Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹11.2 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹13.2 L+₹2.0 L (17.9%)Rejected-Finance 79 MAHENDRA BANARJEE ROAD BEHALA KOLKATA 700060 | KOLKATA | WEST BENGAL | 700060 | L2 | Rejected-Finance L2 | |
| 3 | L3₹13.6 L+₹2.4 L (21.2%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | L3 | Rejected-Finance L3 | |
| 4 | L4₹13.9 L+₹2.7 L (24.2%)Rejected-Finance 306 BAKSHI HOUSE 40 41 NEHRU PLACE NEW DELHI 110019 DELHI | SOUTH EAST | DELHI | 110019 | L4 | Rejected-Finance L4 | |
| 5 | L5₹14.3 L+₹3.1 L (28.1%)Rejected-Finance | L5 | Rejected-Finance L5 |
Tender Value
₹16.5 L
Closing Date
21 Jan 2022, 6:00 pmClosed
Sr Manager (Engg. Elect.), RHQ ER
Office of GM (Engg), RHQ-ER, NSCBI Airport, Kolkata
Provision of AC and water cooler in ELDIS Radar and other NAVAIDS building in operational Area, NSCBI Airport, Kolkata
2021_AAI_100069_1
AAI/ER/Kol/Sub. Div.-I/AC/NIT-06/2021-22
Open Tender
Electrical Works
Works
90 days
Kolkata Airport
Please refer Tender documents.
14 documents required · 14 mandatory
₹1,180
Exempted
18 Feb 2022
31 Dec 2021
24 Jan 2022
31 Dec 2021
21 Jan 2022
31 Dec 2021
31 Dec 2021 - 13 Jan 2022
Supply of 1 Phase, 1.5 TR high wall split AC of 5 star rating Inverter type Air-conditioners suitable to operate from 230±10%, 50 Hz, 1 phase power supply having high EER Compressor with Indoor & Outdoor Copper coil refrigeration having aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with Eco friendly R-32 or equivalent Refrigeration Gas along with copper conductor PVC insulated PVC sheathed multicore power cable of size not less than 2.5 Sqmm. from indoor to outdoor unit (i/c 3 mtr. copper refrigerant pipe). The indoor unit should have real time clock, operating facility from cordless remote, along with time and temperature display. Outdoor unit to be installed as Directed by Engineer-in-Charge. Nominal Cooling Capacity of the machine shall be 5000 W / 17100 BTU/Hr (Minimum).
Supply of 1 Phase, 2 TR high wall split AC of 5 star rating Inverter Air-conditioners suitable to operate from 230±10%, 50 Hz, 1 phase power supply having high EER Compressor with Indoor & Outdoor Copper coil refrigeration having aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with Eco friendly R- 32equivalent Refrigeration Gas along with copper conductor PVC insulated PVC sheathed multicore power cable of size not less than 2.5 Sqmm. from indoor to outdoor unit (i/c 3 mtr. copper refrigerant pipe). The indoor unit should have real time clock, operating facility from cordless remote, along with time and temperature display. Outdoor unit to be installed as Directed by Engineer-in-Charge. Nominal Cooling Capacity of the machine shall be 6000 W / 20500 BTU/Hr (Minimum).
Supply of 3 Phase, 4 TR Floor mounted Inverter type split AC unit suitable to operate from 415±10%, 50 Hz, 3 phase power supply having Indoor & Outdoor Copper coil refrigeration having aluminium fins firmly bonded to copper tubes assembled in zinc coated steel frame with Eco friendly R-32 or equivalent Refrigeration Gas along with copper conductor PVC insulated PVC sheathed multicore power cable from indoor to outdoor unit. The indoor unit should have operating facility from cordless remote, along temperature display. Outdoor unit to be installed as Directed by Engineer-in-Charge. Nominal Cooling Capacity of the machine shall be 13400 W (Minimum).
ITC of the following TR split type Air-conditioners along with Outdoor/ Indoor unit suitable to operate on 1/3 Phase Power supply.
(a) upto 2 TR Highwall AC
(b) 4 TR Split/Floor mounted AC
Supply and fixing of extra copper refrigerant piping complete with suction / liquid line, insulation (i.e. cunifoam with neoprene / rubber lining), and all the accessories i/c Control Cable as per site requirement as directed by Engineer-in-Charge including additional gas charging as required.
(a) Suitable for 1/1.5 TR Highwall Split Inverter AC along with its Control Cable
(b) Suitable for 2 TR Highwall Split Inverter AC along with its Control Cable
(C) Suitable for 4 TR Floor mounted AC along with its Control Cable
Supply and laying of 25 mm dia cotton braided PVC pipe to be used for drainage of condensate from indoor units to the nearest drain-port as directed by Engineer-in-Charge.
Supply and fixing of fabricated metallic structure with required painting / pre-fabricated L shaped O/D stand of suitable size made of MS angle/ frame as per site requirement etc for suspension of outdoor compressor units as per direction of Engineer-in-Charge.
Supply installation testing and commissioning of the timer for auto/manual operation of the Air Conditioners upto 2 TR. The Timer shall have provision for 02 nos. of Air Conditioners as input and 01 no. as output with provision for switching of Air Conditioners as per the user requirement in the time interval of 4/6/12 Hr.
Supply installation testing and commissioning of the timer for auto/manual operation of the Air Conditioners. The Timer shall have provision for 03 nos. of Air Conditioners as input and 02 no. as output with provision for switching of Air Conditioners as per the user requirement in the time interval of 4/6/12 Hr.
Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top along with 20 amps “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supply, Installation, testing, commissioning of Water Cooler cum in built UV+RO water purifier with storage capacity of 80Ltrs, Cooling Capacity 60Ltr (approx.) having minimum 2(Two) nos. water Faucets suitable to operate on 230V,1-phase,50Hz AC power supply and meeting the Specification as Specified in Technical Specification. (Make :- AquaGuard, Model :Green Pure chill 80 SS- RO+UV or Equivalent).
Supply, installation, Testing and commission of iron remover consisting of 20''/24'' iron vessel-Resin based with filtration capacity 200 LPH equipped backwash facility for flushing out filtered iron sediments.
MANNA ELECTRONICS AND ELECTRICAL WORKS
Lyric International
VOLKS ENERGIE PVT LTD
star refrigeration sales and service
Ganga Enterprises
Industrial Traders
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .