Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAccepted-AOC | ₹4.3 Cr | L1 | Accepted-AOC L1 bidder |
| 2 | L2₹4.4 Cr+₹16.9 L (3.97%)Rejected-Finance 66 102 ARUN JYOTHI MULLASSERY CANAL ROAD ERNAKULAM KOCHI 682 011 | KOCHI | ERNAKULAM | KERALA | 682011 | ₹4.4 Cr+₹16.9 L (3.97%) | L2 | Rejected-Finance L2 bidder |
Tender Value
₹4.8 Cr
EMD Value
₹1 L
Closing Date
6 Jan 2020, 3:00 pmClosed
General Manager
KITCO Ltd P.B.No 4407 Puthiya Road NH Bypass Vennala Kochi 682028
Setting up of Medical College at Painavu Idukki Electrification works for the Residential facilities
2019_KITCO_328864_1
HFWD/KITCO/EL/06/2019
Open Tender
Electrical Works
Item Rate
240 days
Painavu Idukki
As per NIT
7 documents required · 7 mandatory
₹8,850
Yes
KITCO Ltd
₹1 L
Yes
30 Dec 2020
11 Dec 2019
9 Jan 2020
11 Dec 2019
6 Jan 2020
16 Dec 2019
11 Dec 2019 - 14 Dec 2019
Amount
HT EQUIPMENTS
od75620/2019_2020 : 315 KVA 11KV Unitized Substation;Design, fabrication, supply,installation testing commisioning of indoor type Packaged (Unitized) Substation enclosure consiting 315 kVA, 11kV/433V 3 Ph, 50 Hz, vector Dyn -11, dry type, Transformer with IP23 enclosure, winding temperature alarm and trip, necessary louvers,all standard fittings and accessories, LV chamber suitable for termination of 300sq mm cables, necessary power and control cabling for alarm, tripping indication, all required internal cabling etc complete and as per specifications in all respects.The rate shall be inclusive of all materials, lead, lift etc. complete as per single line diagram technical specification. Minor civil works included in the scope. HT Compartment 11kV, 630A, 21kA VCB for 3 sec with spring charging motor rated for 230V AC , tripping coil and closing coil rated for 24V DC-1 No. 630 Amp continously rated Al busbar Self powered microprocessor based three phase over current and earthfault relay with protection CTs - 1 set Transformer Compartment315 kVA, 11kV/433V 3 Ph, 50Hz, dry type, vector Dyn -11 Transformer, copper wound, laser scribed core, Class F insulation, indoor distribution Transformer with forced cooling. The transformer shall have Delta on HV side and Star on LV side with off load tap changer range: + 5% to -5% in steps of 2.5%. The transformer shall also have suitable enclosure including supply and fixing of neutral CT of 100/5A 15VA 5P10 on earthed star point with connector for connection to Earth Fault relay in HT/LT LT Chamber Suitable for terminating LT XLPE cables. The rate quoted shall be inclusive of required foundation, mounting etc.
od75621/2019_2020 : 11kV Outdoor RMU panel-1 (Extensible Type) Design, Fabrication, Supply, Installation Testing and Commissioning of 11KV electrically Operated 21kA for 3 sec, 630A SF6 Insulated,Ring Main Unit outdoor type (IP-54) with 2 nos Load break switch as incomer and 1 no motorized VCB (fully rated earth switch) with fully encapsulated vacuum interrupter panel as outgoings, 630 Amp continously rated Cu busbar complete with all accessories, protective relays, indicators,battery and battery charger, Manometer for indicating SF6 gas pressure with green zone marked on the scale,provision for padlocking for open, close, earth and test position etc. on a suitable foundation. The RMU must be both side extensible type .The rate quoted shall be inclusive of required foundation, mounting accessories, hoisting to its location,assembling of units,lining up, bolting the units and checking all control wiring complete as per single line diagram technical specification.
od75622/2019_2020 : 11kV Outdoor RMU panel-2 (Extensible Type) Design, Fabrication, Supply, Installation Testing and Commissioning of 11KV electrically Operated 21kA for 3 sec, 630A SF6 Insulated,Ring Main Unit outdoor type (IP-54) with 2 nos Load break switch as incomer and 2 nos motorized VCB (fully rated earth switch) with fully encapsulated vacuum interrupter panel as outgoings, 630 Amp continously rated Cu busbar complete with all accessories, protective relays, indicators,battery and battery charger, Manometer for indicating SF6 gas pressure with green zone marked on the scale,provision for padlocking for open, close, earth and test position etc. on a suitable foundation. The RMU must be both side extensible type .The rate quoted shall be inclusive of required foundation, mounting accessories, hoisting to its location,assembling of units,lining up, bolting the units and checking all control wiring complete as per single line diagram technical specification.
od75623/2019_2020 : HT Meteing Kiosk with Meteing Supply, installation, testing and commissioning of TOD meter KIOSK withTOD meter (with RS485 communication facility), CT(0.2S) and PT(0.2) ,test terminal block, control fuses,armoured copper cable between CT PT unit. The KIOSK shall be made out of 2mm thick CRCA sheet steel, totally enclosed, IP 65 with canopy, weather proof,undergone seven tank process,powder coated finish ,earthing,entire civil work including suitable foundation and all mounting accessories as required complete as per the rquirement of State Electricity Board. The metering cubicle shall have glass window for meter reading. 11kV, 21 kA, 630A Load Break Switch with earth switch - 1 no HT HRC fuse 50A - 3 nos Seal off Bushing - 1 set 11kV Outdoor CT(0.2S) and 11kV/110V PT(0.2) units-1set 30/5A ,110V Class 0.2s TOD meter- 1no Shunt trip coil, 230V AC - 1 set Space heater with thermostat - 1 set Suitably rated Aluminium busbars and support insulators ON-OFF indication- 1 set The rate is inclusive of transportation, insurance, lift, lead and all associated works. The panel shall be with bottom entry to receive incoming outgoing cable, all necessary interconnection accessories as per particular specification single line diagram.
od75624/2019_2020 : Supplying and filling the proposed yard with 40 mm size blue jelly of 150 mm thick including cost and conveyance of all materials, labour charges etc. complete.
od75625/2019_2020 : 11 kV DP structure Supply, Installation testing and commissioning of 11 KV DP structure using 200x100 mm ISMB for poles and cross channel of ISMC 100x50mm and supporting structure for 11 KV components with 65x65x6 mm MS angle bracings between consumer and supplier structure,cross arms,11 KV pin,disc and stay insulators, supports, jumpering / interconnecting conductors with '0'SWG Cu, anticlimbig arrangement using barbed wire,earthing etc. on a suitable concrete foundation including the civil foundation .The DP structure shall consists of the following (Note:All the MS items shall be hot dip galvanised) 11 KV,400A ,TP,AB switch - 1 No. 11 KV Lighting Arrestor -1 set of 3 Nos 11 KV DO fuses-1 set of 3 Nos
od75629/2019_2020 : 200 KVA 11KV Unitized Substation Design, fabrication, supply,installation testing commisioning of indoor type Packaged (Unitized) Substation enclosure consiting 200 kVA, 11kV/433V 3 Ph, 50 Hz, vector Dyn -11, dry type, Transformer with IP23 enclosure, winding temperature alarm and trip, necessary louvers,all standard fittings and accessories, LV chamber suitable for termination of 300sq mm cables, necessary power and control cabling for alarm, tripping indication, all required internal cabling etc complete and as per specifications in all respects.The rate shall be inclusive of all materials, lead, lift etc. complete as per single line diagram technical specification. Minor civil works included in the scope. HT Compartment 11kV, 630A, 21kA VCB for 3 sec with spring charging motor rated for 230V AC , tripping coil and closing coil rated for 24V DC-1 No. 630 Amp continously rated Al busbar Self powered microprocessor based three phase over current and earthfault relay with protection CTs - 1 set Transformer Compartment 200 kVA, 11kV/433V 3 Ph, 50Hz, dry type, vector Dyn -11 Transformer, copper wound, laser scribed core, Class F insulation, indoor distribution Transformer with forced cooling. The transformer shall have Delta on HV side and Star on LV side with off load tap changer range: + 5% to -5% in steps of 2.5%. The transformer shall also have suitable enclosure including supply and fixing of neutral CT of 75/5A 15VA 5P10 on earthed star point with connector for connection to Earth Fault relay in HT/LT LT Chamber Suitable for terminating LT XLPE cables . The rate quoted shall be inclusive of required foundation, mounting etc.
od75636/2019_2020 : Chain link fencing :Supply, Installation testing and commissioning of 1.8 mtr high chain link fencing over 600 mm high random rubble masonry as per drawing and specification, using 4 mm thick PVC coated chain link with a framework of 50x50x6 mm MS angle between vertical posts of ISMC 75 mm at 2400 mm interval, which are fixed to the concrete footing (1:3:6) of size 450x450x300 mm (above GL) with adequate footing depth, between the RR masonry. RR masonry (450 mm thick) and 300 mm from ground level for foundation plinth in cement mortar (1:6). The random rubble masonry is to be pointed using cement mortar 1:3 to have a flush finish. Earthing as per KSEI/KSEB standards shall be done around the periphery of the fencing.The MS frame work for chain link fencing is finished using zinc chromate primer 2 coats of synthetic enamel paint. 1.5 mtr wide gate shall be provided with suitable locking arrangements.The rate shall be inclusive of all materials, labour, lead, lift, etc including excavation works and fabrication and assembly works including all nuts, bolts other miscellaneuos items, etc. complete as per drawing.
PANEL BOARD AND ACCESSORIES
od75465/2019_2020 : DG PANEL (TYPICAL)Supply, Installation, Testing Commissioning of LT Switch Board (DG PANEL) ,cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. The Panel shall be of Form 4b Construction.Incomer160A, FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Meters4A, C curve SP MCB - 3 Nos.RYB indication lamp, LED type - 3 Nos.(0-500)V voltmeter, Acc. class 1 with 90 deg defl. scale - 3 Nos(0-160)A ammeter Acc. class 1 with 90 deg defl. scale - 3 Nos.160/5A 5VA class 1 resin cast CT - 3 NosDigital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos. Type 1&2 SPD - As mentioned in SLD. Busbar160A TPN busbar chamber with Aluminium busbar.Out goings100A,TP+NL 35kA MCCB with thermal based adjustable release with OL SC protection - 3 Nos.
od75468/2019_2020 : SSB QUARTERS -1 (TYPICAL PANEL ) Supply, Installation, Testing Commissioning of LT Switch Board (SSB QUARTERS-1), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification.Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer160A, FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 160A TPN busbar chamber with Aluminium busbar Outgoings3 phase kWh meter - 8 No.s40A HRC fuse with fuse link - 24 nosNeutral link - 8 no. s40A, FP MCB isolator - 8 nos40A TPN /2.5A SPN Automatic current changerover with current limiter(ACCL)-8NosAll outgoing feeders should have glass window for meter reading and locking facility.
od75473/2019_2020 : SB QUARTERS (TYPICAL PANEL ) Supply, Installation, Testing Commissioning of LT Switch Board ( SB Quarters) , cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing .Type 1&2 SPD - As mentioned in SLD. specification. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer320A, FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 320A TPN busbar chamber with Aluminium busbar Outgoings160A,TPN SDFU with necessary fuses - 2 No160/5 A 5 VA Class 1 CTs -3 NosThree Phase kWH meter-1 No, 160A FP MCCB Isolator - 1 No. 160A cutout fuse with fuse link and neutral link - 3 Nos. Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.
od75479/2019_2020 : MSB (Teaching Quarters 2 BHK )Supply, Installation, Testing Commissioning of LT Switch Board, MSB cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be lockable type as per requirements of EB.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.630A,FP 50kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.630A TPN busbar chamber with Aluminium busbar.Out goings3 phase 4 wire 415V, kWH meter -2 Nos100/5 A 5 VA Class 1 CTs -6 Nos100A HRC fuse with fuse link - 6 nosNeutral link - 2 nos 100A, TPN MCCB Isolator - 2 No400A TPN SDFU with necessary fuses - 2 NoNecessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility. Necessary relays for protection of transformer, control cabling etc. is in the scope.
od75482/2019_2020 : MSB (Non Teaching staff Quarters (2 BHK) -No.3)Supply, Installation, Testing Commissioning of LT Switch Board (MSB-Non Teaching staff Quarters (2 BHK) No.3), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc. .The panel shall be lockable type as per requirements of EB.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.Incomer160A,FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V,160A TPN busbar chamber with Aluminium busbar Outgoings63A HRC fuse with fuse link - 3 nos40A HRC fuse with fuse link - 24 nosNeutral link - 9 nos 40A, FP MCB isolator - 8 nos63A, FP MCB isolator - 1 nos3 phase 4 wire 415V, kWH meter -9 Nos40A TPN /2.5A SPN Automatic current changerover with current limiter(ACCL)-8Nos.Necessary relays for protection of transformer, control cabling etc. is in the scope.Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.
od75487/2019_2020 : SB PANEL- HOSTEL (TYPICAL)Supply, Installation, Testing Commissioning of LT Switch Board( SB Panel - HOSTEL ), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer250A,FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 250A TPN busbar chamber with Aluminium busbar Meters4A,C curve SP MCB-3nosRYB Indicating lamps LED type -3 Nos.(0-500)V Class 1 with 90 deg defl. Scale-3 Nos(0-250)A Class 1 with 90 deg defl. Scale-3 Nos250/5 A 5 VA Class 1 CTs -3 NosDigital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos.Outgoing100A, 25kA, TP+NL MCCB with thermal release and neutral link (Ics = 100% Icu = 25kA) - 2 Nos63A, 25kA, TP+NL MCCB with thermal release and neutral link (Ics = 100% Icu = 25kA) - 3 Nos
od76820/2019_2020 : SSB QUARTERS-2 ( TYPICAL) Supply, Installation, Testing Commissioning of LT Switch Board (SSB QUARTERS-2), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification..Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction..The panel shall be lockable type as per requirements of EB. Incomer 160A, FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos. Busbar 415V, 25kA, 160A TPN busbar chamber with Aluminium busbar Outgoings 40A HRC fuse with fuse link - 21 nos Neutral link - 7 nos 40A, FP MCB isolator - 7no 3 phase 4 wire direct reading type, 415V kWH meter- 7 No. Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.
od76821/2019_2020 : MSB- HOSTEL (TYPICAL) Supply, Installation, Testing Commissioning of LT Switch Board(MSB- HOSTEL), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification..Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction. Incomer 400A,FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos. Busbar 400A TPN busbar chamber with Aluminium busbar Meters 4A,C curve SP MCB-3 Nos RYB Indicating lamps LED type -3 Nos. (0-500)V Class 1 with 90 deg defl. Scale-3 Nos (0-400)A Class 1 with 90 deg defl. Scale-3 Nos 400/5 A 5 VA Class 1 CTs -6 Nos Digital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos Outgoings 250A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 3 Nos 100 A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 1 Nos
CABLE AND CABLING
od75448/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 400 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75454/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 300 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75457/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 240 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75461/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 185 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od77633/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 120sqmm cable
od75466/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 70 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75469/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 35 Sqmm Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date.
od75474/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 16 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75476/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 10 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od75485/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 2C 6sqmm Al
od75490/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 2.5sqmm Cu
od77635/2019_2020 : Supply of following sizes of XLPE insulated PVC sheathed, FRLS , Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date.. 12C 2.5 Sq.mm Al
9.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)
9.1.35 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)
9.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)
9.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)
9.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)
9.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)
9.1.30 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)
9.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)
9.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)
9.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)
od75503/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed copper conductor cable of 1.1 kV grade as required. 4C 2.5 sqmm Cu
od75505/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 3C 4sqmm Al
od77788/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 12 C X 2.5 sq. mm
7.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mm
7.1.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mm
7.1.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.2.1 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mm
7.2.4 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mm
7.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mm
7.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mm
7.5.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 95 sq. mm and upto 185 sq. mm
7.5.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 185 sq. mm and upto 400 sq. mm
7.6.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mm
7.6.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 35 sq. mm and upto 95 sq. mm
7.6.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mm
7.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.7.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.7.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
7.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)
7.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
7.8.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
7.8.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
14.13.1 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm dia
14.13.3 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm dia
od75517/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thickness
od75518/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thickness
7.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.
od75519/2019_2020 : Providing fixing Fire Barrier mortar with minimum 2 hours fire rating when tested in accordance with BS 476 part 20 and UL 1479 for horizontal openings in fire rated floors or slabs and vertical openings in walls for passing service shafts. The service lines could be of various types like electrical cables trays, metal pipes, GI Ducts for AC, etc.The mortar shall have minimum hardened density of 0.8 g/cm3 and It should have a compressive strength of 2.9N/Sq mm . The product shall be Smoke Air Seal and 30 years Age tested as per Dafstb and DIBT standards. The product shall be tested and approved by third party agencies such as UL and FM. The mortar should be tested in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall bear the UL and FM approval logo on the packing where applicable.
od75520/2019_2020 : Supply, fabricating and installing MS items such as Tees/ angles/ channels etc. on floor/ ceiling/ wall including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required
10.4.4 : Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mm
10.5.4 : Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
10.6.4 : Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mm
8.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mm
8.3.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mm
8.4.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mm
od75521/2019_2020 : Supply of following sizes of XLPE insulated PVC sheathed, FRLS , Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date. 3C X 300 sq.mm.
od75522/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3C 4 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.
od77645/2019_2020 : Providing, laying and fixing following dia RCC pipe NP 4 class (heavy duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching upto 1.5 m depth and refilling etc. as required. 300 mm dia
od77787/2019_2020 : Supply and fixing of chequered plate of 6 mm thick including cutting to required size using gas cutter and lay the same over the trench, fixing of nosing angle and supports for chequered plate, related civil works, finishing etc. and painting with two coats of enamel paint over one coat of Zinchromate primer as required.
WIRING AND ACCESSORIES
1.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
1.10.1 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
1.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group B
1.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
1.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.4 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
1.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.2 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.2 way 5/6 amps switch
1.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.24.6 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outlet
1.24.7 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outlet
1.24.8 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell push
1.55.3 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group C
1.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mm
1.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)
1.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.32 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mm
1.38 : Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
MCBs AND MCB DISTRIBUTION BOARDS
2.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
od75489/2019_2020 : Supply and fixing outdoor type START/STOP (2way) push button station (IP65) including all the necessary accessories as required complete with suitable mounting arrangement.(Cat No Hensel-PBS 0201 or equivalent approved make)
2.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple pole
od75500/2019_2020 : Supply and fixing of 40A DP Isolator in sheet steel enclosure with all other accessories as required complete
od78173/2019_2020 : Supplying and fixing following rating, four pole, 415 volts, MCCB in the existing DB complete with connections, testing and commissioning etc. as required. 100A FP MCCB 16 kA
od78174/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 way (8 + 18), Double door
od78175/2019_2020 : Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of160 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB., with provision of 100/125 amps TP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB./ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 Way
2.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double door
2.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
od75502/2019_2020 : Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C.curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
od75504/2019_2020 : Supply installation, testing and commissioning of DOL starter upto 5HP,3ph motor including auxilliary contactors, 2kVAR capacitor and all necessary accessories as required complete with single phase preventor, function indiaction etc.
od75506/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 2 pole 25 amps. (230 Volts),30mA sensitivity.
od75507/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts),30mA sensitivity.
od75508/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts),100mA sensitivity.
od75509/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 63 amps. (415 Volts),100mA sensitivity.
od75510/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, horizontal type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • 8 way (8 + 24), Double door
od75512/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (8 + 24), Double door
od75515/2019_2020 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (8 + 12), Double door
od75516/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (8 + 12), Double door
od78144/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 12 way double door horizontal type SPN DB
od78145/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 4 way double door horizontal type TPN DB
od78146/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 8 way double door horizontal type TPN DB
od78147/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 6 way Vertical TPN DB (MCCB incomer)
od78148/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for vertical TPN DB (MCB incomer)
od78172/2019_2020 : Supplying and fixing following way,cable end box with all accessories as required compete for the following DBs-8 way double door horizontal type SPN DB
LIGHT FIXTURES AND FANS
1.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweep
od75449/2019_2020 : Installation, testing and commissioning of LED down lighter fittings on false ceiling with all mounting accessories as required complete including interconnections using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor as required.
od75452/2019_2020 : Supply and fixing of 12W LED lamp in the angle holder including all necessary accessories and connections as required complete suitable for 230V, 50 Hz, AC supply
od75462/2019_2020 : Supply of LED Street Lighting luminaire of IP65 protected, pressure die cast aluminium housing body with optimal heat sink, with system wattage less than 40 (+/-5)W with rated life of L70 @ 50,000 hours, CRI greater than or equal to 70 and system efficacy greater than or equal to 90%. The luminaire shall be mounted on GI pipe with 0.5m overhang and necessory accessories and connection.Make Wipro skyline LR02-451-XXX-57-XX or CG LSTS-40-CDL or equivalent approved make
od75464/2019_2020 : Supply of LED surface mounted down light made of die cast aluminium with proper diffusers, along with driver,system wattage of 18+/-2 Watts,lumen output of lamp greater than 1800 lumens, power factor > 0.9, rated life of L70 @ 50,000 hours, system efficacy greater than 100lumen/watt and including all necessary accessories as required complete.Make:- PHILIPS DN 395B LED20S-6500 PSU WH or WIPRO LD901-231-XXX-65-XX or CG LCDN-18-CDLL or equivalent approved make
od75470/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser ,along with driver,system wattage of 20+/-2 Watts,lumen output of lamp greater than 1500, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 80lumen/watt and including all the necessary accessories as required complete.Make:-PHILIPS BN021C LED20S PSU CW GR S2 or WIPRO LL20-221-XXX-65NE3 or CG LCTL 18 CDL or equivalent approved make
od75478/2019_2020 : Installation, testing and commissioning of pre - wired,LED/ fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
od75484/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser,along with driver,system wattage of 10+/-2 Watts,lumen output of lamp greater than 800, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 80lumen/watt and including all the necessary accessories as required complete.Make:- PHILIPS BN 021 LED10S- 6500 PSU GR S1 or WIPRO LL20-111-XXX-65NE3 or CG LCTL 9 CDL or equivalent approved make
1.45 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standardlength (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable,including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
od75492/2019_2020 : Installation, testing and commissioning of High bay/LED/ FLOOD type fittings on wall/Column/truss/false ceiling using suitable MS clamps, nuts, bolts/ 20mm heavy duty GI chain/ pipe (upto 50cm)etc including connections with 3C 1.5 Sq.mm PVC insulated flexible copper conductor cable as required.
1.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
1.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required.
od75496/2019_2020 : Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton Brisk Air or equivalant approved make)
od75497/2019_2020 : Supply of 380 mm sweep heavy duty exhaust fan indie cast aluminium with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton EXHD-380-6-1 or equivalant approved make)
od75498/2019_2020 : Supply of following sizes of 1200 mm sweep. 5 star rated ceiling fan, with double ball bearing, Aluminium pressure die cast body with Aluminium blades, canopies, hanging shackle, 30 cm down rod and without speed regulator suitable for 240V 50 HZ, AC supply confirms to IS 374/1979 as required complete. (Make crompton-Entrust 50 or equivalent approved make).
od75499/2019_2020 : Supply of indoor industrial surface mounted LED tube with Batten along with driver , surge protector,,system wattage of 40+/-4 Watts(2x20 watts),lumen output of lamp greater than 3000 lumen, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 70lumen/watt and including all necessary accessories as required complete.Make:- Cat No: Wipro WIO922208 + 2 Nos. of 18W LED Tube Light or Crompton Greaves IGP132LT8-16+LT8-20
EARTHING AND SAFETY EQUIPMENTS
2.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
2.22 : Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
od75444/2019_2020 : Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete on wall.
od75450/2019_2020 : Supply and fixing anodised aluminum glass framed shock treatment chart.
od75455/2019_2020 : Supplying of Rubber hand gloves suitable for 1.1 KV.
od75456/2019_2020 : Supply and fixing of First aid box
od75459/2019_2020 : Supplying and laying 6.00 mm GI conductor (4 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)
od75467/2019_2020 : Supplying and laying 4.00 mm GI conductor (8 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)
od75471/2019_2020 : Supplying and laying 3.15mm Cu (10 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)
od75472/2019_2020 : Supplying and laying 32mmx6mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)
od75477/2019_2020 : Supplying and laying 50mmx6mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)
od75481/2019_2020 : Providing and fixing 6.00 mm GI conductor (4 SWG) on surface or in recess for connections etc. as required.
od75483/2019_2020 : Providing and fixing 4.00 mm GI conductor (8 SWG) on surface or in recess for connections etc. as required.
od75486/2019_2020 : Supply providing 10 SWG Cu wire on surface/recess using saddles
od75488/2019_2020 : Providing and fixing 50mm x 6mm GI tape (2.4kg/ mtr) on surface or in recess for connections etc. as required.
od75491/2019_2020 : Supply and installation of all the materials required for maintenance free earthing system including 3 mtrs length,17.2mm dia or above 250 microns molecularly copper bonded steel rod with stainless steel connectors and fasteners for connecting earth strip, earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound) and providing masonry enclosure with heavy duty CI cover plate of 300X300 mm having locking arrangement.
5.6 : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
od75493/2019_2020 : Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat(2mx1mx2mm thick ) as per IS:15652
od78185/2019_2020 : Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat as per IS:15652.forthe following sizes. 2mx1mx2.5 mm thick
od75494/2019_2020 : Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt spring washer spaced at 50mm)
od75495/2019_2020 : Providing and fixing 25 mm X 3 mm copper strip on surface or in recess for connections etc. as required.
5.9 : Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
5.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
od75501/2019_2020 : Providing and fixing 32 mm X 6 mm G.I. Tape (1.475 kg/mtr) on surface or in recess for connections etc. as required.
LIGHTNING PROTECTIONS
od75442/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as vertical down conductor with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on surface as needed.
od75443/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors ,glue, expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on sheet roof
od75446/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on parapet
6.14 : Providing and laying G.l. tape 32 mm X 6 mm from earth. electrode directly in ground as required.
od75463/2019_2020 : Providing and Fixing of Test Joint , suitable to fix 8 mm Aluminium conductor to 32 X 6 GI strip
DG SETS AND ANCILLERIES
od75963/2019_2020 : 30KVA DG SET Supply, Installation, Testing and Commissioning of outdoor 30kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering,controls and interlocks, CTs and transducers for all metering and protection and suitable FP MCCB etc. , including antivibration mountings, exhaust silencer and exhaust pipe conforming to latest environment protection regulations for emission and noise levels complete with , water/ coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 30 KVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500RPM, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to BS: 2613 IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads,battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards Fuel tank , fuel piping from fuel tank to Engine, Residential silencer, suitable size Cable termination box with extended Alternator terminal with bus bars etc as required and as per specifications.Rate shall be inclusive of all the civil work including RCC foundation. The work should be as per Electrical Inspectorate/ Pollution control board standards.
od75964/2019_2020 : 100KVA DG SET Supply, Installation, Testing and Commissioning of outdoor 100kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering,controls and interlocks, CTs and transducers for all metering and protection and suitable FP MCCB etc. , including antivibration mountings, exhaust silencer and exhaust pipe conforming to latest environment protection regulations for emission and noise levels complete with , water/ coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 100 KVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500RPM, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to BS: 2613 IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads,battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards Fuel tank , fuel piping from fuel tank to Engine, Residential silencer, suitable size Cable termination box with extended Alternator terminal with bus bars etc as required and as per specifications.Rate shall be inclusive of all the civil work including RCC foundation. The work should be as per Electrical Inspectorate/ Pollution control board standards.
National Electric Co
Bidder Name
Power and Instrumentation Guj. Ltd.
National Electric Co
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .