EXECUTIVE ENGINEER (SDW)-II
S.T.P. OKHLA MATHURA ROAD NEW DELHI-110025
Improvement/ Renovation of LT APFC Panel at 45 MGD STP Okhla.
2021_DJB_210584_8
NIT No-12 EE (SDW) II/ (21-22)
Open Tender
Electrical Works
Works
45 days
S.T.P. OKHLA MATHURA ROAD NEW DELHI-110025
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
A/c.50448339804
Yes
25 Nov 2021
2 Nov 2021
9 Nov 2021
2 Nov 2021
9 Nov 2021
2 Nov 2021
Improvement/ Renovation of LT APFC Panel at 45 MGD STP Okhla including all the required works , materials, arrangements , tools & tackles , workmanship , safety equipments as per NHRC\NGT\ DPCC etc guidelines and as per site requirement , remodeling all the damages up to standard if occurred any complete in all respect as per requirement satisfactorily. Dismantling /checking of all damaged switchgears, capacitors, measurement instrument, indicating lights, relay and removing of complete wiring and mechanical connection at site and cleaning of A.P.F.C. panel by CRC
Super Heavy Duty capacitors cylindrical 25 KVR power 3 phase,440 V AC 50Hz MPP type heavy duty in suitable banking as per requirement for power factor Make: Epcos/L&T
Super Heavy Duty capacitors cylindrical 5-15 KVR power 3 phase,440 V AC 50Hz MPP type heavy duty in suitable banking as per requirement for power factor Make: Epcos/L&T
Super Heavy Duty capacitors BOX 50 KVR power 3 phase,440 V AC 50Hz MPP type heavy duty in suitable banking as per requirement for power factor Make: Epcos/L&T
Banking of capacitors as required with bus bar ,thimble etc.
Installation of capacitors, with wiring etc.
Automatic power factor correction relay 415V digital type with display of power factor 4 SETPS Make: Neptune/L&T/EPCOS
Providing/Fixing MCB 415V FP 32Amp. with handle & spreader DSR2018(2.1.1)
Providing/Fixing MCB 415V FP 63Amp. DSR2018(2.1.2)
Providing/Fixing MCCB 250Amp.415 V TP DSR2018(2.2.6)
PVC insulated copper flexible wire 10sq mm DSR2018(1.10.5)
Power contactor 220V AC 63Anp. Make: L&T/Siemens/TC/GE
Power contactor 220V AC 140 Amp.(MNX140) Make: L&T/Siemens
Power contactor 220V AC 12Amp. Make: L&T/Siemens
indicating lights R.Y.B. & ON 415V Make: siemens/ vaishno/ L&T
Auto- Manual Switch Make: Kaycee/L&T
Senescing current Transformer
Changing of the above components in existing panel by removing of old damaged components, changing of power & control wiring ,ferrule, thimble etc.
Providing the exhaust fan for cooling the APFC panel
Fixing and making connection of bus bar for connection of 2500Amp. ACB size 100x10mm including links, bends, aluminum bus bar will be of electrolytic grade 55% conductivity or as per relevant IS having sufficient cross section area insulated with heat shrinkable PVC sleeve in phase color identification. The bus bar support insulator shall be of class F insulation made out of non-hygroscopic material as SMC/DMC. All hard ware for connection/joints shall be in high tensile.
Testing & commissioning of the APFC panel with relevant IS as follow: - Check equipments specification - Continuity and ear thing -MCCB mechanism and alignment -Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth. - All functional tests -Checking for all tightness of nuts and bolts -Setting of APFC relay parameters to achieve target PF -Alignments of doors etc. -interlocking tests
Prime India Associates
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .