Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
Refer Docs
EMD Value
₹4,956
Closing Date
22 Oct 2026, 11:00 am4d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Resident Enginner
REGPHD GIRINAGAR
O and M of 220 Substation
2026_HPSEB_145770_1
REGPHD-46/2026-27
Open Tender
Repair and Maintenance Works
Percentage
30 days
GIRINAGAR
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Yes
₹4,956
14 Oct 2026
14 Oct 2026
22 Oct 2026
14 Oct 2026
22 Oct 2026
14 Oct 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1O/M of 220/132kV Sub-station at Girinagar | |||||
| 1.01 | Dismantling of 2 Nos. existing defective MiCOM ALSTOM P40 Agile/P141 numerical protection relays installed on 33 kV Nahan Feeder and 33 kV Paonta Feeder and supply, providing, fixing, Programming ,mounting, wiring, testing and commissioning of 2 Nos. suitable Ashida make numerical self powered protection relays Type ADR241S , complete with necessary mounting/adaptor arrangement, panel modification, CT/PT secondary circuit reconnection, 110/220V DC auxiliary supply, trip, alarm and indication wiring, ferruling, lugs and termination accessories, relay configuration and protection settings, secondary injection testing, trip circuit testing and functional testing with associated 33 kV circuit breakers. The work shall also include supply, providing and fixing of 2 Nos. master trip relays with 2NO+2NC contacts, 2 Nos. 4-pole TNC switches, 2 Nos. hooters, R-Y-B indication lamps and 2 Nos. CMO-4 switches, ammeter, Voltmeter ,complete with mounting as per sample , internal control wiring, interconnection, ferruling, termination and necessary panel modification. The complete scheme shall be checked, tested and commissioned including operation of trip, close, alarm, hooter, master trip, TNC/CMO controls and indications, in all respects as per HPSEBL specifications and instructions of Engineer-in-Charge. | 1 | Job | 3,45,000 | ₹3,45,000 |
| 1.02 | Repair & fault diagnosis, testing and commissioning of 2 Nos. existing defective MiCOM Alstom P40 Agile / P141 numerical protection relays installed on 33 kV feeders. The relays are not sensing/measuring fault current properly and not issuing trip command to the associated circuit breaker. The work shall include detailed inspection and fault diagnosis of relay hardware, power supply section, CT input/current sensing circuits, digital input/output circuits, trip output contacts, protection logic, communication/configuration, internal wiring and terminal connections; checking of relay event/fault records and protection settings; rectification/repair/replacement of defective internal components wherever required; checking and correction of CT secondary input circuits and trip command circuits; restoration of required over-current/earth-fault protection functions; relay programming/configuration as per approved settings; secondary injection testing for pickup, timing and tripping characteristics; verification of trip output to 33 kV circuit breaker, alarm/indication functions, trip circuit continuity and functional operation; complete testing, commissioning and handing over of both relays in healthy working condition, including all labour, tools, testing equipment, minor repair components, wiring accessories, ferrules, lugs and consumables required for completion of the work, as directed by Engineer-in-Charge. | 1 | Job | 50,000 | ₹50,000 |
| 1.03 | Dismantling of damaged 220 kV Lightning Arresters (LAs) of Y & B phases installed on the HV side of 100 MVA Transformer No. 1 and replacement with serviceable LAs provided by HPSEBL Department, including transportation of serviceable LAs from Divisional Store to the substation site by tractor-trolley, loading and unloading, shifting, lifting and positioning with the help of Hydra crane, installation, fixing, electrical connections, testing and commissioning, including all labour, transportation charges, Hydra crane, tools and tackles, testing equipment and other incidental charges, complete in all respects as per instructions of the Engineer-in-Charge. Dismantled LAs shall be safely handed over to the Department. | 1 | Job | 25,000 | ₹25,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.56 MB
BOQ_217193.xls
BOQ • 0.24 MB
2026Tenderdocument46.pdf
Tender Documents • 1.19 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .