Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.3 LAccepted-AOC | L1 | Accepted-AOC ok | |
| 2 | L2₹31.3 L+₹5.0 L (18.9%)Rejected-AOC 5D 32B GALI NO 8 VISHNU GARDEN TILAK NAGAR WEST DELHI 110018 | DELHI | WEST DELHI | DELHI | 110018 | L2 | Rejected-AOC ok | |
| 3 | L3₹33.7 L+₹7.4 L (28.2%)Rejected-AOC | L3 | Rejected-AOC ok | |
| 4 | L4₹33.9 L+₹7.6 L (29.0%)Rejected-AOC | L4 | Rejected-AOC ok | |
| 5 | L5₹34.7 L+₹8.4 L (31.9%)Rejected-AOC | L5 | Rejected-AOC ok |
Tender Value
₹40.1 L
EMD Value
₹80,200
Closing Date
5 Mar 2022, 6:00 pmClosed
CWE Dehradun
HQ CWE Dehradun
PROVN OF OXYGEN POINTS FOR 187 BEDS WITH MGPS, INTERNAL AND EXTERNAL ELECTRIFICATION AND HARD STANDING OF OXYGEN GENERATION PLANT AT MH DEHRADUN
2022_MES_499133_2
9669/DDN/E8
Open Tender
Civil Works
Item Rate
60 days
Dehradun
Please refer Tender documents.
5 documents required · 5 mandatory
₹500
GE Dehradun
₹80,200
Yes
1 Apr 2022
11 Feb 2022
7 Mar 2022
11 Feb 2022
5 Mar 2022
19 Feb 2022
Amount
Surface excavation n. exc (not exceeding) 30 cm deep, averaging 15cm deep and getting out in any type soil complete all as specified and directed.
M&L for hard core of broken stone or boulders gauge n. exc 63mm size deposited, spread and leveled in layers n.exe15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
M&L for 100 mm thick PCC (1:4;8), type D-2, using 40 mm graded crushed stone aggregate as in sub base complete all as specified and as directed.
M&L for 100mm thick PCC (1:2 :4) type B-2, using 40 mm graded crushed stone aggregate as in base course complete all as specified and directed.
Removing excavated material to a distance n. exc 50m and deposited where directed complete all as specified and directed.
M&L for forming of construction joint 30mm deep x 10mm wide filled with sealing compound grade 'A' complete all as specified and directed.
S&F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour as approved having tensile strength of 550 Mpa as in roof covering/cladding to wall, fixed with self-tapping screws complete all as specified and directed.
S&F Pre-painted galvalume aluminum zinc coating GI based Plain steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/cladding/ridge to wall, fixed with self-tapping screws complete all as specified and directed.
Excavation in post holes ( or similar holes) each not exc 0.5 cum, getting out in hard/dense soil, returning , filling in and ramming earth or broken rubble mixed with earth around, in layers not exc 25 cm, watering and removing surplus soil to a distance not exc 50 meter and making the surface good complete all as specified and directed.
M&L for PCC (1:3:6) type C-2 using 40 mm graded stone aggregate as in foundation, filling and mass concrete complete all as specified and directed.
S&F mild steel work as in main and cross beam, hip and jack rafters, purlins etc. fixed with angle cleat or other connecting plate complete confirming to Fe – 410-O or Fe – 310-O long complete all as specified and directed.
M&L for preparation of new untreated steel surfaces of any description not otherwise described over 10 cm width or girth and applying two coats of black japan paint over a coat of red oxide primer complete all as specified and directed.
S&F 8 mm plate plain or chequred channels, squares cut or notched ordinary and counter sunk forming holes, without any attachment complete all as specified and directed.
M & L for use and waste form work to edges of concrete flats, treads, breaks in floors, window cills, concrete railing, opening in railing, opening in concrete wall, floor and roofs n exe 20 cm wide and sides of RCC/PCC bands in walls, horizontal or sloping or similar work exc 10 cm but n exc 20 cm wide complete all as specified and directed
Supply, installation, testing & commissioning of following sizes of copper pipe with seamless fittings, flanges, elbows, tees clamps, hanger, saddle, reducer tees, sockets etc duly welded and one coat of red oxide primer and two coats of synthetic enamel paints and soiled drawn seamless deoxidized, non- arsenical, half hard, tempered and degreased as per BS EN 13348:2001 duly supported with manufacturer test certificates for physical properties and chemical composition :- Note :- (i) Copper pipe shall have reputed third party inspection certificate (eg. Llyod's or Kite marked or TUV or SGS). (ii) Fittings shall be made of copper conforming to BS 864 and suitable for working pressure upto 1.7 bar. (iii) All concealed pipe to have gas identification brands/lable at appropriate distance. (iv) All copper pipes shall be inspected and certified for medical use before dispatch and pipe shall be delivered plugged a capped at both ends. (v) After erecting all new pipes shall be cleaned or purged with help of dry nitrogen gas at 2 times of working pressure. (vi) All pipes shall be painted with two coats of synthetic enamel paint and colour identification as per IS: 2379 of 1963. Make : Mexflow/ Jayna/ Mandev Tubes.
Copper pipe 12 mm x 0.9 mm
Copper pipe 15 mm x 0.9 mm
Copper pipe 22 mm x 1.0 mm
Copper pipe 28 mm x 1.0 mm
Supply, fixing, installation and testing of GAS TERMINAL UNIT : Terminal Units (Gas Outlets) with adaptors/probe for oxygen. Matching adaptors to the gas outlet mentioned above i.e. adaptor for oxygen. The terminal units would have following features complete all as specified and directed and conforming to HTM 02-01/EI/ISO/DIN :-
It would be front insertion type.
Terminal unit would have mechanism with check valve.
Allow single hand operation.
On first insertion of probe the probe shall sit in a standby position. At the stage there shall be no gas flow.
Only on pressing the probe second time, the gas supply would start.
They would close automatically when connected apparatus is removed.
For allowing on line maintenance the terminal unit would be equipped with a check valve for all positive pressure gases for closing gas supply whenever the outlet point is opened. Supply, installation, testing & commissioning of outlet point with probe oxygen.
The outlet would be non interchangeable for specific gas and it would accept only correct medical gas adopter/Probe.
It would be color coded as per HTM 2022
The design of this outlet would be compatible to installed vertical on valve horizontally on ICCU panel and area servicing unit and also vertical to fit in pendants.
It would only supply with correct probe/ adopter.
Make :- AKTIV/MEDLINE/MPS/MEC(INDIAN
Supply, fixing, installation and testing of BPC Flowmeter with humidifier bottle would be BPC single type Pipeline Flow Meter unit duly fitted with the fine adjustment valve. It would be backpressure compensated to bear and control the Oxygen Pressure approx 60psi. Flow meter unit would be consisting of double wall rotta- meter has range of flow 0 to 13 ltrs. per minute with fine adjustment valve. The rotta meter and humidifier bottle would be made of clear, impact resistance polycarbonate (duly graduated). This unit would be have attachment to fit humidifier bottle of capacity 100 Ml. consist of clear, impact resistance polycarbonate jar. This would also have Reciprocating on top for flow meter/plastic cap having nozzles for outlet tubes and the inlet tube end would be multi function combination bubblier/ nebulizer to add the humidity and create an aerosol in Medical Gas min marks would be on jar complete all as specified and directed.Make :- AKTIV/MEDLINE/MPS/MEC(INDIAN
Supply, fixing, installation and testing of ISOLATION VALVES (CE certificate/HTM-2022/02-01/DIN/ISO/BS/ENI rated at 400 psig) of following sizes to control the pressure as well as for maintenance quarter turn open at 90-degree ball type valves would be provided. These valves would be of nickel-plated brass body having PTFE seat and inner outer seals. These valves would have stainless steel ball of specific ID clearance so that line pressure would not drop. For installation only PTFE gaskets would be used in between nuts and valve to prevent leakage. All the nuts for fixing the ball valve would be of brass with brass nozzlesfor easily brazing with copper tube complete all as specified and directed. :- Make:-AKTIV/MEDLINE/MPS/MEC(INDIAN)
Supply, fixing, installation and testing of MEDICAL GAS MONITORING ALARM (AREA-WISE/MAIN) SPECIFICATION: (CE certified/HTN-2022/ 02-01 Standard/DIN/ ISO-certified). Supply, fixing, installation and testing of a Gas failure Alarm would be provided which must be capable of monitoring all the Medical Gases. This alarm would be of ELECTOMECHANCIAL TECHNOLOGY, To detect the fault, pressure sensors, which detect deviation from the normal operating limits, would be installed. Each pressure Gas would displayed by colored LEGEND'S to show normal and low conditions. At the time receiving the fault the normal window/ indicator stop indication and other window would blink and it also gives audio alarm. The alarm panel would have a test facility to check the internal circuits, mute facility for making silent the buzzer, acknowledgement facility for receiving the fault and reset facility fo resetting the alarm after rectifying the fault complete all as specified and directed.
Supply and installing commissioning and testing of LT panel/ outdoor Kiosk type factory made weather and vermin proof fixed on and including ventilation and louvers arrangement, PCC (1:2:4) foundation of required/suitable size and as directed at site with angle iron frame of size and as directed at site with angle iron frame of size 40x40x6mm, 3 phase,4 wire, 415 volts, 50 Hz, fabricated out of 3.15 mm thick MS sheet including two coats of synthetic enamel paint over a coat of primer red oxide paint and keeping adequate working space inside the box (outer width of the box not less than 45 cm and gap between bus bar not less than one inch) and double door be provided with proper hinged and sliding door handle including locking arrangement as directed and before manufacturing the panel and the same have the following electric controls :-
Insulation epoxy painted high conductivity Copper bus bar 1000 Amps for 3 phase and neutral complete all as specified and directed.
Digital Voltmeter 0 to 500 Volts - 01 set
Digital Ampere meter 0 to 200 Amps capacity - 01 Set
Indicating lamps Neon type for RYB - 01 set
Incoming
Mannual Drawnout version, ACB 4 pole, 50 KA , 440 Volts, 3 phase, 4 wire, capacity 630 Amps as incoming , Ics = 100 % Icu, with Microprocessor, Release IPR 1, - 01 Nos . (Make - Havells Part No - IHAFE21060 , C&S Part No WX06N4P*A(S), HPL Part No - BN064CM0D0D0NG0)
Outgoing
Thermal Magnetic protection unit type MCCB 4 pole 35 KA, 440 Volts, 3 phase, 4 wire capacity 160 Amps as outgoing - 05 Nos
M&L for earthing complete with GI or steel earth plate electrode 60cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 Mtrs below ground level) with top edge of earth plate not less than 1.5 Mtrs below ground level connected to GI earth strip 32X6 mm by means of nuts, bolts, thimbles, chuck nuts, washers of GI or steel, including PCC (concrete chamber) shall be PCC 1:3:6 type C-1 using 20mm graded stone aggregate, with fair finish internal surface of concrete chamber shall be given 15mm thick plaster in CM 1:4, funnel with wire gauge of (0.68mm) 8 mesh per liner inch, 80 mm thick RCC pit cover 320 mm x 320 mm of RCC 1:2:4 type B-1 using 20 mm graded stone aggregate reinforced with XPM, JALLI and charcoal dust and common salt all as shown in electrical plate No 3 of MES SSR Part-I and specified including provision of earth wire protected by 40mm dia medium grade GI pipe and watering pipe shall be 20mm bore medium grade GI pipe, and including all excavation and earth work & connecting the earthing to an earthing test point /transformer neutral/body/ Lt panel etc. and testing on completion, complete all as specified & directed.
Material and labour for earth continuity conductor or main earthing strip fixed to wall on batten or porcelain insulators or recess or chases or buried in ground or drawn in GI pipe 40 mm or fixed with poles or any other indicated situation for loop earthing etc as required using galvanised iron strip of size 32 X 6 mm complete all as directed. NOTE:- (i) Cost of GI Pipe 40 mm shall be inclusive in the quoted rates.
ANANYA CONSTRUCTION CO.
Raman Bio Medical Engineers
M/s Kamal Builders
M/S C S AITHANI
Singla Electricals
M/S SATPAL AND BROTHERS
BHARAT ELECTRICAL TRADERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .