Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical document are not as per requirement |
Tender Value
₹6.5 L
EMD Value
₹6,500
Closing Date
16 Apr 2022, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
S.E., E.W.C., Lucknow(MVVNL)
TIPE IV/3, TRANSMISSION STAF COLONY DEVA ROAD, CHINHAT,Lucknow
CONSTRUCTION OF INCREASING CAPACITY OF 33/11 KV S/S BASTAULI FROM (2X5 MVA TO 1X5 AND 1X10 MVA) AND ASSOCIATED 11 KV OUTGOING FEEDERS, DISTRICT-LAKHIMPUR KHERI
2022_MVVNL_685014_1
04/EWCL/2022-23
Open Tender
Miscellaneous Works
Fixed-rate
30 days
LAKHIMPUR
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,180
A/CNo.-0758002100009592,IFCS Code-PUNB0586800
₹6,500
19 Apr 2022
6 Apr 2022
16 Apr 2022
6 Apr 2022
16 Apr 2022
6 Apr 2022
180 days
Amount
Dragging, loading, carriage and unloading of following store material with proper stacking from ESC Lakhimpur to JE's dump store and from store to work site:
33/11 KV 10 MVA Transformer
11 KV VCB O/G CTR 200/100/5 AMP, 350 MVA
11 KV 3x300 SQ MM XLPE
11 KV 3x120 SQ MM XLPE
MS Angles 75x75x6mm
Panther Conductor
PCC Pole 8.5mtr long
MS Channel 100x50x2028 mm (Dropper for Fuse Set)
MS Channel 100x50x2240mm Top Channel
11 KV Polymeric Disc Insulator T & C
11 KV Disc fitting T & C type 4500 Kg.
11 KV Composite Polymeric Pin Insulator
Earthing of pole by MS Earthing rod 20x2500 mm & 6 SWG earthing wire etc Complete
MS Angle 65x65x6mm 2028 mm
Complete Stay (GI Stay rod 16x1800 mm, Stay 7/10 SWG 5 Kg.)
11 KV 3x300 SQ MM XLPE Cable Outdoor
11 KV 3x300 SQ MM XLPE Cable Indoor
11 KV 3x120 SQ MM XLPE Cable Outdoor
11 KV 3x120 SQ MM XLPE Cable Indoor
ST Pole 11 Mt Long-SP-55
V-type cross arm 65x65x6 mm
11KV Disc Insulator T&C. Type 4500 Kg.
Disc Fittings Dog/ Racoon 4500 Kg
11KV Pin Insulator
11 KV Pin with Nut
M.S. Angle Iron 65x65x6mm, 2700 mm long for Braching
GI wire 8 SWG for guarding along the line
Guarding Angle 65x65x6mm
ACSR Rabbit Conductor
Plinth of 10 MVA 33/11KV T/F: Repairing of existing 5 MVA T/F plinth for 10 MVA T/F.
Erection and installation of 33/11KV 10 MVA T/F
Erection and installation of 33/11KV 10 MVA T/F in a levelled position of the plinth. The work includes shifting of T/F to the site & installation within the S/S premises, assembling, fixing and fitting of all accessories and filling of T/F oil to the desired level and ensuring that there is no leakage. All jumpering & connection are included in the scope of work.
Earthing for power T/F by way of boaring and lowering of 40mm dia, 2.9 mm thick GI Pipe from ground upto the water level (minimum 60 feet deep) as per standard practice as per REC Drg.
Fabrication and grouting (1:4:8) of MS Channel 100x50mm in L Shape & in proper size and alignment to provide support for the two separate earthing strips (50x6)mm size for power transformer neutral including supply & fixing of two no. flexible copper bonds for neutral earthing as per Drg.
Fabrication and erection of cable support made of two pieces of MS channel 100x50mm, 3.0 mtr. long joined to each other by means of 5 no. MS Fat 50x6mm pieces of size 150mm long each by welding at equal intervals as per drawing and grouting in block of size 300x300x700mm (1:4:8) complete with one coat of ready mixed primer and two coats of Al. Paint. This includes providing of four no. MS Clamp made of MS Flat holding the cable including nuts & bolts and fixing of XLPE cable.
Installation of Switchgears in Control Room:
Shifting carefully & installation safely 11KV O/G switchgears from outside the switchgear room placing and fixing of switchgear on foundation providing G.I. Bolt & Nuts of proper size in proper position and alignment and checking, complete work with proper testing & commissioning of switchgears.
Fixing and making Bus Bar connections in between all switchgears after cleaning and tapping with H.T. Tape, empire tape and PVC tape properly, providing and fixing of 6 mm thick Bakelite separators and plugging of all opening & holes with plastic compound complete work as per satisfaction of site incharge.
HT Cable Laying :
Laying & dressing of 11KV 3x300 Sq.mm U/G cable from 10MVA T/F to 11KV incoming Switchgear by excavation of earth in the trench 450mm wide, 900mm deep providing 150mm fine sand cushion below the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable. (All the matrical provided by the contrector Expect Cable).
Layng & dressing of 11KV 3x120 Sq.mm U/G cable from 10MVA T/F to 11KV incoming Switchgear by excavation of earth in the trench 450mm wide, 900mm deep providing 150mm fine sand cushion below & above the cable. The cable shall be duly protected by bricks, sand & stone slab and refilling & ramming of the left out soil. Spare cable shall be left and buried in the trench in the shape of rings at both ends. Cable laying work includes unrolling, cutting, making ring and sealing both ends of the cable.(All the matrical provided by the contrector Expect Cable).
Supply & Fixing of 11KV Cable Ends:
Hoisting of 11KV Cable with 100 mm dia 3 Mtr. long GI Pipe on the feeder cable before mounting the cable on the double pole, lifting, mounting and clamping of 11KV feeder cable boxes on the feeder double pole structure and making connection including supply of cable mounting clamps. The work includes the sealing of GI Pipes, lower end of the pipe is to be buried into the earth by about one foot. (All the matrical provided by the contrector).
Hoisting of 11KV Cable for 11 KV switchgears & 33/11KV T/F.
Making vertical/horizontal jumper connections using Panther/Dog Conductor with existing busbar gantry through PG Clamps and connecting all equipments with each other through connecting clamps. The work includes all the jumpes from busbar to T/F (1no. T/F bay)
Supply and laying of following size Copper Control Cable through underground/cable trench/trenching SGR interlinking through proper connections to T/F Control panel/protection board/Battery and Battery Charger/Bunch joints, Relay 33/11KV T/F junction Box/33KV VCB, CTs etc. as per site conditions:
6x2.5 Sq.mm
Painting of all structures and equipments.
(a) Excavation of foundation pit in mix soil/normal soil, soft & hard rack and its back filling and levelling etc. The size of the pit will be 800x900 mm and having a depth of 1/6 of the full length of the support. Erection of supports by providing stone pad, fixing all clamps and other accessories such as No. Plate, Danger Board, Barbed Wire (2Kg.), Painting etc. as per relevant RESPO/ RES. drawing . This includes any fabrication, if required. (b) Grouting of above supports with cement, concrete (CC will be of cement coarse sand & brick ballast) Grouting will be done with the help of wooden/steel formers in a block of size 450 mm x 450 mm x 1/6 of the full length of the support in the CC 1:4:8 ratio as per RESPO/ RES. drawing including back filling and proper ramming. (c) Making of plinth of STP 300 mm, dia & 300 mm above ground level in CC of 1:4:8 & plastering of the same with 12 mm thick plaster of cement & sand in 1:4 ratio. (d) Earthing of supports with Earth Electrode 2.5 mtr. length including excavation of pit and driving M.S. Rod upto proper depth and connecting the earth electrode with the help of 8 SWG G.I. Wire and earthing lugs. RESPO/ RES. drawing.
For Single Support 11Mtr. STP :
For Single Support 8.5 mtr PCC :
For Section Double Support 8.5 Mtr. PCC :
(a) Grouting of stay rods 1800x16 mm including all works of excavation grouting by , cement concrete in size 0.60x0.60x0.3 mtr. with ratio 1:4:8 as per relevant drawing including back filling of earth and proper ramming. (b) Fixing, tightening & nuzzling of stay with the poles and required tension as per RESPO/ RES. drawing.
Laying, spreading, lifting, Stinging, jointing and final sagging of ACSR Dog Conductor in accordance with profiles and sag chart including binding, jumpering and fixing of all accessories in 3 nos. conductor in parallel with PG Clamp binding wire etc requested for job.
Guarding between two poles like single/double/Tri./Four Poles etc. to guardLT/11 KV/Telephone lines, Road/River Crossing etc. with G.I. Wire 6 SWG and G.I. Wire 8 SWG including fixing of guarding channel of requested site with clamps and nuts and bolts as per RESPO/ RES. drawing
Supply and fixing of Rubber mat 8/10mm, 2x4mtr.
NATIONAL CONTRACTOR & GENERAL ORDER SUPPLIER
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .