| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹9.1 CrAccepted-AOC 15 281 CHHILI INT ROAD GHATIYA AZAM KHAN AGRA UTTAR PRADESH 282003 | AGRA | UTTAR PRADESH | 282003 | ₹9.1 Cr Quoted ₹9.2 Cr | L1 | Accepted-AOC Accepted being L1 |
| 2 | L2₹11.7 Cr+₹2.6 Cr (27.9%)Rejected-Finance | ₹11.7 Cr+₹2.6 Cr (27.9%) | L2 | Rejected-Finance Not being L1 |
| 3 | L3₹12.1 Cr+₹2.9 Cr (31.8%)Rejected-Finance | ₹12.1 Cr+₹2.9 Cr (31.8%) | L3 | Rejected-Finance Not being L1 |
| 4 | L4₹12.8 Cr+₹3.7 Cr (40.2%)Rejected-Finance FLAT NO 03 PANCHAVATI BUILDING ADARSH NAGAR CHICALIM GOA 403711 | SOUTH GOA | GOA | 403711 | ₹12.8 Cr+₹3.7 Cr (40.2%) | L4 | Rejected-Finance Not being L1 |
| 5 | L5₹13.0 Cr+₹3.8 Cr (41.8%)Rejected-Finance | ₹13.0 Cr+₹3.8 Cr (41.8%) | L5 | Rejected-Finance Not being L1 |
Tender Value
₹9.0 Cr
EMD Value
₹7.8 L
Closing Date
9 Jul 2024, 6:00 pmClosed
Chief Engineer AF Bangalore
Chief Engineer AF Bangalore No. 2 DC Area MES Road Yeshwantpur Post Bangalore 560022
PROVSION OF BRIEFING HALL AND WAR GAMING CENTRE AT CAW
2024_MES_641463_2
801536
Open Tender
Civil Works
Lump-sum
540 days
GE (AF) Hakimpet
As per NIT
8 documents required · 8 mandatory
₹3,000
GE (AF) HAKIMPET
₹7.8 L
Yes
25 Jul 2024
11 Jun 2024
12 Jul 2024
11 Jun 2024
9 Jul 2024
25 Jun 2024
11 Jun 2024 - 18 Jun 2024
Amount
GENERAL SUMMARY NOTE: Schedule ‘A’ Part I to XIV are prepriced by MES under Ser No. 1 to 13. Bidders shall insert their lumpsum amount in the Green coloured field under Col-6 only.
Lumpsum price worked out by the contractor for “Building or Works ” as listed in Schedule ‘A’ Part–I
Lumpsum price worked out by the contractor for “Internal Water Supply” as listed in Schedule ‘A’ Part–II
Lumpsum price worked out by the contractor for “Internal Electric Supply" as listed in Schedule ‘A’ Part–III
Lumpsum price worked out by the contractor for “Demolition of Buildings” as listed in Schedule ‘A’ Part – IV.
Lumpsum price worked out by the contractor for “Road / Path /Culvert " as listed in Schedule ‘A’ Part V .
Lumpsum price worked out by the contractor for "Sewage Disposal" as listed in Schedule ‘A’ Part VI .
Lumpsum price worked out by the contractor for “Area Drainage” as listed in Schedule ‘A’ Part – VII.
Lumpsum price worked out by the contractor for “Rain Water Harvesting” as listed in Schedule ‘A’ Part – VIII.
Lumpsum price worked out by the contractor for “Refrigeration and Air Conditioning” as listed in Schedule ‘A’ Part – IX.
Lumpsum price worked out by the contractor for “Fire alarm and fire fighting system” as listed in Schedule ‘A’ Part – X.
Lumpsum price worked out by the contractor for “ Lightining Conductor” as listed in Schedule ‘A’ Part – XI.
Lumpsum price worked out by the contractor for “External Electric Supply” as listed in Schedule ‘A’ Part – XII.
Lumpsum price worked out by the contractor for “External Water Supply” as listed in Schedule ‘A’ Part – XIII.
Sch 'A' Part - XV : Fittings / Fixtures & Misc items.
Central Air Conditioning plant Supply, install, test and commissioning of high efficiency Central Chilled water type air conditioning plant of water cooled chiller unit with capacity not below 76 TR and 38 TR Standby ( 3 units of 38 TR with 2 running at a time and one as standby) comprising of Water cooled Chiller with scroll compressor working on R-407C refrigerant (Green Gas)/410A/ R134A , including Chilled Water Pump, Condenser Water Pumps, Cooling Tower, AHU, Water softener, Fill up water tank with staging , electrical LT Cabling with panel Board, Chilled water Piping, Ducting, Drain Piping, necessary control valves, pressure gauge, air vent and other connected necessary accessories all as specified in Drg No :MECS/23/CAW/HAVC/01, 02 & 03 to obtain the following desired conditions inside Briefing hall complete in respect all as specified and as directed by Engineer-in-Charge. Desired parameters as per user Data Sheet (as mentioned BP's) Inside temperature : 23 Deg Cent +/- 3 Relative Humidity : 50 to 60 % Occupancy : 270 Nos No of Air Changes : 8 to 10 (Note : The Manning, Operation & Maintenance of central AC plant including consumables during defect liability period of 2 years after completion of work for one shift of 08 hours in a day shall be measured and paid seperately under BOQ item No. 88)
(f) Chilled Water Piping "Supply, erection, testing & commissioning of Mild Steel Chilled Water Piping with Class 'C' as per IS 3589 for dia 150mm and above ( wall thick ness minimum 6 mm ) and as pr IS 1239 for dia upto 150mm , cut to required length, and installed with welded joints, including all necessary fittings such as elbows, tees, bends, reducers, flanges and necessary Civil/MS supports ,pressure testing etc complete all as specified and directed by Engineer-in-Charge. Make : Tata /Jindal" i) 125mm dia -45 RM ii) 100mm dia - 60 RM iii) 80mm dia - 40 RM iv) 65mm dia - 25 RM v) 50 mm dia - 05 RM vi) 40 mm dia - 05 RM vii) 32 mm dia - 05 RM viii) 25 mm dia - 05 RM "(g) Thermal Insulation Supply and laying of Thermal insulation with closed cell elastomeric 32mm thickness nitrile rubber class O insulation of density 40-60 kg/m3, covered vapour barrier and finished with 26G Aluminium Cladding. scope includes the puf pipe saddles etc complete in all respect all as specified and directed by Engineer-in-Charge." i) 125mm dia -45 RM ii) 100mm dia - 60 RM iii) 80mm dia - 40 RM iv) 65mm dia - 25 RM v) 50 mm dia - 05 RM vi) 40 mm dia - 05 RM vii) 32 mm dia - 05 RM viii) 25 mm dia - 05 RM "(h) Supply and fixing LONG NECK Butterfly valves PN16 shall be designed to fit without gaskets between mating flanges as per following specification complete all as specified and directed by Engr-in-Charge.
Note. The valves shall be suitable for flow in either direction and seal in both directions. The valves shall be of integral moulded design. Upto 200 mm will be lever operated and above 200 mm to be with gear operated. Specifications are as per enclosed" (i) 125 mm - 1 Nos (ii) 100 mm - 10 Nos (iii) 80 mm - 12 Nos (iv) 65 mm - 8 Nos (v) 50 mm - 01 Nos (vi) 40mm(bronze ball value) - 01 No "(j) Supply and fixing Ball valves, Bronze ball valve Threaded Conn, Valves shall be of PN 25 rating as per following specification complete all as specified and directed by Engineer in charge" (i) 32 mm -1 No (ii) 32 mm with Strainer - 01 No (iii) 25 mm - 01 No (iv) 25 mm with Strainer - 01 No "(k) Supply and fixing Y Strainers PN16 flange ended permanent magnetic plug , 24 G ss mesh etc as per following specification complete all as specified and directed by Engineer -in-charge. " (i) 100 mm dia - 3 Nos (ii) 80 mm dia - 3 Nos (iii) 65 mm dia - 2 Nos "(l) Supply and fixing NON RETURN VALVES (Check Valves) PN16 : Dual plated check vlave made out CI body as per following specification complete all as specified and directed " (i) 100 mm dia - 3 Nos (ii) 80 mm dia - 3 Nos "(m) Supply, fiixng,testing and commissioning of Manual Balancing Valve PN 16 Flanges, provision to measure the pressure drop for balancing, etc as per following specification complete all as specified and directed by Engineer -in Charge " (i) 100 mm dia - 02 Nos (ii) 80 mm dia - 03 Nos
"(n) Supply, Installation,Testing and commissioning 02 Nos of 2 way Pressure Independent Control Valve of Size 50mm dia having equal percentage flow characteristics with copper alloy metal gun body and disc must be copper alloy rod and bars EPDM diaphram screw and unique connections with pressure port and actuator This includes digital display type smart actuator to show the opening of flow rate , with required supports and accessories like flanges, bolts, nuts & gaskets, pressure rating PN 25. It should have a provision of auto closing module able to set the valve to Zero signal position when the AHU motor is stopped which includes integrating cables between AHU starter , Actuator and thermostat . Consider that the starters are having one no spare NC point. The control cable qty with in 12 rmt per AHU to be included." "(o) Supply,install,testing and commissioning of 100 mm dia dial type pressure gauges with ball / needle valve complete all as specified and directed by Engineer in Charge - 18 Nos" "(p) Supply,install,testing and commissioning of 100 mm dia thermometer with thermo well complete all as specified and directed by Engr-in-Charge. Note : Pipe size shall be increased locally to install the thermometer. - 18 Nos " "(q) Supply,install,testing and commissioning of Auto Air Vents of 20 mm dia complete all as specified and directed by Engineer in charge - 08 Nos "(s) Supply, installation of set of Pressurised expansion tank of 500 Ltr capacity with N+1 pressurization pumps with suction strainer, discharge NRV & with auto control panel, pressure gauges, pressure switches etc complete all as specified and directed by Engr-in-Charge" "(t) Supply, installation of set of 125mm dia Air Separator made out of MS sheet 2 mm thick chamber along with venting valve, float, rashing rings and protective filter.PN 16 rating complete all as specified and directed by Engineer-in-Charge" "(u) Supply and fixing of Flexible Connections PN 16 of following size at inlet and outlet of chillers and pumps. It should not comprise any split flages and control rods etc complete all as specified and directed by Engr - in - Charge." (i) 100 mm dia - 10 Nos (ii) 80 mm dia - 12 Nos "(v) Supply and fixing of drain piping in hard CPVC of following size with 9 mm thick Closed cell foam insulation (40 kg/m3 density) & all fittings, supports and clamps up to 80 mm dia complete all as specified and directed by Engr-in-Charge. Note : Drain piping shall be runs up to the nearest drain point available at site with proper slop and U trap at AHUs." (i) 32 mm dia - 10 RM (II) 40 mm dia - 20 RM "(w) Supply and fixing of total 500 Kgs of Structural MS steel for supporting & base frame structures for unit mountings, piping & ducting complete all as specified and directed. Note : All kind of Supports like angle, channels, plates & flats strip etc shall be duly painted."
"(x) Air Distribution. Supply, Installation, testing and commissioning of following Factory fabricated and boxed GI ducting using class VIII sheets / coil, galvanised hardware & supports, silicon sealant at all joints, hot dip galvanised iron angle flanges for all the joints, bracing angles and minimum 5mm thick neoprene rubber gasket. complete all as specified and directed. Note -1. Duct pressure testing at 75mm to be carried out before insulating the duct. pressure testing to be done as per SMACNA ." (i) 24g - 125 Sqm (ii) 22g - 300 Sqm (iii) 20g- 200 Sqm (iv) 18g - 400 Sqm "(aa) Supply, laying of Duct insulation with Class O Nitrile material by using SR998 adhesive of following thickness complete all as specified and directed " "(i) Supply and fixing of Acoustic Insulation with - 50 Sqm 10mm Open cell Class 1 nitrile rubber material density 110 to 140 kg/cum for Ducting. It should be applied by using manufacturer recommended adhesive and also to use either stick pins or nut bolts and washer. " "(ii) 32mm thickness with aluminium foil - 250 Sqm faced - for supply ducting _ out side with glass cloth and 2 coats of UV painting " "(iii) 25mm thickness with aluminium foil - 250 Sqm faced - for Return ducting _ outside with glass cloth and 2 coats of UV painting " "(iv) 19mm thickness with aluminium foil - 200 Sqm faced - for supply ducting _Inside" "(v) 13mm thickness with aluminium foil - 300 Sqm faced - for supply ducting _inside" "(vi) 3mm thick self adhesive aluminium foil - 1000 RM faced nitirial tapes for longitudinal & transverse joints." "(ab) Dampers & Diffusers Supply and installation of Dampers & Diffusers as per following complete all as specified and directed " "(i) Aluminum low leakage aerofoil design volume - 2 Sqm control dampers suitable for manual / auto operation." (ii) GI Volume control dampers with 18G blades - 5 Sqm
"(iii) CBRI approved 16G GI Spring return - 3 Sqm actuated fire dampers rated for 120 minutes including Fusible linkage mechanism with limit switch." "(iv) Aluminum powder coated collar - 3 Sqm dampers for supply & return air diffusers / grilles" "(vi) Aluminium powder coated intake louvers - 1 Sqm with bird screen and insect screen for the fresh air intake." (vii) JET DIFFUSERS of 400mm Dia as per the dwgs - 55 Nos "(viii) Extruded aluminum powder coated perforated grilles - 4 Sqm for supply / return air." (ac) Supply, installation of insulated flexible duct with all required clamps and supports of 250mm dia complete all as specified - 75 RM (ad) Supply, installation of GI butterfly dampers with spigot of 250mm dia - 55 Nos (ae) WATER TREATMENT PLANT "(i) Supplying, installing, testing and commissioning of approved make centrifugal monobloc pumps (1 No working + 1 No Standby) of deliver capacity not below 1 Cum/Hr @ 25 M head for Raw water Filter feed water inside the Pump room complete all as specified and directed. - 02 Nos. Note: The quoted rate shall include Automatic control panel with level switches, starters, dry run preventer, O/L relays, necessary wiring upto the pumps and control panel, the pumps shall run 415V 50Hz electric supply, etc" (ii) Supplying, Installing, testing and commissioning of approved make Dua media filter of Max. working pressure = 3.5kg/sqcm and Max flow rate = 1 cum/hr at 10 hrs cycle with FRP Filter with UPVC frontal piping and manual multiport valve with pressure gauges necessary accessories. The cost of filter shall also include initial charge of multi - grade filter media (Sand & gravel, Anthracite) to suit the requirement etc., complete in all respects. "(iii) Supplying, Installing, testing and commissioning of approved make Softener of OBR (Output between regeneration ): 10000lpd, Max. working pressure = 3.5kg/sqcm, Max flow rate = 1 cum/hr at 10 hrs cycle with FRP Filter with UPVC frontal piping and manual multiport valve with pressure gauges and Suitable Brine tank necessary accessories including provision of 01 Number of Hardness testing kit complete all as specified and directed. Note : The cost of filter shall also include initial charge of filter media to suit the requirement etc., complete in all respects. " (iv) Supplying, installing, testing and commissioning Electronic dosing system of flow rate of 6LPH for dosing Chlorine into the treated water with pre - set dosage based on the quantity of water. The dosing system shall consist of Electronic dosing pump with positive displacement type with adjustable stroke length & frequency. The quoted rate shall also include HDPE chemical solution tank necessary electrical to make the operation automatic. (v) Supplying, installing, testing and commissioning inter unit piping of UPVC Sch 40 pipes as required with necessary flanges, bolts, nuts, neoprene gaskets, with necessary control valves, non return valves etc. complete in all respects.
(af) Fill up water tank for Cooling Tower (i) Supply and fixing of 3 Layered PVC Tanks of capacity 5000 lts each of approved make with all appurtenances complete all as directed by Engineer in Charge - 02 Nos (ii) Supply and fixing 50mm dia PVC pipe length complete all Fittings such as bend, elbows, tees, short piece jointer,connector,back nut, cap etc laid in trench or on surface of wall/ structure complete all as specified and directed. (iii) Supply and Erection of Structural Steel Support Structure and Platform including Foundations to rest above PVC Tanks as per Geometry (Height of Structure, Platform Size etc , ) shown on HVAC/E&M drawings. Design of Structure to be as per Standard Practice and details to be submitted to Engr-in-charge fro approval. (ag) Supply , laying in trench/duct /floor or on wall with suitable support clamps & testing cable LT Cupper cable of following size complete all as specified and directed by Engineer In charge (i) 35 Sqmm x 4 Core cupper armoured cable - 60 RM (ii) 16Sqmm x 4 Core cupper armoured cable - 30 RM (iii) 4Sqmm x 3 Core cupper armoured cable - 250 rm (ah) LT PANEL BOARD (i) Supply & fix cubical type, factory made LT panel board, suitable for 3 phase, 415 volts, 50 Hz system, with aluminium bus bar for R,Y,B and Neutral and bus bar size shall be suitable to carry current at 1.5 times current carrying capacity of out going switch gears, ,Indoor type, factory fabricated with 3 mm thick CRCA sheet inclusive of necessary suitable glands, opening for vent and cable entry, Spare terminal for MCCB with angle Iron of size 50x50x5 mm thick, grouted in floor complete with the following accessories, duly pre-treated and powder coated finish complete (Main panel Board at Ground Floor) (aa) MCCB, 4 pole 320A, 36 KA- 01 No (Incoming) (ab) MCCB, 4 pole 63A, 25 KA- 01 No (FF Panel Board) (ac) MCCB, 3 pole 125 A, 25 KA- 04 No ( 3xChillern and spare) (ad) MCCB, 3 pole 32 A, 16KA- 01 No (for Water Softener) (ae) MCCB, 3 pole 25 A, 16KA- 07 No (for Chilled & condenser Pump and Bldg Lt) (af) Starter( DOL) 5 HP/3.75KW - 06 No (for Chilled & condenser pump ) (ag) Digital display VAF Panel meter- 01 No with CT coils (ah) LED Indicator RYB - 01 Set
(ii) Supply & fix cubical type, factory made LT panel board, suitable for 3 phase, 415 volts, 50 Hz system, with aluminium bus bar for R,Y,B and Neutral and bus bar size shall be suitable to carry current at 1.5 times current carrying capacity of out going switch gears, ,Indoor type, factory fabricated with 3 mm thick CRCA sheet inclusive of necessary suitable glands, opening for vent and cable entry, Spare terminal for MCCB with angle Iron of size 50x50x5 mm thick, grouted in floor complete with the following accessories, duly pre-treated and powder coated finish complete (Main panel Board at First Floor) (aa) MCCB, 4 pole 63A, 25 KA- 01 No (Incoming) (ab) MCCB, 3 pole 25 A, 16KA- 05 No (for CT & AHU and Spare) (ac) Starter( DOL) 5 HP/3.75KW - 04 No (for CT & AHU ) (ad) Digital display VAF Panel meter- 01 No with CT coils (ae) LED Indicator RYB - 01 Set (aj) Earthing (i) M&L for Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick buried directly in ground connected and including to galvanized earth strip of size 25.x 3 mm as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel - 04 Nos (ii)Supply and fix Galvanised iron strip 25x3 mm as earth continuity or main earthing lead fixed to wall / pole / buried in ground - 60 RM (iii) Supply and fix 2.5 Sqmm cupper wire as earth continuity or main earthing lead fixed to wall / pole / buried in ground - 600 RM
(ak) LT UG Cable "Supply and Laying, testing and commissioning of (2 Run in one trench - 240 RM per run) 185 Sqmm 3½ Core of 1100 volts grade LT UG Cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (heavy duty) with stranded aluminium conductor, laid in trenches/ducts, fixed on wall/inside panel, drawn through pipe complete all as specified and directed. Note : Necessary excavation , Cable protection cover, river sand cushioning, returning and removal of soil to be carried out as per SSR part-I and Cost of the same is deemed to be included in the quoted rate . " (ak) All connected items & accessories and minor variations in the Quantity which are essential & technically required for the installation, testing ,commissioning of the plant and as per E-in-C Technical instruction 07 on Air conditioning plant, other latest policy guidelines is deemed to be included in the Quoted Rate. "(al) Testing : Phase I test shall be 24 hours continuous running test to be carried out by the contractor in presence of the GE / Engineer-in-charge. Phase II Tests shall be 72 hours continuous running tests and shall be carried out when the extreme summer, monsoon and winter conditions in presence of the GE and Officer detailed by the Accepting Officer, within the 12 months period following phase-I test. The artificial load for phase I and phase II shall be provided by the contractor without any extra cost to the department. " (am) Free Servicing offered by the OEM shall come under the part of defect liability for two year (an) Execution of Air Conditioning system shall be carried out as per the following Indian/International codes : (1) ASHRAE (2) ASME (3) ARI (4) AMCA (5) UL181- Factory made Air duct and connectors,(6) UL-555- Fire dampers (7) NFPA 90A- Installation of Air conditioning and ventilation system (8) IS 3615- Glossary of terms used in refrigeration and air conditioning (9) IS325- Three Phase Induction motor (10) IS-1239- Mild steel tubes, tubular and other wrought steel fittings,(11) IS277- Galvanised sheet steel (12) IS655- Metal Air ducts (13) IS3588 - Axial flow fans electric,(14) IS 4894 Centrifugal fan (15) IS659 - Air conditioning safety codes (16) 616- Mechanical refrigeration safety code (17) NBC- National building code (18) IS 3043 - Code of practice for earthing (19) ECBC 2007/2009 (20) And any other relevant codes related to Air conditioning.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with built-in thermal overload protection, intitial time delay system, Low and High voltage cut-off protection and of capacity 4 KVA complete all as specified and as directed by Engineer-in-Charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with built-in thermal overload protection, intitial time delay system, Low and High voltage cut-off protection and of capacity 5 KVA complete all as specified and as directed by Engineer-in-Charge.
Supply and fix refrigerator electric driven (single phase, 230V, AC, 50Hz ) having capacity (gross volume) not less than 320 litres, minimum 3 star rated, Frost free, double door, inverter type compressor complete all as specified and as directed by Engineer-in-Charge.
Supply and fix Voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 270 V with built-in thermal overload protection, intitial time delay system, Low and High voltage cut-off protection and of capacity 2 KVA complete all as specified and as directed by Engineer-in-Charge.
Providing and applying two coat of 4 mm thick 'PYPKOTE' antirust protection including primer and lap of 25 mm on 100mm dia M.S. pipe in trenches or complete including surface preparation coating and wrapping shall be confirm to ISI 10221 including conducting Holiday Test complete all as specified and as directed by Engineer-in-Charge. ( Make :- IWL / STP / Tikitak )
Providing & fixing air release valve of 25 mm dia and 25 mm dia gun metal gate valve with fittings etc. to be installed at risers complete all as specified and as directed by Engineer-in-Charge. (Make :- Kartar / Zoloto/ Beer/ )
Supply, Installation Testing & Commissioning of Active Repeater Panel to be integrated with Fire Alarm Control Panel,larger display Full colour 800 x 480 LCD with resistive touch screen and automatic back-light dimming and the status of any Fire/Fault of Integrated Fire Alarm Panels, Panel should compliant with EN54-2, EN54-4 and Approved by LPCB (Make: Advance/ Hochiki/ Argus/ Appollo) .
Supply, Installation Testing & Commissioning of microprocessor based Networkable Analogue Addressable 2 loop Fire Alarm Control Panel. The Panel shall be compliant with EN54-2, EN54-4 and approved by LPCB. The Panel shall have LCD with resistive touch screen and automatic backlight dimming. The Panel must also have the capability to take Addressable Intelligent Wired and Wireless Devices on same loop. Each loop shall have a capacity of 127 analogue Addressable devices and 127 Base sounders/Base Sounder Beacons. The panel shall have an event log of minimum 1000 events @ 1 second resolution, Filterable and Printable. The Panel shall have Three access levels. Panel shall support upto 5000 Cause & Effects entries, with upto 20,000 inputs controlling & 20,000 Controlling outputs across the network. The Panel shall have capability for Peer to Peer networking through RS485 network card. The Panel must have 4 inbuilt programmable sounder circuits, each circuit rated at 2.5A.The Panel must have inbuilt 3 programmable inputs and 5 inbuilt programmable relay outputs. The Panel shall have up to sub-addressable 512 programmable Inputs/Outputs via optional RS485 COMMS serially connected expansion cards. The Panel shall have 240 V AC power supply along with automatic Battery Charger.
The Panel shall be fully expandable via common plug in loop driver boards. The user shall have a choice of using the panel with 5.25 Amp or 10.25 Amp power supply unit which is inbuilt in the FACP and should be approved to EN54-4. The Panel shall have configurable via USB port to PC or memory stick. The Panel shall have dedicated RS232 serial port for optional printer. (Make: Advance/ Hochiki/ Argus/ Appollo)
Supply, laying, testing and commissioning of cabling for fire detection and alarm system with 1.5Sq.mm 2 core annealed tinned multi strand copper conductor PVC Insulated flexible FRLS wire in MS conduit as required. ( Make :- Polycab / Havalls/ Finolex/ RR kabel /KEI)
Providing and fixing of 16 Gauge MS Conduit in size 20mm including the cost of junction box bends, elbow, sockets, Tee and GI flexible conduit to connect from ceiling to false ceiling etc laying in slab, cutting chasses and making good or surfaces mounting including all fixing hardware. ( Make :- BEC Industries / AKG / Kalinga / Bharat )
Providing & fixing of ISI marked (IS: 2878) portable Co2 fire extinguisher of capacity 4.5 kg flat base including valve discharge hose of not less than 10mm dia. meter complete in all respect including initial fill with Co2 gas confirming to IS 307-1966 and filled to filling ratio of not more than 0.367. ( Make :-Victor/Envos/MEC/Kanex)
Providing & fixing of ISI marked (IS: 15683) portable AFFF foam type fire extinguisher, Capacity 9 liter complete in all resp. ( Make :-Victor/Envos/MEC/Kanex)
Providing & fixing of ISI marked (IS: 15683) portable ABC multipurpose mono monioum phosphate powder , nitrogen pressurised type fire extinguisher, Capacity 6 kg complete in all resp.( Make :-Victor/Envos/MEC/Kanex)
Providing & fixing of ISI marked (IS: 13886) trolley mounted fire extinguisher, AFFF Mechnical foam type (gas pressurized) Capacity 50 liter complete in all respect.( Make :-Victor/Envos/MEC/Kanex)
Providing & fixing of ISI marked (IS: 2878) portable Co2 fire extinguisher of capacity 22.5 kg flat base including valve discharge hose of not less than 10mm dia. meter complete in all respect including initial fill with Co2 gas confirming to IS 307-1966 and filled to filling ratio of not more than 0.367.( Make :-Victor/Envos/MEC/Kanex)
Supply, Installation, Testing and Commissioning of 4 kg capacity FM 200 , DHP Assembly with automatic valve CE & pie approved, push in connector for tube, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. Make (Rotarex/Siemens/ Ceasefire/Enovs).
Supply, Installation, Testing and Commissioning of 6 kg capacity FM 200 , DHP Assembly with automatic valve CE & pie approved, push in connector for tube, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. Make (Rotarex/Siemens/ Ceasefire/Enovs).
Supply, Installation, Testing and Commissioning of 9 kg capacity FM 200 , DHP Assembly with automatic valve CE & pie approved, push in connector for tube, mounting bracket, End of Line adopter and low pressure switch for monitoring system activation. Make (Rotarex/Siemens/ Ceasefire/Enovs).
Supply, Installation, Testing and Commissioning of Hooter with accessory. Make (Rotarex/Siemens/ Ceasefire/Enovs).
Supply,Installation,Testing and Commissioning of UL Listed Linear Pneumatic heat Detection Tube with all necessary fittings & supports. Make (Rotarex/Siemens/Ceasefire/ firedetec/Enovs).
Emergency Lighting Control Panel (Approved as per BS EN 60598-2-2 by LIA laboratories ltd) with two lighting lines with maximum of 254 devices on both lines, up to 127 devices per line, luminare line length 500/1000 Metres .The System shall work on Extra Low Voltage and shall be Addressable. MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
ELS Panel Transformer 230 V with an output of 35V AC and is placed between mains and EL2 Control panel. (Approved as per BS EN 60598-2-2 by LIA laboratories ltd) ,MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
Key pad with an LCD to control, read and configure the Main ELS Control Panel. MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
Addressable Exit Signage visible from 20 mtrs (Approved as per BS EN 60598-2-2 by LIA laboratories ltd) with integral battery capacity of 3 hrs and bicoloured LED status indicator. Available in Left, Right, Down signs with Batteries incorporated into each luminaire shall be Polymer Lithium Ion technology and incorporate over voltage, over current and deep discharge protection circuitry.Provides at least 3 hours luminaire operation when fully charged. (Approved as per BS EN 60598-2-2 by LIA laboratories ltd), MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
Addressable Closed Area LED Down lighter (Approved as per BS EN 60598-2-2 with BS EN 60598-1:2008 +A11 by LIA laboratories ltd) with integral battery capacity of 3 hrs and bicoloured LED status indicator. MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
Addressable Open Area LED Down lighter (Approved as per BS EN 60598-2-2 with BS EN 60598-1:2008 +A11 by LIA laboratories ltd) with integral battery capacity of 3 hrs and bicoloured LED status indicator.MAKE HOCHIKI, NEPTOLUX, TAMLITE, SCHNEIDER, HONEYWELL, CEASEFIRE
Supply & testing of screened and twisted single pair with 1.5Sq.mm 2 core annealed tinned multi strand copper conductor PVC Insulated flexible FRLS wire in MS conduit as required. ( Make :- Polycab / Havalls/ Finolex/ RR kabel /KEI). Note : Cost of MS conduit shall be included in quoted rate.
UL Listed NOVEC 1230 /FM200 Pressure fire Suppression System Supply, installation, testing & commissioning of 80 Litres Capacity Seamless Cylinder CCOE Approved, complete with valve assembly and pressure gauge with a safety burst disc and a safety cap with switch in gauge Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde
Supply, installation, testing & commissioning of Novec 1230/FM200 gas compound of carbon, fluorine and oxygen (CF3CF2C(O)CF(CF3)2). Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde/3M
Supply, installation, testing & commissioning of Electric Control Head operated electrically from the Detection & Control System or locally with a manual lever on the control head. Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde/Ceasefire
Supply, installation, testing & commissioning Discharge of Nozzles are designed to provide the proper flow rate and distribution of FK-5-1-12 to total flood a hazard area :360 degMake :- Honeywell/Crypto/Rotarex/Sevo/Kidde
Supply, installation, testing & commissioning of Master Cylinder Adapter Kit used to actuate the Slave Cylinder. Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde
Supply, installation, testing & commissioning Discharge Hose, 1-1/2” (Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde
Supply, installation, testing & commissioning of 1-1/2" Manifold Check Valve installed at the discharge manifold to allow removal of any FK-5-1-12 cylinder from the manifold while still retaining a closed system. Make :- Honeywell/Crypto/Rotarex/Sevo/Kidde
Supply, installation, testing & commissioning of Supervisory Switch for indication of discharge of system.
Supply, installation, & fixing of of Cylinder Strap for 80 Ltr. Cylinder.
Supply, installation, testing & commissioning of Brass Male Elbow.
Supply, installation, testing & commissioning of M.S.seamless schedule 40 Pipe up to 50 mm dia size including all forged fittings such as tee, elbow, supports and paitning as per requirement of site, etc. Pipe (S) : M.S. Seamless To ASTM A-106, SCH. 40
Supply, installation, testing and commissioning of 2 Zone Gas Release panel with release module and battery backup. Make (Kidde/Hochiki/Siemens/ Ravel/Ceasefire/Honeywell).
Supply, installation, testing and commissioning of Manual Release Switch. Make (Kidde/Hochiki/Siemens/Ravel/Ceasefire/Honeywell).
Supply, installation, testing and commissioning of Abort Switch. Make (Kidde/Hochiki/Siemens/Feuerx/Ravel/Ceasefire/Honeywell).
Supply, installation, testing and commissioning of convensional smoke detector.(Make: Advance/ Hochiki/ Argus/ Appollo/Ravel/Ceasefire/Honeywell)
Supply, installation, testing and commissioning of convensional manual call point.(Make: Advance/ Hochiki/ Argus/ Appollo/Ravel/Ceasefire/Honeywell)
Supply, installation, testing and commissioning of convensional hooter.(Make: Advance/ Hochiki/ Argus/ Appollo/Ravel/Ceasefire/Honeywell)
Supply, laying, testing and commissioning of cabling for fire detection and alarm system with 1.5 Sqmm 2 core annealed tinned multi strand copper conductor PVC Insulated flexible FRLS wire in MS conduit as required. ( Make :- Polycab / Havalls/ Finolex/ RR kabel /KEI) Note : Cost of MS conduit shall be included in quoted rate.
S&F Recessed mounted Accent Lighting luminaire 42W suitable for 230V AC 50Hz supply with diecast aluminum heat sink and sand grain finishing reflector, with 2.5 KV Surge protection, angle of light beam spread-24 degree, available in two lumen packs with option of DALI dimmable driver. Type , Make - Phillips Cat Part No - RS -271B LED 40/840 Or its Equivalent to Bajaj / Havells /Wipro
S&F Lux Space Pro is a deep recessed downlighter 18W range suitable for 230V AC 50Hz supply with extremely low glare (UGR <19) & high quality faceted reflector for superior lighting and aesthetics. The range is available in Medium (32°) & Wide Beam (65°) optics for both standard and high ceiling applications. Make:Phillps Cat Part No DN590B M LED20S
S&F Sit Row Indicator and Foot Light 10Watt , suitable for 230V AC 50Hz supply With Marking and Direction
S&F Excess Electronic Control System
S&F LED Light 18 watt Dimmable type suitable for 230V AC 50Hz supply Cat part No DN195 Make Phillips or equivalent to Bajaj Havells or Wipro (for motivation hall 12 Nos)
S&F Decorative Roof Light at Reception Room of Diamonds are forever gold Crystal chandelier complete suitable for 230V AC 50Hz supply .
S&F IP65, Dust and Waterproof LED luminaire 36W suitable for 230V AC 50Hz supply with Polycarbonate Housing suitable for wall & ceiling mount applications. Type Make -Phillips Cat part No -WT201CLED-445/6500PSU or its equvilant to Bajaj/Wipro
S&F LED Light 2'x2' 42W suitable for 230V AC 50Hz supply decorative type Cat Part No RC740BLED 36WS(2X2) Make Phllips or equivalent to Bajaj ,Wipro
S&F High performance LED Downlights suitable for 230V AC 50Hz supply100 lumen / watt efficacy , Efficient heat sink (die cast) with Steel clips, Integrated driver control (for easy installation) Type HSN, 16 Watt Cat Part No DN 194B-LED20S-365/865 W60L60 Make Phillips or Its equvilant to Bajaj /Havells /Wipro
S&F electrically Operated Chimney Single phase 230 Volt for Modular Kitchen, Faber 90cm 1200Mcub/hr Heat Auto clean Chimney suitable for Kitchen of size 8100mm x 5000mm and height 3500mm
S&F telehpone socket special type (for Telephone / Data cable)
S&F TV socket special Modular fiush type
S&F garden LED Bollard Light 10WCat Part NO-LBLSR-10-WW Make -Crompton
S&F garden /Pathway LED post top Light 20WCat Part NO-LPTH 20-WW- Make 7/6/2021Crompton
S&F Junction box of minimum size 100mmx100mmx75mm consisting of 4 way connector, insulators etc suitable for post top light with fixing clamps all as specified and as directed.
External Electric Supply : Supply & fix cubical type, factory made LT panel board, suitable for 3 phase, 415 volts, 50 Hz system, with aluminium bus bar for R,Y,B and Neutral and bus bar size shall be suitable to carry current at 1.5 times current carrying capacity of out going switch gears, , Outdoor type, factory fabricated with 3.15 mm thick CRCA sheet with inspection doors at front & rear side inclusive of necessary locking arrangement, suitable glands, opening for vent and cable entry, Spare terminal for MCCB with angle Iron of size 50x50x5 mm thick, grouted in floor complete with the following accessories, duly pre-treated and powder coated finish complete. (a) MCCB, 4 pole 500A, 50 KA- 01 No (Incoming). (b) MCCB, 4 pole 320A, 50KA- 01 No (To AC Plant). (c) MCCB, 4 pole 250A, 50KA- 01 No (To Briefing Hall). (d) MCCB, 4 pole 160A, 50KA- 01 No (To APFC). (e) MCCB, 4 pole 160A, 50KA- 01 No (Spare). (f) Spare box/space for fixing MCCB 01 No (MCCB not to be provided). (g) Digital display VAF Panel meter- 01 No with CT coils. (h) LED Indicator RYB - 01 Set. (j) Sufficient space shall be provided within LT panel for installation of 4 Kg Fire Extinguisher (Cost of Fire extinguisher is not included).
Supply & fix cubical type, factory made LT panel board, suitable for 3 phase, 415 volts, 50 Hz system, with aluminium bus bar for R,Y,B and Neutral and bus bar size shall be suitable to carry current at 1.5 times current carrying capacity of out going switch gears, , indoor type, factory fabricated with 2 mm thick CRCA sheet with inspection doors at front & rear side inclusive of necessary locking arrangement, suitable glands, opening for vent and cable entry, Spare terminal for MCCB with angle Iron of size 40x40x5 mm thick, grouted in floor complete with the following accessories, duly pre-treated and powder coated finish complete (a) MCCB, 4 pole 250A, 35 KA- 01 No (Incoming). (b) MCCB, 3 pole 125A, 35KA- 01 No. (c) MCCB, 3 pole 100A, 35KA- 02 No. (d) MCCB, 3 pole 63A, 35KA- 02 No. (e) Spare box/space for fixing MCCB 01 Nos (MCCB not to be provided). (f) Digital display VAF Panel meter- 01 No with CT coils. (g) LED Indicator RYB - 01 Set. (h) Sufficient space shall be provided within LT panel for installation of 4 Kg Fire Extinguisher (Cost of Fire extinguisher is not included)
Supply, Installation, Testing and commissioning of diesel engine driven generating set alongwith acoustic enclosure 415V, AC, 3 phase 4 wire 50Hz having capacity 320KVA including PCC platform as recommended by the manufacturer automatic on mains failure (AMF) type 0.8 power factor 50 Hz 1500 RPM self excited, self regulate brushless AC generator suitable for ambient conditions complete with relay panel, for automatic starting on main failure control panel and confirming to IS with the following for DG set complete with acoustic enclosure.
(A) ALTERNATOR : Standard design alternator rated at 320 KVA net output at site after considering de-rating as per site conditions at power factor 0.8, AC 3, phase 4 wire, 415 volts, 50 cycles, 1500 RPM self excited self regulated screen protected drip proof IP 23 brushless design with hub and shield / roller bearing with winding in each face insulating class 'H' band of voltage regulation ± 5% of rated voltage from no load to full load the alternator shall be in position to generate supply with frequency / regulation within ± 1% tolerance.
(B) DIESEL ENGINE Adequate capacity diesel engine (not less than 400HP) Water cooled to drive independently above alternator and after considering de-rating as per site conditions generating and reducing power consumed by accessories. Directly coupled through flexible coupling , multi stroke direct injection, cold starting 1500 RPM as per with on overload capacity of 10% one hour in a day 12 hours continuous running complete with standard accessories all as specified and required for safe handling and operations. (B1) RETROFIT EMISSION CONTROL DEVICE (RECD) Suitable capacity RECD shall be supplied, fixed, commissioned and tested by contractor alongwith all required items for its satisfactory working. This device should control DG set emissions such as Oxides of Nitrogen, Hydrocarbon, Carbon Monoxide, Particulate Matter and smoke within limits as prescribed by CPCB. Necessary testing arrangement shall be provided by contractor at his own cost.
(C ) CONTROL PANEL (CONTROLLER) It shall be microprocessor based, integrated with AMF panel, graphical LCD display. Monitoring features:- Phase Voltages & Currents, Frequency, Reverse power, Genset kVA, kW, kWh, kVAr, Power Factor, Canopy Temperature, Lube oil Pressure, Engine Temperature, RPM, Run Hours,Number of starts, Fuel Level, Auto / Manual Stop, Battery charge condition. Diagnostic features:- Battery charging failure, Over/Under speed, Over Current , Over / Under Voltage, Over kW, Phase Seq., Phase missing, Mains Under voltage, Earth Fault trip, Fuel usage Alarm, Low lube oil Pressure, High E n g i n e Te m p e r a t u r e , Low/High battery voltage, Low Fuel Level, Over Crank protection , Routine maintenance indicator, Gen set Test Facility, Mains Frequency.
(D) ACCOUSTIC ENCLOSURE Noise level less than 75dBA, Ease of Access and Serviceability, Aesthetically designed, weather and sound resistant enclosure, Insulation conforms to UL94-HF1 class for flammability, shall be provided with Anti Vibration Pads
(E ) AMF PANEL :- AMF (Auto on Mains Failure) panel, Kiosk type outdoor, weather and vermin proof factory made cubicle made out of CRCA sheet 3.15mm thick front and rear opening of 415 volts, 3 phase 4 wire AC 50 cycles having bus bar capacity suitable to carry current of 110% full load 320 KVA DG set generation complete with following items:- MCCB TP 500A, 50KA Qty-02 Nos, Contactor 500A, 3P Qty-02 Nos, Aluminium bus bars (R,Y,B,N) of suitable rating, relay, AMF logic controller, battery charger, Single phase preventor, Auto/manual switch, Start, Stop push button, Volt meter, Ammeter, KWH Meter, RYB indicators, Load on DG Indiacator, Load on Mains indicator, protection gears etc. Any item other than above but required for Automatic operation, protection of life and components shall be provided by contractor without additional cost.
AMF Functioning Starting the DG set when there is a failure of main supply / single phasing or when the voltage is lower /higher than the pre set value or where there is failure of one / two phases. Transferring the load to the DG set from the mains. Transferring the load back to the mains when healthy mains supply is restored and stoppage of DG set. NOTE : The above functions shall be carried out automatically without human intervention.
(F) CIVIL WORKS All civil works related to foundation installation of panel and equipments including making good of existing structure if disturbed during installation and commissioning of GEN SET, (Total depth of foundation shall be minimum 300mm with anti vibration pads).
(G) TESTING (i) Necessary testing equipment and heater load for testing before handing over the work (Phase -I & Phase -II tests) shall be carried out by the contractor to the entire satisfaction of the accepting officer or any person authorized by him and the satisfactory results shall be kept in MES records duly signed by the contractor, Engineer-in-Charge and testing officer. (ii) Phase -I test will be performed for 1 hour without load after completion of installation by Engineer-in-Charge. (iii) Phase-II test will be performed for 12 hours by the rep of Accepting Officer. (iv) DHPP (Diesel) required for Phase-I and Phase-II testing shall be supplied by contractor on his own cost.
External Water Supply : Material & labour for cutting of existing bituminous road / hard standing upto 15cm depth for laying of pipe & making good to the disturbed surfaces by providing PCC or same material after laying of pipe and returning filling of soil complete all as specified and as directed. Note:- Excavation and earth work will be measured and paid under relevant items.
Construction of valve chamber having inner dimension 600 x 600 x 600 mm (suitable for gate valve upto 50mm) with PCC 1:4:8 type D2 for foundation, brick work wall in cement mortar (1:4), PCC 1:2:4 type B1 for coping, rendering plaster in CM 1:4, 15 mm thick including provision of MS Sheet top cover 3 mm thick with brazing of MS flat of size 25 mm x 4 mm at edges and in diagonal and angle iron base frame of 40 x 40 x 5 mm, painting with two coat of synthetic enamel paint over a coat of red oxide primer on iron surfaces, lime wash on internal and external cement surfaces and locking arrangements necessary excavation earth work complete all as specified and as directed.
Cutting existing iron pipe in position and inserting new GI TEE of 50x50x50 mm dimension complete all as specified and as directed. Note:- Excavation and earth work will be measured and paid under relevant items.
Internal Water Supply : Supply and fix 15mm bore 2 way bib tap brass chromium plated fancy type with wall flange complete all as specified and as directed.
Internal Electric Supply : Supply and fix vertical TPN distrubtion board IP43 6way suitable for MCCB triple pole as incommer complete all as specified and as directed. Note:- Incomming MCCB and outgoing MCB's will be measured and paid separately.
Supply and fix MCB single pole C Curve 6-32 Amps 10KA complete all as specified and as directed.
Supply and fix MCB triple pole C Curve 63 Amps 10KA complete all as specified and as directed.
Sch 'A' Part - XVI : Manning and operation Operation and comprehensive maintenance of central AC plant as detailed below in single shift per day with 01 No of Qualified Tradesman including Sunday and holidays (During defects liability period.) (a) OPERATOR SCHEDULE Shift of 8 hours (b) The operation and maintenance ofcentral AC plant shall be carried out for a period of 24 (Twenty four) months after the date of completion of the project i.e. during the defects liability period. Note: Repair / replacement of minor spares, consumables and overall workmanship of central AC plant is already covered under material and performance warranty
C R R CONSTRUCTIONS
R. Wadhumal and Sons
M/s. P S REDDY
M/s R.L.PAREEK
Shree Construction Co.
VERMA BROTHERS
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .