Premonsoon maintenance and repair of HT electrical installations such as switchgear transformer VCB HT Relay ACB control panel including allied works of 3rdACPS CPSACPS2nd ACPS at Paschim Chowbhaga PS Anandapur District South 24 Parganas duri
2026_IWD_993254_1
WBIW/EE/MDMD/e-NIT-20/2025-26
Open Tender
ELECTRICAL WORKS M/R
Percentage
Chowbhaga
Please refer Tender documents.
5 documents required · 5 mandatory
₹63,712
11 Sept 2026
23 Jan 2026
12 Feb 2026
23 Jan 2026
11 Feb 2026
23 Jan 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Opening the Transformer breather and refitting the same after changing the sillica jel including the supply of necessary gasket and silica jel. | 6 | Per Job | 1,632.77 | ₹9,796.62 |
| 2 | Dehydration & filtration of power transformer oil to raise the dielectric strength to the value specified in IS including submission of test result. The cost includs man, machinary, and tools & plant hire charges to complete the at site as per direction of the EIC. | 5,900 | Ltr. | 12.55 | ₹74,045 |
| 3 | Maintenance and servicing of Dry type Cast Resin Transformer 11kv/.415 kv ( 1000kva/630 kva) , with engagement of suitable manpower and tools and tackles, testing equipments, air blowers etc as per manufacturer maintenance guideline including checking core and core assembly to ensure that HT tap links of all the three phase are at proper position and adequately tightened and locked, to check and ensure that all HT/LT connection nut bolts are fully tightened and locked, to check and ensure that the core, coil and its connections are thoroughly checked for any cobwebs, dust, dirt using air blower etc. Checking the enclosure perforated sheet/ mesh and clean thoroughly for cobwebs, dust, dirt to ensure adequate and proper ventilation of air through the same. Checking the Marshalling box , to check and ensure that Winding Temperature indicator (WTI) and Winding Temperature Relay (WTR), WTR alarm, trip contacts are in working condition and its temperature scanner/sensing thermisters are healthy and functional, to check and ensure that alarm trip circuit of WTI/WTR are working satisfactorily, also to check and ensure that HT/LT circuit breakers for its tripping on getting signals from WTI/WTR, to check WTI for its proper temperature setting for alarm and trip. Checking of HT/LT bushing and examine for dirt deposits and cleaning with non-fibrous, non fluffy cloth. Also checking of Earth resistance and to take corrective action if found more. Also taking note of winding temperature (WTI) hourly for at least seven days and submission of report mentioning the findings and test report for Insulation Resistance Test: HV-LV, HV-Earth, LV-Earth, Winding Resistance Test to check phase imbalance. (Note: The work shall be done on CRT, after isolation/ disconnection of HT/LT cables and ensuring that its HT/LT windings are solidly earthed at its main terminals. Also It must be ensured before closing that no metallic parts viz nuts, bolts, electrical cut wire pieces, cotton waste, spanners etc are left inside the enclosure/ on core/ on coils as this cause hazardous accident and failure of the CRT) :- job | 1 | Job | 44,201.48 | ₹44,201.48 |
| 4 | Maintenance and servicing of Dry type Cast Resin Transformer 11kv/6.6 kv (2000kva/1600kva), with engagement of suitable manpower and tools and tackles, testing equipments, air blowers etc as per manufacturer maintenance guideline including checking core and core assembly to ensure that HT tap links of all the three phase are at proper position and adequately tightened and locked, to check and ensure that all HT/LT connection nut bolts are fully tightened and locked, to check and ensure that the core, coil and its connections are thoroughly checked for any cobwebs, dust, dirt using air blower etc. Checking the enclosure perforated sheet/ mesh and clean thoroughly for cobwebs, dust, dirt to ensure adequate and proper ventilation of air through the same. Checking the Marshalling box , to check and ensure that Winding Temperature indicator (WTI) and Winding Temperature Relay (WTR), WTR alarm, trip contacts are in working condition and its temperature scanner/sensing thermisters are healthy and functional, to check and ensure that alarm trip circuit of WTI/WTR are working satisfactorily, also to check and ensure that HT/LT circuit breakers for its tripping on getting signals from WTI/WTR, to check WTI for its proper temperature setting for alarm and trip. Checking of HT/LT bushing and examine for dirt deposits and cleaning with non-fibrous, non fluffy cloth. Also checking of Earth resistance and to take corrective action if found more. Also taking note of winding temperature (WTI) hourly for at least seven days and submission of report mentioning the findings and test report for Insulation Resistance Test: HV-LV, HV-Earth, LV-Earth, Winding Resistance Test to check phase imbalance. (Note: The work shall be done on CRT, after isolation/ disconnection of HT/LT cables and ensuring that its HT/LT windings are solidly earthed at its main terminals. Also It must be ensured before closing that no metallic parts viz nuts, bolts, electrical cut wire pieces, cotton waste, spanners etc are left inside the enclosure/ on core/ on coils as this cause hazardous accident and failure of the CRT) :- job | 2 | Job | 47,540.9 | ₹95,081.8 |
| 5Schedule for testing of 11 kv VCB, 4 panel complete set at 3rd Additional Chowbhaga Pumping station at Paschim Chowbhaga, P.S.: Anandapur, Dist: South 24 Parganas. | |||||
| 6 | Following tests are to be performed for the 11 kv VCB, 4 panel (1 no incoming and 3 nos outgoing) and test report to be submitted in tabular format in triplicate mentioning the instrument used with calibration certificate.
I Electrical Test:
Insulation Resistance Test (5 kV): Phase-Phase, Phase-Earth.
H.V test of 4 nos VCB Panels
ii CT/PT & Metering Compartment
IR test for CT/PT secondaries.
Polarity & ratio checks.
Check wiring tightness, PT fuses.
iii Busbar System
IR test of busbars.
Inspect for dust, corona marks, rodents.
iv Cable Terminations
Inspect heat shrink/ epoxy terminations.
IR testing of cables.
Tightness check & thermography.
v Transformer IR & H.V test. For 3 nos transformer
vi Earthing System
Earth continuity inside panels.
Earth electrode resistance.
Check earthing of CT/PT frames and panel body. | 1 | Job | 1,07,262 | ₹1,07,262 |
| 7 | Taking out samples of oil and carrying out chemical test of oil in respect of its acidity test through reputed test house and submission of Test Result. | 6 | Per Test | 1,543.38 | ₹9,260.28 |
| 8 | Takingout sample of oil from power/voltage transformer, OCB etc. & testing their dielectric strength according to specification and submission of test result. | 6 | Per Test | 635.53 | ₹3,813.18 |
| 9Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :3M / Raychem mak | |||||
| 9.01 | 120 -185 sq. Mm | 7 | Each | 17,935.4 | ₹1,25,547.8 |
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.72 MB
BOQ_2429258.xls
BOQ • 0.39 MB
2911i.pdf
Tender Documents • 0.93 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .