Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.3 LAccepted-AOC | ₹9.3 L Quoted ₹9.6 L | L1 | Accepted-AOC Being L1 |
| 2 | L2₹9.9 L+₹30,116 (3.13%)Rejected-Finance DOOR NO 44 19 10 RAILWAY NEW COLONY BEHIND SIVALAYAM VISAKHAPATNAM AP 530016 | VISAKHAPATANAM | ANDHRA PRADESH | 530016 | ₹9.9 L+₹30,116 (3.13%) | L2 | Rejected-Finance Being not L1 |
| 3 | L3₹10.5 L+₹83,170.90 (8.63%)Rejected-Finance D NO 35 14 13 1 R P PETA KANCHARAPALEM VISAKHAPATNAM 530 008 | VISAKHAPATANAM | ANDHRA PRADESH | 530008 | ₹10.5 L+₹83,170.90 (8.63%) | L3 | Rejected-Finance Being not L1 |
Tender Value
₹10 L
EMD Value
₹20,000
Closing Date
24 Jun 2023, 6:00 pmClosed
Nitesh Kumar Singh, IDSE AEE(Civ)
AGE (I) R and D, NSTL Complex, Visakhapatnam 530027
8446 REPAIR AND REPLACEMENT UNSERVICEABLE OF 50 KVA ONLINE UPS AT TALWAR BUILDING AND SPECIAL REPAIRS/REPLACEMENT OF OLD ALUMINIUM ELECTRICAL WIRING WITH NEW COPPER WIRING IN WORKS AND ESTATE OFFICE BUILDING INSIDE NSTL AREA UNDER AGE (I) RnD NSTL
2023_MES_594079_2
AGE I R AND D NSTL VIZAG 8446
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Visakhapatnam
Class E Category b(i)
7 documents required · 7 mandatory
₹500
AGE I R and D NSTL Visakhapatnam
₹20,000
Yes
1 Sept 2023
10 Jun 2023
26 Jun 2023
10 Jun 2023
24 Jun 2023
11 Jun 2023
Amount
M & L for Dismantling/taking out all electrical connections from unserviceable 50 KVA 3 phase input & 3 phase output UPS of make Consul and lifting UPS with the help of crane & loading into vehcile and sending it to nearest local company workshop from site and after repairing send it to site back & re-connection of all electrical connections to UPS as per existing complete all as specified and directed by Engr-in-charge.
M & L for opening of 50 KVA 3 phase input & 3 phase output online sine wave conversion UPS,drawing out of isolation transformer core assembly and winding,replacement of unserviceable parts of isolation transformer including repair,rewinding of transformer winding with suitable gauge of super enamelled copper wire/strip, the following undermentioned items also replaced with new one & also replacement of all unserviceable parts of UPS then after assembling the isolation transformer after repair and make it fully functional along with smooth operational with rated load and submit the test report to the department complete all as specified and directed by Engr-in-charge. (i) 6 pulse rectifier control card-01 Nos. (ii) Inverter control card-01 Nos. (iii) Inverter card-01 Nos (iv)Input sensing transformers -03 Nos. (v) SMPS control card-01 Nos. (vi)LCD display -01 set. (vii) IGBT DRIVERS 3 or 6 Nos-01 Job. (viii) Pulse trigger control card-01 Nos. (ix) Digital voltmeter-01 Nos. (x) Digital Ammeter-01 Nos. (xi) Repair/replacement of IGBT/SCRs 3 Phase-03 Nos. (xii)HRC fuse 80/100 A mps-03 Nos
Supply & fixing of 12 Volts,120 AH VRLA SMF batteries including all necessary fixing arrangements with all connected items complete make it operatinal all as specified and directed by Engr-in-charge.
Taking down old point wiring complete for light/fan/Power socket(5/15 Amps, bell point etc complete with all light fittings accessories, such as switch sockets 5/15 Amps, ceiling rose etc including making good to the disturbed surface to match with the existing complete all as specified and directed by Engineer-in-Charge.
Taking down old DBs with MCCB , MCBs of any size and capacity & making good to the disturbed surface to match with the existing complete all as specified and directed by Engineer-in-Charge.
Taking down old sub main wiring/cable of any size and capacity including making good to the disturbed surface to match with the existing complete all as specified and directed by Engineer-in-Charge.
Material and labour point wiring with 1.5 sqmm (nominal cross section area) single core PVC insulated unsheathed cable of 1100 Volts grade (FRLS) multistrand with copper conductor drawn through and including non metallic, rigid PVC conduit of adequate size with all fittings and conduit accessories concealed in wall/ceiling/floor/roof etc. including 1.6 mm thick sunk mild steel terminal box with 3mm thick plastic laminated sheet top cover, cadmium plated iron screws for housing the switches, socket outlets including provision of 1.5 sqmm green in colour PVC insulated copper conductor single core multistrand (FRLS) for earth continuity conductor and connected to common earth dolly all as specified for the following:- (a) One light point control by one switch
(b) One ceiling fan/exhaust fan control by one switch
ditto as per tiem No. 7 but wire 2.5 sq mm cable for switch socket outlet independent 3 pin 6 amps with 2.5 sq mm cable as earth continuity conductor.
ditto all as per item No.7 above but below/parallel the switch board of 3 pin 6 Amps socket in the same vertical/horizontal plane.
ditto as per item No. 7 above but wire 4.0 sq mm cable for switch socket outlet 3 pin 16 Amps with 4.0 sq mm as earth continuity conductor.
Supply and fix modular switch one way 6 Amps, 1 module including cover plate and metal flush box complete all as specified and directed.
Supply and fix ceiling rose, surface bakelite 3 terminals, PVC/polycarbonate, isolated body, ISI marked.
Supply and fix modular socket outlet 6 amps, 2/3 pin combined 2 module including cover plate and flush box complete all as specified and directed.
Supply and fix modular switch one way 16 Amps, 1 module including cover plate and metal flush box complete all as specified and directed.
Supply and fix modular socket outlet 6/16 amps, 2/3 pin combined 2 module including cover plate and flush box complete all as specified and directed.
Supply and fixing fan regulator electronic stepped modular type 120 watts, 2 module AC 240 Volts complete.
Taking down exsitingnexhaust fan of any size and making good to the disturbed surface to match with the existing complete all as specified and directed by Engineer-in-Charge.
Supply and fix in repair exhaust fans AC single phase 230/240 V of size 250 mm sweep with louvres complete including connecting up with 3 core cord flexible from ceiling rose to exhaust fan etc. all as speified and directed by Engr-in-charge.
Taking down old light & Supply and fixing LED lights fitting 1x 22 W, 220V,AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.Make: Havells/Philips/Bajaj
Taking down the old mirror light & Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete.Make: Havells/Philips/Bajaj
Taking down the old unserviceable SK fitting/ FTL fitting/ lamp holder and taken as credit and Supply and fixing (4FT) 20 W LED fitting baten fro surface and wall conduit mounting High Transmissitivity diffuser High lumen Output PF > 0.98, thd < 10 % wall mounted type fitting with LED tube rod , complete all as specified and directed by Engr-in-Charge. Make : Bajaj Cat No.BCLAB20WLEDPS/Havells/Philips
Taking down the old light & Supply and fixing LED street/Bldg security light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.Make: Havells/Philips/Bajaj
Supply and fixing in repair VTPN DB's 8 way vertical type 415 V, double door suitable for housing of 100 Amps MCCB as main incoming complete all as specified and directed.
Supply and fix in repair single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps complete all as specified and directed.
Supply and fixing in repair MCCB, AC 415 V, 50 HZ, fixed type, capacity 100 Amps, 4 Pole, 16 KA, suitable to be fixed in 4/6/8/12 way TPN DB complete all as specified and directed. Make: L&T, Schneider, Havells
S & F in repair MCB DB double door SPN 12 Way with 200 Amps rated copper bus bar complete all as specified and directed.
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.(i) SP 5 To 32 AMP
Supply and fixing amp rating 240V, 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the MCB DB complete with connection testing and commissioning.(i) SPN 40 To 63 AMP
Supply and fixing 415V 10KA 'C' curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning. (i) TP 25 To 63 AMP
M&L for earthing to switch gear/MCB DB with mild steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25m deep below normal ground level) connected to galvanised iron earth lead 4.0 mm dia by means of galvanised iron nuts, bolts and washer, earth lead connected to eqpt as directed, earth plate surrounded with adequate quantity of charcoal dust mixed with common salt to a packed thickness of 15 cm all around the plate including necessary earth work, PCC chamber and reinforced PCC cover made by PCC 1:3:6 type C-1 as in pit chamber and RCC pit cover 50 mm thick precast RCC 1:2:4 type B-1 duly reinforced with 6mm dia MS bar at 150mm c/c both ways with 10 mm dia MS round bar as handle, 20 mm bore GI pipe medium grade for watering and 40 mm dia GI pipe light grade for protection of earth lead up to 3 mtr with funnel, wire mesh etc with and including testing complete all as specified and as shown in electrical plate No 3 of MES sch Part I.
Earthing continuity galvanised iron earth lead of 4.0 mm dia or main earthing lead fixed to wall with clamps or recess or croses or buried in ground or drawn in conduits/pipe or fixed to poles or any other indicated situation for loop earthing etc as required all as specified and directed by Engr-in-Charge.
S & F in repair sub main wiring for circuit of size 4 sq mm 2 core (FRLS) alongwith earth wire of 4 sq mm single core of FRLS PVC insulated unsheathed cable, 1100 volts grade with multistranded copper conductor including PVC conduit of suitable size complete all as specified and directed by Engr-in-Charge.
All as per item No. 33 above but of size 2X6.0 sqmm+1x6.0 sqmm size in pvc conduit of suitable size complete all as specified and directed by Engr-in-Charge.
All as per item No. 33 above but of size 2X10 sqmm+1x10sqmm size in pvc conduit of suitable size complete all as specified and directed by Engr-in-Charge.
Supply, laying of cable XLPE Insulated galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq mm 3.5 core complete all as specified and directed.
Excavation in trenches in soft/loose soil n.exc. 1.5M wide & n exc 1.5M deep for laying of LT cable ,GI pipe line & for street light pole getting out including forming bottom surface all as specified and directed.
Returning, filling in, trenches including spreading, levelling, watering and well ramming in layer n.exc. 25 CM in any type of soil after the pipe laid & tested complete all as specified and directed.
Removing excavated surplus soil to a distance n.exc. 50mtr and depositing where directed at a level n.exc. 1.5 m above the starting point all as specified and directed
Material and labour for road cutting of trench width & depth of 30cm,60 cm for laying of UG XLPE LT cable complete all as specified and directed by Engr-in-charge.
Disconnecting of existing unserviceable LT UG cable from trench or duct or from wall with removing clamps/ pipes all as specified and directed. Note : Excavation and earth work measured and paid separately.
Supply and laying un-reinforced precast concrete cable cover Class LV type I, size 250 x 150 x 40mm.
M&L for dry sand cushioning to under ground cable intrenches including spreading, levelling and hand punning complete all as specified.
M&L for plain cement concrete (1:3:6) type C2 using 40mm graded stone aggregate in foundations filling and mass concrete complete all as specified
M&L for GI tubes light grade of 50 mm dia complete with all fittings laid in floors/trenches for cable protection at road crossing & cable protection for street light poles including taking down of old GI pipe complete all as specified and directed by Engr-in-charge. Make: Jindal/TATA/Surya prakash
ANJALI ENTERPRISES
M/S CHANDRA ENGINEERS AND CONTRACTORS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .