Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.4 LAccepted-AOC PLOT NO D 2 COAL DEPOT FOSBERY ROAD SEWRI E MUMBAI 400 015 | MUMBAI | MUMBAI | MAHARASHTRA | 400015 | L1 | Accepted-AOC BEING L1 | |
| 2 | L2₹31.7 L+₹68,688 (2.21%)Rejected-Finance | L2 | Rejected-Finance BEING L2 | |
| 3 | L3₹33.4 L+₹2.4 L (7.81%)Rejected-Finance | L3 | Rejected-Finance BEING L3 |
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
6 Feb 2024, 6:00 pmClosed
GE AF BARODA
GE AF BARODA PO DARJIPURA BARODA 390022
REPAIR / REPLACEMENT OF INTERNAL ELECT WIRING, DB SUB MAIN WIRING AT TECHNICAL AREA DAY TO DAY MAINT, REPAIR OF CEILING FAN AND GEYSER AT AFS MAKARPURA
2023_MES_632213_2
8852/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
GE AF BARODA
AS PER TENDER DOCUMENTS AND NIT
4 documents required · 4 mandatory
₹500
GE AF BARODA
₹60,000
Yes
13 Mar 2024
19 Jan 2024
13 Feb 2024
19 Jan 2024
6 Feb 2024
25 Jan 2024
Amount
Taking down carefully copper / Aluminium point wiring of light, fan, socket or power points complete including fittings, such as switches, ceiling roses, pendant holders, Batten holders, shades conical, fan regulators, light or power sockets etc and removing materials from site and making good disturbed surfaces of walls roofs etc complete all as specified and directed.
Material and labour for point wiring with using 2 x 1.5 Sqmm (nominal area) stranded copper conductor single core, PVC insulated (FRLSH) & unsheathed cable, 1100 volts grade as per IS 694 for Phase and Neutral, 1.5 Sq mm (nominal area) stranded copper conductor single core conductor, PVC insulated (In Green colour)& unsheathed cable as in earth wire connected to common earth dolly in existing concealed PVC conduit any type as per site requirement of suitable size all as specified and directed with and including providing new SS sunken box and Moduler cover plate for fixing of switch socket, fan regulators etc and incl all accessories complete all as specified and directed for the following:-
Note: (i) The quoted rates shall be deemed to be inclusive for any cutting chases in brick walls/pillars etc for fixing of suncken boxes and flush it & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with existing surfaces and provision of covering modular sucken box and modular cover plate of any shape . (ii) Fittings like switches sockets regulators, lamp holders light fittings shall be measured and paid for separately under respective items of BOQ.
One light / fan point controlled by one, one way switch.
One 3 pin 5 Amps socket outlet on same board with other switches.
One 3 pin 5 Amps socket outlet on independent board with cable of 1.5 sqmm size
One bell point controlled by one bell push
One light point controlled by two, two way switches
Description all as per item No. 2.00 here-in-before but using 2.5 Sqmm PVC insulated, unsheathed copper conductor cable and earth conductor of 2.5 sqmm copper cable for one 3 pin socket outlet 15 Amps on independent board.
Material and labour for concealed point wiring with using 2 x 1.5 Sqmm (nominal area) stranded copper conductor single core, PVC insulated (FRLSH) & unsheathed cable, 1100 volts grade as per IS 694 for Phase and Neutral, 1x 1.5 Sq mm (nominal area) stranded copper conductor single core conductor, PVC insulated (In Green colour)& unsheathed cable as in earth wire connected to common earth dolly in and including concealed rigid PVC conduitsize not less then 20mm dia as per site requirement of suitable size all as specified and directed with and including providing new SS sunken box and Moduler cover plate for fixing of switch socket, fan regulators etc and incl all accessories complete all as specified and directed for the following :-
Note: (i) The quoted rates shall be deemed to be inclusive for any cutting chases in brick walls/pillars etc for fixing of suncken boxes and flush it & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with existing surfaces and provision of covering modular sucken box and modular cover plate of any shape . (ii) Fittings like switches sockets regulators, lamp holders light fittings shall be measured and paid for separately under respective items of BOQ. (iii) The size of conduits shall be determined on permissible No of runs of wires as specified in SSR part I (2010) However minimum size of conduits shall be 20 mm dia (medium grade).
One light / fan point controlled by one, one way switch.
One 3 pin 5 Amps socket outlet on same board with other switch.
One 3 pin 5 Amps socket outlet on independent board with cable of 1.5 sqmm size
One bell point controlled by one bell push
One light point controlled by two, two way switches
Description all as per item No.4.00 here-in-before but wiring with 2.5 sqmm multistranded copper conductor unsheathed and 2.5 sqmm copper conductor unsheathed cable as earth continuity conductor for one 3 pin 15 Amps socket outlet point on independent board.
M&L for point wiring with using 1.5 Sqmm (nominal area) stranded copper conductor single core PVC insulated & unsheathed cable 1100 volts grade in and incl PVC casing and caping of suitable size fixed on surface all as directed with using new sunken type pressed steel box/terminal boxes for mounting fittings/junction boxes not less than 1.6 mm thick duly painted with two coats of black bituminous paint over a coat of red oxide primer with and incl all accessories and using 1.5 Sq mm (nominal area) stranded copper conductor single core conductor PVC insulated & unsheathed cable as in earth wire connected to common earth dolly complete all as specified and directed for the following:-
Note: (i) The quoted rates shall deemed to be inclusive for any cutting chases in brick walls/pillars etc for fixing of suncken boxes and flush it & making good the disturbed surface in cement mortar 1:4 including finishing the surface to match with existing surfaces and provision of covering modular sucken box and modular cover plate of any shape . (ii) Fittings like switches sockets regulators, lamp holders light fittings shall be measured and paid for separately under respective items of BOQ. (iii) The size of PVC casing caping shall be determined on permissible No of runs of wires as specified in SSR part I (2010) and as specified in preamble 1 (a) to (q) of section 19, sub section 13 - Internal work of SSR-II, 2020.
One light point controlled by one, one way switch.
One fan point controlled by one, one way switch.
One 3 pin 5 Amps socket outlet on same board with other switch.
One 3 pin 5 Amps socket outlet on independent board with cable of 1.5 sqmm size
One light point controlled by two, two way switches
Description all as per item No. 6.00 here-in-before but wiring with 2.5 sqmm multistranded copper conductor unsheathed and 2.5 sqmm copper conductor unsheathed cable as earth continuity conductor for one 3 pin 15 Amps socket outlet point on independent board.
Note: (for item 01 to 7): Being maintenance work Contractor shall carry out even single point wiring or associated work as per the direction of concerned JE(E/M)/AGE E/M. In case contractor fails to execute the allocated work within 3 days from the date of allocation a recovery at the dauble of quoted rate shall be levied upon contractor and no claim whatsover on this account shall be entertained by the Government.
M & L for sub main wiring using two single core 6 Sqmm fire retardant PVC insulated and unsheathed cable with copper conductor 1100 volts grade ISI marked drawn through and including PVC Casing Caping/PVC Conduit or in existing concealed conduit (as required & directed by Engr-in-Charge) with accessories like bends, tee, etc fixed on wall and ceiling including 6 Sqmm earth wire, FR PVC insulated & unsheathed and connecting to earth dolly including taking down existing wiring complete all as specified and directed. Note: (i) Two runs of 6 sqmm and one run of 6 sqmm earth wire and one run of PVC conduit / casing caping shall be measured as one unit. (ii) Necessary plastering to the disturbed surface of wall and distempering /white washing to match the existing colour shall deemed to be included in the quoted rate.
M & L for sub main wiring using two single core 4 Sqmm fire retardant PVC insulated and unsheathed cable with copper conductor 1100 volts grade ISI marked drawn through and including PVC Casing Caping / PVC Conduit or in existing concealed conduit (as required & directed by Engr-in-Charge) with accessories like bends, tee, etc fixed on wall and ceiling including 4 Sqmm earth wire, FR PVC insulated & unsheathed and connecting to earth dolly including taking down existing wiring complete all as specified and directed. Note: (i) Two runs of 4 sqmm and one run of 4 sqmm earth wire and one run of PVC conduit / casing caping shall be measured as one unit. (ii) Necessary plastering to the disturbed surface of wall and distempering /white washing to match the existing colour shall deemed to be included in the unit rate quoted .
M & L for sub main wiring using two single core 2.5 Sqmm fire retardant PVC insulated and unsheathed cable with copper conductor 1100 volts grade ISI marked drawn through and including PVC Casing Caping / PVC Conduit or in existing concealed conduit (as required & directed by Engr-in-Charge) with accessories like bends, tee, etc fixed on wall and ceiling including 2.5 Sqmm earth wire, FR PVC insulated & unsheathed and connecting to earth dolly including taking down existing wiring complete all as specified and directed. Note: (i) Two runs of 2.5 sqmm and one run of 2.5 sqmm earth wire and one run of PVC conduit / casing caping shall be measured as one unit. (ii) Necessary plastering to the disturbed surface of wall and distempering /white washing to match the existing colour shall deemed to be included in the unit rate quoted .
Attending the complaints lodged by the occupants/users including Identifying and rectifying of electrification nature & rectification of the fault as per the complaint lodged by the user in day time 8.30 Hrs to 1730 Hrs in respect of main fixture /breakdown for light/fan/bell/light or power socket and LT line etc complete repairs to the extent by removing connections from the system removing faults in wires, battens, conduit, sunken boxes, junction boxes, main switches, MCBs/DBs utility light fitting, lamp holders AC ceiling/ Exhaust fans and other type of complaints to connected fixtures of the internal electrification including providing of petty stores such as wires of appropriate size and conductor matching to existing one upto the length of 1 mtr including insulation tape, screws , nuts as required to rectified the fault with regard to the complaint lodged and refixing of fittings, fixtures to their position as dismantled and respect of item if required to be paid under respective item as required complete all as directed at site to the entire satisfaction of Engr-in-Charge/users.
Attending the complaints lodged by the occupants/users including Identifying and rectifying of electrification nature & rectification of the fault as per the complaint lodged by the user in day time 8.30 Hrs to 1730 Hrs like taking out old unserviceable item and fixing of Switches, sockets, regulators, ceiling rose, Bell push, lamp holder, laying of wire all any type etc complete all as specified and directed
Attending the complaints lodged by the occupants/users including Identifying and rectifying of electrification nature & rectification of the fault as per the complaint lodged by the user in day time 8.30 Hrs to 1730 Hrs like fixing of LED Batten any size, T-08 Fittings, LED 2X2 Recess mounting lights, PVC Conduit fixing any size etc complete all as specified and directed
Attending the complaints lodged by the occupants/users including Identifying and rectifying of electrification nature & rectification of the fault as per the complaint lodged by the user in day time 8.30 Hrs to 1730 Hrslike fixing of MCBs, Ceiling fans, Wall Fans, ExhaustFans, Ceiling fans, Wall Fans, Exhaust Fans and DBs etc complete all as specified and directed
Attending the complaints lodged by the occupants/users including Identifying and rectifying of electrification nature & rectification of the fault as per the complaint lodged by the user in day time 8.30 Hrs to 1730 Hrs No light complaint, loose wire, sparking etc. in LT panel at AFS Makrpura and all HT LT fault emergency complain and any type of Complain regarding electricity complete all as specified and directed
Load balancing on three phase DBs of buildings inclding checking of load by using amp meter/tong tester rearreging the connections withing the DBs and providing copper lugs with wires tightening of all connection and testing and verify the lthe load current on each phase in persence of JE E/M/ Engr-incharge complete all as specified and directed
Notes for items Ser No 11.00 to 16.00 :- (a) All T & P/Stationeries and labour team required comprising of sufficient trained technician (Electrician/helper ) will be provided by the contractor daily for two location ie harni camp and harni airfield baroda area as directed.During MES mela or any other occason the contractor will be arrage additional menpower to rectify the complaint with justified time. b) Rep of the contractor will present in complaint cell & responsible for receiving & attending the complaints from 08.30 Hrs to 17.30 Hrs the time of lodging the complaint. In absence of rep of Contractor penal recovery as decided by GE shall be imposed & on contractor. (c) Cost of minor stores such as screws,clamps,insulation tapes,nuts/bolts, nail of required size, lubricating oil/grease etc shall be deemed included in the above quoted rate. However, major items such as switches, sockets, bell push, fan regulator, capacitor, wires etc shall be measured and paid separately under appropriate items of Schedule 'A'. (d) Complaints where complete replacement of circuit/point wiring required shall be measured under relevent item. (e) If contractor fails to rectify the complaint with in 24 hours after receiving, Rs 500/- per complaint will be penalised.
Supply Only switch piano Modular type single pole one way 6 Amp 240 Volts complete all as specified and directed.
Supply Only switch piano Modular type single pole one way 16 Amp 240 Volts complete all as specified and directed.
Supply Only switch piano Modular type single pole two way 6 Amp 240 Volts complete all as specified and directed.
Supply Only modular socket outlet 6 Amps 3 pin 2 module 240 Volt complete all as specified and directed.
Supply Only socket outlet 6/16 Amps 5 pin 2 module 240 Volt complete all as specified and directed.
Supply Only Bell push switch Modular type single pole one way 10 Amp 240 Volts complete all as specified and directed.
Supply Only Fan Regulator 1/2 Module FSC Modular type 240 Volts complete all as specified and directed.
Supply Only switch piano Modular type single pole two way 10 Amp 240 Volts complete all as specified and directed.
Supply Only piano switch flush type 5 Amps single pole, one way, 230 volts AC circuit complete all as specified and directed.
Supply Only Bell push flush type single pole 5 Amp 240 Volts complete all as specified and directed.
Supply Only piano switch flush type 15 Amps single pole, one way, 230 volts AC circuit complete all as specified and directed.
Supply Only socket out let 2 in 1, 3 pin 5 Amps flush type, 230 volts AC circuit complete all as specified and directed.
Supply Only socket out let 2 in 1, multipurpose, three 6/16 Amp flush type, 230 volts AC circuit complete all as specified and directed.
Supply Only switch socket combination 2 in 1, 3 pin, 5 and 15 Amps flush type universal 240 Volt complete all as specified and directed.
Supply Only replacement switch socket combination 2 in 1, 3 pin, 5 Amps flush type universal 240 Volt complete all as specified and directed.
Supply Only Stepped/socket type electronic fan regulator heavy duty typeA/C 240 V.complete all as specified and directed.
Supply Only ceiling rose surface bakelite three terminal 65 x 50 mm three terminal 250/230 volts ISI marked complete all as specified and directed.
Supply Only ceiling rose surface bakelite three terminal 65 x 50 mm three terminal 250/230 volts ISI marked complete all as specified and directed.
Supply only for lamp holder PVC/polycarbonate type with back plate suitable for batten fittings complete all as specified and directed
Supply Only Bell ding dong type, one way, 240 volts, AC, ISI marked complete all as specified and directed.
Supply only Concealed Galvanised (GI) metal flush Boxes Modular 3 module with white cement concealed and making good the disturbed surface by white cement & Existing color of bld distemper complete all as specified and directed. Note:- Cost of labour shall be paid separatly.
Supply only Concealed Galvanised (GI) metal flush Boxes Modular 4 module with white cement concealed and making good the disturbed surface by white cement & Existing color of bld distamper complete all as specified and directed Note:- Cost of labour shall be paid separatly.
Supply only white cover plates with frame (white) Modular type 2 way complete all as specified and directed.
Supply only white cover plates with frame (white) Modular type 3 way complete all as specified and directed.
Supply only white cover plates with frame (white) Modular type 4 way complete all as specified and directed.
Supply only white cover plates with frame (white) Modular type 6 way complete all as specified and directed.
Supply only white cover plates with frame (white) Modular type 8 way complete all as specified and directed.
Supply Only single pole and neutral enclosure with a two pin and earth plug and socket complete with one single MCB SP 20 Amps C Curve complete all as specified and directed.
Supply only sheet metal enclosure SP with two pin and socket with one single pole MCB 25 Amps ,'B Curve 240 Volts complete all as specified and directed
Supply and fixing of Motion/Thermal sensor LED Street light fittings 30 watt, 220 V AC complete with driver, holders & LED lamp suitable for wall including connecting up with driver three core flexible copper conductor , inbuilt electronic driver with motion sensor, Pf .9, Efficiency 100 Lm/W, Sensor range 5 Mtr at an angle 360 degree, High efficiency thermal design, wide spread of light to cover maximum area , with 10 KV surge protection including connecting up with driver three core flexible copper conductor all as directed and specified Note: (i) When switch on detect motion it again to full intensity(100%) eventually dims when detect sensor in next 10 Second and as motion recedes it switchs to power saving mode 30 %
Supply only LED batten 10 Watt (Mirror Light) 2 Feet with polycarbonate housing and diffuser AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable from ceiling rose to connector of the light, fixing the same complete all as specified and directed
Supply only LED batten 20 Watt with polycarbonate housing and diffuser AC 220-240 volts, 50 Hz and connecting with copper conductor flexible cable from ceiling rose to connector of the light, fixing the same complete all as specified and directed
Supply only LED light fitting recess mounted/pendent mounting ultraslim LED flat panel 2x2 down light aluminium extruded housing with full opal diffuser IP 20 suitable for perfect lighting condition 36 watt 240 volt, 50 Hz AC supply complete all as specified and directed.
Supply only MCB FP pole 40-63 amps 415 Volts C series complete all as specified and directed.
Supply only MCB, single pole 240 volts 6 to 32 Amps capacity C series fixed in DB's complete all as specified and directed.
Supply only MCB, single pole and neutral link 240 volts 6 to 32 Amps capacity C series fixed in DB's complete all as specified and directed.
Supply only MCB, single pole 240 volts 40 to 63 Amps capacity C series fixed in DB's Complete all as specified and directed.
Supply only MCB, Singal pole and neutral link 240 volts 40 to 63 Amps capacity C series fixed in DB's Complete all as specified and directed.
Supply only of PVC conduit size 25mm Rigid non-metallic PVC conduit exclusive of boxes (junction/terminal) but inclusive of all tees, bends,elbows, reducers, bell mouth tube ends and fixing accessories including chase cutting such as couplers, lock nuts, saddles, pipe hooks etc Complete all as specified and directed
Supply only LED bulb 09 Watt 5 star rating Complete all as specified and directed.
Supply only FR-LSH PVC insulated, unsheathed, single core, flexible copper conductor wire suitable upto voltage grade 110 volt of different colours and following sizes complete all as specified and directed:- (a) 1.5 Sqmm
Supply and fixing ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed.
Supplyand fixing wall mounted fan 400 mm 5 star rating Hi-Speed metallic white, dust resistantwith remote control complete all as specified and directed.
Supply only of exhaust fan, steel body heavy duty turboforce, AC single Phase. 230 V of size 300 m sweep, 1400 RPM air delivery 1950 CM with, 4 blades, and frame and louvers gray colour, dust resistant complete all as specified and directed. Note: All necessary arrangement such as wodden frame/cut in existing window frame/or making hole/ making same the disturbed surfacesor wall included in item rates
Supply only of exhaust fan, steel body heavy duty turboforce, AC single Phase. 230 V of size 380mm sweep, 1400 RPM air delivery 1950 CM with, 4 blades, and frame and louvers gray colour, dust resistant complete all as specified and directed. Note: All necessary arrangement such as wodden frame/cut in existing window frame/or making hole/ making same the disturbed surfacesor wall included in item rates
Supply and fix in repairs MCB DB 4 way (VTPN) vertical sheet metal enclosure TPN 415 volts, 50 Hz, with IP-43 protection, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting with one MCB as incommer complete all as specified and directed Notes : (i) MCB SP/TPN shall be measured and paid seperately under appropriate items of this schedule (ii) Copper thimble shall be used for connection of cable
S & F in repairs MCB DB 4 way sheet metal enclosure SPN 240 volts, 50 Hz, with IP-42 protection, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting complete all as specified and directed. Notes : (i) MCB SP/TPN shall be measured and paid seperately under appropriate items of this schedule (ii) Copper thimble shall be used for connection of cable
S & F in repairs MCB DB 8 way sheet metal enclosure SPN 240 volts, 50 Hz, with IP-42 protection, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting complete all as specified and directed. Notes : (i) MCB SP/TPN shall be measured and paid seperately under appropriate items of this schedule (ii) Copper thimble shall be used for connection of cable
S & F in repairs MCB DB 12 way sheet metal enclosure SPN 240 volts, 50 Hz, with IP-42 protection, double door with 200 Amps standard bus bar of suitable size and common neutral link all enclosed in standard sheet flush mounting complete all as specified and directed. Notes : (i) MCB SP/TPN shall be measured and paid seperately under appropriate items of this schedule (ii) Copper thimble shall be used for connection of cable
Material and labour for taking down of ceiling/exhaust/wall mounted fan of any size and location for stripping of fan,washing throughly of bearing/bush by petrol, washing/cleaning fan blade, body greasing and oiling complete and refixing the same position after complete repairs including provision of twisted twin core flexible wire of size 23/0.0076 nt less than 0.5 sqmmand testing of fan on full load to entire satisfaction of Engr-in-charge complete all as specified and directed. Notes:- a) Replacement of u/sspare parts as required shall be measured and paid seperatly under respective items. b) Rewinding shall be measured and paid seperatly.
M & L for rewinding of ceiling fans 1200/1400mm sweep, strip opening and removal of burnt winding wire, rewinding the fans with suitable size of heavy grade (ISI mark ) copper winding wire, duly providing leatherite sheets, cotton tape, insulation sleeves, varnish, etc, 6 month waranty period shall given by the dealer/contractor after repair, complete incl taking down, dismantling, reassembling and refixing at site and shifting/transporting to wksp including testing complete all as specified and directed Note:- Contractor shall make the suitable arrangement at Makarpura (MES) premises for replacing of accessories, testing upto the satisfactory level in front of concerned E/M in charge without fail.
M & L for rewinding of Exhaust fan 300 / 350 mm sweep, strip opening and removal of burnt winding wire, rewinding the fans with suitable size of of heavy grade (ISI mark ) copper winding wire, duly providing leathoride sheets, cotton tape, insulation sleeves, varnish, etc, 6 month waranty period shall given by the dealer/contractor after repair, complete incl taking down, dismantling, reassembling and refixing at site and shifting/transporting to wksp including testing complete all as specified and directed
M & L for rewinding Exhaust fan 400 / 450 mm sweep, strip opening and removal of burnt winding wire, rewinding the fans with suitable size of of heavy grade (ISI mark ) copper winding wire, duly providing leathoride sheets, cotton tape, insulation sleeves, varnish, etc, 6 month waranty period shall given by the dealer/contractor after repair, complete incl taking down, dismantling, reassembling and refixing at site and shifting/transporting to wksp including testing complete all as specified and directed
M & L rewinding for Wall Mounted Fan of any sweep, strip opening and removal of burnt winding wire, rewinding the fans with suitable size of of heavy grade (ISI mark ) copper winding wire, duly providing leathoride sheets, cotton tape, insulation sleeves, varnish, etc, 6 month waranty period shall given by the dealer/contractor after repair, complete incl taking down, dismantling, reassembling and refixing at site and shifting/transporting to wksp including testing complete all as specified and directed.
M&L for changing of fan bearing 6201/6202 of ceiling fan of any capacity any size complete all as specified and directed Note: Replacement of bearing to be carried out at AFS Makarpura only exceptional case where lathe work is required then only fan to be taken at workshop.
M&L for changing of bearing/bush of exhaust fan/cabin fan/air circulator of any capacity any size complete all as specified and directed Note: Replacement of bearing to be carried out at power house at AFS Makarpura only exceptional case where lathe work is required then only fan to be taken at workshop complete all as specified and directed.
Supply and fixing capacitor of 2.5 MFD (PVC Body) complete all as specified and directed.
Supply and fixing capacitor of 3.15 MFD (PVC Body) complete all as specified and directed.
Supply and fixing complete hanging assembly set comprising with rubber reel, MS clamps, nuts, bolts with one lock hole and lock pins suitable for any type of fans & down rods including taking down existing defective assembly complete all as specified and directed.
Supply and fixing PVC insulated, flexible cable, twin core twisted of size 23/0.0076 with copper conductor in pieces for connecting fans including taking down exisiting cable complete all as specified and directed.
Supply and fixing in repair down rod 15 mm dia and length upto 1 mtr as required on site, MS tube (medium grade), duly finished with powder coating of white colour, including necessary holes and threading etc. complete all as specified and directed.
supplying & fixing new louvers made out of MS sheet 22 gauge thick suitable for exhaust fan of 450/300mm sweep including taking down existing worn out louvers of any description and in any position complete all as specified and directed. Note: The louvers shall be of shape, size and pattern as approved by the Engineer-in-Charge duly painted with two of synthetic enamel paint over a coat of red oxide primer
M&L for painting enamel white paint by spraying on ceiling fans/exhaust fan of any sweep/ size and description complete in situ with synthetic enamel paint by spraying including filling cavities with fine finishing surface by filler one coat after removing/cleaning all dust/dert etc including taking down/ refixing complete all as specfied and directed. Note:- marking/numbering with MES No/Qtr no included in item rates, no extra payment shall be made for marking/numbering.
Supply and fixing ceiling fan blade of size 1200 mm Sweep of material stainless steel flexible type suitable for all make fan complete all as specified and directed.
Supply and fixing Wall fan blade of size 300/350/400 mm Sweep of material stanless steel flexible type suitable for all make fan all as specified and directed.
Supply and fixing Ceiling fan canopy suitable of 1200/1400 mm sweep all as specified and directed.
Supply and fix electric water heater, storage type steel body with copper inner tank and heating element upto 2 KW capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, connection piece etc complete all as specified and directed.
Dismantling the Geyser of any capacity and of any description material and labour for cleaning and de-scaling the inner tank and other parts / accessories including inlet, outlet , overflow Geyser element, thermostat , ‘U’ assembly etc. with brush, cleaning rod, and using / circulating concerned de-scaling solution mixed with water in suitable proportion till the complete deposits /scale is removed as approved by Engineer-in-Charge, brazing for stopping leakage of copper inner tank/gas welding for inner steel tank, re- assembling the complete Geyser after cleaning, Fixing and installation of Geyser in position and testing to the entire satisfaction of engineer-in-Charge complete all as specified and directed.
Material and labour for finding defect and Replacement of defective existing ‘U’ assembly of 25 Ltr cap any description and in any position from Geyser installed at site and fixing new ‘U” assembly to match with the existing system complete all as specified and directed
Material and labour for finding defect and Replacement of defective Thermostat suitable for existing make and type with setting range 30°C to 80°C suitable for 230 volts AC, electric supply complete all as specified and directed.
Material and labour for finding defect and Replacement of defective /nonfunctional Fusible plug/safety valve as per sample ISI marked having melting point 90°C to 95°C complete all as specified and directed.
Material and labour for finding defect and Replacement of defective/nonfunctional Geyser element of 2000 Watt, 230 volts complete all as specified and directed.
Material and labour for finding defect and Replacement of defective /non functional Indicating lamp of size /shape as per existing complete all as specified and directed.
Material and labour for finding defect and replacement of existing unserviceable PVC connection and supply and fixing new PVC connection 15 mm dia 450 mm long having brass nut and washer on both end suitable for Hot/Cold water complete all as specified & directed.
Disconnecting and taking up/down existing unserviceable copper conductor flexible cable of any size and any description and supply, connecting, testing new 3 core copper conductor cable of 40/0.0076 size PVC insulated and PVC sheathed suitable for 1100 volts grade complete all as specified & directed.
Material and labour for finding defect and replacement of existing defective/nonfunctional metal clad socket of any description and supply and connecting metal clad top socket 25 Amp 3 pole 230 volts complete all as specified and directed.
Disconnecting and taking out existing defective / nonfunctional metal clad top plug of any description and supply and connecting metal clad top plug 25 Amp 3 pole 230 volts complete all as specified and directed.
Material and labour for finding defect and replacement of existing gun metal non return valve 15 mm dia including making proper connection complete all as specified and directed.
Supply and fixing LED light fitting 1x30 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum housing with heat resistant well glass, with LED light fixtures driver with high grade diffuser,, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and directed.
Supply and fixing Switch flame proof rotary type with termination box in LM6, 16A, single pole 250V complete all as specified and directed.
Supply and fixing Switch flame proof rotary type with termination box in LM6, 25A, double pole 250V complete all as specified and directed.
Supply and fix Flame proof switch socket & plug combined in LM6 cable termination box in LM6, 25A, 250V, 2P+earth complete all as specified and directed.
M&L for Rewinding of Flame proof single phase Exhaust Fan of size 350 to 450 mm sweep including copper winding, bearing and other fixing accessories of suitable size complete all as specified and directed.
M&L for providing earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6.0mm thick buried dirictly in ground (Earth pit not less than 2.25 meters deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to galvanised earth lead wire 4.0 sqmm size upto 7.5 meter long by means of bolts,nuts check nuts and washers of all galvanised iron or steel all including providing alternate layer of charcoal and salt as shown in electrical plate No.3 of SSR Part-1 and connected to test point including necessary excavation/ earth work in any type of soil/rock strata, PCC 1:3:6 type C1 cement concrete 1:2:4 type B1 reinforced with welded steel wire fabric (AMP) not less than 4 KG per Sqm funnel with wire mesh and watering pipe 20 mm dia bore (GI medium grade), PCC pit with 50mm thick PCC cover etc. including testing on completing including GI protection pipe 15 mm dia light grade for earthing lead complete all as specified and directed.
JAI HANUMAN CONTRACTOR
NISHA CONSTRUCTIONS
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .