Loading…
Loading…
Tender Value
₹47.8 L
EMD Value
₹95,500
Closing Date
2 Oct 2026, 6:00 pm
GE (AFA) Hyderabad
GE (AFA) Hyderabad, Dundigal, Hyderabad
SPECIAL REPAIRS TO REWIRING AT TWIN HANGAR ALONG WITH ANNEXES AND SPECIAL REPAIRS REPLACEMENT TO UNSERVICEABLE EARTHING PITS AT VARIOUS LOCATIONS AT AFA HYDERABAD
2026_MES_789206_1
8745/E8
Open Tender
Civil Works
Item Rate
HYDERABAD
As per NIT
5 documents required · 5 mandatory
₹500
GE (AFA) HYDERABAD
₹95,500
Yes
12 Sept 2026
12 Sept 2026
5 Oct 2026
12 Sept 2026
2 Oct 2026
25 Sept 2026
12 Sept 2026 - 25 Sept 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking down old, unsv aluminium point wiring (light, fan, socket or power) complete, incl fixture & fittings such as switches, ceiling roses, pendants, regulators, sockets, light fittings, air circulator fans etc. removing materials to store for keeping in safe custody for reuse or for taking credit & making good the disturbed surfaces of walls, floors, etc. complete all as specified and as directed & to the entire satisfaction of Engr-In-Charge. | 85 | Point | 100 | ₹8,500 |
| 2 | Taking down old sub-main wiring including fixture & fittings etc. removing materials to store for keeping in safe custody or for taking credit & making good the disturbed surfaces of walls, floors, etc. complete all as specified and directed by Engr-In-Charge. | 2,500 | RM | 100 | ₹2,50,000 |
| 3 | Disconnecting/dismantling of old existing un serviceable DB's any type/way 240/415 Volts with their old/un serviceable burnt MCCB/MCB's etc. complete all as specified and directed by Engr-In-Charge. | 12 | Each | 100 | ₹1,200 |
| 4 | Refixing of Air Circulator Fans any type / rating / wattage dismantled against Item Sl No 1 above after dusting, cleaning, making necessary electrical connections & testing complete all as specified & as directed. | 38 | Each | 100 | ₹3,800 |
| 5 | Refixing of High Bay Lights any type / rating / wattage dismantled against Item Sl No 1 above after dusting, cleaning, making necessary electrical connections & testing complete all as specified & as directed. | 66 | Each | 100 | ₹6,600 |
| 6 | Refixing of 2' x 2' Recess Lights any type / rating / wattage dismantled against Item Sl No 1 above after dusting, cleaning, making necessary electrical connections & testing complete all as specified & as directed. NOTE for Item Nos 1 to 6 : Cost of making good the disturbed surfaces is deemed to be included in the unit quote rates. | 21 | Each | 100 | ₹2,100 |
| 7 | M & L for surface flame proof point wiring with two single core 1.5 sqmm PVC insulated, unsheathed, FRLSH cable, 1100 volts grade, ISI marked with multi stranded copper conductor drawn through and including stove enamelled steel conduit of size not less than 20 mm dia with all fittings and accessories ISI marked, ISI marked with all fittings and accessories ISI marked incl provision of 1.5 sqmm PVC insulated, multistranded, unsheathed, copper conductor cable, FRLSH, ISI marked as earth continuity conductor (green in colour) & incl fixing of flame proof Metal Junction / Inspection boxes (if any) with including cutting chases (if any) for conduits & sinkings for modular boxes, necessary fixing arrangements & making good the disturbed surfaces, matching to the existing one etc. complete all as specified & as directed for the following : Make of cable : Havells/Polycab/Finolex/KEI. Make of Steel Conduit : ISI Marked
(a) One Light point etc. controlled by one flame proof switch. | 4 | Per Point | 100 | ₹400 |
| 8 | M & L for surface flame proof sub-main wiring alongwith earth wire of size (2 x 2.5) sq. mm + (1 x 2.5) sq. mm earth wire, ISI marked, FRLSH, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enamelled steel conduit of size not less than 20 mm dia with all fittings and accessories ISI marked for conduits & sinkings for Flame Proof Junction Boxes (if any) & making good to any surfaces etc. complete all as specified & as directed. Make of cable : Havells/Polycab/Finolex. Make of Steel Conduit : ISI Marked [For High Bay Lights, Air Circulators, 15 A Sockets] | 1,600 | RM | 100 | ₹1,60,000 |
| 9 | M & L for surface flame proof sub-main wiring alongwith earth wire of size (2 x 4.0) sq. mm + (1 x 4.0) sq. mm earth wire, ISI marked, FRLSH, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enamelled steel conduit of size not less than 20 mm dia with all fittings and accessories ISI marked for conduits & sinkings for Flame Proof Junction Boxes (if any) & making good to any surfaces etc. complete all as specified & as directed. Make of cable : Havells/Polycab/Finolex. Make of Steel Conduit : ISI Marked [For SPN DBs] | 250 | RM | 100 | ₹25,000 |
| 10 | M & L for surface flame proof sub-main wiring alongwith earth wire of size (4 x 4.0) sq. mm + (1 x 4.0) sq. mm earth wire, ISI marked, FRLSH, PVC insulated, multi stranded, copper conductor, single core cable drawn through and including stove enamelled steel conduit of size not less than 25 mm dia with all fittings and accessories ISI marked for conduits & sinkings for Flame Proof Junction Boxes (if any) & making good to any surfaces etc. complete all as specified & as directed. Make of cable : Havells/Polycab/Finolex. Make of Steel Conduit : ISI Marked [For 3 Phase Sockets] | 320 | RM | 100 | ₹32,000 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.12 MB
BOQ_884675.xls
BOQ • 0.55 MB
TENDERPAGES8745.pdf
Tender Documents • 0.46 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .