| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.7 LAccepted-AOC KHATA NO 254 529 KHASRA NO 364 2 MIN PREET NAGAR A GALI NO 2 HARERI ROAD OPP STAR STUDIO HERARI SANGRUR | SANGRUR | SANGRUR | PUNJAB | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹29.7 L+₹1.9 L (6.97%)Rejected-Finance RAJKOT ROAD AIR FORCE STATION HALWARA 141106 PUNJAB | HALWARA | LUDHIANA | PUNJAB | 141106 | L2 | Rejected-Finance Other than lowest | |
| 3 | L3₹33.5 L+₹5.8 L (20.9%)Rejected-Finance 303 GHS 888 SECTOR 20 PANCHKULA 134116 HARYANA | PANCHKULA | PANCHKULA | HARYANA | 134116 | L3 | Rejected-Finance Other than lowest |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
24 Jun 2021, 6:00 pmClosed
GE (AF) Halwara
GE (AF) Halwara
REPAIR MAINT OF LT PANELS AND VOLTAGE STABLIZERS AND ALLIED WORKS AT AF STATION HALWARA
2021_MES_449275_1
GE/HAL-09/2021-22
Open Tender
Civil Works
Item Rate
273 days
GE (AF) Halwara
MES ENLISTED CONTRACTORS CLASS D CATEGORY b i
8 documents required · 8 mandatory
₹500
Yes
GE (AF) Halwara
₹60,000
Yes
28 Jun 2021
7 Jun 2021
26 Jun 2021
7 Jun 2021
24 Jun 2021
12 Jun 2021
Amount
M&L in replacement for feeder pillers box factory made -out door type made out of MS sheet (CRCA) of thickness not less that 3 mm. of size 75 x 75 x 45 cm with aluminium bus bar strip 4 Nos of 600 Amps rated suitable for 1100 volt (LT) mounted on LT porcelain insulator front opening door two leaf braced with hinged, mounted on 4 Nos of angle iron 50x50 mm duly welded with box and grouted in PCC block of size 30cmx30cmx 15cm in concrete 1: 3 : 6. Top of box MS sheet duly bent in/slope, tapper with projection of 30 mm on all side, weather/vermin proof with high quality of rubber beeding on panel door, cable entry arrangements at bottom includes earthing terminals 2 Nos at both side and painted with two coats of smoke grey stove enameled paint over a primer coat including providing MCCB, 4 pole,fixed type 400 Amps, 36 KA rating-01 No complete all as directed by Engr-in-Charge.
Cleaning, scrapping , preparing the old painted steel surface of any description and applying two coats of synthetic enamel paint over one coat of red oxide primer to HT/ LT panel of any size complete all as specified.
M & L in replacement for earthing complete with GI earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried directly in ground vertically at a depth not less than 2.25 mtr below normal ground level with top edge of earth plate at depth not less than 1.5 mtr below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcol dust and common salt filling in alternate layers and electrode connected by galvanised iron strip 32 mm x 6 mm by means of bolts, nuts, check nuts and washers connected to test termination point protected by 40mm bore GI pipe light grade and GI pipe light grade 20mm bore for watering and including funnel, wire mesh, RCC pit cover and PCC chamber pit with PCC 1:2:4 type B1 including exluvation and earth work, disposal of surplus soil to a distance not exceeding 50 mtr all as specified and shown in electrical plate No 3 of SSR Part I complete all as specified and directed. Note-- (i) The unit rate shall include for GI water pipe, protection pipe wire mesh, funnel, excavation, RCC pit cover, PCC, test point, G I strip 32 X 6 mm from top of earth plate upto 5 mtr (ii) PCC pit shall be provided at least 1.5m away from the earth pit and extra cost of additional length of water pipes and fixing junction, Elbows etc. shall be deemed to be included in the unit rate. (iii) RCC pit cover shall be percast of RCC 1:2:4, type B-1, 80 mm thick reinforced with XPM weighing not less than 4kg/Sqm in lieu of cast iron cover.
S&F in replacement MCB 63 A TPN complete all as specified and directed.
S&F in repairs MCCB 63 A 4pole 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 100 A 4pole 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 160 A 4pole 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 200 A 4pole 25KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 250 A 4pole 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 315 A/320 A 4pole 36KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 400 A 4pole 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
S&F in repairs MCCB 630 A 4pole 36 KA with Adjustable Thermal & fixed magnetic setting Ics =100% of Icu.complete all as specified and directed.
Material and Labour for inspecting and servicing of Oil cooled/ air cooled servo controlled voltage stabilizer of 5 KVA, 415V, 50 Hz, Three phase capacities installed at various locations within Air Force Station Halwara by cleaning the complete unit with suitable cleaning agent and checking the serviceability state of all the switchgears/ components such as variacs, ECC box, stepper motors, RC networks, control PCB, Carbon Brushes, sensing transformers, synchronising motor, drive gears etc complete and replacing the defective spare parts and testing for proper fuctioning complete all as specified and directed by Engineer-in-Charge. Note : Components / spare parts will be measured and and paid separately under relevant items of Schedule 'A', however the the cost of suitable wires, lugs, nuts, bolts and washers required for control wiring shall be included in quoted rate.
All as per Sl Item No 16 above but 10 KVA, 415V, 50 Hz, three phase
All as per Sl Item No 16 above but 20 & 25 KVA, 415V, 50 Hz, three phase
All as per Sl Item No 16 above but 30 KVA, 415V, 50 Hz, three phase
All as per Sl Item No 16 above but 50 KVA, 415V, 50 Hz, three phase
All as per Sl Item No 16 above but 100 KVA, 415V, 50 Hz, three phase
All as per Sl Item No 16 above but 150 & 160 KVA, 415V, 50 Hz, three phase
Supply and replace AC stepper motor of capacity 3Kg/CM suitable for servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge. Make: Servomax/Servocon/SCAN power stabilizer
Supply and replace AC stepper motor of capacity 10Kg/CM suitable for servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge. Make: Servomax/Servocon/SCAN power stabilizer
Supply and replace motor gear and variac shaft gear set suitable for servo controlled voltage stabilizer complete all as specified and dircted by Engineer-in-Charge.
Supply and replace RC Network 3Kg/CM to 10 Kg/CM suitable for servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace sensing transformer with triac board complete all as specified and directed by Engineer-in-Charge.
Supply and replace control PCB with wiring complete all as specified and directed by Engineer-in-Charge.
Supply and replace voltmeter 0 to 500 V of existing type suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace limit switches suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace POT meters suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace carbon brushes of various capacity suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace VARIAC of rating upto 15A suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace VARIAC of rating above 15A and upto 35A suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Supply and replace ECC box suitable for existing servo controlled voltage stabilizer complete all as specified and directed by Engineer-in-Charge.
Material and labour for Filtration/dehydration of transformer oil of oil cooled servo voltage stabilizer of various capacities installed at various locations within Air Force Station Hakimpet with mobile type filtration plant to achieve di-electric strength of 30 KV for 1 minute at 2.5mm gap as per relevant IS including testing and recording the values of dielectric strength of oil before and after filtration at site with transformer oil testing machine complete all as directed by Engineer-in-Charge.
Supply and Topping up of transformer oil into the body of servo controlled voltage stabilizer to the desired level complete all as specified and directed by Engineer-in-Charge.
Taking up/down worn out/damaged/unserviceable PVC insulated underground cable armoured, heavy duty with aluminium conductors of any size, 1100V grade from trench/duct/pole/wall/pipes/rooftops etc. complete all as specified and directed. Note:- Excavation and earth work shall be measured and paid separetely.
LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 35 sqmm 3.5 core. complete all as specified and directed.
LT UG cable XLPE insulated, PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches/on poles/walls/in ducts/passing through pipes etc including jointing materials such as cable glands, lugs etc of size 25 sqmm 3.5 core. complete all as specified and directed.
Excavation in trenches in soft or loose soil, not exceeding 1.5 metre deep and not exceeding 1.5 metre wide and getting out complete all as specified and directed.Notes : (i) Payment for excavation shall be made for one time in case the newcable is laid in the same trenches. (ii) Excavation upto top of brick protection shall be measured for payment purposes.
Returning, filling in trenches including spreading, leveling, watering and well ramming in layers not exc 25 cm thick in soft/loose soil complete all as specified and as directed.
Removing surplus excavated soil to a distance not exceeding 50 Mtr and depositing where directed at a level not exceeding 1.5 Mtr above the starting point complete all as specified and as directed.
Brick protection with sub class "B" bricks (old size) laid dry, flat in trenches over cable with longest dimension perpendicular to the axis of the cable complete all as specified and directed specified .
Sand cushioning in trenches and well ramming in layers below and above the cable with fine dry sand for cable protection and complete all as specified and directed.
GI tubing light grade as in cable protection pipe including all fittings complete all as directed for 40mm bore
M&L for boring upto 80mm dia under road/path/hardstanding to pass the HT/LT UG cables using mechanical machines including f PVC pipe 75mm dia complete all as specified and directed.
M/S SANGA SINGH AND CO
R D Bansal
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .