PROVN OF 11KV ELECTRIC SUPPLY TO DIV CAMP AT KIARI UNDER GE 860 EWS
2022_MES_536036_2
180085/E8
Open Tender
Electrical and Maintenance Works
Lump-sum
550 days
KIARI
Please refer tender documents
9 documents required · 9 mandatory
₹1,000
GE 860 EWS
₹2.3 L
Yes
14 Mar 2023
17 Sept 2022
3 Jan 2023
17 Sept 2022
27 Dec 2022
13 Dec 2022
17 Sept 2022 - 26 Sept 2022
Amount
NOTE: Schedule ‘A’ Part - I, II(Sec-1), III(Sec-1), IV(Sec-1), V, VI and VII are Prepriced by MES. Bidders shall insert their lumpsum amount in the Green coloured field under Col- 6 only.
Total amount of Sch 'A' Part - I (BUILDINGS)
Total amount of Sch 'A' Part - II (SEC-1) (INTERNAL ELECTRIFICATION)
Total amount of Sch ‘A’ Part - III (SEC-1) ( EXTERNAL ELECTRIFICATION)
Total amount of Sch ‘A’ Part - IV (Sec-1) (SEWAGE DISPOSAL)
Total amount of Sch ‘A’ Part - V (ROAD, PATH AND CULVERT)
Total amount of Sch 'A' Part-VI (SITE CLEARANCE)
Total amount of Sch 'A' Part-VII (INTERNAL WATER SUPPLY)
SCHEDULE 'A' Part - II (SEC- 2) (INTERNAL ELECTRIFICATION) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
Supply and fixing LED Bulb 12 Watt, 6500K complete all as specifeid and directed by Engr-in-Charge. Make: Philips/ Crompton/ Havells.
Supply and fixing new energy saving LED Street light with glass diffuserr, elegant design with lens optics for uniform light distribution. Rated IP66, 70 watt with protection and impact resistance of IK07 as reqd to be mounting wall/floor bracket hook type with and including 1.5 mtr long GI pipe 40 mm dia Med grade, 90 degree bends MS hook and stay or gay complete all as specifeid and directed by Engr-in-Charge.
SCHEDULE 'A' Part - III (SEC- 2) (EXTERNAL ELECTRIFICATION) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
M&L for precast PCC cable route indicator of size 15 cm x 15 cm x 75 cm (L x B x H) with projection of 45cm above ground level and 30cm grouted in PCC foundation (1:2:4) of size (25 cm x 25 cm x 30 cm), PCC shall be painted with brown colour above ground and HT 11000 Volts/ LT 1100 Volts marked in red colour complete all as specifeid and directed by Engr-in-Charge.
Supply, installing, testing , connecting and commissioning of distribution transformer outdoor type step down 11/0.433 KV (at no load) with HT 3 phase and LT 3 phase 4 wire AC , 50Hz, 500KVA copper wound with off load tap changing arrangement on HT side for a variation of secondary voltage +/- 7.5% in steps of +/- 2.5% including suitable cable entry boxes on LT side and HT bushing on primary side complete in all respects with standard accessories and fitments confirming to IS 1180 (Revised 2014) and test ECBC as specified and directed including the following :- Make: (i) JK Transformer & Switch Gear, Jammu (ii) Rajasthan Transformer (iii) Oriental transformer, Jammu (iv) Continental Transformer, Jammu (a) Earthing terminal and rating diagram plate. (b) Air release device (c) Oil Filling inlet pipe with plug. (d) Drain outlet pipe with brass gate valve with dummy plug (e) Conservator with level gauge. (f) Silica gel with breather
(g) First oil fill up to the recommended level by the manufacturer with new oil confirming to IS 335. (h) Type of connector - Star/Delta (j) Type of Cooling - ONAN (k) Vector Group- DYN 11 (l) Type of connecting arrangement - ACSR conductor connection on HT side and cable connection box on LT side (m) Provision of thermometer with pocket. (n) Oil and winding alarm and trip relay including marshal box. (o) The transformer of 500 KVA full capacity shall be designed to fuction properly at high altittute of appx 3865M above sea level and outside temperature conditions between -40 degree celcius to +30 Degree celcius. (p) Factory inspection shall be carried out by the representative detailed by the Accepting Officer.
Supply, installing, testing , connecting and commissioning of distribution transformer outdoor type step down 11/0.433 KV (at no load) with HT 3 phase and LT 3 phase 4 wire AC , 50Hz, 250KVA copper wound with off load tap changing arrangement on HT side for a variation of secondary voltage +/- 7.5% in steps of +/- 2.5% including suitable cable entry boxes on LT side and HT bushing on primary side complete in all respects with standard accessories and fitments confirming to IS 1180 (Revised 2014) and test ECBC as specified and directed inlcuding the following :- Make: (i) JK Transformer & Switch Gear, Jammu (ii) Rajasthan Transformer (iii) Oriental transformer, Jammu (iv) Continental Transformer, Jammu (a) Earthing terminal and rating diagram plate. (b) Air release device (c) Oil Filling inlet pipe with plug. (d) Drain outlet pipe with brass gate valve with dummy plug (e) Conservator with level gauge. (f) Silica gel with breather
(g) First oil fill up to the recommended level by the manufacturer with new oil confirming to IS 335. (h) Type of connector - Star/Delta (j) Type of Cooling - ONAN (k) Vector Group- DYN 11 (l) Type of connecting arrangement - ACSR conductor connection on HT side and cable connection box on LT side (m) Provision of thermometer with pocket. (n) Oil and winding alarm and trip relay including marshal box. (o) The transformer of 250KVA full capacity shall be designed to fuction properly at high altittute of appx 3865M above sea level and outside temperature conditions between -40 degree celcius to +30 Degree celcius. (p) Factory inspection shall be carried out by the representative detailed by the Accepting Officer.
Supply, installing, testing , connecting and commissioning of distribution transformer outdoor type step down 11/0.433 KV (at no load) with HT 3 phase and LT 3 phase 4 wire AC , 50Hz, 125KVA copper wound with off load tap changing arrangement on HT side for a variation of secondary voltage +/- 7.5% in steps of +/- 2.5% including suitable cable entry boxes on LT side and HT bushing on primary side complete in all respects with standard accessories and fitments confirming to IS 1180 (Revised 2014) and test ECBC as specified and directed inlcuding the following :- Make: (i) JK Transformer & Switch Gear, Jammu (ii) Rajasthan Transformer (iii) Oriental transformer, Jammu (iv) Continental Transformer, Jammu (a) Earthing terminal and rating diagram plate. (b) Air release device (c) Oil Filling inlet pipe with plug. (d) Drain outlet pipe with brass gate valve with dummy plug (e) Conservator with level gauge. (f) Silica gel with breather (g) First oil fill up to the recommended level by the manufacturer with new oil confirming to IS 335.
(h) Type of connector - Star/Delta (j) Type of Cooling - ONAN (k) Vector Group- DYN 11 (l) Type of connecting arrangement - ACSR conductor connection on HT side and cable connection box on LT side (m) Provision of thermometer with pocket. (n) Oil and winding alarm and trip relay including marshal box. (o) The transformer shall be pole mounted and of 125 KVA full capacity shall be designed to fuction properly at high altittute of appx 3865M above sea level and outside temperature conditions between -40 degree celcius to +30 Degree celcius. (p) Factory inspection shall be carried out by the representative detailed by the Accepting Officer.
Supply installing, Commissioning & testing HT 11 KV, 3 Phase 50 Hz, rupturing capacity 250 MVA indoor type, totally metal clad withdrawable type Vacuum Circuit Breaker including suitable for incoming, including Cable connection with Copper bus bar of suitable rating horizontal isolation type VCB of capacity minimum 800 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC or equivalent not less than 2.5 mm thickness for load bearing section and not less than 2 mm thickness for non- load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25KA, No of operation of Vacuum Interrupter Bottles for better performance. (a) Mechanical life 30,000. (b) Rated electrical operations – 10,000 Cycle (c) All the main components like VCB/Relays/ Meters should be as per OEM. Panel and VCB parameters are as below:- (i) Rated Voltage level/ PF withstand voltage/impulse level – 12 KV/38KV/95KV. (ii) Continuous current rating minimum 800A. (iii) Short circuit withstand current minimum 25 KA for 1 sec (iv) Horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:-
(aa) Manually & Motor operated (230V,AC, 50HZ) Spring charged type, manually electrically open (electrical- 220VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication ‘OFF” push button, test/service position limit switches with minimum 6NO+6NC breaker auxiliary contacts in C5 service position"(ab) Epoxy cast wound current transformer (CT), 11 KV, 400-200/5-5A, Core 1: Class 1, 15VA for 3 phase Core 2 : 5P10, 15VA burden with metering and protection core including necessary control wiring. (ac) Manual Charging of breaker should be done without operating the front door. (ad) Cast resin potential transformer 11 KV/V3/110V/V3/110V/3, 50VA, Cl 1.0, Cl 3P and HT fuse at the primary end and pole MCB at the secondary end of the PT (Conforming to IS specification). (ae) Protection arrangements for the breaker shall comprise of the following:- (i) E/F, O/C & S/C Numerical protection relay. (ii) Complete with Master Trip/Anti pumping relay. (iii) Auxiliary Relay Alarm/ Trip OTI/WTI
Supply installing, Commissioning & testing HT 11 KV, 3 Phase 50 Hz, rupturing capacity 250 MVA indoor type, totally metal clad withdrawable type vacuum Circuit Breaker including provision for outgoing including Cable connection with Copper bus bar of suitable rating horizontal isolation type VCB of capacity minimum 400 Amps rated current, as per IEC 62271-100-200. The switchgear panel shall be of sheet steel construction with ALUZINC or equivalent not less than 2.5 mm thickness for load bearing section and not less than 2 mm thickness for non- load bearing and shall be totally dust and vermin proof. The offered panels shall be tested for IAC level of 25KA, No of operation of Vacuum Interrupter Bottles for better performance. (a) Mechanical life 30,000. (b) Rated electrical operations – 10,000 Cycle (c) All the main components like VCB/Relays/ Meters should be as per OEM. Panel and VCB parameters are as below :- "(i) Rated Voltage level/ PF withstand voltage/impulse level – 12 KV/38KV/95KV. "(ii) Continuous current rating minimum 400A." "(iii) Short circuit withstand current minimum 25 KA for 1 sec" "(iv) Horizontal draw out type vacuum circuit breaker in 12KV metal clad floor mounting panel complete with following:- "
"(aa) Manually & Motor operated (230V,AC, 50HZ) Spring charged type, manually electrically open (electrical- 220VDC) operation type, incorporating mechanical as well as electrical ON/OFF indication ‘OFF” push button, test/service position limit switches with minimum 6NO+6NC breaker auxiliary contacts in C5 service position" "(ab) Epoxy cast wound current transformer (CT), 11 KV, 400-200/5-5A, Core 1: Class 1, 15VA for 3 phase Core 2 : 5P10, 15VA burden with metering and protection core including necessary control wiring." "(ac) Manual Charging of breaker should be done without operating the front door." "(ae) Protection arrangements for the breaker shall comprise of the following:-"
SCHEDULE 'A' Part - IV (SEC- 2) (SEWAGE DISPOSAL) Note: This schedule is not pre-priced by MES and the rate indicated as "Rs 0.00" under Col 5 signifies this fact only
Supply and fixing of LLDPE Septic tank for 05 users designed to carry sewage and sludge water complete all as per manufacturer's instructions and all as directed. Notes :- (a) The LLDPE septic tank shall be ISI marked/ conforming to IS specification. In case the product is manufactured as per British Standards/ American Standards, same shall be certified by the NABL approved laboratories. The tank shall be suitable for High altitude areas and suitable for temperature range from (-) 40 to (+) 30 degree celcius. (b) Rates are deemed to be inclusive of excavation in any type of soil/ rock upto the depth as recommended by the OEM alongwith all connected civil works required such as PCC foundations, making connections etc to make the tank functional complete all as recommended by the OEM.
Vinayaka Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .