Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹97.7 LAccepted-AOC | L1 | Accepted-AOC L1 Bidder | |
| 2 | L2₹99.7 L+₹2.0 L (2.09%)Rejected-Finance | L2 | Rejected-Finance L2 Bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical Documents as per SQC not submitted |
Tender Value
₹98.1 L
EMD Value
₹50,000
Closing Date
23 Dec 2021, 4:00 pmClosed
The Regional Manager,WAPCOS Limited
The Regional Manager, 4th Floor, ISAACS Tower, Jawahar Nagar, Kadavanthra, Kochi, Kerala-682020
Establishment of Pediatric Care Units(24 Bedded ICU and 8 Bedded HDU) Under ECRP II at SAT Hospital Trivandrum
2021_WAPCO_460081_1
WAP/INFRA/KERALA/SAT/2021/365
Open Tender
Civil Works - Others
Item Rate
90 days
SAT Hospital Trivandrum
As per Tender Documents
22 documents required · 22 mandatory
₹2,800
₹50,000
5 Apr 2022
11 Dec 2021
23 Dec 2021
11 Dec 2021
23 Dec 2021
11 Dec 2021
Amount
HDU Civil & MGPS Works
od202017/2021_2022 : Supply and Installation of recessed mounted bottom opening LED clean room luminaire 595x595 of powder coated housig (Make: Crompton/Wipro/ Philips/Luker)<br>
12.45.1 : Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum plain board conforming to IS : 2095-Part 1
21.1.1.2 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
21.3.2 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
21.2.2 : Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
21.1.2.2 : For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
21.4.1 : Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness
9.97.3 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm
9.100.1 : Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
od202407/2021_2022 : SITC of 4 feet long bed head trunking with 8 nos switch and socket with provision for medical gas outlet
od202409/2021_2022 : Gas outlet - SITC of surface mounted gas outlet oxygen,vaccum,airfore
od202455/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 12mm size
od202460/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 15mm size<br>
od202464/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 22mm size
od202468/2021_2022 : Butterfly valve 12mm size
od202473/2021_2022 : SITC of Isolation ward 15mm size<br>
od202647/2021_2022 : SITC of Isolation ward 22mm size
od202859/2021_2022 : SITC of AVSU Box 3 sevice
od203215/2021_2022 : SITC of Area Alarm Panel 3 service<br>
od203234/2021_2022 : SITC of BPC Flowmeter<br>
od203403/2021_2022 : SITC of ward vaccum unit
od203446/2021_2022 : SITC of 2 bay scrub sink(manual) 304 grade ss make<br>
od203779/2021_2022 : Design, Supply and Installation,of internal Name board in SS 304 grade with pictogram laser etched in English in Black colour.The Name boards will be fixed on to the wall with suitable hardware. Size : 120 mm x 120 mm
9.47.1 : Providing and fixing nickel plated M.S. pipe curtain rods with nickel plated brackets:20 mm dia (heavy type)
22.6 : Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed with water proofing cement compound consisting of applying : a) after surface preparation, first layer of slurry of cement @ 0.488 kg/ sqm mixed with water proofing cement compound @ 0.253 kg/ sqm. laying second layer of fibre glass cloth when the first layer is still green. Overlaps of joints of fibre cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @ 1.289 kg/ sqm mixed with water proofing cement compound @ 0.670 kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire treatment will be taken upto 30 cm on parapet wall and tucked into groove in parapet all around. d) fourth and final layer of brick tilling with cement mortar (which will be paid for separately. For the purpose of measurement the entire treated surface will be measured)
13.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.80 : Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
13.91 : Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
13.98.1 : Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade:One or more coats on old work
13.99.1 : Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :One or more coats on old work
HVAC Works
od252202/2021_2022 : Supply, Installation, testing commissioning of factory built Ceiling Suspended DX double Skin horizontal Air handling units made of 40mm thick panels consisting of pre plasticized GI casing of thickness 0.8mm outside layer and inner layer shall be of 0.8mm plain AL sheet with polyurethane form(PUF) insulation factory injected between them by injection moulding machine with thermal break profile complete with fan section with backward curved plug fans suitable for static pressure as required with VFD drives , coil section with aluminium finned copper tubes (min. 10 fins per inch, tube thickness not less than 0.5mm),Cooling coil of 6 rows deep, filter section with 50mm thick metal viscous/washable synthetic type air prefilters (10 micron) & 5 micron fine filters, mixing box with fresh air intakes with dampers,drain connections, SS drain pan(18G) with PUF insulation, TEFC sq.cage induction motor of efficiency class IE3 suitable for 415+-10% volts, 50 Hz, 3 phase AC supply including mounting and fixing arrangements, anti vibration springs/ isolator bearings , strip heaters, germicidal UV-C lamps etc complete as per specification and of following capacities.The cost shall be inclusive of VFD starter panel in a separate enclosure with necessary rating incomer isolator / MCCB /contactor with all accessories including necessary connections, inter connections and control wiring with pressure sensors (minimum 2 Nos.) for complete installation. Only HVAC application VFDs shall be used. Horizontal Ceiling Suspended AHU<br>14 TR/4800 CFM/ 6 RD/ 40 mm wg ESP.
od252203/2021_2022 : Supply, Installation testing and commissioning of the air cooled outdoor unit (condensing unit). It shall be of corrosion resistant galvanized powder coated or equivalent sheet steel assembly installed on suitable vibration isolators and comprising of energy efficient Scroll compressor with controls such as thermal protector, HP/LP cutouts, Pressure relief valve and condenser fan unit; the units shall have integral refrigerant copper piping within compressor and condenser and accessories such as refrigerant shut off valves at compressor / compressors and liquid refrigerant outlet if required & filter dryer, with R 410 A refrigerant; Cooling fans shall have protective metal frame.The Outdoor units within Sunshade and on Terrace shall be installed on MS angle iron frame duly corrossion proof painted and supplied as welded structure which shall be securely grouted on floor and duly painted with anti-corrosive paint; the frame shall be isolated from floor through adequate vibration isolation; Price shall be inclusive of all required MS supports.<br>Rates shall be including supply and commissioning of matching rated factory supplied Electrical Starter & Control Panel. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 deg C ambient temperature without tripping. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5.<br><br>Note: Control cables connecting the IDU and the ODU & 6 SMG GI wire loop Earthing shall be included in Split unit cost and on lot basis and run on the Power cable trays with adequate supports and electrical protection. 8.5 TR
od252204/2021_2022 : Supply, Installation testing and commissioning of the air cooled outdoor unit (condensing unit). It shall be of corrosion resistant galvanized powder coated or equivalent sheet steel assembly installed on suitable vibration isolators and comprising of energy efficient Scroll compressor with controls such as thermal protector, HP/LP cutouts, Pressure relief valve and condenser fan unit; the units shall have integral refrigerant copper piping within compressor and condenser and accessories such as refrigerant shut off valves at compressor / compressors and liquid refrigerant outlet if required & filter dryer, with R 410 A refrigerant; Cooling fans shall have protective metal frame.The Outdoor units within Sunshade and on Terrace shall be installed on MS angle iron frame duly corrossion proof painted and supplied as welded structure which shall be securely grouted on floor and duly painted with anti-corrosive paint; the frame shall be isolated from floor through adequate vibration isolation; Price shall be inclusive of all required MS supports.<br>Rates shall be including supply and commissioning of matching rated factory supplied Electrical Starter & Control Panel. The unit shall deliver the rated capacity at AHRI conditions and work even at 50 deg C ambient temperature without tripping. The unit shall be filled with first charge of the refrigerant and ready for use as required. The COP at AHRI conditions shall not be less than 3.1 and IEER not less than 6.5.<br><br>Note: Control cables connecting the IDU and the ODU & 6 SMG GI wire loop Earthing shall be included in Split unit cost and on lot basis and run on the Power cable trays with adequate supports and electrical protection.5.5 TR
od252205/2021_2022 : Supply Installation Testing & Commissioning of Inverter 4-Way Cassette AC with 5 stage Filteration including cordless remote, refrigerant piping, first charge of R410A refrigerant gas, condensate drain piping, electrical works, fresh air provision and all other associated works for the complete installation of this item. 2 TR
od252208/2021_2022 : Supply, Installation, Testing & Commissioning of GI Sheet metal ducting work complete with all fittings such as Tee, Bends, Turning vanes including, suspension and supporting arrangement as required and necessary joints sealed with silicon. 0.8mm GSS Ducting
od252209/2021_2022 : Supply, Installation, Testing & Commissioning of GI Sheet metal ducting work complete with all fittings such as Tee, Bends, Turning vanes including, suspension and supporting arrangement as required and necessary joints sealed with silicon.
od252210/2021_2022 : Supply & fixing of 10 mm thick open cell nitrile rubber form with density 140-180kg/m3 along with antimicrobial product protection as acoustic insulation for ducts using suitable adhesive as per the recommendation of the insulation manufacturer.
od252211/2021_2022 : Supplying and fixing of following thickness duly laminated aluminium foil of mat finish closed cell Nitrile rubber(Class O) insulation on existing duct after applying suitable adhesive for Nitrile rubber. Density of insulation material shall be between 40 to 55 Kg/m3.The joints shall be sealed with 50mm wide and 3mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.13 mm thick Anti Microbial Nitrile Rubber insulation.
od252212/2021_2022 : SITC of Powder Coated Extruded Aluminium Supply Air Diffuser with volume control dampers.
od252213/2021_2022 : SITC of Powder Coated Extruded Aluminium return Air Diffuser without volume control dampers.
od252214/2021_2022 : Supply, installation, testing and commissioning of Extruded Aluminium Volume Control Dampers complete with flanges, channels and control levers suitable for duct mounting
od252215/2021_2022 : Supply, fabrication, installation, testing of flexible connections made out of fire resistant flexible double canvas sleeve.
od252216/2021_2022 : SITC of 25mm OD uPVC Sch 40 pipe with 9mm thick aniti microbial nitrile rubber sleeve insulation for condensate drain piping of AHUs to the nearest drain point.
od252217/2021_2022 : Supply Installation Testing and commissioning of inline type exhaust fan with speed regulator of following CFM including UVC Lamp mounted inside plenum box with all necessary supports & fixing arrangement. 800 CFM/25 mm ESP
od252218/2021_2022 : Supply Installation Testing and commissioning of inline type exhaust fan with speed regulator of following CFM including UVC Lamp mounted inside plenum box with all necessary supports & fixing arrangement. 300 CFM/15 mm ESP
ICU Civil & MGPS Works
od206055/2021_2022 : Supply and Installation of recessed mounted bottom opening LED clean room luminaire 595x595 of powder coated housig (Make: Crompton/Wipro/ Philips/Luker)<br>
12.45.1 : Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum plain board conforming to IS : 2095-Part 1
21.1.1.2 : Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
21.2.2 : Providing and fixing 12 mm thick prelaminated particle board flat pressed three layer or graded wood particle board conforming to IS : 12823 Grade I Type II, in panelling fixed in aluminum doors, windows shutters and partition frames with C.P. brass / stainless steel screws etc. complete as per architectural drawings and directions of Engineer - in- Charge.Pre- laminated particle board with decorative lamination on both sides
21.3.2 : Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of Engineer - in -Charge. ( Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 5.50 mm thickness
21.4.1 : Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness
9.97.3 : Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:200x10 mm
9.100.1 : Providing and fixing aluminium handles, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS : 1868) transparent or dyed to required colour or shade, with necessary screws etc. complete:125 mm
od206865/2021_2022 : SITC of 4 feet long bed head trunking with 8 nos switch and socket with provision for medical gas outlet
od206970/2021_2022 : Gas outlet - SITC of surface mounted gas outlet oxygen,vaccum,airfore <br>
od206976/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 12mm size<br>
od207011/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 15mm size<br>
od207015/2021_2022 : Medical Gas Pipeline system SITC of Copper Pipe 22mm size<br>
od207185/2021_2022 : Design, Supply and Installation of internal Name board in SS 304 grade with pictogram laser etched in English in Black colour.The Name boards will be fixed on to the wall with suitable hardware. Size : 120 mm x 120 mm
9.47.1 : Providing and fixing nickel plated M.S. pipe curtain rods with nickel plated brackets:20 mm dia (heavy type)
od207188/2021_2022 : SITC of 2 bay scrub sink(manual) 304 grade ss make<br>
od207189/2021_2022 : SITC of ward vaccum unit <br>
od207190/2021_2022 : SITC of BPC Flowmeter<br>
od207191/2021_2022 : SITC of Area Alarm Panel 3 service<br>
od207192/2021_2022 : SITC of AVSU Box 3 sevice<br>
od207193/2021_2022 : SITC of Isolation valve 22mm size<br>
od207194/2021_2022 : SITC of Isolation valve 15mm size<br>
od207195/2021_2022 : Butterfly valve 12mm size <br>
21.1.2.2 : For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron)
13.43.1 : Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.80 : Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
13.91 : Removing dry or oil bound distemper, water proofing cement paint and the like by scrapping, sand papering and preparing the surface smooth including necessary repairs to scratches etc. complete.
13.98.1 : Wall painting with plastic emulsion paint of approved brand and manufacture to give an even shade:One or more coats on old work
13.99.1 : Painting with synthetic enamel paint of approved brand and manufacture of required colour to give an even shade :One or more coats on old work
RAJAN P
Bidder Name
RAJAN P
RAGUNATH CHERIYATH
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .