Loading…
Loading…
Tender Value
₹21.8 L
EMD Value
₹43,600
Closing Date
5 Oct 2026, 3:00 pm
No
No
Single Packet System
Normal Tender
No
Not Applicable
Lowest to Highest
60 days
Expenditure
Capital (Works)
POWER
16 conditions · 1 needing a document upload
The tenderer should have a valid Electrical Contractor License from the concerned statutory authority. The above said Electrical Contractor License is to be submitted along with the offer otherwise the offer shall be summarily rejected.
a. Work shall be carried out by contractor, having valid Electrical Contractor License for carrying out installation work under direct supervision of persons holding valid certificates of competency issued by State Government.
b. Tenderer shall have a valid Electrical Contractor'sLicense issued in name of firm by any StateGovernment and shall furnish all particulars of theElectrical license held by him along with the tenderdocuments.
c.Successful tenderer shall furnish names andparticulars of certificate of competency ofsupervisor and workmen to be engaged for carryingout this work.
d. By a Gazette notification, Govt. of India hasappointed Chief Electrical Engineer, N. Rly to be theElectrical Inspector and has directed that he shallexercise powers and perform functions of anElectrical Inspector under the Indian Electricity Act2003 and Indian Electricity Rules 1956
I/we the tenderer (s) am/are signing this document after carefully reading the contents.
I/We the tenderer(s) also accept all the conditions of the tender and have signed all the pages in confirmation thereof.
I/we hereby declare that I/we have downloaded the tender documents from Indian Railway website www.ireps.gov.in . I/we have verified the content of the document from the website and there is no addition, no deletion or no alteration to the content of the tender document. In case of any discrepancy noticed at any stage i.e. evaluation of tenders, execution of work or final payment of the contract, the master copy available with the railway Administration shall be final and binding upon me/us.
I/we declare and certify that I/we have not made any misleading or false representation in the forms, statements and attachments in proof of the qualification requirements.
I/We also understand that my/our offer will be evaluated based on the documents/credentials submitted along with the offer and same shall be binding upon me/us.
I/We declare that the information and documents submitted along with the tender by me/us are correct and I/we are fully responsible for the correctness of the information and documents, submitted by us.
I/we certify that I/we the tenderer(s) is/are not blacklisted or debarred by Railways or any other Ministry / Department of Govt. of India from participation in tender on the date of submission of bids, either in individual capacity or as a HUF/ member of the partnership firm/LLP/JV/Society/Trust.
I/we understand that if the contents of the certificate submitted by us are found to be forged/false at any time during process for evaluation of tenders, it shall lead to forfeiture of the Bid Security and may also lead to any other action provided in the contract including banning of business for a period of upto two year. Further, I/we and all my/our constituents understand that my/our offer shall be summarily rejected.
I/we also understand that if the contents of the certificate submitted by us are found to be false/forged at any time after the award of the contract, it will lead to termination of the contract, along with forfeiture of Bid Security/Security Deposit and Performance guarantee and may also lead to any other action provided in the contract including banning of business for a period of upto two year.
I/We have read the clause regarding restriction on procurement from a bidder of a country which shares a land border with India and certify that I am/We are not from such a country or, if from such a country, have been registered with the competent Authority. I/We hereby certify that I/we fulfil all the requirements in this regard and am/are eligible to be considered (evidence of valid registration by the competent authority is enclosed)
30 conditions · 6 needing a document upload
GSTIN number: Bidder shall submit attested or self attested copy of GSTIN certificate.
Following documents shall be submitted by the tenderer: (A)SOLE PROPRIETOR SHIP FIRM: (i)All other documents in terms of clause 1.1.12 of tender document . (B)HUF: (i) A copy of notarized affidavit on Stamp Paper declaring that he who is submitting the tender on behalf of HUF is in the position of 'Karta' of Hindu Undivided Family (HUF) and he has the authority, power and consent given by other members to act on behalf of HUF. (ii)All other documents in terms of clause 1.1.12 of tender document. (C)PARTNERSHIP FIRM:(i)A notarised copy of the Partnership Deed or a copy of the Partnership deed registered with the Registrar. (ii)A notarised or registered copy of Power of Attorney in favour of the individual to tender for the work, sign the agreement etc. and create liability against the firm.(iii)An undertaking by all partners of the partnership firm that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP in which they were / are partners/members. Any Concealment / wrong information in regard to above shall make the bid ineligible or the contract shall be determined under Clause 62 of the Standard General Conditions of Contract.(iv)All other documents in terms of clause 1.1.12 of tender document . (D)JOINT VENTURE (JV): APPLICABLE ONLY FOR WORKS COSTING MORE THAN Rs.10.00 Cr. Not applicable for this tender. (E)Company registered under Companies Act- 2013:(i)The copies of MOA (Memorandum of Association) / AOA (Articles of Association) of the company.(ii)A copy of Certificate of Incorporation.(iii)A copy of Authorization / Power of Attorney issued by the Company (backed by the resolution of Board of Directors) in favour of the individual to sign the tender on behalf of the company and create liability against the company.(iv)All other documents in terms of clause 1.1.12 of tender document. (F)LLP (Limited Liability Partnership) Firm under LLP Act-2008: (i)A copy of LLP Agreement.(ii)A copy of Certificate of Incorporation.(iii)A copy of Power of Attorney / Authorization issued by the LLP in favour of the individual to sign the tender on behalf of the LLP and create liability against the LLP.(iv)An undertaking by all partners of the LLP that they are not blacklisted or debarred by Railways or any other Ministry / Department of the Govt. of India from participation in tenders / contracts as on the date of submission of bids, either in their individual capacity or in any firm/LLP or JV in which they were / are partners/members. Concealment / wrong information in regard to above shall make the contract liable for determination under Clause 62 of the Standard General Conditions of Contract. (G)Registered Society & Registered Trust: The tenderer shall submit: (i)A copy of the Certificate of Registration.(ii)A copy of Memorandum of Association of Society/Trust Deed.(iii)A copy of Power of Attorney in favour of the individual to sign the tender documents and create liability against the Society/Trust.(iv)A copy of Rules & Regulations of the Society.(v)All other documents in terms of clause 1.1.12 of tender document .
The tenderer shall submit a copy of certificate (Annexure 19(A)) in case of other than Company/Proprietary firm by each member of a Partnership Firm / Joint Venture (JV) / Hindu Undivided Family (HUF / Limited Liability Partnership (LLP) etc, as the case may be. Non submission of above certificate(s) by the bidder shall result in summarily rejection of his/their bid. It shall be mandatory incumbent upon the tenderer to identify, state and submit the supporting documents duly self attested/digitally signed by which they/he is qualifying the Qualifying Criteria mentioned in the Tender Document. Note:- As per railway board letter No. 2022/CE-I/CT/GCC Correspondence Dated: 14.05.2024 "On IREPS Module, a facility has already been created for online submission of Annexure-V. Therefore, the provision of downloading of Annexure-V of GCC & uploading of physically signed Annexure-V by the tenderer had been discontinued on IREPS".
Please enter the percentage of local content in the material being offered. Please enter 0 for fully imported items, and 100 for fully indigenous items. The definition and calculation of local content shall be in accordance with the Make in India policy as incorporated in the tender conditions.
Payment of Bid-security in respect of E- tendering will be deposited either in cash through e payment gateway or submitted as Bank Guarantee bond from a scheduled commercial bank of India or as mentioned in tender documents. The Bank Guarantee bond shall be as per Annexure-VIA of GCC Works 2022(Annexure-21 of tender document) and shall be valid for a period of 90 days beyond the bid validity period and any offer without the same will be treated as invalid. Details of bank account no. and technical details have been provided for in the software (IREPS) to which prospective registered tenderers will have access at the time of tendering.
In case, submission of Bid Security in the form of Bank Guarantee, following shall be ensured: (i) A scanned copy of the Bank Guarantee shall be uploaded on e-Procurement Portal (IREPS) while applying to the tender. (ii) The original Bank Guarantee should be delivered in person to the official nominated as indicated in the tender document before closing date for submission of bids (i.e. excluding the last date of submission of bids). (iii) Non submission of scanned copy of Bank Guarantee with the bid on e-tendering portal (IREPS) and/or non submission of original Bank Guarantee within the specified period shall lead to summary rejection of bid. (iv) The Tender Security shall remain valid for a period of 90 days beyond the validity period for the Tender. (v) The details of the BG, physically submitted should match with the details available in the scanned copy and the data entered during bid submission time, failing which the bid will be rejected. (vi) The Bank Guarantee shall be placed in an envelope, which shall be sealed. The envelope shall clearly bear the identification "Bid for the ***** Project" and shall clearly indicate the name and address of the Bidder. In addition, the Bid Due Date should be indicated on the right hand top corner of the envelope. (vii) The envelope shall be addressed to the officer and address as mentioned in the tender document. (viii)If the envelope is not sealed and marked as instructed above, the Authority assumes no responsibility for the misplacement or premature opening of the contents of the Bid submitted and consequent losses, if any, suffered by the Bidder. (ix) BG/EMD shall be made in the favor of Sr Divisional Finance Manager/FZR.
1. Only firm recognized by department of industrial policy and promotion (DIPP) as "Startups" shall be exempted from payment 4.1.1 of Bid Security as per GCC 2022. 2. All other firms except described above shall be required to submit the Bid Security as per terms and conditions of tender.
PAN CERTIFICATE : PAN The tenderer shall submit the photocopy of Permanent Account Number (PAN) issued by Income Tax authority attested by Gazetted officer / self attested.
The tenderer shall study the Northern Railway General Conditions of Contract Regulations for Tenders & Contracts - 2022 or latest along with tender documents before submission of the tender.
Applicable charges/recoveries/Advance etc. (Deployment of Technical supervisors per attached Annexure XIII) is applicable.
There is an option of payment to contractor through a letter of credit (LC) arrangement (Authority Railway Board's letter no. 2018/CE-I/CT/9 dated 04.06.2018)as given in clause 1.3.14 of tender document.
GCC works 2022(or latest if any) should be the integral part of this tender.
The instructions issued under ACS 1 to ACS 12 and any latest circular/letter of Railway Board of GCC Works 2022 shall also prevail.
Electrical work in c/w Raising and extension of existing platform and other passenger amenities work including improvement to facade of station building etc at RDS station
251-Elect-T-07-2026-27~NR
251-Elect-T-07-2026-27
Open
Works - General
6 Months
Firozpur, Punjab
₹0
₹43,600
14 Sept 2026
14 Sept 2026
21 Sept 2026
77 items across 1 schedule
| # | Description | Unit | Qty | Rate | Amount |
|---|---|---|---|---|---|
| — | — | — | Above/ 2178442.20 Below/P | ||
| — | 15.00 | — | — | ||
| Supply and Erection of modular metal boxes concealed boards with white finish single mounting plate and fixing of switches/plug socket and connection wiring. Make Legrand (Myrius), Schneider (Zencelo), Anchor (Ave) or equivalent. Metal boxes boards are to be concealed in the wall for 12 Module | — | — | — | 5,821.35 | |
| — | 10.00 | — | — | ||
| Supply and Erection of modular metal boxes concealed boards with white finish single mounting plate and fixing of switches/plug socket and connection wiring. Make Legrand (Myrius), Schneider (Zencelo), Anchor (Ave) or similar make. Metal boxes boards are to be concealed in the wall for 6 Module | — | — | — | 3,700 | |
| — | 150.00 | — | — | ||
| Supply, fixing, testing, and commissioning of modular type switch 6/10 Amps as per IS/IE rules and site requirement. Make Legrand (Myrius), Schneider (Zencelo), Anchor (Ave) or similar make. | — | — | — | 24,292.5 | |
| — | 50.00 | — | — | ||
| "Supply, fixing, testing and commissioning of modular type multi socket 6 Amps 5 pin as per IS/IE rules and site requirement. Make Legrand (Myrius), Schneider (Zencelo), Anchor (Ave) or equivalent." | — | — | — | 7,455 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing, and commissioning of modular type switch 16 Amps as per tech. specification IS/IE rules and site requirement. | — | — | — | 1,934.4 | |
| — | 10.00 | — | — | ||
| Supply, fixing, testing, and commissioning of modular type 6 pin switch socket 6/15 Amps as per tech. specification IS/IE rules and site requirement. | — | — | — | 2,641 | |
| — | 600.00 | — | — | ||
| Supply and recessing/fixing of 25 mm (Medium) PVC conduit pipe conforming to IS9537/Pt.III/1983 or Latest Version with accessories, junction box, etc including making chase, plastering/clamping etc as per technical specifications. | — | — | — | 22,170 | |
| — | 1500.00 | — | — | ||
| Supplying, laying, testing and commissioning of FRLS 1.0 sq mm PVC insulated multistranded copper conductor s/core cable1100 Volt conforming to IS-694 (latest version) and ISI marked, make Finolex, Havells, Polycab, KEI or equivalent in the recessed PVC conduit pipe 20 mm dia as required at site. | — | — | — | 18,510 | |
| — | 2000.00 | — | — | ||
| Wiring for light points with supply and laying of FRLS PVC insulated multistranded copper conductor cable 1100 Volt 1.5 Sq.mm multi stranded confirming to IS-694 latest and ISI marked in the existing PVC pipe. | — | — | — | 28,300 | |
| — | 2000.00 | — | — | ||
| Supply, laying, fixing, testing and commissioning of 2.5sq mm FRLS, PVC insulated multistranded copper conductor single core cable 1100 Volts confirming to IS-694(latest version) ISI marked, make Finolex, Havells, Polycab, KEI or equivalent in the existing PVC conduit for wiring of point wiring/circuit wiring/sub main/main as per Tech Spec-I attached, IS & IE rules | — | — | — | 36,200 | |
| — | 800.00 | — | — | ||
| Supplying, laying, testing and commissioning of FRLS 4.00 Sq mm PVC insulated multistranded copper conductor s/core cable1100 Volt conforming to IS-694 (latest version), ISI marked, make Finolex, Havells, Polycab, KEI or similar in the recessed PVC conduit pipe 20 mm dia as required at site. | — | — | — | 20,872 | |
| — | 60.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED light luminaries, having system wattage 1x > 18w (Max.), LED tube and inbuilt LED driver, CRCA body powder coated, complete with a l l mounting arrangement, accessories. The LED based 4 ft. tube light (lamp) shall be of make Phillips, Bajaj,Havells or similar conforming to CEE/NR's spec. No. CEE/NR/121-Elect/PS/2018 (Rev- '3'), & PCEE/NR's spec. No. PCEE/NR/121- Elect/PS/2019 (Rev- '4') or latest | — | — | — | 32,592 | |
| — | 150.00 | — | — | ||
| Supply, fixing,testing and commissioning of 3-pin ceiling rose 5 Amp capacity on existing MS/PVC conduit junction boxes/casing caping Anchor, Cona, Kinjal, SSK or equivalent as per IS, IE rules and site requirement. | — | — | — | 2,035.5 | |
| — | 30.00 | — | — | ||
| Supply and erection of 36 W recess type LED light fitting (2x2 ft) complete with control panel & all accessories including connection with 2x2.5 sq.mm PVC insulated multi stranded FRLS copper conductor cable, testing,commissioning &earthing required and as per CEE/NR specification No. CEE/NR/121-Elect/PS/2018 (Rev.03)dated 28.06.2018 & CEE/NR/121-Elect/PS/2019 (Rev.4) dated04.11.2019 | — | — | — | 1,42,994.7 | |
| — | 20.00 | — | — | ||
| Supply, fixing, testing and commissioning of LED down lighter, housing aluminum die cast, white powder coated and PMMA diffuser having system wattage less than or equal to 15Watt complete with all mounting arrangement, accessories complete of make Phillips, Bajaj, Havells or similar conforming to CEE/NR's spec. No.CEE/NR/121-Elect/PS/2018 (Rev-'3') or latest & PCEE/NR's spec. No.PCEE/NR/121-Elect/PS/2019 (Rev-'4') or latest | — | — | — | 16,451.2 | |
| — | 20.00 | — | — | ||
| Supply, fixing, testing and commissioning of energy efficient 230V, 50Hz a c ceiling fan size of 1200mm sweep having wattage of 28W, range of voltage operation at various speed - 120 to 260V AC with 5 step speed control electronic regulator, copper winding complete as per IS : 374 - 1979 or latest, IE rule & site requirement. Make Bajaj, Usha, Havells, Crompton, Orient or equivalent. | — | — | — | 58,834.8 | |
| — | 3.00 | — | — | ||
| Supply, fixing, testing and commissioning of 380 mm sweep, 1400 rpm (approx) propeller type exhaust fan complete as per IS, IE rule & site requirement. Make Usha, Orient, Bajaj or equivalent | — | — | — | 9,007.47 | |
| — | 2.00 | — | — | ||
| Supply, erection, testing and commissioning of the following Double door wall mounted Pre-fabricated L.T. Distribution Boards of approved make, as per explanatory note & comprising; (i) Incoming MCCB 4Pole 63 A 35 KA B/C - 1 No. (ii). Outgoing MCB 6 to 32 A. SP 10 KA B/C (4 Nos. On each Phase) - 12 Nos. | — | — | — | 27,766.26 | |
| — | 2.00 | — | — | ||
| Supply, erection, testing and commissioning of the following Double door wall mounted Pre-fabricated L.T. Distribution Boards of approved make, as per explanatory note & comprising; (i) Incoming MCB 40 A DP 10 KA B/C - 1 No. (ii) Outgoing MCB 16 A. SP 10 KA B/C - 6 Nos. | — | — | — | 7,140.16 | |
| — | 20.00 | — | — | ||
| Supply & erection of 5M pole with single arm bracket hot dip galvanized octagonal pole with top 70 mm and bottom 130 mm around face made of 3 mm thick, steel base plate size 200x200x12 mm complete with appropriate sleeve at the top of the pole for mounting arm bracket 300 mm long suitable for LED street light fittings including casting, muffing with cement concrete foundation (1:2:4) painting, earthing and foundation GI nut, bolts with washer and smart pack junction box with single pole MCB and terminals as per explanatory note | — | — | — | 1,66,824.8 | |
| — | 25.00 | — | — | ||
| Supply and erection of minimum 45 W LED Street light fitting operating voltage single phase 230 volts AC, 50Hz complete with all accessories as per CEE/NR Specification. No.CEE/NR/121-Elect/PS/2018 (Rev '3') Dated 28.06.2018 & CCE/NR/121-Elect/PS /2019 (Rev.4) dated 04.11.2019 or latest respectively including connection with 2x2.5 sq.mm PVC insulated multi stranded FRLS copper conductor cable, testing, commissioning & earthing required and as per explanatory note. | — | — | — | 87,106.25 | |
| — | 15.00 | — | — | ||
| Supply, fixing, testing and commissioning of RCBO 25A,double pole, 30mA with Earth leakage, over load and short circuit protection. | — | — | — | 37,588.95 | |
| — | 3500.00 | — | — | ||
| Transportation, Laying, underground/road/Railway track, recessing in platform /wall along with Rly. Track/in laid RCC/GI pipe as required 1.1 KV grade LT XLPE insulated armoured, aluminium conductor cable including making chase & plastering after laying of cable/digging of cable trench, sand cushioning, protective covering with second class bricks, provision of cable route marker as per Tech. Specification including end terminations with Aluminium Clamping socket/lugs, testing and commissioning of upto 25 sq.mm | — | — | — | 2,09,580 | |
| — | 10.00 | — | — | ||
| Design, manufacturing of floor mounted MS feeder post made of MS sheet 16 SWG Die pressed of size 550mm x 450mm x 275mm deep complete with 400A Aluminium bus bars four Nos. having cable glands 2 Nos. duly grouted with cement concrete ratio 1:2:4 duly earthed with earthing terminals. | — | — | — | 38,070.7 | |
| — | 2.00 | — | — | ||
| Supply, Erection, Testing and commissioning of 2 KVA Online UPS Single phase output voltage 220-230V(+/-1%), Sinewave IGBT-PWM with inbuilt isolation transformer operated on 72V Battery bank as per IS: 16242/IEC62040 or latest, with provision of 12 Volt 65ah SMF-VRLA Battery (06nos) with trolley/rack. Warranty for UPS and battery: minimum 2years | — | — | — | 1,34,910.04 | |
| — | 2.00 | — | — | ||
| Supply, installation and commissioning of 1400 VA sinewave inverter with following features of make SUKAM, Luminous or Microteck with supply of tubular plate 150 AH batteries of make Exide model IT500 or similar. The complete inverter unit with batteries should be housed in MS /Plastic portable trolley duly paint finished. (i) Input DC voltage 24 Volt DC (ii) Input AC Voltage 135-275 Volt (iii) Output voltage 220 Volt + 8% (iv) Output Waveform Sinewave (v) Output 1400 VA or above (vi) LED display Main ON, Inverter ON, Low Battery, Main ON, Inverter ON, Low Battery, Over Charge, Mains Low and High Input Voltage (vii) Protections: Over Load, Short Circuit, Low Battery Over Charge Mains Low and High Input Voltage. | — | — | — | 84,603.96 | |
| — | 200.00 | — | — | ||
| Design, Manufacture, supply, fixing, testing and commissioning of single sided LED type signages at platforms of suitable size as CEE/NR specification No. CEE/NR/121-Elect/PS/2018 (Rev'3') Dated 28.06.2018 or latest. and as per site requirement. Note:- Static/single sided board of different sizes name is required. prior approval of message color and size to be taken from competent authority. | — | — | — | 2,91,778 | |
| — | 2.00 | — | — | ||
| Supply of ISI mark , 4 and above star rated ,energy efficient submersible pump motor set 7.5 HP/15 stage ,415 volt AC, three phase, H/range 59-150 MTRS ,discharge 300-100 LPM, del. Size 50 mm, suitable for 150 mm bore well water lubricated type confirming to IS no 8034/2002 or latest MAKE:SHAKTI,KSB,KIRLOSKAR,CG,CRI,FLOTECH or equivalent (With One Year Warranty) | — | — | — | 87,770 | |
| — | 2.00 | — | — | ||
| "SITC of star delta starter panel board suitable for 7.5 HP submersible pump motor set 3 phase 415 volt AC complete as per following technical specification (1) push button with light 230V- 2nos (2)auto time switch 16amp 230V-01 nos (3) single phasing preventer switch 415v-01 nos (4) digital ampere meter with selector switch 0-50amp-01nos (5) digital voltmeter 0-500 VAC with selector switch-01 nos (6) MCCB 3 pole breaking capacity 35KA. 32amp- 01 nos (7) digital hour meter 230V-01 nos (8) HRC fuse unit 32 amp complete- 3 nos (9) over load relay14-23amp- 01 nos (10)two way toggle switch 10 amp for manual and auto -01 nos(11) star dlta timer 0-60 sec.-01nos (12) 03 pole power contactor 32 amp 3 phase with aux. block (2NO+2NC)-03 nos (13) CT 50/5 per unit -3nos (14) control fuse -03 nos (15) water level control guard of 3 prode system -01nos (16) dimension 650X840X290MM. Switch gear Make ABB,L&T,SIEMENS,BCH,HPL,GEC OR equivlant" | — | — | — | 34,220 | |
| — | 1.00 | — | — | ||
| Supply, testing, commissioning of 16 meter high mast system suitable for 9 Nos. LED flood lightluminaries (Min.150 Watt) with the help of suitable equipment including accessories control panel for high mast system. Each high mast shall also have one twin dome aviation obstruction light with 2 nos. LED lamp equivalent to BJAOL -2. Make BAJAJ, Osram, PHILIPS, GE B10 or equivalent. Note-Accessories includes 3 point suspension head frame, steel wire rope of suitable dia, double drum winch, galvanized lantern carriage & other arrangement for each high mast shall have one Fedder Pillar box as per specification. Control panel includes the control circuit for lowering/raising operation of mast integral detachable power tool with motor including torque limiter time switch and lighting final including lines required for switching. Design / casting ofshallow foundation of mast/panel shall be with M-20 concrete. Considering safe soil bearing capacity at site as 10 T/sq mtrs at 2 mt. depths. Foundation both nuts, washes, anchor plates, templates should be made of Spl. Steel. Any alteration/modification shall be done as per site/tech. specification requirement to the satisfaction of Rly. Representative at the cost of firm. The tower shall be as per Tech. Specification, IS, IE rules and site requirement. | — | — | — | 2,48,293.97 | |
| — | 9.00 | — | — | ||
| Supply, installation,testing and commissioning of 150 Watt LED based flood light fitting, operating voltage single phase 230V AC, 50Hz complete with led lamp & all mounting arrangement, accessories & flexible copper wire for connetion as per ISS/IR rules & as per CEE/NR Specification No. CEE/NR/121-Elect/PS/2018 (Rev.03) dated 28.06.2018 & CEE/NR/121-Elect/PS /2019 (Rev.4) dated 04.11.2019 respectively or latest | — | — | — | 1,18,210.68 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing& commissioning of astronomical timer based control panel for high mast tower lighting suitable for 25 A 4 P Contactor as per model no. Alpha Rex3 D21, 1 channel cat part 412654 of Legrand or equivalent | — | — | — | 7,648.63 | |
| — | 1.00 | — | — | ||
| S.I.T.C of contained drinking water cooler capacity 150 LTR with Non CFC refrigerant ) energy efficient compressor cooling capacity LTR/HR150, storage type ,confirming to IS-1475-1PART 1, of 2001 or latest make blue star, voltas or similar. | — | — | — | 52,010.11 | |
| — | 1.00 | — | — | ||
| "Lowering of submersible pumps (3 phase) from existing bore upto depth of 200 feet ." | — | — | — | 4,200 | |
| — | 100.00 | — | — | ||
| Supply and fixing of GI pipe B Class 3 inch dia with MS flanges holding, locking system for safety and checking dropping down of submersible pump upto non return valve and connection with sluice valve to be matched with delivery pipe at ground level. | — | — | — | 52,564 | |
| — | 1.00 | — | — | ||
| Supply, fixing, testing and commissioning Sluice Valve 3 inch dia and Non return Valve 3 inch dia and CI bends complete with connection etc. of make Standard, BEER, or similar conforming to latest version of relevant IS CODE. | — | — | — | 5,921.27 | |
| — | 20.00 | — | — | ||
| "Earthing arrangement by providing earth electrode of GI pipe 50 mm dia (B class) 4.5 meter long with flange including 6 SWG GI earth wire from earth pipe to connecting point on switch board to distribution board/pole etc. as per site requirement including masonry enclosure as per Tech specification at annexure 'A' relevant ISS & IE rules and site requirements. A suitable CI/MS/RCC cover as approved by Rly . Representative, cover with locking arrangement shall be provided." | — | — | — | 46,120 | |
| — | 250.00 | — | — | ||
| Supply & recessing/fixing on surface 6 SWG GI wire for loop earthing as required as mentioned in explanatory note. | — | — | — | 2,302.5 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
ACS11.pdf
ATTACHMENT
GCC_April-2022_2022_CE-I_CT_GCC-2022_POLICY_27_04_22.pdf
ATTACHMENT
LEDSpecification.pdf
ATTACHMENT
LEDSpec.1.pdf
ATTACHMENT
LEDSpec2.pdf
ATTACHMENT
GCCCorrectionSlip.pdf
ATTACHMENT
ACS3.pdf
ATTACHMENT
ACS2_1.pdf
ATTACHMENT
ACS5.pdf
ATTACHMENT
ACS6.pdf
ATTACHMENT
ACS4.pdf
ATTACHMENT
RewirngSpec-I.pdf
ATTACHMENT
ACS7.pdf
ATTACHMENT
ACS8.pdf
ATTACHMENT
ACS9.pdf
ATTACHMENT
ACS10.pdf
ATTACHMENT
GCCClarificationRegarding.pdf
ATTACHMENT
ACS12_compressed.pdf
ATTACHMENT
FinalSpecRDSO_compressed.pdf
ATTACHMENT
T-07tenderDocument.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .