Loading…
Loading…
Tender ID
Tender Value
₹35.4 L
EMD Value
₹35,380
Closing Date
7 Feb 2026, 6:00 pmClosed
Executive Engineer, Public Health Mechanical Division Rajkot
ITC of SCF pumpset and SITC of electro-mechanical item at Khirai HW & NC-6 GWIL HW under Khirai Group RWSS (Part of MMJ RWSS)
271746
45/2025-26 3rd attempt
Open
Pumps/Motors
Works
Rajkot
9 documents required · 8 mandatory · 1 optional
₹1,500
Yes
Executive Engineer, Public Health Works Division, Morbi
₹35,380
Yes
31 Jan 2026
31 Jan 2026
31 Jan 2026
7 Feb 2026
31 Jan 2026
ABSTRACT Of Schedule-B
Name of Project :Khirai Group RWSS (Part of MMJ RWSS)
Name of Work : ITC of SCF pumpset and SITC of electro-mechanical item at Khirai HW & NC-6 GWIL HW under Khirai Group RWSS (Part of MMJ RWSS)
Estimated Cost Rs.
Sr. Name of Head Types Of
Section. Duty Point - Pump Type Elec Sec. Total Rs. Total Rs.
No. Works Pump Mech Sec. (A)
Khirai to khakhrechi Section SCF 61 LPS X 32 Mts.X 30 KW ( 1W + 1S )
1 Khirai HW Khirai to ESR Section SCF 61 LPS X 32 Mts.X 30 KW ( 1W + 1S )
Khirai to Moti Barar Section SCF 98 LPS X 55 Mtr X 82.5 KW ( 1W + 1S ) 2032366.89 1505098.92 3537465.81
2 NC-6 GWIL sump to WTP Section 128 LPS X 16 Mts.X 30 KW ( 1W + 1S +1 Extra)
Estimated cost in words Rupees - :- thirty five lakh thirty seven thousand four hundred sixty six Only
Amount of my / our tender works out as under :
Estiamted Amount ( For Above) Rs.3537466.00 Estiamted Amount (for Below) Rs.3537466.00
Executive Engineer
P.H.Mechanical Division Rajkot
Name of Project :Khirai Group RWSS (Part of MMJ RWSS)
Name of Work : ITC of SCF pumpset and SITC of electro-mechanical item at Khirai HW & NC-6 GWIL HW under Khirai Group RWSS (Part of MMJ RWSS)
Name of RWSS : MMJ RWSS
Name of Head work: Khirai Head works and NC-6 GWIL Head works
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
(A)MECHANICAL SECTION
Installation, testing & commissioning of Submerged Centrifugal pump set (water immerrsed, dry air filled class F insulated
TEWC Motor intergrally mounted on volute casing pump set for water duty) 3 phase, 1450 RPM, 50 Hz ± 3%, 415 V ± 10% along
with suitable foundation / installed device with cable length from pump to junction box. Material of construction: Impeller :-
CF8M, Casing CIFG 260 Weiring Ring SS TC Mechanical seal, CS/S.S.bearing,S.S. Shaft with sleeve SS Strainer & MS Motor
Duty Point 61 LPS X 32 Mtr Head x 30 KW Khirai HW to Khakharechi (2 Set)
Installation, testing & commissioning of Submerged Centrifugal pump set (water immerrsed, dry air filled class F insulated
TEWC Motor intergrally mounted on volute casing pump set for water duty) 3 phase, 1450 RPM, 50 Hz ± 3%, 415 V ± 10% along
with suitable foundation / installed device with cable length from pump to junction box. Material of construction: Impeller :-
CF8M, Casing CIFG 260 Weiring Ring SS TC Mechanical seal, CS/S.S.bearing,S.S. Shaft with sleeve SS Strainer & MS Motor
Duty Point 61 LPS X 32 Mtr Head x 30 KW Khirai HW to ESR (2 Set)
Installation, testing & commissioning of Submerged Centrifugal pump set (water immerrsed, dry air filled class F insulated
TEWC Motor intergrally mounted on volute casing pump set for water duty) 3 phase, 1450 RPM, 50 Hz ± 3%, 415 V ± 10% along
with suitable foundation / installed device with cable length from pump to junction box. Material of construction: Impeller :-
CF8M, Casing CIFG 260 Weiring Ring SS TC Mechanical seal, CS/S.S.bearing,S.S. Shaft with sleeve SS Strainer & MS Motor
Duty Point 98 LPS X 55 Mtr Head x 82 KW Khirai HW to Barar (2 Set)
Installation, testing & commissioning of Submerged Centrifugal pump set (water immerrsed, dry air filled class F insulated
TEWC Motor intergrally mounted on volute casing pump set for water duty) 3 phase, 1450 RPM, 50 Hz ± 3%, 415 V ± 10% along
with suitable foundation / installed device with cable length from pump to junction box. Material of construction: Impeller :-
CF8M, Casing CIFG 260 Weiring Ring SS TC Mechanical seal, CS/S.S.bearing,S.S. Shaft with sleeve SS Strainer & MS Motor
Duti Point 128 LPS X 16 Mtr Head x 30 KW Khirai GWIL HW WTP Section (1 Set)
Supply at Site, Storage, Erection, Installation, Testing & Commissioning of following size individual Delivery & Header MS
Piping with specials with Suction Strainer, Flanges, Concentric Nozzles Bolts, Nuts, and Pipings with Y-Tee Connection
Flanges, Eccentric Nozzles etc. Complete. As per relavant IS and requirement.
(A) Khakharechi Delivery pipe - 200 mm Dia
(B) ESR Delivery pipe - 200 mm Dia
5 (C) Barar Delivery pipe - 250 mm Dia 6150 Kg. 98.00 9.80
(D) WTP Section Delivery pipe - 300 mm Dia
(E) Khakharechi Delivery Header Line - 300 mm Dia
(F) ESR Delivery Header Line - 300 mm Dia
(G) Barar Delivery Header Line - 350 mm Dia
(H) WTP Delivery Header Line - 400 mm Dia
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Supply, testing & Commissioning of flange ends Expansion Bellow as per EJMA standards of overall length of minimum 300 mm
designed for 15 mm axial compression and 5 mm axial extension with tie rods etc of follwoing MOC and pressure ratings.MOC:
Bellows SA 240 Gr 304 ; Internal Sleeve SA 240 Gr 304 ; Weldends : IS 2062 Gr B: ( Drilling as per IS 1538 IS 6392 ) & limit Rods &
Size :- 200 MM Dia PN-1.0 Rating For (Delivery Pipe)
6.1 (A) Khakharechi Section - 2 Nos 4 Nos. 6216.00 0.00
(B) ESR Section - 2 Nos
Size :- 250 MM Dia PN-1.6 Rating For (Delivery Pipe)
(A) Barar Section - 2 Nos
Size :- 300 MM Dia PN-1.0 Rating For (Delivery Pipe)
(A) WTP Section - 1 Nos
SITC of ISI mark Manually Gear Operated CI D/F Butterfly Valves as per IS 13095 (having ISI mark embossed on the valve) with
Sleeve of EPDM and disc., shaft & internal part of SS-410 including all taxes, insurance, transportation, freight charges, octroi,
7 inspection charges, loading, unloading, conveyance to departmental stores, stacking with lowering, laying and jointing in position
including cost of all labour, jointing material, including nut bolts and giving satisfactory hydraulic testing etc. complete.
Size :- 200 MM Dia PN-1.0 Rating For (Delivery Pipe)
7.1 (A) Khakharechi Section - 2 Nos 4 Nos. 5866.00 742.00
(B) ESR Section - 2 Nos
Size :- 250 MM Dia PN-1.6 Rating For (Delivery Pipe)
(A) Barar Section - 2 Nos
Size :- 300 MM Dia PN-1.0 Rating For (Delivery Pipe)
(A) WTP Section - 1 Nos
7.3 Size :- 300 MM Dia PN-1.0 Rating For (Delivery Header Pipe) 3 Nos. 16804.00 1141.00
(A) Khakharechi Section - 1 Nos
(B) ESR Section - 1 Nos
Size :- 350 MM Dia PN-1.6 Rating For (Delivery Header Pipe)
(A) Barar Section - 1 Nos
SITC of CI Dual Plate Check Valve as per API-594/598 with lowering, laying and jointing in position including cost of all labour,
jointing material, including nut bolts and giving satisfactory hydraulic testing etc. complete.
Size :- 200 MM Dia PN-1.0 Rating For (Delivery Pipe)
8.1 (A) Khakharechi Section - 2 Nos 4 Nos. 13000.00 742.00
(B) ESR Section - 2 Nos
Size :- 250 MM Dia PN-1.6 Rating For (Delivery Pipe)
(A) Barar Section - 2 Nos
Size :- 300 MM Dia PN-1.0 Rating For (Delivery Pipe)
(A) WTP Section - 1 Nos
8.3 Size :- 300 MM Dia PN-1.0 Rating For (Delivery Header Pipe) 3 Nos. 35750.00 1141.00
(A) Khakharechi Section - 1 Nos
(B) ESR Section - 1 Nos
Size :- 350 MM Dia PN-1.6 Rating For (Delivery Header Pipe)
(A) Barar Section - 1 Nos
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Supply and installation of MS fabricated structure cabin @ site of work using 65 mm, 50 mm & 25 mm square pipes with cabin minimum size
mtr X 8.0 mtr X 3 mtr or required size as per site situation including providing & fitting of (1) backalite sheet 3.5 mm thick in sides, (2) 20 guage
MS sheet outer side for side walls, (3) backalite sheet 3.5 mm thick sheet for roof side, (4) 24 guage GI sheet out side with 15 mm plywood
9 sandwitch fitting & flooring with 19 mm water proof plywood sheet and (5) shock proof rubber mating. Job includes oil painting two coats, door 1 Job 372959.99 0.00
locking handle arrangement, providing proper air entilation and fuse box. The meter & fuse box should be fitted on timber hold fast for holding screw
or nut bolts by semi skilled labour as per detailed technical specifications, drawings and instructions of the Engineer-in-charge.
Supply at site, Storage, Erecting Istallation Testing & commissioning of Bourdon type pressure gauge, ± 1% Accuracy, direct
bottom 1/2" ,NPT(M) process connection, IP 67, Glycerine filled SS304, Case with Bayonet type Bezel, SS 316 L bourden tube, SS
10 316 Movement material Aluminium Dial with black graduation on white background, Micro Zero adjustable pointer, neoprene 13 Nos. 1303.00 109.00
gasket, Blow out disk,shatter proof glass, SS tag plate etc as per IS 3624 (150 MM Dia) (of range 0 -10 kg/cm2 with IS 3624)
Providing & Laying Reinforced Cement Concrete in Thrust Block/Piping/Valves/cabin Supports etc. with Tar steel, Black Trap
11 Kapchi as Coarse Aggreate for Raft,Grillage Footing with Necessary Centering Form work, Consolidating as per Directive in 1:2:4 12 Cu. Mtr. 8566.40 0.00
Ratio comp. as per site requriement.
Providing,erecting,fabricating the M.S. structure as per requirement(for preventive grass & floating material upto strainer of pump)
on the site incorporating proper size of M.S. angles,flats,bars,channels,sections complete with cutting,welding,grinding & finishing
12 duly painted with one coat of red oxide with erection on site as per direction of engineer in charge with necessary 1000 Kgs. 67.00 23.00
grouting,cementing,plastering & finishing complete.
Dismentling of SCF pumpset,DPCV Valves,Sluice Valve,Expansion Bellow,pressure gauge,MS piping,Panel,TC etc Compelete as
per attached annexure A in volume II technical specification
Total of MechanicalSection Rs.
(B) POWER DISTRIBUTION SECTION
250KVA TC servicing including following items
(a) Routine maintenance of Transformer in operation covering check for Insulation Resistance, oil breakdown strength,
reconditioning /replacement of silica gel, cleaning of transformer & topping up of oil if required. (excluding cost of transformer oil)
(b) Testing of transformer oil for dielectric breakdown strength.
(c) Replacing old and unserviceable gasket of Top cover plate of Transformer having following capacity. (250 kVA)
(d) Replacing old & unserviceable gasket bushing of HT for the following capacity Transformer (250 kVA)
(e) Replacing old & unserviceable gasket bushing of LT for the following capacity Transformer (250 kVA)
(f) Outside painting of Transformer for the following capacity (250/ 315/ 400/ 500 kVA)
(g) Replacing the oil level glass of the 250/ 315/ 500/ 750/ 1000kVA by new one
(h) Replacing the breather of the Transformer of following capacity. (250 kVA)
(i) Conveyance charges for transformer from workshop to site or back one side) -Outside Divisional Head Quarter for first 30km
(j) Loading/ Unloading transformer on one side (250/ 315/ 500kVA )-4 Job
(k) Transformer oil having good resistance to high electrical stress,high di-electric strength(50KV) low viscosity,low pour point,high
flash point and excellent thermal properties for efficient heat transfer and cooling as per IS 335-1972
(l) filtration of treansformer oil as per IS for removal of moisture,carbon,slurry etc.by means of circulating oil through vacuum pump
from heating elements and filters to with stand the breaking strength of the oil above 40KV beyond one minute tested in oil testing
kit (A) On site
15 Installation, testing & commissioning of 250KVA Transformer after Repairing. 1 Job 0.00 31500.00
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Supply, installation, testing & commissioning of of 11 KV two pole 9 Mtr high (From ground Level) structure Made of 6"X3" -
"I" Section girder having min 8 mtr length, 4" X 2" M.S. channel, Clamps, hardware etc. Suitable for erection of the following duly
connected with necessary ACSR Conductors as per approved Drawing & in compliance with requirements of IEC (without earthing &
16 (A). 11 KV 200 Amps Drop Out fuses With S.R.B.P. tubes Carries- Three nos. (B) 11 KV G.O.D. Switch comp. with Insulators, 1 Nos. 96120.00 24543.00
Operating handle With galvanised Pipe, Sq.bar etc. 400Amp. two Set. (C) 11 KV Lightining arrestor With Clamp.three nos.(D) 11 KV
Disc Inaulators-Nine Nos.(E) 11 KV Pin Inaulators-Six Nos. 25mmx3mm thick Copper earth Strips in two parallel runs in required
quantity ie from LA to earthing chamber with Chemical Earthing Etc. Complete as per IEC Rule.
LV POWER CONTROL CENTER (PCC)
SITC of 630 A LV POWER CONTROL CENTER (PCC) SITC of LV Distribution Board (LVDB) totally enclosed, dust & vermin proof, indoor
type, fabricated from CRCA sheet steel with minimum thickness of 3 mm for base frame/ channel/ gland plates, 2.0 mm for load bearing
members/ doors & 1.6 mm for internal partitions, minimum degree of protection - IP 52 as per IS: 2147, suitable for operation on 3-Phase,
4 Wire, 415V, 50Hz, Neutral effectively grounded, with instrumentation compartments accomodating meters, aux / protective relays, LED
type indicating lamps & control MCBs as per IS: 13947, current & voltage transformers as per IS: 2705, air insulated electrolitic grade
Aluminum/ Copper busbar for three phase & neutral system, GI earth bus for entire length, power/ control wiring using 1100V grade,
17 FRLS insulated copper conductor wires conforming to IS: 694 & 8130, equipment fittings, horizontally running busbar compartment
height of minimum 300 mm, incoming & ougoing cable connections for 1100V grade, Aluminium/ Copper conductor XLPE/ PVC insulated
& PVC sheathed armoured cable. LVDB shall have required incomming/ buscoupler/ outgoing modules of following type & ratings.
(1) 01 Nos. of 630 A, 4 Pole, ACB (Draw-out Type) with Microprocessor release (O / C, S / C & E / F) having breaking capacity Icu of 50 kA
at 415V with 6NO+6NC potential feee auxiliary contacts, secondary isolating contacts with all necessary Electro Mechanical protections
& interlocks etc. ACB module shall have enclosure dimension: 2000 (H) x 800 (W) x 1000 (D) & following technical features.
Outgoing feeders :-
(1) 250 Amp. - 1 No (For 30 KW pump- Khakharechi Section)
(2) 250 Amp. - 1 No (For 30 KW pump- ESR Section)
(3) 250 Amp. - 1 No (For 82 KW pump- Barar Section)
(4) 250 Amp. - 1 No for APFCR panel.
17 (5) 80 Amp - 3 No ( 1 No. Feeder for Miscellaneous & 1 No. Feeder for Lighting Load & 1 No.WTP) 1 Nos. 344584.00 0.00
4 Pole MCCB with Breaking Capacity of Icu=50 KA at 415V (Ics = 100% of Icu), Microprocessor release - conforms to IS/ IEC 60947-2 with
trip free mechanism, current limiting type with Microprocessor release (O / C, S / C & E / F) with adjustable settings & having minimum
2NO+2NC potential free auxiliary contacts with all necessary Electro-Mechanical protections & interlocks etc. MCCB module, when used
as Outgoing(s), shall have enclosure dimensions - Minimum 600 (D)
3P and 2P MCB shall be provided for spare
(6) No Load Compansation KVAR banks (APP type) 12.5 kVAR for approx. 5% kVAR of 250 kVA Transformer etc. Complete.
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
LV APFC PANEL - 80 KVAR - SITC of LV APFC panel consisting of required capacitor banks for continuous duty to improve P.F.
0.85 to 0.99 in required steps enclosed in dust & vermin proof compartment, indoor type, fabricated from CRCA sheet steel with
minimum thickness of 3 mm for base frame / channel / gland plates, 2.0 mm for load bearing members / doors & 1.6 mm for internal
partitions, minimum degree of protection - IP 42, busbar chamber, required size of Al bus bar/ terminals, minimum 10 stage APFC
relay, metering, indicating lamps, push buttons, with detuned reactor complete as per IS: 16636-2017 with latest ammendment &
detailed technical specification and data sheet as under. - Above 50 & up to 100 KVAR: APFC panel consisting following items. a)
18 250 A, 50kA for 1sec. TP, TM based MCCB with spreader terminals & rotary handle b) 0-250 A range analogue ammeter of 96 x 96 1 Nos. 182370.00 0.00
mm size with selector switch c) 3nos. 250 / 5A, 10 VA CL-1.0 cast resin type current transformer d) Suitable rating of MCCB / MCB
& Contactors for each capacitor bank e) Suitable rating APP type capacitor banks (vacuum impregnated with non-PCB / non toxic oil,
internally delta connected with built in internal fuses complete with discharge resistances & terminal cover) of approved make in
required steps with well suited detuned reactor is placed in series with each capacitor step. ( e.g., 100 KVAR capacity will be provided
in steps of 2 nos x 5 KVAR, 2 nos x 10KVAR, 2 nos x 15 KVAR & 2 nos x 20 KVAR) f) Enclosre dimensions- 2100 (H) x 1150 (W)
x Minimum depth of 600 (D)
MCC Panel with ATS starter :S.I.T.C of LV MCC Panel 30 KW For Khakharechi Secction, ESR Section totally enclosed, dust
& bermin proof, indoor type, minimum degree of protection - IP 52 as per IS: 2147, operation on 3- Phase, 4 Wire, 415V, 50Hz,
Neutral effectively grounded, with instrumentation compartments accomodating LED type indicating lamps, control contactors as per
IS: 13947, CT of accuracy class- I as per IS: 2705, relays, meters & control MCBs, air insulated electrolitic grade Aluminum busbar for
three phase & neutral system with incomming breaker- microprocessor based Air Circuit Breakers (electrically operated drawout type)/
air break fixed type MCCB with trip free mechanism, current limiting type as per IS: 8828, Motor Contractor (as per type -2
coordination), Overload Relay with built-in single phasing prevention feature & auxiliary feeders as per SLD drawings, momentary
contact type push buttons, equipment fittings, bus bars, cable boxes, cable gland, incoming & ougoing cable connection for 1100V
19 grade, Aluminium/ Copper conductor XLPE/ PVC insulated & PVC sheathed armoured cable, 10% spare terminals, power wiring 2 Nos. 103676.00 0.00
using 1100V grade, FRLS insulated copper conductor wires conforming to IS: 694 & 8130, cable compartments/ alleys of minimum
300 mm size, GI earth bus bar for entire length. MCC shall be fabricated from cold rolled, coled annealed (CRCA) sheet steel &
minimum thickness of various members shall be as follows: Base Frame/ Channel/ Gland Plate - 3 mm, Load Bearing Members/ Doors
- 2 mm and Internal Partitions - 1.6 mm. ATS Starter as per Technical Specification With required (min. 15 KVAR) KVAR APP Type
Capacitor Bank to maintain PF and Encloser size Minimum x 600 mm Depth required (1500mm H x 2175 mmL or as per requirement)
01 No. Incomer and 02 Nos. of outgoing feeders suitable to 30 kW motor rating with GI earth busbar for entire length of incomer
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
MCC Panel with ATS starter :S.I.T.C of LV MCC Panel 30 KW For WTP Section totally enclosed, dust & bermin proof, indoor
type, minimum degree of protection - IP 52 as per IS: 2147, operation on 3- Phase, 4 Wire, 415V, 50Hz, Neutral effectively grounded,
with instrumentation compartments accomodating LED type indicating lamps, control contactors as per IS: 13947, CT of accuracy
class- I as per IS: 2705, relays, meters & control MCBs, air insulated electrolitic grade Aluminum busbar for three phase & neutral
system with incomming breaker- microprocessor based Air Circuit Breakers (electrically operated drawout type)/ air break fixed type
MCCB with trip free mechanism, current limiting type as per IS: 8828, Motor Contractor (as per type -2 coordination), Overload Relay
with built-in single phasing prevention feature & auxiliary feeders as per SLD drawings, momentary contact type push buttons,
equipment fittings, bus bars, cable boxes, cable gland, incoming & ougoing cable connection for 1100V grade, Aluminium/ Copper
20 conductor XLPE/ PVC insulated & PVC sheathed armoured cable, 10% spare terminals, power wiring using 1100V grade, FRLS 1 Nos. 34500.00 2651.00
insulated copper conductor wires conforming to IS: 694 & 8130, cable compartments/ alleys of minimum 300 mm size, GI earth bus
bar for entire length. MCC shall be fabricated from cold rolled, coled annealed (CRCA) sheet steel & minimum thickness of various
members shall be as follows: Base Frame/ Channel/ Gland Plate - 3 mm, Load Bearing Members/ Doors - 2 mm and Internal Partitions
- 1.6 mm. ATS Starter as per Technical Specification With required (min. 15 KVAR) KVAR APP Type Capacitor Bank to maintain
PF and Encloser size Minimum x 600 mm Depth required (1500mm H x 2175 mmL or as per requirement) of
01 No. Incomer and 01 Nos. of outgoing feeders suitable to 30 kW motor rating with GI earth busbar for entire length of incomer
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip /
round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
21 existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part- 60 mtr 1174.00 37.00
1) & IEC:60502 (Part-1) of following sizes: 3.5 C X 400 Sq mm
(Transformer to LVDB to APFC)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip /
round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
22 existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part- 20 Mtr. 152.00 13.00
1) & IEC:60502 (Part-1) of following sizes: 3.5 C X 35 Sq mm
(LVDB to Khakharechi and ESR section MCC Panel)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip /
round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
23 existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 20 Mtr. 479 24
(Part-1) & IEC:60502 (Part-1) of following sizes: 3.5 C X 150 Sq mm
(LVDB to changeover switch to Barar section Control Panel)
SITC of 11 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip/ round wire armoured, extruded
PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable trays /
conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502(Part-2), of sizes: -
1 X 3 X 120 Sqmm (DP to Transformer)
Providing & fitting heat shrink cable termination/ jointing kits for 11 kV (UE) grade XLPE insulated cable including necessary earth
25 connectivity connection, material & consummables making the termination/ joint complete ensuring the joint resistance is within the 2 No 7943.00 850.00
permissble limit as per IS, of following types & sizes: outdoor Terminations Kit suitable for 1X3X120 SQ MM
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip /
round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
26 existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part- 320 Mtr. 136.00 8.00
1) & IEC:60502 (Part-1) of following sizes: 3 C X 35 Sq mm
(MCC Panel Khakharechi and ESR section to Pumpset)
SITC of 1.1 kV (UE) grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip/ round wire armoured,
extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in existing cable trench / cable
27 trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 (Part-2) & IEC:60502(Part-2), of 160 mtr 421.00 13.00
sizes: - 1 X 3 X 150 Sqmm (MCC Panel Barar Section to Motor 82.5 KW)
Supply, laying, testing & commissioning 1.1 kV grade, XLPE insulated, stranded Aluminium conductor, galvanised steel flat strip /
round wire armoured, extruded PVC type ST2 sheathed, heavy duty cable (to be laid on wall surface with necessary clamps / in
28 existing cable trench / cable trays / conduit / pipe sleeves at road crossing or floor as per site requirement) conforming to IS:7098 80 Mtr. 136 8
(Part-1) & IEC:60502 (Part-1) of following sizes: 3 C X 35 Sq mm
(MCC Panel WTP Section to Motor 30 KW)
Supply of Approved make Iron Clad or metal clad four pole change over switch 415V. confirming to IS of following capacity
29 Changeover switch (250 A ) Cat - III 1 No. 17162.60 0.00
Providing and erecting busbar chamber confirmingtoIS-375fabricatedfrom16G.M.S. sheet,dust&verminproofhavinghingeddoor with
rubber gasket and necessary busbar supportswithAluminiumbusbarhavingcurrent density not more than 0.8 Amp. / sq.mm (Rated
current /crosssectionarea)dulywrappedwith colour insulation tape for phase sequence, three phase & neutral each Suitable for
following current capacity with necessary paintingmountedonwall orpedestal frameof required size with necessary connections.
Suitable for 200 Amp. capacity(For ESR & Khakharechi Section & WTP section)
(we required 0.40 Mtr. long busbar chamber)
Providing and erecting busbar chamber confirmingtoIS-375fabricatedfrom16G.M.S. sheet,dust&verminproofhavinghingeddoor with
rubber gasket and necessary busbar supportswithAluminiumbusbarhavingcurrent density not more than 0.8 Amp. / sq.mm (Rated
current /crosssectionarea)dulywrappedwith colour insulation tape for phase sequence, three phase & neutral each Suitable for
31 following current capacity with necessary paintingmountedonwall orpedestal frameof required size with necessary connections. 2 Nos. 1879.44 90.2
Suitable for 300 Amp. capacity(For Barar Section)
(we required 0.40 Mtr. long busbar chamber)
Supplying & erecting funnel type earthing having earth plate of following size burred in specifically prepared earth pit 3 mtr. below
ground with 40 kg. charcoal and salt with alternate layers of charcoal
& salt, 20mm.dia. G.I. pipe with Funnel with a wire mesh for watering & bricks masonry block, C.I. Cover complete as per para
of IS 3043 with necessary length of copper earth wire No 6 SWG bolted with lug to the plate and covered in 12 mm dia. G.I. pipe
mtr long complete connected to the nearest switch gear with end socket as per direction & duly tested by earth tester confirming to
IS (As per drawing) with With 45 x 45 x 0.35 cms. C.I. earth plate For Pump, Panel
Providing and erecting required size HOT dip Galvinized Strip of size 50 mm width X 12 mm thickness for earthing of
33 HT/OCB/ACB/Transformer/LT Panel Board/Motors etc. using copper clamp for the purpose of connecting panel body earth to earth 500 Kgs. 57.40 16.40
pit etc complete as per site requirement.
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Supplying & erecting funnel type earthing having earth plate of following size burred in specifically prepared earth pit 3 mtr. below
ground with 40 kg. charcoal and salt with alternate layers of charcoal
& salt, 20mm.dia. G.I. pipe with Funnel with a wire mesh for watering & bricks masonry block, C.I. Cover complete as per para
34 of IS 3043 with necessary length of copper earth wire No 6 SWG bolted with lug to the plate and covered in 12 mm dia. G.I. pipe 2.5 2 Nos. 6888.00 656.00
mtr long complete connected to the nearest switch gear with end socket as per direction & duly tested by earth tester confirming to
IS (As per drawing) with with 60 x 60x 0.315 cms. Copper earth Plate for Transformer Neutrals (02 Earthing for transformer
Providing and erecting required size COPPER Strip of size 50 mm width X 12 mm thickness for earthing of transformer neutrals
35 using copper clamp for the purpose of connecting panel body earth to earth pit etc complete as per site requirement. 200 Kgs. 728.16 32.80
Supplying and erecting 12 mm thick rubber mat as per IS 5424 for LT of required length & breadth with good insuklation propoerty
Supplying of 12mm rubber matting of following thickness as per IS:15652 /IEC
Mains with 1.1kV grade FRLS PVC insulated ISI marked stranded copper conductor wire in following type of pipe to be erected in/
37 on wall /ceiling with 2.5 sq. mm copper conductor FRLS PVC insulated stranded wire of green colour for earth continuity of following 100 mtr 95.94 4.92
size. With medium class Rigid PVC pipe and accessories a. 2 wire 4 sq.mm (with 2.5 sq.mm earth wire)
Providing following type of Modular type accessories mounted with PVC/ metallic box, single mounting base frame covered with
38 textured/ metallic front plate, modules erected with necessary connection as desired by Engineer In charge 12 Each 236.98 9.02
16A single Pole Modular MCB Switch, Cat. II
Supplying and erecting LED indoor fittings with LEDs of wattage 0.2 Watt to 0.5 Watt assemble don single MCPCB, with housing
use dasa heat sink shall be made of thick sheet Steel conforming to IS:513 / CRCA / aluminium pressure die cast powder coated
and high U.V. & corrosion resistance with diffuser house din aluminium casted body with company mark/name 160 V to 270 V
Power Factor more than 0.95, THD < 15 %,CCT 3000 K to 6500K, Luminaire efficacy> 85 lumens/watt ,LED driver efficiency >
%(fitting required LM - 79 & LM -80 Certificates ) (NOTE: Below description have shown ranges of Wattage capacity of LED fittings.
The Engineer incharge may select any wattage capacity between the ranges shown.)
(A) Square / Circular shaped Surface / Recessed Mount Down light with provision for spring loaded mounting clips complete.IP20
22-24 Watts, Surge - 2KV,IP-20, 4 feet, Cat-III
Supplying and erecting LED streetlight/ Flood light fittings with High power White LEDs wattage of 3 Watt and above assembled on
single MCPCB, efficiency more than 130 lm/w and corrosion free High pressure die cast aluminium housing with smooth finish
powder coated and heat sink extruded aluminium with diffuserand Polycarbonateoptics/ lenses with company mark /name engraved
or embossed160 to 270 V, Power Factor more than 0.95, THD < 10%, CCT 3000 K to 5700 K, Uniformity ratio > 0.45, Luminaire
40 efficacy > 100 lumens/watt. LED driver efficiency > 85%. (fittings required LM - 79 & LM-80 certificates) (NOTE: Below description 5 Each 3080.74 123
have shown ranges of Wattage capacity of LED fittings. The Engineer incharge may select any wattage capacity between the
(A) Street Light (IP-65), Surge protection - 4 KV integraland, Light must have 440 VAC line supply with over-voltage protection.
36-48 Watts, Surge - 2KV,IP-20, 4 feet, Cat-III
Description of Items Qty. Unit Amount (Rs.)
No. Supply 10% or
Point wiring Arrangement:
Design, supply, erection, testing and commissioning of suitable general arrangement of point wiring for pump house.
Point wiring for Light / Bell with 2-1.5 sq.mm & earth wire of 1.5 sq.mm (Green) both are of ISI marked 1.1 KV grade FRLS PVC
insulated multi strand copper wires upto 10 mtr length, in below type of pipe erected with 6A Modular types witch / bell push &
41 accessories and earth continuity of following type, erected on PVC /Metallic /Wooden box, single mounting base frame covered with 12 Pt. 277.16 56.58
textured / metallic / white front plate module serected on / in wall / ceiling as per pipe erected, with necessary Lamp holder / ceiling
rose / H.D. Connector as directed.
(a)with medium class Rigid PVC pipe and accessories erected flushed on wall / ceiling complete
Providing and erecting Approved make Ceiling fan with double ball bearing ISI mark with condenser
42 A.C.23OV.50c/s.1200mm.sweep complete, can opyerected on existing hook or clamp with earthing. [Make shall be approved by 2 Each 1480.10 49.20
Engineer in charge]
Total of Section B Rs.
Total of Section ( A+B) Rs.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
1.0 General Terms Condition Khirai.pdf
2.0 Technical Specifications Electro- Mechanical khirai.pdf
3.0 Volume -I V Vendor List.pdf
4.0_Volume - V Price Bid.pdf
5.0 PRICE BID.pdf
6.0 Price Variation Paripatra 2023.pdf
7.0 SD EMD GR.pdf
8.0 BANK LIST and GR NEW.pdf
9.0 GST GR.pdf
10.0 Bank Gaurantee DMO 2876 01 May 2025 273.pdf
11.0 SD GR.pdf
Schedule B.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .