabarmati Riverfront of Ahmedabad Municipal Corporation (AMC).
308176
06 /2026-27
Open
Miscellaneous Works
Ahmedabad
3 documents required · 3 mandatory
₹3,600
Municipal Commissioner, Ahmedabad
₹2.0 L
25 May 2026
25 May 2026
25 May 2026
4 Jun 2026
25 May 2026
Name of Work : Augmentation work for Electrical, Mechanical & Instrumentation works with 3 years Comprehensive O&M for Existing W-5
Sewage Pumping Station (SPS) at Usmanpura, Sabarmati Riverfront of Ahmedabad Municipal Corporation (AMC).
Earnest Money Rs. : Rs. 2,00,300/-
Date of Opening of Tender :
Estimated Price : Rs. 2,00,20,763/-
1) I / We am / are willing to carry out work at _________ % above/below percent (in figures) (should be written in figures and words) of the
estimated cost, as mentioned above. Amount of my / our tender works out for Rs. ________________ (in figures)
Estimated amount put to tender Rs. Estimated amount put to tender Rs.
Signature of Contractor
Company’s seal :
SUMMARY OF SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-
MECHANICAL & INSTRUMENTATION WORKS WITH 3 YEARS OPERATION AND
COMPREHENSIVE MAINTENANCE FOR W-5 SPS AT USMANPURA - SABARMATI
RIVERFRONT OF AMC.
Sr. No. Name of Work
A MECHANICAL & INSTRUMENTATION WORKS
B ELECTRICAL WORKS
C O&M FOR 3 YEARS
I TOTAL CAPITAL COST WITHOUT GST (A + B + C)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
1.1.1 SUBMERSIBLE NON-CLOG PUMP SET 5 Set 11,88,257.00
SITC of Submersible NC Pump-Motor set suitable for sewage application with semi-open
or enclosed or suitable type Impeller & wear Rings in CF8M with CI FG 260 Casing &
casing cover, SS 410 shaft & with motor suitable for 3-Phase, 415 V, 50 Hz., AC
induction Air filled dry type submersible motor of mini. rating as specified having max.
1500 RPM sync. speed, insulation Class 'F' With temp. rise limited to class B and IP-68
The scope shall include all required accessories viz. automatic coupling device, SS-304
heavy duty & of suitable size double guide pipes of length to suit the sump height with
required supports, SS-304 or suitable stainless steel grade Chain with shackles (shall be
with dual hook / shackles of 100 mm or suitable higher size at app. every 1.5m C-C
distance) & of length as per existing sump height + min. 3m, Submersible Power & control
cable (copper flexible & stranded type conductor of reqd. cores & size for each pump
motor set) & 20 m length of each run with necessary electrical termination connection at
junction box / starter panel and auto coupling & delivery bend, PMU etc. complete as per
IS, and Specification and also including in scope any other parts / accessories / fittings
required to complete the work in all respects & satisfactory operation of pump set.
Pump Capacity: 1800 m3/hr.,
Motor Rating: min. 75 kW (or higher rating as reco. by pump mfg.)
Over all Efficiency at Duty- min. 71%
(Note: 1. The scope also includes ensuring the pump set's compatibility with the existing
duck foot bend and pump foundation block. This compatibility will be verified at the time
of supply at existing location.
2. The scope also includes all civil work items / Foundation with positioning / fixing /
strengthening / anchoring / grouting / required hardware’s, any other fittings, accessories,
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.1.1 FIXED TYPE ELECTRIC CHAIN HOIST 2 Set 1,33,130.00
SITC of Electrically Operated Chain Hoist, suitable to fix on Existing Girder, having
motorised motion in vertical lifting, manufactured as per IS:6547-1972-Class-II & IS-
3177- Class-II, complete with electrically operated chain hoist, brake, chain-gear, motors,
safety device, pendant push button, starter panel, cables from motor to starter panel and all
other required accessories like limit switches, panel, power supply system (Fastoon cable
type), fasteners, epoxy painting, etc. tested for over load as per IS complete as per
specifications and complete in all respect.
Capacity : 1 Ton. Min. (For Manual Screen lowering & lifting)
'Lift : 18.00 m as mini. or as per site req.
3.1.1 LEVEL MEASURING SYSTEM FOR SUMP (RADAR TYPE) 1 Set 1,08,000.00
Supply, installation, testing and commissioning of Non-Contact Radar Type Level
Transmitter with 20 meter cable along with Process Indicator for Local Display (local
mounted process indicator shall be 2 wire supported) in WP enclosure with signal
retransmission, required length of power and signal cable from ICP cubicle, gland,
termination, required accessories, hardware, consumables, mounting stand, etc. complete
in all respects and as per specification etc. and having following measurement ranges for
Sewage application:
Meas. Range: upto 20 m (at sump)
The scope also includes providing 4" flanged puddle pipe approximate 300 mm long
including fixing of the same in existing civil structure slab of Sump for mounting of
sensor .The work also include all necessary work like make hole,repair / modificationin
existing slab, etc.
4.1.1 SITC of Rolling shutter with red oxide primer & colour made of 80 mm wide M.S. laths 1 Lot 31,605.00
inter-locked together through their entire length and jointed together at the ends by locks
mounted on specially designed pipe shaft with bracket plates, guide channels and
arrangement for inside and outside locking with push-pull with gear operated complete but
excluding the cost of hood cover and spring. (B) shutters having width above 3.5 m or
following size at room and other required accessories to complete the work in all respects.
Size : 3.5 m H x 3 m W - 1 No. shutter (size shall be as per actual existing site) - approx.
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
5.1.1 Providing, Supply of Structure Steel at site of work with freight, loading, unloading 2,000 kg. 64.838
carting, etc. including all taxes and duties complete such as joints, channels, angles, Iron
Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered plates (min. 8mm thickness) for cable
trench etc. required for support structure of all Electro-mechanical equipment, piping, etc.
for support on floor / wall / beam / brackets etc. as per tender and IS.
5.1.2 Labour Charges for lowering, laying, Fixing with fabrication various size section of MS 2,000 kg. 11.365
such as joints, channels, angles, Iron Rails, ISA/ISMC/ISMB/MS flat, Plates, Chequered
plates, for cable trench etc Complete with two coats of red oxide and two coats of
approved colour shade of epoxy paint as per relevant IS and as per specification.
6.1.1 Job-Work of repairing the inlet sluice gate by releasing jammed spindle 2 Nos. 1,20,692.35
rod from head stock, by repairing or replacing the gunmetal nut and servicing and
functionalizing the gate at Existing SPS.
Scope also include straightening of bent spindle, removing and releasing the bent and
jammed spindle from head stock foundation after breaking the concrete by electric
demolition hammer, reinstating the buckled head stock, removing bent lengths, adding new
straight length of spindle with new coupler, welding and fixing the bolts to hold the head
stock, replacing the fixing gun metal nut and set of thrust bearings, replacing gears
damaged inside the gear box, fabrication and fixing of brackets to hold straight the spindle
during up-down operations, greasing all parts and refaxing the gate, with arrangement of
welding set, gas cutting set, demolition hammer, rotary hammer drill, hand tools, all safety
equipment’s to work inside the inlet chamber, hanging zoola, safety ropes, safety belts, etc.
complete work in all respect. (Satisfactory erection & operation of Gate shall be
responsibility of Bidder/contactor.)
6.1.2 Job-Work of repairing, fabricating and fixing brackets in between the barrier and head 2 Nos. 76,541.90
stock fixed by anchor bolts on inlet chamber inlet, and repairing of railings to work safely
around top of screen chamber, at Existing SPS.
Scope also include removing and cutting old bolts by arranging and carting all tools,
welding and gas cutting sets, MS angles, pipes, arrangement of skilled workers who can
work at heights with safety, and hand tools, all safety equipment’s to work, anchor bolts,
and misc. jobs as directed by E-I-C & complete work in all respect. (Satisfactory erection
& operation of Gate shall be responsibility of Bidder/contactor.)
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
6.2.1 Job-Work of repairing the inlet screens by releasing / removing / recovering old 2 Nos 1,43,284.90
damaged / bent / jammed screens from over head lifting arrangement, repairing or
replacing the damaged angles / channels / screen flat bars and side rollers, strengthening of
the screens, repairing inner guides installed in walls up to full possible bottom sewage
level, adding new mild steel flat bars, fabricating and fixing roller guide brackets in walls
in screen chamber inlet wall, at SPS.
Rate to include removing and cutting old fixtures by arranging and carting all tools,
welding and gas cutting sets, MS. angles, structural steel, arrangement of skilled workers
who can work at heights with safety, and hand tools, all safety equipment’s to work,
anchor bolts, and misc. jobs as directed. (Satisfactory erection & operation of Screen shall
be responsibility of Bidder/contactor.)
7.1.1 MISCELLANEOUS WORK 1 Lot 90,000.00
Dismantaling & removal / shifitng & reinstall in existing SPS like 5 nos. Submersible NC
Pump sets, Rolling shutter, ECH, manual screen, all electrical cables, LT Panel,
TRANSFORMER, Cable end termination, etc. any other equipments not listed here in but
installed in pump house & required to be dismantled / shifting and including all Loading,
Transportation, Unloading & Stacking them at Store or location as per instruction of
Engineer-In-Charge of AMC and as per the tender scope / BOQ.
7.1.2 Providing and applying epoxy paint of approved make to concrete surface for RCC 1900 m2 90.00
structure including cleaning the surface by scrapping and air blowers to the satisfaction of
Engineer-in-charge necessary scaffolding etc. complete with all leads and lifts and giving
satisfactory hydraulic test for water tightness as per IS codes. For new surface-Two coats
7.1.3 Providing and laying 50 mm thick heavy duty cement concrete flooring in 1:2:4 (1 33 m2 431.94
cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) with ironite
powder including finishing with a floating of neat cement etc. complete laid in one layer in
wet well area below GL, and for platform of pumphouse 50 mm thick
7.1.4 Providing and fixing 40mm dia. GI pipe medium weight quality as openable type with 100 m 1,784.00
angle iron support at 1.5 m c/c using 75 x 75 x 10 mm angles, 1 m long with three rows of
pipes as railing including necessary painting with two coats of approved quality oil paint
over one coat of approved primer including necessary welding, bolting required, id any.
7.1.5 Providing and applying of Wall Painting of Ex. SPS 1000 Sq. ft 71.50
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS
FOR EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.1.6 Miscellaneous Civil Work 1 Lot 65,000.00
This scope also includes any unforeseen or emergency civil work arising during pump
dismantling and installation within the operational pump house. the bidder is responsible
for providing all necessary arrangements for the installation of a new LT panel in the
existing LT room, including all required modifications and rectifications. Any unlisted
work deemed necessary on site by the Engineer-In-Charge of the AMC and consistent with
the tender scope.
8.1.1 All-in-One Computer with 27-inch FHD (1920 x 1080) Display, Intel Core i7 (13th 1 Set 1,00,799
Generation) Processor, 16 GB RAM, 1 TB SSD Storage, Pre-installed Windows
Operating System and Microsoft Office Suite 2024 or above or 365, with a dedicated
Graphics Card of minimum 2 GB.
A TOTAL OF MECHANICAL WORK WITHOUT GST
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL AND INSTRUMENTATION WORKS FOR
EXISTING W-5 SPS AT USMANPURA RIVERFRONT OF AMC.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
1.1 ELECTRICAL WORKS 1 No. 9,07,630.00
DISTRIBUTION TRANSFORMER
SITC of 400kVA, 11/0.433 kV, Outdoor Transformer continuously rated, 3-phase, 50 Hz,
OFF Load Tap Changer, OCTC, ONAN cooled, copper double wound core type, vector
group Dyn11, Delta(HT)/Star(LT), Oil immersed winding with temperature rise in oil /
winding 40/45 deg.C above design temperature with neutral brought out to connect to
separate earthing including Terminal arrangement bushing / cable Box on HT side and
cable Box on LT side, first fill of oil along with Fittings & accessories as per Energy
efficiency Level-2 of IS:1180 (Part-1):2021 and its latest ammendments and as per
Tender Specification.
Note: Transformer shall be suitable for parallel operation. Minimum requirement
shall be as below:
Both transformer shall have " Identical X/R ratio, phase angle shift, polarity, phase
sequence, frequency, position of tap changer. Turns ratio & voltage ratio".
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.1 LOW VOLTAGE (LT) PANEL BOARD (PMCC) : 1 Set 20,86,000.00
Dismantaling of Existing LT Panel, disconnection of existing all connected cables without
any damage, considering & subject to resposibility of comlpete the reconnection work in
all respect with required all miscellineous rectification / modification work required due to
dismentaling of existing working LT Panel, shall be carred out as directed by Eng. in
charge of AMC & SITC of PMCC Panel (50kA), compartmentalized, Floor mounted /
Stand mounted or as per site condition / requirement, operating height maximum
mm, Extensible on both ends, suitable for Manual & Auto operation -Local & through
PLC/SCADA operation as per site conditions complete in all respects as per Tender SLD /
Specification / IS and including following as minimum:
(1) INCOMER 1&2: FP, 800A, 50 KA Microprocessor EDO ACB LSIG with inbuilt
RS 485 MODBUS communication with Digital Voltmeter with VSS, Digital PF Meter,
Digital Ammeter with ASS, Resin Cast CT- Cl : 0.5,10VA, MFM with RS-485 Cl. 0.5,
Breaker Control Switch (TNC), A/M, L/R switch, Indicating lamps, Push buttons etc,.
with electrical & mechanical interlocking between Incomer. (1.1) Surge protection device,
3P + N, Type 2 for lightning/surge protection. Load sensing CT in Incomer for APFC
panel with Cl.-0.5. Constant voltage/control voltage transformer 1500VA, 415V/230V
AC, with tapping +/-5% in steps of 2.5%, 32A DP MCB & 25A Power contactor.
(2) BUS-COUPLER: One no. FP 800A ACB (same as per Incomer)
(2.1) 800A TPN, EC grade AL Main busbars. (Busbars size as per 50KA fault level and
Temperature rise with current density 0.8A/Sq.mm)
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
(3) TRANSFORMER FIXED COMPENSATION FEEDER (15 kVAR): 2 Set: Each rate incl in
comprising of 63A FP Thermal Magnetic MCCB, Ind. Lamp, with Capacitor duty above price
contactor, ON Delay timer, individual MCCB/MCB as per Tender SLD.
(4) STAR-DELTA STARTER FOR 75 KW MOTOR (SUBM.) : 5 NOS:
75 KW or higher as per pump manufacturer recommendation Star-delta starter with 320A
TPN MP MCCB (LSIG) with Adjustable O/L & Adjustable S/C protection, 250A AC3
duty contactors (3 Nos), O/L Relay, star-delta timer, MFM with RS-485, Resin Cast CT
Cl: 0.5, MPR with RS-485, CBCT, SPP, PMU as per pump vendor reco., A/M, L/R
switch, ON, OFF, TRIP Indication & Start, E-Stop & Reset pushbutton etc. for S/D
starter. complete in all respects, & LCS (PBS) for Actuator-valve with 16A FP MCB,
open,close,stop PB, open,close,trip & L/R indication & 2 nos. terminal strip, SP MCB etc.
Note : For Actuator LCS (PBS) shall be provide potential free contact for
(open,close,trip & L/R ) indication and terminal for Open,close and stop command
because actautor shall be operator from PLC Panel also in addition to LCS (PBS).
(5) DIRECT ONLINE (DOL)-2.5 KW Starter Feeder: 1 NO:(for Drain Pump For
Each starter comprising of 6.3-10A TPN MPCB with adjustable overload & adjustable
short circuit, 25A contactor, Digital Ammeter, ASS, 32A/1A, Cl.-1.0, 10VA CT, Start,
Stop, Reset push Button, ON, OFF, trip Indications etc.
(6) DIRECT ONLINE (DOL)-1 KW Starter Feeder : 1 NO: (for Drain Pump For
Each starter comprising of 2.5-4A TPN MPCB with adjustable overload & adjustable
short circuit, 12A contactor, Digital Ammeter, ASS, 32A/1A, Cl.-1.0, 10VA CT, Start,
Stop, Reset push Button, ON, OFF, trip Indications etc.
(7) 160 KVAR APFC POWER FEEDER: 2 NOS.
Each feeder comprising of 400A TPN TM MCCB, 50kA with Digital Ammeter with ASS,
CT, Indicating lamp,SP MCB etc.complete in all respects.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
(8) 63A TPN TM MCCB FEEDER : 4 Nos. (1 no. PDB, 1no. for EOT crane at PH, rate incl in
2nos. for spare) above price
Each feeder comprising of 63A TPN Thermal Magnetic (TM) MCCB, with indicating
(9) 32A TPN TM MCCB FEEDER : 4 Nos. (2 no. Dewatering Pump, 2 nos. Spare)
Each feeder comprising of 32A TPN Thermal Magnetic (TM) MCCB, with indicating
(10) 63A TPN TM MCCB FEEDER FOR ALL MCB FEEDERS: 2 sets:
Incomer: 63A TPN Thermal Magnetic (TM) MCCB, with indicating lamp etc.
10.1) 6 nos. 32A 'C' curve 4P MCB feeders (for 1 no. Ind LDB, 1 no. for ICP/PLC Panel,
1 no. EOT Crane, 1 no. Exhaust Lighting, 2 nos. Spare)
10.2) 1 no. 32A 'C' curve 4P MCB with Time switch,32A contactor 4P,ON lamp feeders
(for Outdoor LDB)
10.3) 4 nos. 16A DP MCB feeders for 1-phase supply (1 no HT Panel, 2 no. X'mer
marshaling box(trans-1, trans-2 & 1 nos. Spare)
10.4) 6 nos. LCS (PBS) with 16A FP MCB, indicating lamp,Push Button, A/M,L/R
swithc, SP MCB, etc. ( 4 nos. Screen Hoist, 2 no. Sluice Gate)
Note : For Actuator LCS (PBS) shall be provide potential free contact for
(open,close,trip & L/R ) indication and terminal for Open,close and stop command
because actautor shall be operator from PLC Panel also in addition to LCS (PBS).
(11) Multiplication relay as required for dry run protection of pumps.
NOTE: 1). All MCCB shall be 50KA, Ics = 100% Icu, inbuilt protection with adj O/L and
Adj.S/c (LSIG for MP MCCB),Extended rotary handle, Terminal spreader, Auxiliary
Change over contact and trip contact as required.2) All MFM, ACB, Soft
Starter,MPR,Temp.Scanner etc shall be with inbuilt RS
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.2 SITC of 160 KVAR at 415V, APFC Panel,compartmentalised, Floor mounted, extensible 2 Set 4,61,976.70
type on both sides with Horizontal bus bar arrangement as per site requirement & complete
in all respects as per SLD / Specification / IS and including following as minimum:
1.1 400A, TPN, 50 KA TM MCCB with Digital Voltmeter with VSS, Digital Ammeter
with ASS, Resin Cast CT- Cl : 1.0,10VA, A/M, L/R switch, Indicating lamps, Push
1.2 Microprocessor based APFC Relay,144sq.mm, 16 STEP with RS 485 with minimum
operating current 10mA.
2. OUTGOING CAPACITOR FEEDER:
Capacitor feeder of following rating comprising of TPN MCCB/MCB with ON & TRIP
Indication, Capacitor duty contactor,Heavy duty MPP / gas filled capacitor unit, A/M
Switch, ON Delay timer,ON / OFF Push button, ON, TRIP, Auto & Manual Indication
lamp etc. as per Tender SLD& Specification
2.1 25 KVAR FEEDER: 4 NOS
2.2 20 KVAR FEEDER: 2 NOS
2.3 5 KVAR FEEDER: 3 NOS
2.4 2 KVAR FEEDER: 2 NOS
2.5 1 KVAR FEEDER: 1 NO
2.6.Two nos. Vacant feeder suitable for 1-25KVAr and 1-20KVAr to be provided.
NOTE: 1. cooling/exhaust fan : Heavy duty 8" Metalic Housing and Metal Impeller /
Blade / Vanes of Minimum2nos. or higher as required at the top of the panel with
2. For Capacitors of rating ≤ 5 KVAr only, All types viz. APP/MPP/Gas Filled are
2.3 SITC of Lighting Distribution Board (LDB) as under: 2 Nos. 7,568.94
SITC of 3 Phase 4 Wire 4P, double door Prewired LDB each for Indoor Lighting &
Outdoor Lighting Suitable to house :
Incoming: 32A FP, ELMCB (30mA)
Outgoing: 20A SP MCB (9 nos.) & 16A SP MCB (9 nos.)
2.4 SITC of Aux-Power Distribution Board (PDB) as under: 1 No. 14,353.11
3 Phase 4 Wire TPN, 8way Pre-wired-MOG / MOV PDB for Auxiliary accessories Load
power supply (Aux. supply & Rest spare)
Incoming: 63A TPN, MCCB
Outgoing: 8 nos. 32A 4P MCB 'C' Curve
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
2.5 SITC of LCS pushbutton station ON & OFF (E-stop) set complete with Enclosure, 5 Nos. 2178.82
necessary mounting/ fixing arrangement on wall / pipe support etc. to be installed near
motors for remote operation, etc. as per IS and specifications. (including structural steel)
2.6 SITC of stand / wall mounting type MS Junction Box, minimum 2.5mm thick, with 5 Nos. 5,080.00
detachable cable gland plate of 3mm thick, duly powder coated, with earthing terminals,
steel structure stand for mounting of JB, etc. for Jointing/Termination suitable for 1.1 kV
Submersible Flexible Copper Power & control cable with Aluminium/ Copper
armoured power cable from PMCC . Scope shall include providing suitable rating AL
bus bars, Support insulators, Crimping type lugs,nuts,bolts,washers etc. complete in all
respects as instructed by E.I.C. Drawing shall be got approved before Supply &
commissioning of the same. Lugs of cables shall not be connected directly. (Structure
steel for Stand shall be measured separately)
JB of minimum Size: 900mm x 900mm x 100mm or higher as required.(for Subm. Pump)
3.1(a) LOW VOLTAGE (LT) CABLES 50 Mtr. 923.00
Supply, laying , testing and commissioning of 1.1 kV, A2XFY(X)/2XWY(X) XLPE
insulated (IS 7098) AL / Cu stranded conductor, Extruded inner sheath cables as per
specification & IS.
The cable when laid outside the building shall be laid underground in trench with brick &
sand protection/in DWC pipes as per specified method and shall be laid in prepared
trench/ on cable tray when laid inside the building.
Supply of 3.5C x 300 sq. mm. A2XFY(X) Cable (1 run for PMCC Panel to 2 no. APFC
3.1 Laying, testing and commissioning of above cable 50 Mtr. 31.00
3.2(a) Supply of 3.5C x 240 sq. mm. A2XFY(X) Cable (3R from new tr. To PMCC Panel) 150 Mtr. 753.00
3.2(b) Laying, testing and commissioning of above cable 150 Mtr. 31.00
3.3(a) Supply of 3C x 50 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 5nos. 300 Mtr. 171.00
Proposed 75 kW Pump motor JB)
3.3(b) Laying, testing and commissioning of above cable 300 Mtr. 8.00
3.4(a) Supply of 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. Outdoor LDB, 400 Mtr. 112.11
1no. PDB, 1 no. EOT at Pump House 4 nos.for screen hoist, 2 nos. for Dewatering pump)
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
3.4(b) Laying, testing and commissioning of above cable 400 Mtr. 12.12
3.5(a) Supply of 4C x 2.5 sq. mm. 2XWY(X) Cable (5 nos. MOV at pump Delivery, 2nos 350 Mtr. 259.57
MOG at Inlet, 1 no.for ICP)
3.5(b) Laying, testing and commissioning of above cable 350 Mtr. 10.10
3.6(a) Supply of 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (For 2 nos. Tr. Marshalling 150 Mtr. 166.65
Box, 2 nos. APFC CT)
3.6(b) Laying, testing and commissioning of above cable 150 Mtr. 10.10
3.7(a) Supply of 5C x 2.5 sq.mm. 2XWY(X) Cable (For 5nos. Pump-Motor LCS) 150 Mtr. 210.00
3.7(b) Laying, testing and commissioning of above cable 150 Mtr. 10.50
3.8(a) Supply of 10C x 2.5 sq.mm. 2XWY(X)Cable (2 Run Tr. to HT Panel control cable) 200 Mtr. 480.00
3.8(b) Laying, testing and commissioning of above cable 200 Mtr. 24.00
3.9(a) Supply of 12C x 1.5 sq.mm. 2XWY(X) Cable (5 nos. MOV at pump Delivery, 2nos MOG 350 Mtr. 350.00
3.9(b) Laying, testing and commissioning of above cable 350 Mtr. 17.50
4.1 CABLE END TERMINATION AND CONNECTION: 4 Nos. 976.00
SITC of Double compression Ni-Plated brass cable glands and crimping type Bimetallic
lugs / sockets with necessary tools and equipment's as specified in specifications and IS.
The glands and lugs / sockets shall be suitable for cable size and type mentioned below &
as per specifications.
1) Earthing the glands and armouring with earthing clamp and jumper and also connecting
to common earth bar.
2) The job also includes, if necessary, supply & fixing of extension busbar of same
material on MCCB or panel board terminal / connector to connect more than one no. of
parallel cables or to connect higher size cable to lower size unit. The job also includes
earthing the glands and armour of the cable with common earth bar or flexible copper
mesh.(Cable termination qty. shall be as per site requirement)
SITC of 3.5C x 300 sq. mm. Cu. 2XFY Cable (1 run for PMCC Panel to 2 no. APFC
4.2 Same as above But, 3.5C x 240 sq. mm. A2XFY(X) Cable (3R from new tr. To PMCC 6 Nos. 838.00
4.3 Same as above But, 3C x 50 sq. mm. A2XFY(X) Cable (2R for each PMCC Panel to 20 Nos. 255.00
2nos. Proposed 75 kW Pump motor JB)
4.4 Same as above But, 4C x 6 sq. mm. A2XFY (X) Cable (For 1 no. Indoor LDB, 1 no. 18 Nos. 111.00
Outdoor LDB, 1 no. EOT at Pump House 4 nos.for screen hoist, 2 nos. for Dewatering
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
4.5 Same as above But, 4C x 2.5 sq. mm. 2XWY(X) Cable (5 nos. MOV at pump Delivery, 16 110.00
2nos MOG at sump Inlet, 1 no.for ICP)
4.6 Same as above But, 2C x 2.5 sq. mm. Multi strand 2XWY(X) Cable (For 2 nos. Tr. 8 65.65
Marshalling Box, 2 nos. APFC CT)
4.7 Same as above But, 5C x 2.5 sq.mm. 2XWY(X) Cable (For 5nos. Pump-Motor LCS) 10 180.00
4.8 Same as above But, 10C x 2.5 sq.mm. 2XWY(X)Cable (2 Run Tr. to HT Panel control 8 240.00
4.9 Same as above But, 12C x 1.5 sq.mm. 2XWY(X) Cable (5 nos. MOV at pump Delivery, 14 250.00
2nos MOG at sump Inlet)
5.1 CABLE TRAY 100 Mtr. 694.88
SITC of G.I. (hot dip galvanised ) Ladder type medium duty (2mm thick) Cable Tray
with necessary bends, tees, reducers, covers and clamps for fixing. All material shall be
Hot dip galvanised. All hardware shall be Electro-galvanized/ SS 304 complete in all
respects as per Specification. And including all accessories.
600 x 100 mm - Ladder type
5.2 300 x 100 mm - Ladder type 200 Mtr. 556.51
5.3 150 x 50 mm - Ladder type 300 Mtr. 276.00
6.1 CHEMICAL EARTHING SYSTEM 8 Set 10,593.89
SITC of Maintenance free chemical earthing (copper) with earthpit of minimum bore size
dia. 225mm Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-
3043:1987 /Tech spec. made of corrosion free Pipes having Outer pipe dia of 48 mm
having 250 Micron copper plating, Inner corrosion free Hot dip galvanised (80 to
micron) pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with
constant ohmic value surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical installation & of 3Mtr.
length of Pipe with two nos. 25Kg. bag of Back filling compound.. (2 nos. Each for 11 KV
HT Panel,Neutral of Tr.-1 & 2, ICP panel)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
6.2 SITC of Maintenance free chemical earthing with earthpit of minimum bore size dia. 10 Set 7,095.25
225mm Safe Earthing Electrode consisting Pipe-in-Pipe Technology as per IS-3043:1987
/Tech spec. made of corrosion free Hot dip Galvanised (min 150 Microns) Pipes having
Outer pipe dia of 76 mm , Inner corrosion free Hot dip galvanised (80 to 100 micron)
pipe dia of 26 mm with copper flat strip type connection terminal 14mm dia with
constant ohmic value surrounded by highly conductive corrosion resistant chemical
compound with high charge dissipation suitable for electrical installation & 3Mtr. length
of Pipe with two nos. 25Kg. bag of Back filling compound. (2 Nos. Each for Tr.1 & Tr.
Body, 2nos. for LT panel, 2nos. for Pump motor set & 2nos. for all elect. Equipments)
NOTE: Earthing Resistance value & date shall be painted on the chamber cover.
6.3(a) SITC of 50mm(w) x 8mm(T) etc. sizes as required, HOT dip galvanized GI Strip 936 Kg. 77.77
including supply & fixing using GI spacers, saddles when laid inside the building and
inclusive of excavation & refilling of earth when laid outside the building &
interconnection with earth pit & all electro-mechanical equipments.
(50X8 G.I Strip wt.3.12 kg/m, 3.12x300Mt.=936kg.)
6.3(b) Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes as required, HOT dip 120 Kg. 77.77
galvanized GI Strip including supply & fixing using GI spacers, saddles when laid inside
the building and inclusive of excavation & refilling of earth when laid outside the building
& interconnection with earth pit & all electro-mechanical equipments. (25X3 G.I Strip,
6.3(c) Supply, laying and erection of 25mm(w) x 3mm(T) etc. sizes Copper Strip including 38 Kg. 794.87
supply & fixing of bolts, saddles when laid inside the building and inclusive of excavation
& refilling of earth when laid outside the building & interconnection with earth pit & PLC
Panel (25X3 Cu. Strip, 0.761 Kg/m, 0.761 x 50 mtr.=38.05Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual eqp.
Bitumen shall be used at the place of joint/welding. (For PLC Panel to Earthing)
6.3(d) Supply, laying and erection of 40mm(w) x 6mm(T) etc. sizes Copper Strip including 113 Kg. 794.87
supply & fixing of bolts, saddles when laid inside the building and inclusive of excavation
& refilling of earth when laid outside the building & interconnection with earth pit & Tr.
nutral. (40X6 Cu. Strip, 1.88 Kg/m, 1.88 x 60mtr.=112.8Kg.)
Copper Bolt,Nuts ,Washers shall be used for Connecting Earth electrode to individual eqp.
Bitumen shall be used at the place of joint/welding.
6.3(e) SITC of HOT Dip Galvanized iron strip wire 8 SWG (For LDB, LCS, etc.) 31 Kg. 77.77
(8 SWG G.I Strip, 0.103 Kg/m, 0.103 x 300Mt.=30.9)
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.1 INTERNAL WIRING 100 Mtr. 78.78
SITC of Mains & outlet points wiring with 1.1 kV grade FRLS PVC insulated ISI marked
flexible stranded copper conductor wires with medium class min. 25mm. dia. Rigid PVC
pipe and accessories to be erected concealed in / to be run on surface / wall / ceiling with
following sizes as mentioned below. The unit rate wirings shall be with connector, PVC
junction box, wires, holder, ceiling rose, angle holder, switch, sockets, switch board, brass
chromium / cadmium plated machine screws, phase and neutral wires, green Earth
continuity wires etc. as required to complete wiring from LDB panel to the final outlet
termination points. The wiring shall be as per IS:732, IS:4648 and as per tender
specification / IS.
(a) SITC of Mains wiring with 3 wire 1.5 sq.mm.
7.2 As per Sr. No.-9.1 (b) SITC of Mains wiring with 3 wire 2.5 sq.mm as per tender 150 Mtr. 96.96
specification & IS.
7.3 As per Sr. No.-9.1 (c) SITC of Mains wiring with 4 wire 1.5 sq.mm as per tender 200 Mtr. 86.86
specification & IS.
7.4 As per Sr. No.-9.1 (d) SITC of Mains wiring with 4 wire 2.5 sq.mm as per tender 250 Mtr. 120.19
specification & IS.
7.5 SITC of Point wiring for Light / fan / Bell / Primary Point with 2nos. 1.5 sq. mm & earth 58 Nos. 329.26
wire of 1.5 sq. mm (green) both are of ISI marked 1.1 kv grade FRLS PVC insulated
multistrand copper wires , pipe to be erected concealed in flushed on wall / ceiling,
complete with 6A Tissino Type ISI marked flush type switch / bell push & accessories
erected on metal / PVC Box covered with 3 mm thick PC (Polycarbonate) / Acrylic sheet
with necessary lamp holder / ceiling Rose / H. D. connector as directed with medium class
Rigid PVC pipe & accessories.
7.6 SITC of 6A independent Plug with 2nos. 1.5 sq.mm Cu. Mains size wiring & earthwire of 5 Nos. 290.88
1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated multistrand
copper wires with medium class Rigid PVC pipe and accessories to be erected on wall /
ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type switch erected with
earth continuity connection erected on Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
7.7 SITC of 6/16A independent Plug with 2nos. 4 sq.mm Cu. Mains size wiring & earthwire 5 Nos. 570.65
of 1.5 sq.mm (green) both are of ISI marked 1.1 KV grade FRLS PVC insulated
multistrand copper wires with medium class Rigid PVC pipe and accessories to be erected
on wall / ceiling, complete with ISI marked 3 / 5 Pin socket and tissino type switch erected
with earth continuity connection erected on Metal / PVC box covered with 3 mm thick
PC(Polycarbonet) / Acrylic sheet.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
7.8 SITC of Single Phase 20A 3 Pin Matal clad Industrial Type Socket with plug top and 5 Nos. 820.00
20A SPMCB, suitable for flush mounting, in 16 SWG MS box of suitable size and
covered with 3 mm thick electrical grade hylam sheet or eqivalent ISI marked Electrical
grade bakelite sheet and earthing with 2.5 sq.mm insulated copper wire run inside the
conduit including interconnections etc. complete as required.
7.9 SITC of One 300/380 mm dia. Ex fan 16A independent Plug point near Ex. Fan with 2nos. 11 Nos. 570.65
4 sq.mm Cu. Mains size wiring & earthwire of 1.5 sq.mm (green) both are of ISI marked
1.1 KV grade FRLS PVC insulated multistrand copper wires with medium class Rigid
PVC pipe and accessories to be erected on wall / ceiling, complete with ISI marked 3Pin
socket and tissino type switch erected with earth continuity connection erected on Metal /
PVC box covered with 3 mm thick PC(Polycarbonet) / Acrylic sheet. Plug point shall be
7.10 SITC of 380mm sweep 1400 R.P.M exhaust fan, capacitor type, having double ball 11 Nos. 3,082.52
bearing, M.S.blades, mounting frame, forearms, suitable to operate on 230V,50 HZ AC
supply conforming to IS: 2312.Fan shall be painted with epoxy grey colour controlled by
one 6 A flush type switch on board and 6A plug point near Ex. fan.
8.1 LED LIGHT FIXTURES & LIGHTING: 20 Nos. 589.84
SITC of Indoor wall mounting 20Watt or up to 25% higher wattage LED 4 feet Tube
Light indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assembled on single
MCPCB, with housing used as a heat sink shall be made of thick sheet Steel conforming
to IS: 513/CRCA polyester powder coated and high U.V. & corrosion resistance with
diffuser and/or Polycarbonate optics with company mark/name
120 to 300 V,Power Factor more than 0.9, THD < 10 %,
CCT 4000 K to 6500K, Uniformity ratio >0.7,
Luminaire efficacy> 85 lumens/watt
LED driver efficiency > 85 %
(Each fitting required LM-79 & LM-80 Certificates)
Tube Light with integral / non-integral driver, Surge-4KV,IP-20, 4 feet, Cat-III
8.2 Item description as per Sr. No. 8.1.1 SITC of 7 watts LED Lamps integral type,cool 5 Nos. 220.18
white with PC diffuser suitable for B22 LAMP holder.
8.3 1200mm sweep ceiling fan, capacitor type, having double ball bearing 450mm down rod, 3 Set 1,596.81
canopies, shackle, rubber bush, blades, electronic speed regulator, suitable to operate on
230V,50Hz AC supply conforming to IS: 374/1979.Fan shall be painted with white colour.
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
8.4 SITC of 70W LED Surface / Wall mounted LED Flood Light fittings with High power 20 Nos. 6,088.28
White LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more
than 130 lm/w and corrosion free High pressure die cast aluminum housing with smooth
finish powder coated and heat sink extruded aluminium with diffuser and Polycarbonate
optics/ lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Indoor use: ( Pump House)
8.5 SITC of 'B' class galvanised iron pipe 32 mm outside dia 45 cms long duly welded on 20 30 Nos. 558.53
cms x 20 cms x 3 mm thick M.S. base plate, erected on wall or corner for mounting
luminaire with necessary hardware materials duly painted for wall mounting indoor flood
light fixtures on Wall of Buildings & post top lantern.
9.1 EXTERNAL LIGHTING (Flood LIGHT): 10 Nos. 7,266.95
SITC of 100W LED Wall mounted LED Flood Light fittings with High power White
LEDs wattage of 1Watt and above assembled on single MCPCB, efficiency more than
lm/w and corrosion free High pressure die cast aluminum housing with smooth finish
powder coated and heat sink extruded aluminium with diffuser and Polycarbonate optics/
lenses with company mark/name engraved or embossed
120 to 300 V,Power Factor more than 0.95, THD < 20 %, CCT 5000 K to 5700K,
Uniformity ratio >0.45, Luminaries efficacy> 85 lumens/watt . LED driver efficiency >
( Each fittings required LM-79 & LM-80 certificates)
(IP-65), Surge -4KV Cat-III
For Outdoor use: (area lighting)
10.1 SAFETY ACCESSORIES 1 No. 8,671.86
SITC of following safety accessories complete with necessary fixing brackets, other
accessories and tools etc. as required to complete the job.
Supply & Erecting carbon dioxide (CO2) fire extinguisher of 6.5kg capacity with
necessary clamps made from 50 x 6 mm M.S. Flat with nut & bolts grouted in wall
(For 1 no. for LT Room cum Pump House)
10.2 Supplying of standard first AID box with antiseptic cream, medicine for use on wounds 1 No. 299.97
due burn, crepe bandage, gauge bandage, medicated ready to use bandage (Band-aid)
adhesive tape for medicinal user, scissors, antiseptic solution (Savlon or similar) etc. (1 no.
for LT Room cum Pump House)
ITEM DESCRIPTION QTY UNIT RATE AMOUNT
10.3 Supply & fixing of printed instruction (First Aid) Chart both in English and Gujarati and 1 No. 130.29
duly framed with front glasses, for treatment of person suffering from electric shock. (1 no.
for LT Room cum Pump House)
10.4 Supplying & fixing of floor mounting stand for keeping four nos. of FIRE buckets 3 Nos. 1,798.81
comprising 1500 mm in length, 900 mm height frame made out of 30mm X30 mm X
mm angle iron with cross supports for legs, welded with 4 hooks and duly painted with one
coat of red lead and two coats of approved enamelled silver paint. (HT Panel, Tr. 1&2)
10.5 Supply and fixing of 20 W fluorescent lamp operated emergency light with maintenance 1 No. 2,540.00
free battery for 3 hours operation during mains power failure.
(1 no. for LT Room cum Pump House)
10.6 Supply and laying of Synthetic Insulating Mat of Class - A of min. thickness 2mm as per 20 Sq.mt 1,027.17
IS:15652 and with good electrical insulation property for 1.1KV/3.3KV as per site r.
requirement. (For LT Panel)
10.7 Providing pair of rubber hand gloves ISI make suitable for working on 22 KV supply 2 Nos. 214.12
B TOTAL OF ELECTRICAL WORKS WITHOUT GST
SCHEDULE OF QUANTITIES AND RATES FOR SITC OF ELECTRO-MECHANICAL WORKS WITH 3 YEARS O&M FOR EXISTING W-5 SPS
AT USMANPURA - SABARMATI RIVERFRONT OF AMC.
(C) OPERATION & MAINTENANCE
The works of this schedule comprises of the supply of all spare parts as required including the supply of all labour (including reliever to ensure presence of specified
type and no. of manpower per shift), materials, consumables (except electrical power), equipments, tools and tackles and comprehensive operations and
maintenance of W-5 SPS of AMC during the 3 Year of O & M from the date of successful commissioning as shown in table below.
Item No. Rate per Amount
Item of Work Duration Unit
1.0 Staff Salary
1.1 During First year 12 Months 1,13,226
The work of this schedule comprises of deployment of all operating crew/labour
(including reliever to ensure presence of specified type and no. of manpower per shift) at
Ex. SPS of AMC during 3 Years of O & M from the date of successful commissioning as
shown in table below.
Total staff salary for First years for Operation and security, repairing and maintenance for
the complete year period.
a) Pump operator - (ITI-Wireman/Eletrician) (3 nos - One for each shift of 8 hrs.)
b) Security cum Helper - (10th pass-of age < 45 years) (3 nos. - One for each shift of
1.2 Total of Manpower for Second Year (5% of Escalation on previous year) 12 Months 1,18,888
1.3 Total of Manpower for Third Year (5% of Escalation on previous year) 12 Months 1,24,833
2.0 Comprehensive Maintenance
2.1 Comprehensive repairing, supply of spares and maintenance of entire works in existing 12 Month -
SPS alongwith administration & management charges including running office, cost of
lubricants, consumables, spares, tools & tackles, statutory periodical approvals & testing
of eqipment etc. required in all except supply of electric power and sewage during O&M
period for First Year of O&M period.
(Covered under Defect Liablity Period for First Year)
Item No. Rate per Amount
Item of Work Duration Unit
2.2 Total of Comprehensive Maintenance, repairing, Spares, Consumables etc. for entire 12 Month 28,252
works in existing SPS including Proposed as well as all existing Electro-Mech.
equipment’s, for second year of O&M period.
2.3 Total of Comprehensive Maintenance, repairing, Spares, Consumables etc. for entire 12 Month 29,665
works in existing SPS including Proposed as well as all existing Electro-Mech.
equipment’s for Third year of O&M period (5% of Escalation on previous year)
3.0 Operation, Comprehensive repairing and maintenance for 10 months (during 10 Months 1,48,170.50
Upgradation Phase) of existing SPS during installation, testing commissioning of
Proposed Electro-mech. & Inst. equipment’s etc.
C TOTAL OF O&M FOR 3 YEARS WITHOUT GST