| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.4 CrAccepted-AOC NOT AVAILABLE | ₹20.4 Cr Quoted ₹23.0 Cr | L1 | Accepted-AOC Award |
| 2 | L2₹25.0 CrRejected-Finance | ₹25.0 Cr | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹27.7 CrRejected-Finance | ₹27.7 Cr | L3 | Rejected-Finance Other than lowest |
Tender Value
₹19.9 Cr
EMD Value
₹19.9 L
Closing Date
28 Feb 2023, 5:00 pmClosed
Executive Engineer JSV Mandi
Executive Engineer Jal Shakti Division Mandi Tarna Hill
Provision for development of site construction of percolation well 6 mtr dia and 10 mtr deep drilling and lowering of bore well 50 mtr deep Const Pump House Providing laying jointing and testing of Rising Mains Laying Jointing and Testing of Gravity
2023_HPIPH_69322_1
16929-78
Open Tender
Civil Works
120 days
Mandi Town
Please refer Tender documents.
9 documents required · 9 mandatory
₹2,500
Yes
EE Mandi
₹19.9 L
Yes
8 Jun 2023
21 Feb 2023
1 Mar 2023
21 Feb 2023
28 Feb 2023
22 Feb 2023
Amount
Excavation in foundation for digging well in dry excavation from GL upto the level where well curb is placed from natural surface to 1.50 meter depth in all leads and lifts.
Wet well sinking gravel including all pumping, soring etc. in all leads and lifts. From spring level to 3.00 mtr. Depth in all leads and lifts.
From spring level to 3.00 metre to 6.00 meter Depth in all leads and lifts.
From spring level to 6.00 mtr. Depth 9.00 meter Depth in all leads and lifts.
From spring level to 9.00 mtr. Depth 10.00 meter Depth in all leads and lifts.
Steel work in single sections including cutting, hoisting, fixing in position and applying a priming coat of red lead paint: - In R.S. Joists, channels angles, tees in all leads and lifts.
Lowering of well curb complete in all respect in all leads and lifts.
Transportation of suitable truck mounted DTH and ODEX/Percussion Calyx/RC drilling rigs alongwith necessary accessories etc to the site of work and errection of rig including levelling etc. complete in all respects as per the directions of the Engineer-in-Charge in all leads and lifts.
Drilling bores of 200 mm dia as per IS 2800-1979 from ground level in the overburden as per direction of the Engineer-in-Charge/hydrogeologist with suitable rigs for drilling through rocky formation consisting of sand stone, limestone, dolomites, congiomerate, boulder pebble, gravats, silt, clay or any other type of sedimentary, metamorphic and igneous rocks including cost of attachements consumables stores bils, water, POL etc complete in all respect in all leads and lifts.
Supplying and lowering IS marked 175 mm nominal bore 6 mm thick MSERW casing plain end casing pipe as per IS 4270-2001 with upto date amendments in a length of 3.00 metres including cost of cutting welding, transportation charges complete in all respect as per directions of the Engineer-in-Charge. The pipe shall be slotted at a suitable interval thickness 6 mm in all leads and lifts.
Providing and fixing suitable casing shoe and bit tube as per requirement of ODEX attachment complete in all respects as per directions of the Engineer-in-Charge in all leads and lifts.
Collection and preservation of soil samples in polythene bags complete in all respects as per the directions of the Engineer-in-Charge in all leads and lifts.
Development of bore well and yield testing with air compressor through V notch and disinfection etc. complete in all respects as per IS-2800-1979 and as per directions of the Engineer-in-Charge in all leads and lifts.
Cutting in earth work and disposal of excavated earth work in all kinds of soil such as pick work, jumper work, blasting work, chiselling work soft/hard rocks where blasting is prohibited in all leads and lifts.
Excavation in foundations trenches etc. (for pipes and pits) upto all depths in all kinds of soil such as pick work, jumper work, blasting and chiselling soft/hard rocks where blasting is prohibited in all leads and lifts including trimming and dressing of sides levelling of bed to correct excavation and returning the stacked soil after laying jointing and testing of G.I.Pipes in trenches in 15 cm. layers including consolidating each deposited layer by ramming and watering and then disposing of all surplus excavated soil as directed in all leads and lifts and soring strutting/timbering and dewatering where ever required including restoration of un-metalled/metalled paved surface of its original conditions including cost of diversion for traffic night signals Fixing caution boards and fencing etc.complete in all respects.
Providing and laying cement concrete 1:6:12 (1 cement : 6 sand : 12 crushed stone aggreagte 40 mm nominal size) and curing complete excluding cost of form work in foundation and plinth in all leads and lifts.
Providing and laying cement concrete 1:5:10 (1 cement : 5 sand : 10 crushed stone aggreagte 40 mm nominal size) and curing complete excluding cost of form work in foundation and plinth in all leads and lifts.
Providing and laying cement concrete 1:4:8 (1 cement : 4 sand : 8 crushed stone aggregate 40 mm nominal size) and curing complete excluding cost of form work in foundation and plinth in all leads and lifts.
Providing and laying cement concrete 1:3:6 (1 cement : 3 sand : 6 crushed stone aggregate 40 mm nominal size) and curing complete excluding the cost of form work in foundation and plinth in all leads & lifts.
Random rubble masonry /polygonal rubble masonry (uncoursed brought to courses ) with hard stone of approved quality in foundation and plinth including levelling up with cement concrete 1:6:12 (1cement:6 sand:12 crushed stone aggregate 20 mm nominal size) at plinth level in cement mortar 1:6 (1 cement : 6 sand) in all leads and lifts.
Brick work using common burnt clay building bricks in foundation and plinth in cement mortar 1:6 (1cement : 6 sand ) in all leads and lifts. 2nd class bricks.
Providing and Fixing pressed steel doors frames manufactured from commercial mild steel sheet of 1.25 mm thickness including hinges jump lock jamb,beed and if required angle threshold of mild steel angle of section 50x25mm or base ties of 1.25 mm pressed mild steel welded or rigidly fixed together by mechanical means,adjustable lugs with split and tails to each jamb including steel butt things 2.5 mm thick with guards lock strike plate and shock as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-Charge.
Providing woodwork in frames of doors,windows,clerestory,windows and other frames wrought,framed and fixed in position 2nd class deodar wood in all leads and lifts.
Providing and Fixing panneled glazed or panelled and glazed shutters for doors, windows and clerestory windows, including black enamelled iron butt hinges with necessary screws. 40 mm thick. 2nd class deodar wood in all leads and lifts.
Providing form work with steel plates 3.15 mm thick welded with angle iron in frames 30x30x5 mm, so as to give a fair finish including centering, shuttering, propping etc.with wooden battens and ballies, height of propping and centering below supporting floor to ceiling not exceeding 4 meters and removal of the same for-in-situ reinforced concrete and plain concrete work in:- Foundation footings bases of columns and the like and mass concrete in all leads and lifts. Vertical surface such as walls (any thickness) partitions and the like including attached pillasters, butteresses, plinth and string courses and the like in all leads & lifts.
Vertical surface such as walls (any thickness) partitions and the like including attached pillasters, butteresses, plinth and string courses and the like in all leads & lifts.
Beam, cantilever, girders and lintels, sides and soffits of beam, beam haunching, cantilever, bressumers and lintels not exceeding 1 mtr. In depth in all heights from floor in all leads and lifts.
Flat surfaces such as soffits of suspended floors, roofs landings and the like: floors etc. up to 200 mm in thickness in all leads & lifts.
Stair cases with slopping or stepped sofits including risers and stringers excluding landing in thickness in all leads & lifts.
Edges of slabs and Breaks in floors and walls Under 20 cm. wide in all leads & lifts.
Providing form work of ordinary timber plankings so as to give a rough finish including centering, shuttering, propping etc. height of propping and centering below supporting floor to ceiling not exceeding 4 meters and removal of the same for-in-situ reinforced concrete and plaiin concrete work in:- Arches, domes, vaults up to all span in all leads and lifts.
Providing and laying cement concrete 1:11/2 :3 ( 1cement : 1 1/2 sand: 3 crushed stone aggregate 20 mm nominal size ) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :- Foundation footings bases of columns and the like and mass concrete in all leads and lifts.
Walls (any thickness but not less than 0.1 mtr thickness) attached pilasters, buttresses, plinth and string courses etc. from top of foundation level up to floor two level in all leads & lifts.
Columns, pillars, post and struts Square, rectangular or polygonal in plan in all leads and lifts.
Beam, cantilever, girders and lintels, sides and soffits of beam, beam haunching, cantilever, bressumers and lintels not exceeding 1 mtr. In depth in all heights from floor in all leads and lifts.
Suspended floors, roofs, landings and shelves and their supports, balconies, beams, girders, bressumers and cantilivers up to floor two level in all leads & lifts.
Dome roofs, landings shelves and their supports balconies, beams, girders, bressumers and cantilevers etc. any shape in all leads & lifts.
Providing and Laying No Fine concrete1:6 (1 cement : 6 graded stone aggregate 40 mm nominal size) and curing complete :- in walls (any thickness but not less than 0.1 mtr thickness) attached pilasters, buttresses, plinth and string courses etc. from top of foundation level up to floor two level in all leads and lifts.
Providing and laying cement concrete 1:2:4 ( 1 cement : 2 sand : 4 crushed stone aggregate 20 mm nominal size) and curing complete excluding the cost of form work and reinforcement for reinforced concrete work in :- Foundation footings bases of columns and the like and mass concrete in all leads and lifts.
Walls (any thickness but not less than 0.1 mtr thickness) attached pilasters, buttresses, plinth and string courses etc. from top of foundation level up to floor two level in all leads & lifts.
Suspended floors, roofs, landings and shelves and their supports, balconies, beams, girders, bressumers and cantilivers up to floor two level in all leads & lifts.
Providing and laying Tor Steel reinforcement for reinforcement cement concrete work including bending, binding and placing in position includig the cost of binding wire and cutting in all leads and lifts as per the directions of the Enginerer-in-Charge.
Boulder/Stone filling dry hand packed tightly complete under lean conrete to prevent the entry of surface water in all leads and lifts.
Half bricks masonry in common burnt clay building bricks in cement mortar 1:4 (1cement:4 sand) in all leads and lifts. 2nd class Bricks.
Pointing on brick work with cement mortor 1:3 (1cement : 3 sand) Raised and Cut in all leads and lifts.
Providing and laying brick tiles over mumty roofs grouted with cement mortar 1:3 ( 1 cement :3 sand ) over a 12 mm layer of C.M 1:3 ( 1 cement : 3 sand ) and finished neat with in all leads and lifts complete in all respect in all leads and lifts.
6 mm cement plaster to ceiling in cement mortor 1:3 (1 cement : 3 Sand) complete in all leads and lifts.
15 mm thick cement plaster in single coat on rough side of brick/concrete/stone walls for interior plastering upto floor two level brick/concrete/stone walls for interior plastering upto floor two levels including arrises internal rounded angles chamfers and or rounded angles not exceeding 80 mm in girth and finished even and smoothing cement mortar 1:6 (1cement:6 sand) in all leads and lifts.
15 mm thick cement plaster in single coat on rough side of brick/concrete/stone walls for interior plastering upto floor two level brick/concrete/stone walls for interior plastering upto floor two levels including arrises internal rounded angles chamfers and or rounded angles not exceeding 80 mm in girth and finished even and smoothing cement mortar 1:3 (1cement:3 sand) in all leads and lifts.
20 mm thick cement plaster in single coat on rough side of brick/stone/concrete walls for interior plastering up to floor two level including arrisses,internal rounded angles,chamfers and or rounded angles not exceeding 80 mm in girth and finished even and smooth with in all leads and lifts in C.M 1:6 ( 1 cement : 6 sand ) in all leads and lifts.
Providing & fixing M.S. grills of required pattern in wooden frame of window etc.with M.S. flats, square or round barswith round headedbolts and nuts by screws plain grills in all leads and lifts.
Providing and fixing wire gauge shutters using galvanised M.S. wire gauge of IS gauge specification 8 S.G with wire of dia 0.56 mm for doors,windows i/c bright finished black enamelled iron butt hinges with necessary screws 30 mm thick of 2nd class deodar wood with in all leads and lifts complete in all respect.
Cement concrete flooring 1:2:4 (1 cement : 2 sand : 4 crushed stone aggregate 20 mm nominal size) laid in one layer finished with a floating coat of neat cement 40 mm thick in all leads and lifts.
White glazed tiles 6 mm thick in flooring cement mortar 1:3 (1cement : 3 sand) finished with flush pointing in white cement in all leads and lifts.
White glazed tiles 6 mm thick in skirting risers of steps and dado 12 mm thick cement mortar 1 :3 ( 1 cement : 3 sand ) and jointed with cement slurry in all leads and lifts.
Providing plinth protection 50 mm thick in cement concrete 1:3:6 (1cement : 3 sand : 6 crushed stone aggregate 20 mm nominal size) in all leads and lifts.
Constructing coursed rubble hammer dressed "U" shape open surface drain with side wall 15 X 22 cm in cementy mortar 1:6 ( 1 cement, 6 sand ) and inside plastering with cement mortar 1:3 ( 1 cement, 3 sand ) i/c earth work and laying 10 cms cement concrete in 1:5;10 ( 1 cement,5 sand,10 graded stone aggregate 40 mm nominal size ) and 7.5 cms cement concrete 1:2:4 ( 1 cement,2 sand,4 graded stone aggregate 20 mm nominal size ) and finished with a floating coat of neat cement complete as per standard design with in all leads and lifts complete in all respect.
White washing with lime on undecorated wall surfaces two coats to give an even shade including thoroughly brooming the surface to remove all dirt,dust and other foreign matters in all leads and lifts.
Distempering with dry distemper of approved brand and manufacture (two coats)and of required shade on un-decorated wall surface to give an even shade sand papered smooth in all leads and lifts.
Finishing wall with water proofing cement paint of approved brand and manufacture (two coats) brushing to give an even shade I/c cleaning of oil,dirt,dust and other foreign matters,sand papering and knotting etc. with in all leads and lifts complete in all respect in all leads and lifts.
Providing 40x3 mm flat iron hold fast 40cm. Long including fixing to frame with 10mm diameter bolts & nuts and wooden plugs and embeding in cement concrete block 30x10x15cm. 1:3:6 ( 1 cement : 3 sand: 6 graded stone aggregate 20mm nominal size) in all leads and lifts.
Providing and Fixing anodized MS sliding door bolts with bolts and nuts screws etc.complete. 300 x 16 mm in all leads and lifts.
Providing and Fixing anodized MS tower bolts(barrel type)with screws etc.complete in all leads and lifts. 250X10 mm .
Providing and Fixing anodized MS handles with necessary screws etc. complete in all leads and lifts.125 mm
Applying priming coat on new wood and wood based surfaces after and including preparing the surface by thoroughly cleaning oil,grease,dirt and other foreign matters,sand papering and knotting.Ready mixed paint brushing wood primer pink in all leads and lifts.
Painting two coats (excluding priming coat)on new wood and wood based surfaces with enamel paint to give an even shade including cleaning the surface of dirt,dust and other foreign matters sand papering and stopping with enamel paint other than white in all leads and lifts.
Precast terrazzo tiles hydraulic compressed 20 mm thick with marble chips of specified size in flooring cement mortar 1:6 (1cement : 6 sand) jointed with neat cement slurry. (Dark shade) in all leads and lifts.
Providing and Fixing of Steel / fibre reinforcement concrete (SFRC) manhole cover with frame conforming to IS-12592 (Part - I)-1998 with latest ammendments 560 mm dia medium duty in all leads and lifts.
Providing and Fixing of Steel / fibre reinforcement concrete (SFRC) manhole cover with frame conforming to IS-12592 (Part - I)-1998 with latest ammendments 560 mm dia heavy duty in all leads and lifts.
Supplying and fixing of cast iron manhole cover with frame 455 x 610 mm rectangular C.I. cover (light duty) single seal pattern the weight of cover 116 Kg. and weight of frame 15 Kg. The total weight of cover and frame to be not less than 38 Kg. compelete in all leads and lifts.
Supplying and fixing of cast iron manhole cover with frame 455 x 610 mm rectangular C.I. cover (light duty) single seal pattern the weight of cover 23 Kg. and weight of frame 15 Kg. The total weight of cover and frame to be not less than 38 Kg. compelete in all leads and lifts.
Providing and Fixing cast iron rungs 200 mm wide with chequered of ribbed non slip surface including Fixing in manhole with 200x200x100 mm cement concrete 1:3:6 (1 cement:3 sand:6 graded stone aggregate 20mm nominal size) in all leads and lifts.
Fixing of G.I. pipe dia mentioned below for inlet, outlet and scour pipe etc in all leads and lifts. 150 mm diameter
125 mm diameter
100 mm diameter
80 mm diameter
65 mm diameter
50 mm diameter
Providing and Fixing Cast Iron Stand Post Type Fire Hydrant One outlet as per IS:908:1975 Fig. IA complete 80 mm diameter including sluice valve, duck foot bend. Flange Riser, stand post column, chain, nut bolt and rubber packing etc.in all leads and lifts.(Kiloskar/Leader/Bir/Kartar make)
Providing and Fixing Cast Iron Sluice Valve of BIR make BIS No. 14846 with flange Table - 5 including welding of flanges, Nuts & Bolts and Gasket etc.The sluice valve conforming to IS - 780. The dia of valve as mentioned below complete in all leads and lifts and to the entire satisfaction of the Engineer - in - Charge. 150 MM Diameter Table - 5
125 MM Diameter Table - 5
100 MM Diameter Table - 5
80 MM Diameter Table - 5
65 MM Diameter Table - 5
50 MM Diameter Table - 5
Steel work welded in built up sections, trusses and framed work including cutting, hoisting, fixing in position and applying a priming coat of red lead paint:- in gratting, framed guard bar, ladders, railing brackets and similar works in all leads and lifts.
Providing and Fixing wire gauge using galvanised M.S. wire gauge of I.S. gauge designation 85 G. with wire of dia 0.56 mm for Ventilator of tank complete in all respect in all leads and lifts.
Providing and fixing Aluminium ladder 4.00 m length capable to carry minimum 200 kg load, for lowering/cleaning & inspection of storage tanks in all lead and lifts to the entire satisfaction of Engineer-in-Charge.
Providing and Fixing of MS Fabricated Protection Panel 750 mm x 750 mm made with MS Angle 40 x 40 x 4 mm for frame, MS Angle 30 x 30 x 3 mm for cover, MS Flat 25 x 5 mm for Fixing of sliding door bolt and MS Sheet 4.00 mm thick for protection of manhole covers of storage tanks including the cost of cutting and welding of MS angle, MS Flat & MS Sheet, embedding in RCC Slab by drilling holes in MS angle & in RCC slab, provision for providing and Fixing sliding door bolt 300 x 16 mm, MS Handle 100 mm, Lock and applying a coat of red lead paint & painting two coat with steel paint (Firoza Blue) complete job in all respect in all leads and lifts and to the entire satisfaction of the Engineer - in - Charge.
1.20 metre heigh fencing (as per approved design) 1.80 metres R.C.C.posts 3 metres centre to centre and R.C.C. struts with 7 horizental lines and two diagonals of galvanised steel bar bed wire (IS 278-1962 type I) weighing 9.38 kg./100 metres (minimum) strained and fixed to posts by typing to 6mm galvanised steel bar niles/clips with G.I. binding wire including cost of Excavation, R.C.C. Posts,R.C.C. struts and straining belts and embeded in cement concrete 1:4:8 ( 1cement : 4 sand : 8 graded stone aggregate 40 mm nominal size) and curing complete in all respect with manufacturing & Fixing of MS Gate 1.20X1.50 Meter and to the entire satisfaction of the Engineer-in-Charge.
Providing and fixing automatic flushing cistern with a pair of CI or MS bracket complete with fitting including CI Syphonic apprature masquits proof lid, CP brass unions and coupling for connecting with inlet outlet and over flow pipes including cutting holes and making good the same Over flow pipe to be measured and paid for seperately (Viterous china 5 liters capacity in all leads and lifts.
Providing and fixing vitreous china wash down water closet (Indian Type, W.C pan) with integral P or S trap including jointing the trap with soil pipe in cement mortar 1 : 1 ( 1 cement 1 sand) ( Seat and cover to be measured and paid for separately) (White colour) in all leads and lifts.
Providing and fixing 100 mm size P or S trap for water closet ( Squatting Pan) including jointing the trap with the pan and soil pipe in cement mortar 1:1 ( 1cement : 1 sand) Sand cast iron in all leads and lifts.
Providing & fixing viterious china wash basin with single hole for pillar tap with CI or MS bracket painted white including cutting hole including good the same excluding fitting Cera sanitary work (cornet) white 550x400 white in all leads and lifts.
Providing and fixing viterious china padestral for wash basin complete recessed at the basic for reception of pipe and fittings Cera sanitary work (carnet) white (Viterious China in White Colour) in all leads and lifts.
Providing and Fixing of water storage tank sintex having of capacity 500 liters with necessary fittings including over flow pipes, scour pipes etc. inlet and outlet and inside paint of required size for inlet or outlet and inside paint of approved quality complete including hoisting complete in all respects in all leads and lifts.
Providing and fixing on wall face PVC (D - Plast) rain water pipes of working pressure not less 4.5 Kg/Sqcm including fitting the joints with approved adhesive complete with in all leads , lifts and carriage of materials.110 mm nominal bore in all leads and lifts.
Providing and fixing on wall faces PVC door bend (D-Plast) with oval access door, insertion rubber washer 3 mm thick bolts and nuts ISI marked complete including fixing with approved adhesive complete.75 mm nominal bore in all leads and lifts.
Providing and fixing to wall ceiling and floor galvanised mild steel tubes (Medium grade) tube fittings and clamp including making good the wall ceiling and floor in all leads and lifts.) 15 mm nominal bore in all leads and lifts.
Providing and fixing full way wheel valve 15 mm dia Gun metal in all leads and lifts.
Providing and fixing cast iron spun soil waste and ventilating pipe lead caulked joint to be measured and paid for separately 100mm dia with C.I cowl 100 mm dia nominal size in all leads and lifts.
Providing and fixing brass bib tap (superior qualityor heavy type) 15 mm dia in all leads and lifts.
Providing & Fixing CP Brass Soap Dish with CP breckets fixed to wodden plugs with CP brass screws complete in all respect in all leads and lifts.
Wiring for light point / fan point / exhaust fan / call bell point with 1.5 Sq. mm. PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in PVC casing & capping and earthing the light point with 1.5 Sq.mm. HRFRLS/PVC insulated single core copper conductor cable as required Group C.
Wiring for circuit / sub-main with following size PVC insulated heat resistant flame retardant (HRFR) and low smoke single core (flexible) copper conductor cable in PVC casing & capping along with 1 No.HRFRLS/PVC insulated single core copper conductor cable of same size for earthing as required. 2 x 1.50 Sq. mm.
2 x 4.00 Sq. mm.
Supplying and fixing 3 pin 5/6 amps. Socket outlet on the exists switch box/covers including connections etc. as required.
Supplying and fixing 2 way 5/6 amps. Tumbler/piano type switch on the existing switch box on the switch box/cover including connections etc. as required.
Supplying and fixing 3 pin 15/16 amps. Socket outlet on the exists switch box/covers including connections etc. as required.
Supplying and fixing 15/16 amps. Tumbler/piano type switch on the existing switch box on the switch box/cover including connections etc. as required.
Supplying and fixing wooden box of following size (nominal) on surface or recess with suitable size of phenolic laminated sheet cover of in front as required. 229 mm.x 102 mm.x 60 mm. deep
203 mm.x152 mm.x 60 mm. deep
Supplying and fixing ceiling rose on existing junction box/ wooden block including connections etc. as required.
Supplying and fixing plain pandent with 16/20 mm twin twisted, flexible PVC insulated copper cable and backelite pendant holder including connections, etc. as required.
Supplying and Fixing 5 Amps to 32 Amps rating, 240 Volts, L series miniature circuit breaker of following poles in the existing MCBDB complete with connections, testing and commissioning etc. as required Cat - A. (Single Pole)
Supplying and Fixing of following way, single pole and neutral, sheet steel, MCB distribution board, 240 Volts on surface/ recess, complete with tinned copper busbar, netural link, earthbar, dibnbar, detachable gland plates, inter connections, i/c painting, earthing etc. as required busbar 8 way.
Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. (63 amp. CAT - A)
Providing, installing, testing and commissioning of ceiling fan and regulator i/c wiring the down rod of standard length (upto 30 Cm with 1.5 Sqmm PVC insulated copper conductor signle core cable etc. as required.Ceiling fan 1400 mm sweep category A
Providing and fixing ultra slim decorative extruded box fixture with domestic electronic ballast, snap-on installers, suitable for 28 watt FTL (T5), complete with all accessories (including one No. T-5 Tube), connections, testing and commissioning etc. as required 1 x28 watt-FTL (T5) (Category-A)
Providing and Fixing LED Flood Light watt mentioned below (OREVA make) complete in all respect in all leads and lifts.
Providing and fixing two core service wire 6 Sqmm thick in all leads and lifts.
Providing, laying, fixing, jointing and testing in trenches MS pipe of following dia meters confirming to confirming to BIS 3183-2007, of following grade and having wall thickness as specified below with plain end and capable of withstanding required test pressure in random length of 4 to 7 meters, including specials, short pieces, bends, reducers, tees etc. made from parent tube, providing and welding of MS flanges detailed as below. The MS flanges shall confirm to BIS 6392-1971 (with latest up to date amendments) duly welded in two layers (two inner and two outer) with pipes at both ends as per relevant BIS standards along with nuts and bolts of required sizes, 3mm thick compressed asbestos fiber/synthetic rubber gaskets confirming to relevant BIS standards. The laying of pipe will include all operation such as cutting, welding, jointing, providing & fixing of MS flanges, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipes shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards and the damaged portion of the pipes and specials made form the parent tube shall be provided anticorrosive treatment by applying two coats of anticorrosive bituminous paint over a priming coat as per AWWA specifications C-203-1978. The welding electrodes shall be as per IS 814 of Advani Oerlikon / L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & directin of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately). Phase Ist :- First Stage :- 150 mm dia -MS -Pipe 5.60 mm thickness with F.T-34 (Grade-X-42) or L290
150 mm dia -MS -Pipe 4.80 mm thickness with F.T-34 (Grade-X-42) or L 290
150 mm dia -MS -Pipe 4.40 mm thickness with F.T-34 (Grade-X-42 ) or L 290
150 mm dia -MS -Pipe 4.00 mm thickness with F.T-28 (Grade-X-42) or L 290
Phase 2nd :- First Stage :- 125 mm dia -MS -Pipe 4.80 mm thickness with F.T-34 (Grade-X-42) or L 290
125 mm dia -MS -Pipe 4.00 mm thickness with F.T-28 (Grade-X-42) or L 290
Phase 3rd :- First Stage :- 150 mm dia -MS -Pipe 4.00 mm thickness with F.T-28 (Grade-X-42) or L 290
Phase 4th :- First Stage :- 125 mm dia -MS -Pipe 5.60 mm thickness with F.T-28 (Grade-X-42) or L 290
First Stage :-125 mm dia -MS -Pipe 4.00 mm thickness with F.T-28 (Grade-X-42) or L 290
Phase 6th :- 100 mm dia -MS -Pipe 4.00 mm thickness with F.T-28 (Grade-X-42) or L 290
Providing, laying, jointing (by way of circumfrential butt welded joints by electrical arc welding ) and testing of MS pipe of following dia meters confirming to BIS 3183-2007, steel grade specified below (latest with upto date amendments) having wall thickness as specified below with bevelled ends and capable of withstanding required test pressure in a random length of 4 to 7 meters, including manufacturing reducers/ tapers , all short pieces, beds etc. as per site requirement made from parent tubes . The laying of pipe will include all operation such as cutting, welding, jointing, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in charge. The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipes shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards. The welding electrodes shall be as per IS 814 of Advani Oerlikon/ L&T or ISI marked make. The rates also includes entire carriage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in charge with in all leads and lifts. (Earth work in trenches will be measured and paid for separately).Phase Ist :- First Stage :- 150 mm dia -MS -Pipe 5.60 mm thickness (Grade-X-42) or L290
150 mm dia -MS -Pipe 4.80 mm thickness (Grade-X-42) or L 290
150 mm dia -MS -Pipe 4.40 mm thickness (Grade-X-42) or L 290
150 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42) or L 290
Gravity Main Syphon Portion (i) :- 100 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42) or L 290
Phase 2nd :-First Stage :-125 mm dia -MS -Pipe 4.80 mm thickness (Grade-X-42)
125 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42)
Phase 3rd :-First Stage :-150 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42)
Phase 4th :-First Stage :-125 mm dia -MS -Pipe 5.60 mm thickness (Grade-X-42)
125 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42)
Phase 6th :- First Stage :- 100 mm dia -MS -Pipe 4.00 mm thickness (Grade-X-42)
Providing, laying, jointiong and testing in trenches GMS pipe of following dia meters confirming to BIS: 1239 (Part-i),of following grade having wall thickness as specified below with plain end and capable of with standing required test pressure in random length of 4 to 7 meters, including special, short pieces , beds reducers, tees etc. made from parent tube providing and welding of MS flanges detailed as below. The MS flanges shall confirm to BIS 6392 - 1971 (with latest up to date amendments) duly welded in two layers (two inner and two outer) with pipes at both ends as per relevant BIS standards along with nuts and bolts of required sizes, 3 mm thick compressed asbestos fiber/synthetic rubber gaskets confirming to relevant BIS standards. The laying of pipe will include all operation such as cutting, welding, jointing , providing and fixing of MS flanges, fabrication of bends, tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in Charge . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipe shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards. The welding electrodes shall be as per IS 814 of Advani Oerlikon/L&T or ISI marked make. The rates also includes entire carrage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in Charge with in all leads and lifts (Earth work in trenches will be measured and paid for separately) Phase Ist :- Raw Water Stage :- 150 mm dia -GMS Pipe 4.80 mm thickness with FT-5 (Medium Class)
First Stage :- 150 mm dia -GMS Pipe 5.40 mm thickness with FT-28 (Heavy Class)
150 mm dia -GMS Pipe 4.80 mm thickness with FT-28 (Medium Class)
150 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
Phase 2nd :- Raw Water Stage :-125 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
First Stage :- 125 mm dia -GMS Pipe 4.80 mm thickness with FT-28 (Medium Class)
125 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
Phase 3rd :- Raw Water Stage :-150 mm dia -GMS Pipe 4.80 mm thickness with FT-5 (Medium Class)
First Stage :- 150 mm dia -GMS Pipe 4.80 mm thickness with FT-28 (Medium Class)
150 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
150 mm dia -GMS Pipe 4.80 mm thickness with FT-5 (Medium Class)
Phase 4th :- Raw Water Stage :-125 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
First Stage :-125 mm dia -GMS Pipe 4.80 mm thickness with FT-28 (Heavy Class)
125 mm dia -GMS Pipe 4.80 mm thickness with FT-28 (Medium Class)
125 mm dia -GMS Pipe 4.80 mm thickness with FT-17 (Medium Class)
125 mm dia -GMS Pipe 4.80 mm thickness with FT-5 (Medium Class)
Phase 5th :- Raw Water Stage :-100 mm dia -GMS Pipe 4.50 mm thickness with FT-17 (Medium Class)
First Stage :- 100 mm dia -GMS Pipe 4.50 mm thickness with FT-28 (Medium Class)
100 mm dia -GMS Pipe 4.50 mm thickness with FT-17 (Medium Class)
100 mm dia -GMS Pipe 4.50 mm thickness with FT-5 (Medium Class)
Phase 6th :- Raw Water Stage :- 100 mm dia -GMS Pipe 4.50 mm thickness with FT-17 (Medium Class)
First Stage :- 100 mm dia -GMS Pipe 4.50 mm thickness with FT-28 (Medium Class)
100 mm dia -GMS Pipe 4.50 mm thickness with FT-17 (Medium Class)
100 mm dia -GMS Pipe 4.50 mm thickness with FT-5 (Medium Class)
Providing, laying, jointiong and testing (by way of circumfrential butt welded joints by electrical arc welding) and testing of GMS pipe of following dia meters confirming to BIS: 1239 (Part-i) grade specified below (latest withup to date amendments ) having wall thickness as specified below with bevelled ends and capable of with standing required test pressure in random length of 4 to 7 meters, including manufacturing reducers tapers , all short pieces, beds etc. as per site requirement made from parent tubes. The laying of pipe will include all operation such as cutting, welding , jointing , fabrication of bends , tees etc. including lowering and laying in excavated trenches to ensure required level including flushing, cleaning and hydraulic testing complete in all respects to the satisfaction of the Engineer in Charge . The fabricated bends shall have three or four cuts having its radius not less than five times the dia of pipe. The pipe shall be factory galvanized (zinc coating both inside and outside) as per relevant IS standards. The welding electrodes shall be as per IS 814 of Advani Oerlikon/L&T or ISI marked make. The rates also includes entire carrage of material, flushing, cleaning & hydraulic testing complete to the best satisfaction & direction of Engineer in Charge with in all leads and lifts (Earth work in trenches will be measured and paid for separately)Phase Ist :- Raw Water Stage :- 150 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
First Stage :-150 mm dia -GMS Pipe 5.40 mm thickness (Heavy Class)
150 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
Gravity Main Syphon Portion (i) :-100 mm dia -GMS Pipe 5.40 mm thickness (Heavy Class)
100 mm dia -GMS Pipe 4.50 mm thickness (Medium Class)
Gravity Main Syphon Portion (ii) :- 80 mm dia -GMS Pipe 4.80 mm thickness (Heavy Class)
80 mm dia -GMS Pipe 4.00 mm thickness (Medium Class)
Phase 2nd :- Raw Water Stage :- 125 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
First Stage :- 125 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
Phase 3rd :-Raw Water Stage :- 150 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
First Stage :- 150 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
Phase 4th :-Raw Water Stage :- 125 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
First Stage :-125 mm dia -GMS Pipe 5.40 mm thickness (Heavy Class)
125 mm dia -GMS Pipe 4.80 mm thickness (Medium Class)
Phase 5th :- Raw Water Stage :- 100 mm dia -GMS Pipe 4.50 mm thickness (Medium Class)
First Stage :-100 mm dia -GMS Pipe 4.50 mm thickness (Medium Class)
Phase 6th Raw Water Stage :- 100 mm dia -GMS Pipe 4.50 mm thickness (Medium Class)
First Stage :-100 mm dia -GMS Pipe 4.50 mm thickness (Medium Class)
Pumping Machinery Phase Ist :- (Submersible Pump set) Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama or any approved make of Jal Shakti Vibhag conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date ammendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :- Discharge(Q) 13.62 LPS for each pump Total Dynamic heads:- 28.74 Meter (a)LWL in sump well(h) 716.00 Meter (b) Shaft Level 715.00 Meter (c) Level at Discharge point 740.00 Meter (d)Suction Lift '+ve (e) Discharge Head 24.00 Meter (f) Static head 24.00 Meter Rising Main (a) Length 45 Meter (b) Dia 150 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM (a) Temperature 25 degree centigrade Discharge(Q) 13.62 LPS for each pump Total Dynamic heads:- 28.74 Meter a) LWL in sump well(h) 715.00 Meter b) Shaft Level 716.00 Meter c) Level at Discharge point 740.00 Meter d) Suction Lift +ve e) Discharge Head 24.00 Meter f) Static head 24.00 Meter Rising Main a) Length 45 Meter b) Dia 150 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 10.00 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved make of Jal Shakti vibhag and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amnmendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved make by Jal Shakti vibhag of required class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses make and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Foursesor any approved make by Jal Shakti vibhag of required class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the systematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe. a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe. a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor) (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Set) Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any approved make by Jal Shakti vibhag conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :- Discharge(Q) 13.62 LPS for each pump Total Dynamic heads:- 561.18 Meter a) LWL in sump well(h) 739.00 Meter b) Shaft Level 738.00 Meter c) Level at Discharge point 1280.00 Meter d) Suction Lift +ve e) Discharge Head 542.00 Meter f) Static head 542.00 Meter Rising Main a) Length 2100 Meter b) Dia 150 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 200.00 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any JSV approved make.
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved make by Jal Shakti vibhag and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Foursesor any approved make by Jal Shakti vibhag of required class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved make by Jal Shakti vibhag of required class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any approved make by Jal Shakti vibhag of required class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY or any approved make by Jal Shakti vibhag including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Pumping Machinery Phase 2nd :-(Submersible Pump set) Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama or any approved make by Jal Shakti vibhag conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date ammendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :- Discharge(Q) 7.55 LPS for each pump Total Dynamic heads:- 85.30 Meter a) LWL in sump well(h) 685.00 Meter b) Shaft Level 684.00 Meter c) Level at Discharge point 765.00 Meter d) Suction Lift +ve e) Discharge Head 80.00 Meter f) Static head 80.00 Meter . Rising Main a) Length 150 Meter b) Dia 125 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade.
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Paneof suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 15.00 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec
Energy Saving Variable Frequency Starter of suitable capacity or any approved make (Heavy Duty) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved JSV make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any approved JSV make of suitable class rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Set) Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any approved JSV make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :- Discharge(Q) 7.55 LPS for each pump Total Dynamic heads:- 400.76 Meter a) LWL in sump well(h) 763.00 Meter b) Shaft Level 762.00 Meter c) Level at Discharge point 1150.00 Meter d) Suction Lift +ve e) Discharge Head 388.00 Meter f)Static head 388.00 Meter Rising Main a) Length 1600 Meter b) Dia 125 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade .
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any approved JSV make.
Energy Saving Variable Frequency Starter of suitable capacity ( Heavy Duty) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved JSV make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any approved JSV make suitable class make for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Pumping Machinery Phase 3rd :- (Submersible Pump set) Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama or any approved JSV make conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date ammendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :- Discharge(Q) 14.55 LPS for each pump Total Dynamic heads:- 28.97 Meter a) LWL in sump well(h) 716.00 Meter b) Shaft Level 715.00 Meter c)Discharge point 740.00 Meter d) Suction Lift +ve e) Discharge Head 24 Meter f) Static head = 24 Meter Rising Main a) Length 60 Meter b) Dia 150 Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 10.00 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec of or any approved JSVmake
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved JSV make suitable class make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make of suitable class make and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any approved JSV make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any approved jsv make suitable class make for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under: a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Set) Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any JSV approved make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :-Discharge(Q) 14.55 LPS for each pump Total Dynamic heads:- 284.91 Meter a) LWL in sump well(h) 738.00 Meter b)Shaft Level 737.00 Meter c)Level at Discharge point 1010.00 Meter d) Suction Lift '+ve e) Discharge Head 273.00 Meter f) Static head 273.00 Meter Rising Main a) Length 1050 Meter b) Dia 150 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Paneof suitable capacityl for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each of the rating 100.00 HP . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any JSV approved make
Energy Saving Variable Frequency Starter of suitable capacity (Heavy Duty) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any JSV approved make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve, of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class, of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class make for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Pumping Machinery Phase 4th :- (Submersible Pump set)Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama or any JSV approved make conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date ammendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date amendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :-Discharge(Q) 7.98 LPS for each pump Total Dynamic heads:- 64.79 Meter a)LWL in sump well(h) 700.00 Meter b)Shaft Level 699.00 Meter c) Level at Discharge point 760.00 Meter d) Suction Lift '+ve e)Discharge Head 60.00 Meter f)Static head 60.00Rising Main a)Length 60 Meter b)Dia 125 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec.
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any JSV approved make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class make for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date amendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date amendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Set) Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any JSV approved make of suitable class make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :-Discharge(Q) 7.98 LPS for each pump Total Dynamic heads:- 370.00 Meter a) LWL in sump well(h) 758.00 Meter b) Shaft Level 757.00 Meter c) Level at Discharge point 1100.00 Meter d) Suction Lift '+ve e) Discharge Head 343.00 Meter f) Static head 343.00 Meter Rising Main a) Length 3500 Meter b) Dia 125 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any JSV approved make .
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date amendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any JSV approved make of suitable class and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any jsv approved make of suitable class make and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class make for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date amendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date amendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Pumping Machinery Phase 5th :-(Submersible Pump set)Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama or any JSV approved make of suitable class conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date amendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :-Discharge(Q) 6.23 LPS for each pump Total Dynamic heads:- 65.38 Meter a) LWL in sump well(h) 700.00 Meter b) Shaft Level 699.00 Meter c) Level at Discharge point 760.00 Meter d) Suction Lift '+ve e) Discharge Head 60.00 Meter f) Static head 60.00 Meter Rising Main a)Length 60 Meter b) Dia 100 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any JSV approved make.
Energy Saving Variable Frequency Starter of suitable capacity ( Heavy Duty ) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any JSV approved make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amnmendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date ammendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date ammendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Set)Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any JSV approved make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :-Discharge(Q) 6.23 LPS for each pump Total Dynamic heads:-267.25 Meter a) LWL in sump well(h) 758.00 Meter b) Shaft Level 757.00 Meter c) Level at Discharge point 1000.00 Meter d) Suction Lift '+ve e) Discharge Head 243.00 Meter f) Static head 243.00 Meter Rising Main a)Length 1600 Meter b) Dia 100 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a) Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec
Energy Saving Variable Frequency Starter of suitable capacity Heavy Duty for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date amendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any approved JSV make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date amendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date amendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Pumping Machinery Phase 6th :-(Submersible Pump set)Supply of submersible pumping set of KSB / Kirloskar / Sabar / Johnston / Crompton / Kalama make conforming to BIS:5659-1970 or latest suitable for lifting Water (latest with upto date ammendments) fitted with bronze impellers/suitable alloye. The pump should be fitted with free flow impellers of bronze/suitable alloys directly coupled to squirrell case electric induction motor of same make as (manufacturer standard) conforming to BIS: 9283-1979 (latest with upto date ammendments) and totally water proof for submersible duty, isolated from the pump by intermediate casing with double mechanical seal in oil chamber, grease packed lubricated bearing & provided with stainless steel thrust bearing plate to with stand vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor including water level guard errection clamps, manufacturer cable clips & depth gauge etc. The pump shall be suitable for operation on data given as below :-Discharge(Q) 5.29 LPS for each pump Total Dynamic heads:- 65.02 Meter a) LWL in sump well(h) 685.00 Meter b) Shaft Level 684.00 Meter c) Level at Discharge point 745.00 Meter d) Suction Lift '+ve e) Discharge Head 60.00 Meter f) Static head 60.00 Meter Rising Main a) Length 60 Meter b)Dia 100 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a)Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for submersible pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec or any JSV approved make.
Energy Saving Variable Frequency Starter of suitable capacity (Heavy Duty) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date ammendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T.
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amnmendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date amendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date amendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5 M/second in the suction pipe.
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor.(a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
(Centrifugal Pump Setn)Supply of horizontal spindle horizontal radial split casing / and suctions (back pull out arrangement) Single / double / multistage centrifugal pumps or combination of pumps in series / parellel of KSB / Mathur & Platt / Jyoti / Kirloskar / BE / Maxflow / Beaconweir Sabar or any JSV approved make conforming to BIS 5659-1970) pump (Latest with upto to date amendments, read with BIS: 9137-1978 (latest edition) suitable for lifting water of under mentioned characteristics with bronze / Suitable alloy, priming funnels, casing ring and shaft motor of bronze, shaft of steel grade ASA-410 with cast iron casing coupled directly through a flexible coupling on a common MS/Cast steel plate (base plate from the principal manufacturer of pumping set) to coupling sliperring squirrel cage screen ptotected drip proof electic induction motor/motor of standard make such as Kirloskar / NGEF / Cromption / Siemen / Jyoti / BHEL / GEC / ABB conforming to BIS 325-1978) read as BIS 900- 1972 and IS:12615:2011 with minimum IE-2 specifications or higher efficiency (latest upto date amendments) it should include the cost of bearings, nuts & bolts, painting etc. and shall be and suitable for operation on the data given as below :-Discharge(Q) 5.29 LPS for each pump Total Dynamic heads:- 376.44 Meter a) LWL in sump well(h) 743.00 Meter b) Shaft Level 742.00 Meter c) Level at Discharge point 1100.00 Meter d) Suction Lift '+ve e) Discharge Head 358.00 Meter f) Static Head 358.00 Meter Rising Main a) Length 1600 Meter b)Dia 100 mm Pumping Hours 16 Hours Altitude of installation above MSL 700 Meter Characterstics of water Clear Water with turbidity up to 50 PPM a)Temperature 25 degree centigrade
Supply, Installation, Testing and Commissioning of Energy Saving Variable Frequency Starter Panel of suitable capacity for centrifugal pump made out of 16 Gauge sheet, powder coated dust and vermin proof, wall/base mounted and front opening door type with copper insulated wiring suitable to operate 2 Nos. pumps (1 working & 1 stand by) each . Starter should be capable enough to handle the following faults like short circuit, over current, under current, over voltage, under voltage, dry run protection and phase loss with LED ON/OFF & TRIP indicators, Power Quality Monitoring & Controlling Relay at the Incomer Feeder, Should be fitted with Surge Suppressor Device suiatble to protect against class-1 & 2 surges. Make: Aarmation Electric Private Limited/Tricolite/ELLES/Adlec
Energy Saving Variable Frequency Starter of suitable capacity (Heavy Duty ) for smooth start and smooth stop of pumps and for the energy conservation in the system. It Should be capable to monitor & control the frequecy of pumps through out the operation and to maintain the power factor of the system within acceptable limits. It should be able to withstand ambient temperature upto 50 Degrees celcius without derating and have conformal coating class 3C2, so that it can work in any harsh environment like moisture etc. Make: JSV Approved
Multi function meter indicating different parameters like Current, Voltage, KWH, PF, THD etc. with RS 485 communication. Make:- L&T/Conserve/Schnieder or any JSV approved make.
Main incomer MCCB of suitable capacity of L&T / Schnieder/ABB/Siemens make on the coming feeder for pumping set confirming to BIS 2516-1985 ( Latest edition).
LED Three phase indicating lamps complete with logged switches for individual motors conforming to BIS 3452 ( Part I & II ) latest with upto date amendments.
LED On / Off & Trip indicator and push buttons, Control and power wiring,Power capacitor,Cooling fan 230 VAC, Contorl terminal, Bus Bar, i.e.Bolt, insulator, etc.
Input Choke of required HP for Energy saving variable frequency Starter which should be installed at the input of Energy saving variable frequency starter, so that there should be proper protection in case of any voltage surge and distortions.
Control Transformer.
Power and Control Wiring and Busbar.
Installation, Commissioning and Software Development.
Surge supressor device with Isolating MCCB to eliminate the power surges due to lightening and system surges.
Power quality monitoring & controlling relay with Control Contactor to safeguard the Electronic & Electric elements.
Independent Control Panel with Switch Fuse Unit and Fuses of Suitable Amperage to eliminate the KItKat fuses of HPSEB Make: Siemens/Schnieder/L&T
Providing double flanged CI sluice valve PN-1 of Leader/BHEL/ Kirlosker / GLED/Kilburn /Fourses /Kartar or any JSV approved make and equal to dia of suction pipe and capable of withstanding the normal seat pressure as per IS:780:1984 with up to date amendments)
Providing double flanged cast steel sluice valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged swing type cast steel valve of Leader/BHEL/ Kirlosker/Kilburn /GLEd/Fourses or any JSV approved make of suitable class and having bye pass arrangements of one step higher then delivery line of pump and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing double flanged cast steel reflux valves class of Leader/BHEL/ Kirlosker/Kartar/Kilburn /GLEd/Fourses or any JSV approved make of suitable class for rising main and capable of withstanding normal seat pressure as per BIS standards with upto date amendments)
Providing 100mm dia circular dial analog pressure gauge of suitable range of Fiebig /Bourden/ PREGA/precision make complete with all accessories such as stop cock, copper tubing etc.as per IS: 3624-1987 with upto date amendments.
Providing discharge meter of standard make to be fixed on the rising main in pump house as per the directions of the Engineer in charge as per Is:2373:1981 with upto date amendments.
Installation of all the items apparing as per the syatematic drawing.
Providing and fixing double flanged MS/GI piping work (Layout to be approved by the Engineer in charge) for suction and delivery pipes suitable to pump(s) offered and common header as per the R/Main respectively complete with all specials such as bends, tees, reducers. Increasers with companions flanges matching with the relevant specifications of the accessories including rubber/asbestos gasket of minimum 3mm thckness as per IS:2712:1979 and required number of nuts and bolts as per Is:1364:1983, The Pipes fittings and joints shall be as per relevant IS code & to withstand 1.5 times total head stipulated under item No.12. The size of the various components to be as under:a) Suction pipe : One dia higher then the suction of pump offered and suitable to keep the velocity of flow from 1 to 1.5M/second in the suction pipe
b) Delivery pipe: One dia higher then the delivery of the pump offered and suitable to keep the velocity of flow from 1.5 to 2M/second in the delivery pipe.
c) Common header : One dia higher then delivery of pump will extend upto 5 meters from the outer wall of the pump house in the direction to be jointed.
Providing and laying copper PVC insulated arsoured power cable (One cable carrying all the three phases) of suitable size and capacity to motors and all other electircal equipments as per IS:1554(P-I) 1988 or latest ith upto date ammendments of siemens/GLOSTER /IEC/ICC/EICO/NATIONAL/GRANDLAY make including all other accessories such as thinbles, flexible pipes,solders,nuts and bolts cable glands etc. laid in pipes or trenches under floor. (a) Motor side (From switch to starter and starter to motor)
(b) Supply side (From Meter of HPSEB to bus bar and switch)
Providing and fixing double loop earthing with copper plate 600mmx600x3mm thick electrode complete with material such thimbles nuts and charcoal and common salt, 25mmx5mm copper strips as per IS:3043:1987 with upto date ammendments for motors and other electrical equipments and digging of pits etc. complete in all respect.
Laying and jointing, testing in trenches galvanised mild steel tubes (Light Class) screwed and socketed, ISI marked, conformining to IS :1239 & latest with upto date ammendments including tube fitting such as bends, tees, air valves, unions and collars etc. as per direction and to the entire satisfaction of the Engineer-in-charge (Earth work in trenches to be measured and paid for separately) in all leads and lifts. 125 mm Diameter
100 mm Diameter
80 mm Diameter
65 mm Diameter
50 mm Diameter
40 mm Diameter
32 mm Diameter
25 mm Diameter
20 mm Diameter
15 mm Diameter
Providing and Fixing Brass Stop Cock, Wheel Valve including housing chamber complete in all leads and lifts. 80 mm Diameter
65 mm Diameter
50 mm Diameter
40 mm Diameter
32 mm Diameter
25 mm Diameter
20 mm Diameter
15 mm Diameter
Providing and Fixing Aquamet Multi Jet Class B, Inferential type, Dry Dial Water Meter with end connectors in brass as per ISS 779:1994 and conforming to ISO - 4064 class B of already installed Domestic Connection in the Town with PVC meter dirt box having ready made holes, rubber gasket with saddle and supports and union including freight charges, connection charges complete in all respect and to the entire satisfaction of the Engineer - in - Charge.
Flying Surveying along the alignment of proposed rising main, gravity main & distribution network through Urban/hilly terrain/thickly populated and congested area etc. for preparing L-Section and plan with the help of total station including designing of network with computer software and presenting design data and design results on drawings prepared on "Auto CAD" format and supplying the same through soft copy and hard copy ( six sets each zone).(Item shall only be executed with prior approval of Engineer - In - Charge.
AUTOMATION OF ENTIRE SYSTEM : The Firm / Tenderer should automate the entire project which comprises of all the phases (Phase 1, Phase 2, Phase 3, Phase 4, Phase 5, Phase 6) and it should include Percolation well, Tubewells, Centrifugal Machinery and Instrumentation products till MBR level. The plan of the whole scheme for automation is also to be prepared by the firm, the cost of which has been included in the relevant items. Provision of Main SCADA system in central control room which will control all the pumps and instrumants and access should be given to 10 Users. IOT based devices shall be installed at each tank of every stage which shall send messages through SCADA stations . This data transmission system at each tank of pump station consists of field instruments for providing digital and analog signals to data transfer module. This module will have a communication to web data transfer system module communication. The PLC station will have control station with programmable graphic process, mimics, real time and historical trending face plate and group display, alarm management and report with Laser Jet printers and required furniture. Installation of hardware along with commissioning / programming as per user requirement shall be done. The firm / contractor will provide the Bulk metering at Water Treatment Plants The automation of the entire scheme upto main storage tank shall also include the followingsa).The automation system should include Electro Magnetic Flow meters, Ultrasonic level transmitters, Water Quality Analysers like PH, Turbidity, Residual Chlorine, TDS. The automation system installed at above / aforesaid locations should be theft proof and proper ventilation arrangements be made complete in all respect to the entire satisfaction of Engineer-in Charge and also firm should include operation and maintenance of complete SCADA system and Instrumentation products for the firm / contactor shall submit complete proposal for automation and got approved from competent authority. Make : JSV Approved Makes.(Detail Given as per Data Sheet Automation)
Operation and Maintenance for 5 Years:- Operation and maintenancce of scheme from source to Tail end of the scheme in proper working condition. O & M includes the regular i.e., daily supply of designed / required quantity of potable water having water quality as per of water supply standard / protocol to the beneficiaries of the scheme up to main storage / delivery tank, from source to Pump House, Main and sector storage tanks at different locations as per plan and repair and maintenance of main lines. Gravity Lines and entire distribution system alongwith maintenance of automised system of scheme. Regular maintenance of all the facilities including cleaning, washing, oil and greasing repair, replacement of worn out / damaged part of pumping machinery. pipe line, valves and electrical, Mechanical requirements, regular cleaning of all structures like storage tanks, sumpwells, intakes, channels, collection / distribution channels / pump house etc. and the disposal of the same as per the direction of the Engineer - in - charge. It includes fixing / repairing / leakage in structure, channel, pipe line, pumping machinery etc. & proper distribution of treated water and regular testing of water samples and required stages of treatment. Keeping regular and proper record of water quantity and quality, repair and maintenance work, chemical dosing and time and hours of run of pumping machinery, removal of all akind of slips, slush, uprooting of unwanted grass, shrubs, weeds etc growing near the structure and keeping the area neat and clean to the entire satisfaction of Engineer-in-charge. Planting and maintaining plants of the flowers / trees around the Pump Houses / Storage tanks / Sump wells etc. to the entire satisfaction of Engineer -in - charge. It includes the cost of procurement of edequate and proper tools and plants, skilled & unskilled manpower, spare-parts, oil, grease, lubricants, chemicals and all kinds of regents required for water sample testing, refilling of gaseous cylinders including mechanical and head load carriage etc. and making standby arrangement all times, instruments, equipments, stationary and any other material etc. required for O & M excluding the cost of energy charges. All the operations shall be carried out as per the CPHEEO Manual of the water supply and treatment ( with latest addition (HPPWD / HPJSV specifications, HPJSV Department norms and directions issued by the Engineer - in - Charge from time to time and sound Engineering practices Phase Ist:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
Phase 2nd:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
Phase 3rd:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
Phase 4th:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
Phase 5th:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
Phase 6th:- 1st Year's O & M
2nd Year's O & M
3rd Year's O & M
4th Year's O & M
5th Year's O & M
HARJEET SINGH
Unipro Techno Infrastructure Pvt Ltd
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid