Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹62.7 LAccepted-Finance | L1 | Accepted-Finance Being L1 | |
| 2 | L2₹76.7 L+₹13.9 L (22.2%)Rejected-Finance | L2 | Rejected-Finance Not Being L1 | |
| 3 | L3₹82.5 L+₹19.7 L (31.4%)Rejected-Finance | L3 | Rejected-Finance Not Being L1 | |
| 4 | L4₹85.8 L+₹23.1 L (36.8%)Rejected-Finance | L4 | Rejected-Finance Not Being L1 | |
| 5 | L5₹87.3 L+₹24.5 L (39.1%)Rejected-Finance | L5 | Rejected-Finance Not Being L1 |
Tender Value
₹93 L
EMD Value
₹1.6 L
Closing Date
11 May 2022, 6:00 pmClosed
GE (I) (DM) VISAKHAPATNAM
GE (I) (DM) VISAKHAPATNAM NAVAL DOCKYARD 530014
LOAD TESTING OF PBS/CP, REPLACEMENT OF DEFECTIVE LT CABLES, CABLE END JOINT TERMINAL, REFRESH ALL CABLE CONNECTIONS AT CP/PB/JB/LT PANELS AND SERVICING / MAINTENANCE OF VOLTAGE STABILIZERS AND ALLIED WORKS AT N-4 TO N-24 JETTY AREA AT NAVAL DOCKYARD
2022_MES_505897_2
SSGE/8698/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE (I) (DM) VISAKHAPATNAM
As per Tender Documents
8 documents required · 8 mandatory
₹1,000
Yes
GE (I) (DM) VISAKHAPATNAM
₹1.6 L
Yes
4 Jun 2022
20 Apr 2022
19 May 2022
20 Apr 2022
11 May 2022
27 Apr 2022
Amount
Dismantling old LT panel carefully and supply, installation, testing and commissioning of floor mounted cubical/trunk type indoor made out of 2 mm thick CRCA steel sheet traded and powder coated, prewired, factory made , with provision for two incoming and Bus Coupler,individual comparment dust and vermin proof, weather proof electrical panel and with Godrej type lock, cable glands etc. and consisting of the following all as specified and as directed :- (i) Electrolytic aluminium Bus bar of capacity 2000 Amps for phases and neutral. (ii) ACB 2000 Amps Make scneider 4 pole breaking capacity 50 kA -0 3 Nos as incommer-02 Nos and 01 No for Bus Coupller. (iii) MCCB 630 Amps 4 pole 50 kA -01 Nos out going(iii) MCCB 400 Amps three pole breaking capacity 36 kA -01 Nos as out going . (vi) Digital Ampmeter 0-2000 Amps-02 Nos . (vii) Digital voltmeter 0-500 Volts-02 Nos .(viii) Indication lamps RYB -03 sets. (locatio-550/2 SS) Note : Drawing for LT panel showing layout of incoming and outgoing switch gear with capacity before errection shall be approved by Engr-in-Charge.
M&L for shifting voltage stabilizer of capacity 1500 KVA to another place within dockyard area carefully after disconnecting input and output cable connection and reconnection of cables input and out put in original complete all as specified and as directed. Note :- Nacessary Man power/Transpotation chage included in the quoted rate.
Load testing of PBs,Cope points and voltage stablizer installed at various jetty areas, Gallaries, substations using artificial electrical rectifier load bank of capacity from 1000 Amps to 2000 Amps including necessary required cable input out put connectin for testing to checking Voltage drop will rectified by checking cable size and loose connection, checking and record power factor by mainting 0.9 to 01, Load testing will be carried out in four hours continuously for 25%,50 %, 75% and 100% for one hours each objects respectively and all record will maintain and sheet will be submited to engr-in-charge complete all as specified and as directed. Note :- (i) Artificial rectifier load bank shall be provided by department. (ii) Required man power for collection/handling and shifting from testing place to another place including deposit to original place after complete of testing work shall be arrange by the contractor. (iii) Required cable size and length for testing shall be arrange by the contractor.
Servicing/maintenance of voltage stabilizer of capacity 1000 KVA to 1500 KVA by forced air cleaning of movable and fixed unit, decarbonize busbar chamber and checking for any defects due to any flush/loose contact. Cleaning of all fixeddd and moving contact terminal connection points with CTC, replacement of defective cables complete all as specified and as directed. Note :- All cleaning agents are included in the auopted rate.
Supply and fix dimmer starter for regulating voltage of voltage stabilizer capacity 1000 KVA to 1500 KVA, 3 phase, 415 volts, 50 Hz and taking out old unserviceable one complete all as specified and as directed. (Make Servo max/Jindal as required and as per existing.
Supply and fix forward/reversible synchronous motor of torque 20 kg capacity for voltage stabilizer of capacity 1000 KVA to 1500 KVA, 3 Phase , 415 volts, 50 Hz and taking down old unserviceable one complete all as specified and as directd.
S&F PCB of networking uit with complete resister and capacitor for voltage controlling/regulating for voltage stabilizer of capacity 1000 KVA to 1500 KVA 3 phase, 415 volts, 50 Hz and taking down old unserviceable all as specified and as directed
S&F PCB of electdronic micro processed based controller suitable for voltage stabilizer of capacity 1000 KVA to 1500 KVA 3 phase, 415 volts, 50 Hz and taking down old unserviceable one complete all as specified and as directed
S&F frequency meter relay high/low adjustable 96mmx96mm suitable for voltage stabilizer of capacity 1000 KVA to 1500 KVA 3 phase, 415 volts, 50 Hz and taking down old unerviceable one complete all as specified and as directed.
S&F busbar anodised aluminium off sizes including required drilling holes for fixing with other bus/cable connections and taking down old unserviceable one complete all as specified and as directed
Taking down old and supply, laying and connecting up through surface/wall/duct, cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) 100 volts grade with straded aluminium conductor of size 400 sqmm 3.5 core including necessary lux complete all as specified and as directed.
All as per item No 12.00 above but Size of 500 sqmm 3.5 core.
All as per item No 12.00 above but Size of 300 sqmm 3.5 core.
Supply and fix heat shrink straight through joints, LT 1100 volts grade, 3.5 core. 240 to 300 sqmm including ferral complete all as specified and as directed.
Supply and fix heat shrink straight through joints, LT 1100 volts grade, 3.5 core. 400 to 500 sqmm including ferral complete all as specified and as directed.
S&F LT heat shrink cable end termination for cable sizes 240 to 300 sqmm 3.5 core, 1100 volts grade by cutting out damaged portion of XLPE insulated cable ends for the following sizes including disconnection cable ends from ACG/MCCB/Busbar and reconnection with existing new stainllss steel bolts of size not less than 16 mm dia and 40 mm long complete all as specified and as directed. (Make- 3M Cat No MHI/OX1.1 KV (HESL-4/4C) or eqquivalent of Dension/M seal/RPG
All as fper item No 17.00 above but fdor cable sizes 400 to 500 sqmm Make- 3M Cat No MHI/OX1.1 KV (HESL-6/4C) or eqquivalent of Dension/M seal/RPG
Servicing, repair, maintinance of Air Circuit Breaker 630 Amps to 3200 Amps capacity by drawing out movable unit, forced air cleaning of movable and fixed unit, decarbonize breaker contracts and checking for any defects due to any flush/loose contact, cleaning of all fixed and moving contact point, terminal connection points with CTC, replacement of defective parts and re-fixing ACB, cables completes all as specified and as directed. Note: (a) required male/female ACB contacts, trip coils, closing coils, electronic protection unit will be measured as supply only. (b) all cleaning agents are included in the quoted rate.
Supply only fixed contract of ACB 630A to 3200A complete all as specified and as directed.
Supply only Moving contract of ACB 630A to 3200A complete all as specified and as directed.
Supply Only Electronic protection unit of ACB 630A to 3200A complete all as specified and as directed.
Supply Only shunt trip coil of ACB 630A to 3200A complete all as specified and as directed.
Supply Only closing coil ACB 630A to 3200A complete all as specified and as directed.
Supply only indication lamps (LED type) red, yellow and blue in colours of 22.5 mm dia to monitor on LT panel board suitable for 240 V AC supply and taking down unserviceable indication lamps complete all as specified and as directed. Cat Part No:-1SFA619402R5201 Make:-Siemens/C&S/schneider/ABB
Taking down unserviceable/burnt cable end termination by isolating power supply from transformer/LT panel disconnecting burnt/faulty cable from the bunch of cables in trenches/duct, removing cable loop and material and labour for making Re-rout, cable termination of 3 1/2 core armoured aluminium conductor cable of size 95 sqmm to 500 sqmm, 1100 volts with suitable size of cable glands, aluminium lugs duly crimpled and insulated with insulation tape (in different colours) duly replaced the rusted nuts, bolts and washers of nickel chromium plated with new ones and applying petroleum jelly, testing and commissioning complete all as specified and as directed.
Dismantling taking out LT/HT cable from panel/transformer/floor of sub station for repair or for realingnmetn of cable and refixing the cables with proper staking with proper alingnment of cable and refixing the cables with proper on repaired/existing rack/trench and making feeder wise bundle of cable using PVC cable tie for sizes of cable 3.0/3.5 core 95 sqmm to 185 sqmm 11000/1100 volt grade including required alumium thimble complete all as specified and as directed. (Note : each cable shall be measured separately.
All as per item No 29.00 above but for cable sizes 240 sqmm
All as per item No 29.00 above but for cable sizes 300 sqmm
All as per item No 29.00 above but for cable sizes 400 sqmm
Supply and fix rubber insulating mat in front of LT panel board of size 2 mm thick, 1 m width up tp 3.3 KV, make RPG or equivalent as approved by GE.complete all as specified and as directed.
M&L for writing letter and fixfing LT panel board surface showing incoming and outgoing capacity in Amps and feeder name of letter five not less than 30 X 50 MM complete all as specified and as directed.
M&L for by Weekly cleaning of entire substation building inside wall, ceiling, floor and outside wall, plith protection with suitable brush / broom & wiper, removing wild vegitation around entire substation (Note: recovery shall be made double the quotaed rate if timely cleaning is not carried out) Note :- Each sub station cleaning measured as one job .
Supply and fix MCCB, 3 pole, 630 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with Thermal magnetic release, Make- Schneider cat Part No- LV432876 or equivelent of Legrand/ABB
Supply and fix MCCB, 3 pole, 400 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with Thermal magnetic release, Make- Schneider cat Part No- LV432676 or equivelent of Legrand/ABB
Supply and fix MCCB, 3 pole, 200 amp, 36 KA breaking capacity, Ics = 100% Icu as per IEC 60947-2, with Thermal magnetic release, Make- Schneider cat Part No- LV431631 or equivelent of Legrand/ABB
All as item No 38.00 but of size 3 pole, 250 amp, 36 KA. Make- Schneider cat Part No- LV431630 or equivelent of Legrand/ABB
All as item No 38.00 but of size 3 pole, 160 amps, 25 KA. Make- Schneider cat Part No- LV430310 or equivelent of Legrand/ABB
M&L for painting of outer surface of multiple section of complete LT Panel board size up to 5.5 m x 2.5 M in one substation comprising ACBs/MCCBs/SDFs ,busbar chamber, swich gear chamber, metering chamber cable termination/tray using one coat of synthetic enamel paint after preparation of surface, providing protection cover to all metering equipment, panel meters, switchgears, cleaning of all meters and switch gears complete all as specified and as directed.
Material and labour for filtration/dehydration transformer oil of Servo, Voltage stabilizer, voltage grade 415 volts of any capacity inddoor type floor mountd in situ till achieve dielectric strength min 40 KV at 4 mm gap complete all as specifed and as directed.
Material and labour for topping up / replacement of transformer oil with new transformer oil suitable for working voltage 11000 volts grade incl necessary dehydration to achieve dielectric strength min 40 KV at 4 mm gap complete all as specified and as directed. Make : GULF/Castrol/HP/Power/Savita
B5BUILDING SOLUTIONS
S R CONSTRUCTIONS
Jessica Engineering Works
M/s NATIONAL ENGINEERING CONSTRUCTIONS CO
TECHNO SOFT SOLUTIONS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .