Loading…
Loading…
Tender ID
| # | Company | Status |
|---|---|---|
| 1 | Accepted-Technical 6 35 COLLEGE ROAD 1ST CROSS STREET TIRUPUR 641 602 TAMILNADU | TIRUPUR | TIRUPUR | TAMILNADU | 641602 | Accepted-Technical Bidder qualified the technical bid evaluvation |
Tender Value
₹107.7 Cr
EMD Value
₹5 L
Closing Date
13 Mar 2026, 5:25 pmClosed
MD KITFRA
1st Floor, Sankethika, PF Road, Vrindavan Gardens, Pattom, Thiruvananthapuram - 695004
Construction of multi-storey IT building using precast RCC technology at Infopark Kochi Phase 1 campus, Kakkanad, Kochi, Kerala.
2026_KSITI_834187_2
KITFRA/IPK/2025-26/28
Open Tender
Civil Works - Buildings
Item Rate
Infopark Phase 1 Campus
Please refer Tender documents.
3 documents required · 3 mandatory
₹17,700
Yes
₹5 L
Yes
12 May 2026
6 Mar 2026
14 Mar 2026
6 Mar 2026
13 Mar 2026
6 Mar 2026
SITE CLEARING WORKS
2.33.1 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material. Beyound 30 cm girth up to and including 60 cm girth
2.33.2 Felling trees of the girth (measured at a height of 1 m above ground level) including cutting of trunks and branches, removing the roots and stacking of serviceable material and disposal of unserviceable material.Beyound 60 cm girth up to and including 120 cm girth
OD295095/2025-2026 Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved
15.5 Extra for cutting reinforcement bars manually/ by mechanical means in R.C.C. or R.B. work ( Payment shall be made on the cross sectional area of R.C.C. or R.B work) as per direction of Engineer-in-charge.
OD295101/2025-2026 Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in charge, beyond 50 m initial lead, for all leads including all lifts involved. In cement mortar
OD295159/2025-2026 Demolishing stone rubble masonry manually / by mechanical means including stacking of serviceable material and Disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved In cement mortar
15.12.1 Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area 3 sq. metres and below
15.12.2 Dismantling doors, windows and clerestory windows (steel or wood ) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead:Of area beyond 3 sq. metres
15.18 Dismantling steel work in built up sections in angles, tees, flats and channels including all gusset plates,bolts, nuts, cutting rivets, welding etc. including dismembering and stacking within 50 metres lead.
15.23.1 Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm
15.28.1 Dismantling roofing including ridges, hips, velleys and gutters etc., and stacking the material within 50 metres lead of :G.S. Sheet
15.48 Taking out C.I cover with frame from R.C.C. top slab of manholes of various sizes including demolishing of R.C.C. work manually / by mechanical means and stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead as per direction of Engineer -in- Charge.
15.51 Dismantling of road gully chamber of various sizes including C.I. grating with frame including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead including refilling the excavated gap.
15.52 Dismantling of flushing cistern of all types (C.I. / PVC/ Vitrious China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead
16.83 Taking out existing CC interlocking paver blocks from footpath/ central verge, including removal of rubbish etc., disposal of unserviceable material to the dumping ground, for which payment shall be made separately and stacking of serviceable material within 50 metre lead as per direction of Engineer-in-Charge.
OD295304/2025-2026 Taking out water closet including seat cover, and cistern fittings, nuts bolts and gasket etc complete and stacking of useful materials near the site and disposal of unserviceable materials with 50 metres lead as per direction of Engineer -in- Charge.
OD295306/2025-2026 Taking out water closet including seat cover, and cistern fittings, nuts bolts and gasket etc complete and stacking of useful materials near the site and disposal of unserviceable materials with 50 metres lead as per direction of Engineer -in- Charge.
15.57 Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge
15.60 Disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved
FOUNDATION WORKS
OD291342/2025-2026 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 with minimum cement content of 400 kg /cum of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.500 mm dia piles
OD291297/2025-2026 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 with minimum cement content of 400 kg /cum of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used.600 mm dia piles
OD291357/2025-2026 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 with minimum cement content 400 kg / cum of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used. 800 mm dia piles
OD291363/2025-2026 Boring, providing and installation bored cast-in-situ reinforced cement concrete piles of grade M-30 with minimum cement content 400 kg / cum of specified diameter and length below pile cap, to carry a safe working load not less than specified, excluding the cost of steel reinforcement but including the cost of boring with bentonite solution and temporary casing of appropriate length for setting out and removal of same and the length of the pile to be embedded in the pile cap etc. by Crawler mounted, telescopic boom hydraulic pilling Rig all complete, including removal of excavated earth with all its lifts and leads (length of pile for payment shall be measured up to bottom of pile cap). Note: Truck Mounted rotary/TMR/Tube well boring machine shall not be used. 1000 mm dia piles
OD295343/2025-2026 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile up to safe load 300 tonne capacity Initial test (Test Load 2.5 times the Safe capacity) - 1000 mm dia
OD295351/2025-2026 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile up to safe load 77 tonne capacity Routine test (Test Load 1.5 times the Safe capacity) - 500 mm dia
OD295354/2025-2026 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile up to safe load 110 tonne capacity Routine test (Test Load 1.5 times the Safe capacity) - 600 mm dia
OD295355/2025-2026 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile up to safe load 195 tonne capacity Routine test (Test Load 1.5 times the Safe capacity) - 800 mm dia
OD295358/2025-2026 Vertical load testing of piles in accordance with IS 2911 (Part IV) including installation of loading platform by Kentledge/Anchor piles method and preparation of pile head or construction of test cap and dismantling of test cap after test etc. complete as per specification & the direction of Engineer in-charge. Single pile up to safe load 300 tonne capacity Routine test (Test Load 1.5 times the Safe capacity) - 1000 mm dia
5.22.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelThermo - Mechanically Treated bars of grade Fe-500D or more
OD310805/2025-2026 Chipping and removing the top of R.C.C piles to the cut off level as per drawing or up to the rigid sound concrete(payment will not be given for chipping done below cut off level due to poor concreting of piles) in line and levels carefully by manually/mechanically without damaging the remaining portion of pile, removing and staking of the debris to the designated places pointed out within the project premises, exposing the reinforcement and growth of short reinforcement upto required level as per IS standards/as instructed by PMC, etc all complete as specified and as directed by the Engineer-in-charge.
2.6.1 Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge.All kinds of soil
2.7.1 Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Ordinary rock
2.7.3 Earth work in excavation by mechanical means (Hydraulic excavator )/ manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed.Hard rock (blasting prohibited)
2.26.1 Extra for every additional lift 1.5 m or part there of in excavation / banking excavated or stacked materials.All kinds of soil
2.8.1 Earth work in excavation by mechanical means (Hydraulic excavator) /manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift up to 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil
2.25 Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundation etc. in layers not exceeding 20 cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift up to 1.5 m.
4.1.8 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level:1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources)
4.11 Providing and laying damp-proof course 50mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20mm nominal size derived from natural sources).
4.13 Providing & applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7kg per square metre on damp proof course after cleaning the surface with brushes and finally with apiece of cloth lightly soaked in kerosene oil.
2.34.1 Supplying chemical emulsion in sealed containers including delivery as specified.Chlorpyriphos / Lindane emulsifiable concentrate of 20%
2.35.3.1 Diluting and injecting chemical emulsion for POST -CONSTRUCTIONAL anti termite treatment (excluding the cost of chemical emulsion): Treatment of soil under existing floors using chemical emulsion @ one litre per hole, 300 mm apart including drilling 12 mm diameter holes and plugging with cement mortar 1:2 (1 cement : 2 coarse sand) to match the existing floor:With Chlorpyriphos/Lindane E.C. 20% with 1% concentration
4.2.3 Providing and laying cement concrete in retaining walls, return walls, walls ( any thickness) including attached pilasters, columns, piers, abutments, pillars, posts, struts,buttresses, string or lacing courses, parapets, coping, bed blocks, anchor blocks, plain window sills, fillets, sunken floor, etc. up to floor five level, excluding the cost of centering, shuttering and finishing:1:2:4 (1 Cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
5.33.1.2 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement All work upto plinth levelConcrete of M30 grade with minimum cement content of 350 kg /cum
5.35 Add for using extra cement in the items of design mix over and above the specified cement content therein
5.9.1 Centering and shuttering including strutting, etc. and removal of form for:Foundations, footings, bases of columns, etc for mass concrete
5.9.2 Centering and shuttering including strutting, etc. and removal of form for:Walls (any thickness) including attached pilasters, butteresses, plinth and string courses etc.
5.9.3 Centering and shuttering including strutting, etc. and removal of form for:Suspended floors, roofs, landings, balconies and access platform
5.9.5 Centering and shuttering including strutting, etc. and removal of form for:Lintels, beams, plinth beams, girders bressumers and cantilevers
22.26 Providing and applying of swellable type water stop tape, 19mm x 25mm thick in linear meter (expansive nature) for construction joints treatment of RCC structure such as raft slab, retaining walls, water storage tank and at the junctions of raft slab with the retaining walls etc.. After cleaning the surface, one coat of required primer for swellable water stop tape shall be applied throughout the length of the joint @3.78 litre per 240 running meter. Over the primed surface swellable type water stop tape shall be placed. The work shall be carried out all complete as per specification and the direction of the engineer-in-charge. The product performance shall carry guarantee for 10 years against any leakage.
7.1.1 Random rubble masonry with hard stone in foundation and plinth including levelling up with cement concrete 1:6:12 (1 cement : 6 coarse sand : 12 graded stone aggregate 20 mm nominal size) up to plinth level with:Cement mortar 1:6 (1 cement : 6 coarse sand)
60.6 PVC WEEP HOLES- Providing weep holes using 75mm dia. PVC pipes working pressure 4kg /sq.cm including cost of materials, conveyance, labour charges etc. complete.
OD316686/2025-2026 Shifting and stacking of excavated earth from site including loading, unloading and stack properly with necessary safety protections and bring back to excavation pits after completion of substructure works as per the direction of Engineer-in-Charge. Lead maximum up to 1 Km. (for measurement - capacity Per Trip 8 cum Net Qty Payable after deduction for looseness 6.4 cum)
26.17 Supplying and laying of drainage composite for use behind walls, between two different fills, alongside drains of road, below concrete lining of canals etc. having thermobonding a draining core - HDPE geonet comprises of two sets of parallel overlayed ribs integrally connected to have a rhomboidal shape with a polyethylene film and a nonwoven geotextile having mass per unit area 130 g/m2 and tensile strength of 8.0 kN/m that will be working as separation or protecting layer, geocomposite having in plane flow capacity of 0.7 L / (m.s) at hydraulic gradient of 1.0 & 20 kPa pressure and tensile strength of 13.5 kN/m , with mass per unit area of 830 gsm, at easily accessible location including top and bottom, with all leads and lifts, manpower and machinery, materials,labour etc. complete and as directed by Engineer - In - Charge.
PRE CAST RCC STRUCTURE
26.74.1 Fabrication and manufacturing of solid precast concrete element with provisions of shear keys, connecting loops, dowel tubes and proper lifting accessories for walls, beams, slabs, stairs, column etc, of various thickness, shape and size of different concrete grades manufactured in controlled factory environment with approved methodology including moulds (Pallet system, Tilts form, table moulds, battery moulds, vertical moulds, beam moulds, column moulds, staircase moulds, Facade mould, etc.), mixing, transporting and placing of concrete, vibrating, curing, finishing, making necessary cutout/ holes of required sizes for services, yard handling & stacking all complete as per IS 11447:1985 and as per approved shop drawings and design mix as per the direction of Engineer-in-Charge (Cost of reinforcement, Mechanical, Electrical and Plumbing inserts will be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately)Concrete grade M-35 (Cement content 370kgs)
26.74.4 Fabrication and manufacturing of solid precast concrete element with provisions of shear keys, connecting loops, dowel tubes and proper lifting accessories for walls, beams, slabs, stairs, column etc, of various thickness, shape and size of different concrete grades manufactured in controlled factory environment with approved methodology including moulds (Pallet system, Tilts form, table moulds, battery moulds, vertical moulds, beam moulds, column moulds, staircase moulds, Facade mould, etc.), mixing, transporting and placing of concrete, vibrating, curing, finishing, making necessary cutout/ holes of required sizes for services, yard handling & stacking all complete as per IS 11447:1985 and as per approved shop drawings and design mix as per the direction of Engineer-in-Charge (Cost of reinforcement, Mechanical, Electrical and Plumbing inserts will be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Extra for using M-60 (Cement content 440kg) instead of M-35
26.73.1.4 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately)Concrete Grade-M-40 (cement content 400 kg ) 200 mm thick hollow core slab
26.76.1 Transportation of Precast Elements by flat bed Trailor (Double / Triple axle 40ft Length with proper accessories like A frame etc) from factory, including the cost of loading, unloading & stacking at site with the help of required capacity cranes.Lead within 15km
26.76.2 Transportation of Precast Elements by flat bed Trailor (Double / Triple axle 40ft Length with proper accessories like A frame etc) from factory, including the cost of loading, unloading & stacking at site with the help of required capacity cranes.Add/Deduct over item 26.76.1 for every additional lead of 5 km
26.77.1 Erection & Installation of Precast/Prestressed Concrete elements in correct & final position with proper line level and plumb at site making all arrangements (i.e cranes, push-pull jacks & all another T & P for lifting Placing & Alignment of elements, within erection tolerance as per IS 15916 as per approved shop drawings and all complete as per the direction of Engineerin-Charge but excluding the cost of sim pads, non shrink grout and steel works i.e hangers. All work up to fifth floor.Prestressed hollow core Slab up to 200mm thickness
OD311069/2025-2026 Extra for Erection & Installation of Precast/Prestressed Concrete elements in correct & final position with proper line level and plumb at site making all arrangements (i.e cranes, push-pull jacks & all another T & P for lifting Placing & Alignment of elements, within erection tolerance as per IS 15916 as per approved shop drawings and all complete as per the direction of Engineerin-Charge but excluding the cost of sim pads, non shrink grout and steel works i.e hangers. All works above 5 floor level .Prestressed hollow core Slab up to 200 mm thickness
26.77.3 Erection & Installation of Precast/Prestressed Concrete elements in correct & final position with proper line level and plumb at site making all arrangements (i.e cranes, push-pull jacks & all another T & P for lifting Placing & Alignment of elements, within erection tolerance as per IS 15916 as per approved shop drawings and all complete as per the direction of Engineer in-Charge but excluding the cost of sim pads, non shrink grout and steel works i.e hangers. All work up to fifth floor.Solid concrete wall elements
26.73.3.1 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Extra for using M-60 (Cement content 440 kg) instead of M-40 100mm thick hollow core slab
26.73.3.2 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Extra for using M-60 (Cement content 440 kg) instead of M-40120mm thick hollow core slab
26.73.3.3 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Extra for using M-60 (Cement content 440 kg) instead of M-40 150mm thick hollow core slab
26.73.3.4 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Extra for using M-60 (Cement content 440 kg) instead of M-40 200mm thick hollow core slab
OD311119/2025-2026 Extra for Erection & Installation of Precast/Prestressed Concrete elements in correct & final position with proper line level and plumb at site making all arrangements (i.e cranes, push-pull jacks & all another T & P for lifting Placing & Alignment of elements, within erection tolerance as per IS 15916 as per approved shop drawings and all complete as per the direction of Engineer in-Charge but excluding the cost of sim pads, non shrink grout and steel works i.e hangers. All work up above fifth floor. Solid concrete wall elements
5.33.2.2 Providing and laying in position ready mixed or site batched design mix cement concrete for reinforced cement concrete work; using coarse aggregate and fine aggregate derived from natural sources, Portland Pozzolana / Ordinary Portland /Portland Slag cement, admixtures in recommended proportions as per IS: 9103 to accelerate / retard setting of concrete, to improve durability and workability without impairing strength; including pumping of concrete to site of laying, curing, carriage for all leads; but excluding the cost of centering, shuttering, finishing and reinforcement as per direction of the engineer-in-charge; for the following grades of concrete. Note: Extra cement up to 10% of the minimum specified cement content in design mix shall be payable separately. In case the cement content in design mix is more than 110% of the specified minimum cement content, the contractor shall have discretion to either re-design the mix or bear the cost of extra cement All work above plinth level upto floor V levelConcrete of M30 grade with minimum cement content of 350 kg /cum
5.38 Extra for R.C.C. /B.M.C/R.M.C. work above floor V level for each four floors or part thereof.
5.22A.6 Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo - Mechanically Treated bars of grade Fe-500D or more
26.75 Providing & laying in position Prestressing steel strands (low relaxation) on hollow core bed by using mechanical pulling arrangement like Rabbit/ Bed master including all accessories for Stressing & destressing operations as per approved make conforming to IS1343 & grade FY-1860 etc, complete as per drawings and direction of Engineer -in-charge.
26.79.1 Providing & Laying of levelling sim pads required sizes (5x5cm to 10x10cm) of PVC / Rubber to adjust level of bearing surface of supporting members as per the direction of Engineer in charge.2mm thick
26.79.2 Providing & Laying of levelling sim pads required sizes (5x5cm to 10x10cm) of PVC / Rubber to adjust level of bearing surface of supporting members as per the direction of Engineer in charge.5 mm thick
26.79.3 Providing & Laying of levelling sim pads required sizes (5x5cm to 10x10cm) of PVC / Rubber to adjust level of bearing surface of supporting members as per the direction of Engineer in charge.10 mm thick
26.80.1 Providing & Grouting of dowel tubes / Shear keys / Joints of precast members with M-60 grade cementitious grout (Non Shrink) of approved make by suitable means ( Free flowing /pump),curing etc. Complete as per directions of Engineer-in-charge. (The payment shall be made on the basis of actual weight of approved grout injected.) Stirrer mixed cementitious grout (non shrink) of approved make in dowel tubes / Shear keys / Joints of precast members.
26.78.1 Providing & Applying weather proof sealant on outer joints of approved make confirming to IS & directed by Engineer-in-charge.Sealant 25mmx10mm at joints
26.73.1.1 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg )100 mm thick hollow core slab
26.73.1.2 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg )120 mm thick hollow core slab
26.73.1.3 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg )150 mm thick hollow core slab
26.73.1.5 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg ) 250 mm thick hollow core slab
26.73.1.6 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg ) 300 mm thick hollow core slab
26.73.1.7 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately)Concrete Grade-M-40 (cement content 400 kg )350 mm thick hollow core slab
26.73.1.8 Fabrication & Manufacturing of Prestressed Hollow Core slab (Hollow area 25 to 30%) of different thickness & modular width 1200 mm in Controlled Factory Environment with approved methodology confirming to IS 10297:1982 by using long line casting method having arrangement of proper steel bed. Concreting should be done by batch mixing plant capable of producing zero slump concrete, transported through automatic shuttels of standard make & layed on bed with the help of extruder/Slipformer, finishing, curing and also provision of steam curing. Cutting, making necessary cutout/holes of required sizes for services in slab element after achieving required strength, yard handling & stacking all complete as per approved shop drawings & design mix as per the direction of the Engineer-in-charge. (Cost of strands should be paid separately). Note: Excess/less cement over the specified cement content used as per design mix is payable/recoverable separately) Concrete Grade-M-40 (cement content 400 kg ) 400 mm thick hollow core slab
BLOCK WORK
OD291428/2025-2026 Providing and laying Autoclaved Aerated concrete (AAC) blocks masonry150mm/230mm/300 mm thick with Grade- I AAC blocks in super structure above plinth level with RCC band at sill level and lintel level with approved block laying polymer modified adhesive mortar all complete as per direction of Engineer-in-Charge. (The payment of RCC band and reinforcement shall be made for seperately).
OD291432/2025-2026 Providing and laying Autoclaved Aerated concrete (AAC) blocks masonry 100 mm/ 125 mm thick with Grade- I AAC blocks of density 551 to 650 Kg/ cum conforming to IS: 2185 (Parts-3) in super structure above plinth level in cement mortar 1:4 (1 cement : 4 coarse sand). The rate includes providing and placing in position 2 Nos 6 mm dia M.S. bars at every third course of masonry work.
OD295420/2025-2026 Half brick masonry with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level .Cement mortar 1:3 (1 cement : 3 coarse sand)
OD295428/2025-2026 Solid block masonry using pre cast solid blocks ( Factory made) of size 30x20x20cm or nearest available size confirming to IS 2185 Part I of 1979 for super structure thickness 20cm and above in: CM 1:6 ( 1 cement : 6 coarse sand) etc complete
6.5 Extra for brick work/ AAC block masonry/Tile brick masonry in super structure above floor V level, for each four floors or part thereof by mechanical means.
PLASTERING
13.7.2 12 mm cement plaster finished with a floating coat of neat cement of mix:1:4 ( 1 cement : 4 fine sand)
13.2.1 15 mm cement plaster on the rough side of single or half brick wall of mix:1:4 (1 cement :4 fine sand)
13.22 Extra for plastering exterior walls of height more than 10 m from ground level for every additional height of 3 m or part thereof.
13.16.1 6 mm cement plaster of mix:1:3 ( 1 cement : 3 fine sand)
13.78 Providing and applying 12 mm thick (average) premixed formulated one coat gypsum lightweight plaster having additives and light weight aggregates as vermiculite / perite respectively conforming to IS : 2547 ( Part - 1 & II) 1976, applied on hacked / uneven background such as bare brick/ block/RCC work on walls & ceiling at all floors and locations, finished in smooth line and level etc. complete.
13.5.1 15 mm cement plaster on rough side of single or half brick wall of mix:1:4 ( 1 Cement : 4 coarse sand)
13.18 Neat cement punning
13.21 Extra for providing and mixing water proofing material in cement plaster work in proportion recommended by the manufacturers.
13.11 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 ( 1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 ( 1 cement : 6 fine sand).
WATER PROOFING
22.23A Providing & Applying polymer modified, flexible cementatious negative side waterproofing coating with elastic waterproofing polymers on interior wall plaster surface in three coats @14.35 kg /10 sqm. one coat of self priming of cementatious waterproofing polymer(dilution with water in the ratio of 1:1) and two coats of cementatious waterproofing polymer (dilution with water in the ratio of 3:1 ) after scrapping and properly cleaning the surface to remove pre-existing paint film and loose particles till plaster is visible, complete in all respect as per the direction of Engineer-in-Charge.
22.22A Providing and applying fibre reinforced elastomeric liquid water proofing membrane with resilient acrylic polymers having Sun Reflectivity Index (SRI) of 105 on top of concrete roof in three coats @10.76 litre/ 10 sqm. One coat of self-priming of elastomeric waterproofing liquid (dilution with water in the ratio of 3:1) and two coats of undiluted elastomeric waterproofing liquid (dry film thickness of complete application/system not less than 500 microns). The operation shall be carried out after scrapping and properly cleaning the surface to remove loose particles with wire brushes, complete in all respect as per the direction of Engineer-in-Charge.
OD295610/2025-2026 Providing and laying water proofing treatment in WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes reparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
22.24A Providing & Applying high quality acrylic modified resin based texture of Dholpur/ Red sand stone Pattern with anti algae and UV resistance properties to be applied as intermediate finish in desired pattern @ 43.04 kgs/10 sqm to form film of 1- 1.5 mm thickness after scrapping and properly cleaning the surface to remove loose particles from the plaster surface, followed by top coating with Premium Acrylic Smooth exterior paint with Silicone additives of required shade by two or more coats @ 1.43 litres/10 sqm, complete as the direction of Engineer -in-Charge
JOINERY WORK
9.1.1 Providing wood work in frames of doors, windows, clerestory windows and other frames, wrought framed and fixed in position with hold fast lugs or with dash fasteners of required dia & length (hold fast lugs or dash fastener shall be paid for separately).Second class teak wood
9.20.1 decorative type, core of block board construction with frame of I st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters.35 mm thick Fixing with hinges of required size and necessary screws (Note: Hinges and necessary screws hall be paid separately)
9.22.1 Extra for Providing and fixing flush doors with decorative veneering instead of non decorative ISI marked flush door shutters conforming to I.S. 2202 ( part I)On one side only
26.86.1 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/ mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately). Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made.Frame size 45 x 70 mm
26.86.5 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid door/window/Ceosetory windows & other Frames/Chowkhat comprising of virgin PVC polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) fabricated with miter joints after applying PVC solvent cement and screwed with full body threaded star headed SS screws having minimum frame density of 750 kg/cum, screw withdrawal strength of 2200 N (Face) & 1100 N (Edge), minimum compressive strength of 58 N/mm2, modulus of elasticity 900 N/ mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixed in position with M.S hold fast/lugs/SS dash fasteners of required dia and length complete as per direction of Engineer-In- Charge. (M.S hold fast/lugs or SS dash fasteners shall be paid for separately). Note: For WPC solid door/window frames, minus 5mm tolerance in dimensions i.e depth and width of profile shall be acceptable. Variation in profile dimensions on plus side shall be acceptable but no extra payment on this account shall be made. Frame size 65 x 100 mm
26.88.1 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid decorative type flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant. WPC to be laminated with PVC foil of minimum 14 microns thick of approved design pasted with hot melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In Charge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately)30 mm thick
26.88.2 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid decorative type flush door shutter of required size comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant. WPC to be laminated with PVC foil of minimum 14 microns thick of approved design pasted with hot melt adhesive on both faces of shutter and fixing with stainless steel butt hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-InCharge. (Note: stainless steel butt hinges and necessary S.S screws shall be paid separately) 35 mm thick
OD314934/2025-2026 Providing and fixing a WPC sliding door of 30 mm thickness with density above 0.70 including sliding fittings and a 50x100 mm thick outer frame. the shutter size shall be100 x 240 cm ( excluding the frame ) . the door shall be fixed properly with all necessary accessories as directed by the engineer in charge. sliding rail (244 cm ) and sliding roller only at the top of the door
9.53 Providing 40x5 mm flat iron hold fast 40 cm long including fixing to frame with 10 mm diameter bolts, nuts and wooden plugs and embeddings in cement concrete block 30x10x15 cm 1:3:6 mix ( 1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
9.70.1 Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete:125x64x1.90 mm
9.82 Providing and fixing bright finished brass hanging type floor door stopper with necessary screws, etc. complete.
9.84 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete.
9.74.1 Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete:250x10 mm
9.74.4 Providing and fixing bright finished brass tower bolts (barrel type) with necessary screws etc. complete:100x10 mm
9.165.1 Providing and fixing bright /matt finished Stainless Steel handles of approved quality & make with necessary screws etc all complete.125 mm
9.77 Providing and fixing bright finished brass 100 mm mortice latch with one dead bolt and a pair of lever handles of approved quality with necessary screws etc. complete
9.170.1 Providing and fixing stainless steel fancy handle of approved make fixed with SS screws etc. complete as per direction of Engineer-in-charge.200 mm
9.171 Providing and fixing stainless steel soft closing spring hinges at 0 degree hinges (hydraulic type) of approved make/brand to cupboard shutters with full threaded steel screws including making necessary recess in board and finished etc. complete as per direction of Engineer-in-charge.
9.174 Providing and fixing 2mm thick 16 to 19mm wide PVC edge binding tape of approved quality for cupboard/wardrobe shutters including necessary synthetic resin hot pressed to edges on binding machine etc. complete as per directions of Engineer in-charge.
21.18 Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and manufacture, including providing and fixing top & bottom pivot & double acting hydraulic floor spring type fixing arrangement and making necessary holes etc. for fixing required door fittings, all complete as per direction of Engineer-in-charge ( Door handle, lock and stopper etc to be paid separately)
21.1.1.2 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately): For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron)
OD315621/2025-2026 Supplying and fixing glazed double door patch fittings, including all costs of materials and labour
OD316142/2025-2026 9.162 A - Providing and fixing factory made ISI marked uninsulated metal fire rated doorset assembly for all non egress application areas like shafts etc consisting of galvanized iron steel frame and double leaf shutter, including necessary hardware accessories conforming to FD 120 UD classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part -1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all four sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 4 numbers at each on vertical sides (up to 2100 mm height) and 2 numbers each on top and bottom sides Door shutter The double skin double leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure slots cut and holes punched, for fixing hardware's with stiffeners as per IS :16074 including resin bonded honey comb paper core infiII material of density 5 kg/cum. Integral astragals to be provided on meeting styles of double leaf door, each on active and inactive leaf The door shutters shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817 both, of minimum size 100x75x3 mm @ minimum 4 numbers hinges per door leaf upto 2100 mm / 2400 mm height or as per test evidence. which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Accessories Hardware Fire doorset shalI be provided with one number fire rated SS 304 grade shaft mortise dead lock, one number 50 mm to 80 mm Back Set with minimum 20mm Square forend with allen key including SS 304 dead strike plate conforming to IS 16015:2022 /EN 12209. Two numbers recessed flush pull handle (SS 104) of minimum size 40 mm x 120 mm One number 300 mm long concealed lever action flush bolt (Dye-Cast Stainless Steel Finish) at bottom with SS dust proof socket and one number minimum 300 mm long concealed flush bolt (Dye-Cast Stainless Steel Finish) at top of inactive leaf of double door, as approved by the Engineer-in-charge. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. Rate shall include for complete fire rated door assembly supply and installation by the approved manufacturer.
OD316147/2025-2026 9.162 B - Providing and fixing factory made ISI marked uninsulated metal fire rated doorset assembly for all non egress application areas like shafts etc consisting of galvanized iron steel frame and single leaf shutter, including necessary hardware accessories conforming to FD 120 UD classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part -1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all four sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 4 numbers at each on vertical sides (up to 2100 mm height) and 2 numbers each on top and bottom sides Door shutter The double skin single leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure slots cut and holes punched, for fixing hardware's with stiffeners as per IS :16074 including resin bonded honey comb paper core infiII material of density 5 kg/cum. The door shutter shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817 both, of minimum size 100x75x3 mm @ minimum 4 numbers upto 2100 mm / 2400 mm height or as per test evidence. which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Hardware Accessories : Fire doorset assembly shalI be provided with one number fire rated SS 304 grade shaft mortise dead lock, one number 50 mm to 80 mm Back Set with minimum 20mm Square forend with allen key including SS 304 dead strike plate conforming to IS 16015:2022 /EN 12209. One number recessed flush pull handle (SS 304) of minimum size 40 mm x 120 mm, as approved by the Engineer-in-charge. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation: The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. Rate shall include for complete fire rated door assembly supply and installation by the approved manufacturer.
OD316146/2025-2026 9.162 C - Providing and fixing factory made ISI marked uninsulated metal fire rated doorset assembly for all egress application areas like utility rooms and service areas consisting of galvanized iron steel frame and double leaf shutter, including necessary hardware accessories conforming to FD 120 UD classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part -1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical sides and 3 numbers on top side Door shutter The double skin doublee leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure slots cut and holes punched, for fixing of hardware with stiffeners as per IS :16074 including resin bonded honey comb paper core infiII material of density 5 kg/cum. Each door leal shall be provided with vision panel, having maximum area of 0.12 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceranic tape having minimum size 13x2 mm to be fixed all around the dlass on both the sides. Integral astragals to be provided for double leaf doors on the meeting style each on both active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817 both, of minimum size 100x75x3 mm @ minimum 5 numbers per leaf upto 2400 mm height or as per test evidence. which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Hardware Accessories : Fire doorset shall provided with one number fire rated SS 304 grade Mortise dead lock. 50-80 mm Back Set, rmnimum 20 mm Square forend with allen key Escutcheon of Stainless Steel, and 65/70 mm cylinder with both side key conforming to IS 16015: 2022/EN12209, two pair of D type Pull handle of SS 304 grade of minimum 22 mm dia Centre to centre distance of 300 mm back to back fixing with spindle. one number 300 mm long Concealed lever action flush bolt (Dye-Cast Stainless Steel Finish) at boaom witñ SS dust proof socket and one number 600 mm long Concealed lever action flush bolt (Dye-Cash Stainless Steel Finish) on top of inactive leaf of double door. Two number fire rated surface mounted heavy duty door closer of size EN 3-5 with standard arm, of desired finish conforming to IS 3564/EN 1154. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shal have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation. The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of worl‹. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer.
OD316145/2025-2026 9.162 D - Providing and fixing factory made ISI marked uninsulated metal fire rated doorset assembly for all egress application areas like utility rooms and service areas consisting of galvanized iron steel frame and single leaf shutter, including necessary hardware accessories conforming to FD 120 UD classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part -1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical sides and 2 numbers on top side Door shutter The double skin single leaf door shutter shall be consisting of minimum 46 mm thick and having box like structure slots cut and holes punched, for fixing of hardware with stiffeners as per IS :16074 including resin bonded honey comb paper core infiII material of density 5 kg/cum. Door leaf shall be provided with vision panel, having maximum area of 0.12 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass pane fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The door shutters shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817 both, of minimum size 100x75x3 mm @ minimum 5 numbers per leaf upto 2400 mm height or as per test evidence. which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Hardware Accessories : Fire doorset shall provided with one number fire rated SS 304 grade Mortise dead lock. 50-80 mm Back Set, minimum 20 mm Square forend with allen key Escutcheon of Stainless Steel, and 65/70 mm cylinder with both side key conforming to IS 16015: 2022/EN12209, one pair of D type Pull handle of SS 304 grade of minimum 22 mm dia Centre to centre distance of 300 mm back to back fixing with spindle. One number 120 minutes fire rated surface mounted heavy duty door closer of size EN 3-5 with standard arm, of desired finish conforming to IS 3564/EN 1154. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation. The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer.
OD316144/2025-2026 9.162 E - Providing and fixing factory made ISI marked partially insulated metal fire rated doorset assembly, for staircase/ exit pathway and refuge areas applications, consisting of galvanized iron steel frame and single leaf shutter, including necessary hardware accessories conforming to FD 120 PI classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity and 30 minutes insulation. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part-1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical sides and 2 numbers on top side Door shutter The double skinned single leaf partially insulated fire rated door shutter shall be consisting of minimum 50 mm thick and having box like structure slots cut and holes punched, for fixing of hardware with stiffeners as per IS :16074 including resin bonded mineral wool/ ceramic wool infill material of density 96 kg/cum. Door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass panel fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaf. The door shutter shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817, of minimum size 100x75x3 mm @ minimum 5 numbers hinges upto 2400 mm height or as per test evidence. which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Hardware Accessories : Fire doorset shall provided with one number of Signle point Panic push bar (cross bar) device of desired finish as per EN 1125 and one number external trim including half cylinder of 42 mm long with one side key as per EN 1125. One number 120 minutes fire rated surface mounted heavy duty door closer of size EN 3-5 with standard arm, of desired finish (suitable upto 1250 mm door width) conforming to IS 3564/EN 1154. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation. The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer.
OD316143/2025-2026 9.162 F - Providing and fixing factory made ISI marked partially insulated metal fire rated doorset assembly, for staircase/ exit pathway and refuge areas applications, consisting of galvanized iron steel frame and double leaf shutter, including necessary hardware accessories conforming to FD 120 PI classification of IS: 3614 : 2021 with fire rating of 120 minutes integrity and 30 minutes insulation. The door frame and shutter shall be made out of minimum 1.20 mm thick GI Sheet with minimum 120 GSM Zinc coating as per IS:277. The entire fire rated doorset assembly shall be tested in unlatched condition as per IS: 17518 (Part-1): 2022 Frame The frame shall be of minimum size 90 x 60 mm with grooved profile to take appropriate fire rated smoke seal having mitred cut joints (self tab/screwed assembled at site) and provided with appropriate reinforcement suitable for taking hardware and flush fixing as per IS:4351. The smoke seal material shall be of EPDM tested in accordance with/ASTM E-84 of minimum size 10 mm x 4 mm fixed within the inbuilt groove or stuck with adhesive on the entire perimeter of the frame. The door frame shall be fixed in all three sides to masonry wall opening with CSK/Hex headed fastener of minimum 8 mm dia size and minimum 80 mm long with 8mm dia polyamide sleeves @ 5 numbers at each on vertical sides and 3 numbers on top side Door shutter The double skinned double leaf partially insulated fire rated door shutter shall be consisting of minimum 50 mm thick and having box like structure slots cut and holes punched, for fixing of hardware with stiffeners as per IS :16074 including resin bonded mineral wool/ ceramic wool infill material of density 96 kg/cum. Each door leaf shall be provided with vision panel, having maximum area of 0.06 sqm, of 120 minute fire rated minimum 6 mm thick clear borosilicate glass panel fixed with clip-on arrangement and fire rated ceramic tape having minimum size 13x2 mm to be fixed all around the glass on both the sides. The intumescent seal of minimum size 15x1.5 mm or of size as per test evidence shall be fixed on all the three edges of the door leaf. Integral astragals to be provided for double leaf door on the meeting style each on active and inactive leaf. The door shutters shall be mounted on the frame with SS 304 grade ball bearing bull hinges as per EN 1935:2002 or butt hinges as per IS :12817, of minimum size 100x75x3 mm @ 5 numbers hinges upto 2400 mm height or as per test evidence, which ever is more, fixed with M6 25 screws AII doors shall be factory prepared for receiving appropriate hardware and provided with necessary reinforcement for hardware accessories. Hardware Accessories : Fire doorset assembly shall provided with one number of Single point Panic push bar (cross bar) for active leak and one number double point panic push bar (cross bar) with bottom strike of desired finish with verticle shoot bolts on top and bottom of inactive leaf of double leaf door as per EN 1125 and one number external trim with half cylinder 42 mm long with one side key as per EN 1125. two number 120 minutes fire rated surface mounted heavy duty door closer of size EN 3-5 with standard arm, of desired finish (suitable upto 1250 mm door width) conforming to IS 3564/EN 1154 and one number surface mounted door coordinator for sequencing of closing. Finishing: Both frame and door shutters shall be factory finished with polyester powder coating of minimum 50 microns thick and shall have passed salt spray test as per IS:13871 of approved colour and shade all complete as per manufacturer's specifications and as per direction of the Engineer-in-charge. Installation. The hollow space in the door frame shall be filled / injected with fire rated self extinguishing type polyurethane foam (PUF) after installation at site of work. The rate shall be inclusive of complete fire rated door assembly, supply and installation by the approved manufacturer.
26.89.1 Providing and fixing factory made single extruded WPC (Wood Polymer Composite) solid board one side white color and other side of board laminted with PVC foil of minimum 14 micron thickness of approved design pasted with hot melt adhesive for cup boards, work stations and bathroom/kitchen cabinet etc. of required sizes comprising of virgin polymer of K value 58-60 (Suspension Grade), calcium carbonate and natural fibers (wood powder/ rice husk/wheat husk) and non toxic additives (maximum toxicity index of 12 for 100 gms) having minimum density of 650 kg/cum and screw withdrawal strength of 1800 N (Face) & 900 N (Edge), minimum compressive strength 50 N/mm2, modulus of elasticity 850 N/mm2 and resistance to spread of flame of Class A category with property of being termite/borer proof, water/moisture proof and fire retardant and fixing with stainless steel piano hinges/soft close clip on concealed hinges of required size with necessary full body threaded star headed counter sunk S.S screws, all as per direction of Engineer-In Charge. (Note: stainless steel piano hinges/soft close clip on concealed hinges and necessary S.S screws shall be paid separately) 18 mm thick
10.6.1 Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters.80x1.25 mm M.S. laths with 1.25 mm thick top cover
10.7 Providing and fixing ball bearing for rolling shutters.
10.9 Extra for providing grilled rolling shutters manufactured out of 8 mm dia M.S. bar instead of laths as per design approved by Engineer -in-Charges, (area of grill to be measured).
FLOORING
11.4 52 mm thick cement concrete flooring with concrete hardener topping, under layer 40 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand: 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate 6mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufacturer's specifications. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete
11.5 62 mm thick cement concrete flooring with concrete hardener topping, under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) and top layer 12 mm thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2 graded stone aggregate, 6 mm nominal size) by volume, hardening compound mixed @ 2 litre per 50 kg of cement or as per manufactures specification. This includes cost of cement slurry, but excluding the cost of nosing of steps etc. complete.
OD290244/2025-2026 Providing and fixing Vitrified wall tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 1200x6 00 mm Providing and laying Glazed vitrified tile flooring 1200 mm x 600 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade &laying pattern as per drawing with 3mm spacer joints including grouting the joints with approved epoxy resin based grout of approved make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete. Basic tile rate of Rs 150/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD290248/2025-2026 Providing and fixing Vitrified wall tiles in different sizes (thickness to be specified by manufacturer in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand. With Glazed vitrified tile of size1600 mm x 800 mm anti skid or glossy tiles of approved shade & laying pattern as per drawing with 3mm spacer joints including grouting the joints with approved epoxy resin based grout of of approved make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete.. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD314772/2025-2026 Providing and fixing Vitrified wall tiles indifferent sizes (thickness to be specified by manufacturer), with water absorption less than 0.08 % and conforming to I.S. 15622, of approved make, in all colours & shade, in skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand), including grouting the joint with white cement & matching pigments etc. complete. Size of Tile 1200x6 00 mm Providing and laying Glazed vitrified tile flooring 1200 mm x 600 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade & laying pattern as per drawing with 3mm spacer joints including grouting the joints with approved epoxy resin based grout of of approved make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete. Basic tile rate of Rs 160/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD290160/2025-2026 Providing and laying Glazed vitrified tile flooring 2400 mm x 1200 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade & laying pattern as per drawing in flooring with 3mm spacer joints, laid on 20mm thick cement mortar 1:4 (1 cement: 4 coarse sand) including grouting the joints with approved epoxy resin based grout of approved make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete. Basic tile rate of Rs 250/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD290189/2025-2026 Providing and laying Glazed vitrified tile flooring 1200 mm x 600 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade & laying pattern as per drawing in flooring with 3mm spacer joints, laid on 20mm thick cement mortar 1:4 (1 cement: 4 coarse sand) including grouting the joints with approved epoxy resin based grout of MYK Laticrete or equivalent make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete. Basic tile rate of Rs 100/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD290192/2025-2026 Providing and laying Glazed vitrified tile flooring 1600 mm x 800 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade & laying pattern as per drawing in flooring with 3mm spacer joints, laid on 20mm thick cement mortar 1:4 (1 cement: 4 coarse sand) including grouting the joints with approved epoxy resin based grout of MYK Laticrete or equivalent make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed & disposed of out of the site after completion, etc., complete. Basic tile rate of Rs 140/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
OD290230/2025-2026 Providing and laying Glazed Vitrified tile flooring 1600 mm x 800 mm anti skid or glossy tiles as per requirement with 3mm Spacers. Approved brand of vitrified tiles of approved shade & laying pattern as per drawing in flooring with 3mm spacer joints, laid on 20mm thick cement mortar 1:4 (1 cement: 4 coarse sand) including grouting the joints with approved epoxy resin based grout of approved make and matching pigments, etc. with water absorption less than 0.08%and conforming to IS:15622, of approved, make, in all colors and shades cleaned & washed with a suitable effective Cleaning agent or any suitable means as per instructions of EIC, covering to protect tile with 275 GSM # 2 mm thick Floor guard make joints to be taped, should remain intact till handing over, removed disposed of out of the site after completion, etc., complete. Basic tile rate of Rs100/sqft to be considered. The quoted rates shall include the cost of laying tiles at the proper level wherever required, including cutting of tiles for borders, patterns, etc, complete in all respects as per details. The work shall be executed strictly in accordance with the drawings issued by the architect and verified by the engineer in charge. All debris shall be cleared from the site, which shall be within the contractor's scope. The rate shall also include the cost and conveyance of all materials, labour, lead, lift etc as directed by the Engineer in-charge
11.55.1 Providing and laying flamed finish Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing, curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge :Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat Eye or equivalent.
11.56.1 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge. Polished Granite stone slab colour of Black, Cherry/Ruby Red or equivalent
8.2.2.2 Providing and fixing 18 mm thick gang saw cut, mirror, polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations, of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 ( 1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels.Area of slab over 0.50 sqm
16.91.1 Providing and laying factory made chamfered edge Cement Concrete paver blocks in footpath, parks, lawns, drive ways or light traffic parking etc, of required strength, thickness & size/ shape, made by table vibratory method using PU mould, laid in required colour & pattern over 50mm thick compacted bed of sand, compacting and proper embedding/laying of inter locking paver blocks into the sand bedding layer through vibratory compaction by using plate vibrator, filling the joints with sand and cutting of paver blocks as per required size and pattern, finishing and sweeping extra sand. complete all as per direction of Engineer-in-Charge.60mm thick cement concrete paver block of M-35 grade with approved colour, design & pattern.
11.54.1 Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of: a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on the G.I. Base plate of size 100mmx100mmx3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5mm welded with GI fully threaded stud 16 mm outer diameter with two GI check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug. b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80 mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge. c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Guages: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with light weight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm. The panel is to withstand a Concentrated Load of 363 Kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50 kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product.300 mm Finished Floor Height (FFH).
11.54.2 Providing and fixing removable raised/false access flooring with system and its components of approved make for different plenum height with possible height adjustment upto 50 mm, comprising of modular load bearing floor panels supported on G.I. rectangular stinger frame work and G.I. Pedestal etc. all complete, as per the architectural drawings, as specified and as directed by Engineer-in-charge consisting of: a) Providing at required spacing to form modular framework, pedestals made out of GI tube of thickness minimum 2 mm and 25 mm outer diameter, fully welded on the G.I. Base plate of size 100mmx100mmx3mm at the bottom of the pedestal tube, G.I. pedestal head of size 75mmx75mmx3.5mm welded with GI fully threaded stud 16 mm outer diameter with two GI check nuts screwed on the stud for level adjustment upto 50mm, locking and stabilizing the pedestal head in position at the required level. The pedestals shall be fixed to the subfloor (base) through base plate using epoxy based adhesive of approved make or the machine screw with rawl plug. b) Stringers system in all steel construction hot dipped galvanized of rectangular size 570x20x30x0.80 mm thick having holes at both ends for securing the stringers on to the pedestal head using fully threaded screws ensuring maximum lateral stability in all directions, the grid formed by the pedestal and stringer assembly shall receive the floor panel, this system shall provide adequate solid, rigid support for access floor panel, the system shall provide a minimum clear uninterrupted clearance between the bottom of the floor for electrical conduits and wiring etc. all complete as per the architectural drawings, as specified and as directed by the Engineer-in-charge. c) Providing and fixing Access Floor panel of 600x600x32 mm medium grade Filled Steel anti static high pressure Lamination of 800H grade (FS800H). Access Floor panel shall be steel welded construction with an enclosed bottom pan with uniform pattern of 64 hemispherical cones. The top and bottom plates of Steel Guages: top 0.6 mm and bottom 0.7 mm fused spot welded together (minimum 64 welds in each dome and 20 welds along each flange). The panel should be Corroresist epoxy coated for lifetime rust protection and cavity formed by the top and bottom plate is filled with Pyrogrip noncombustible Portland cementitious core mixed with light weight foaming compound. The access floor shall be factory finished with Anti-static High Pressure laminate with Non Warp technology upto 1mm thickness for superior adhesion and Surface flatness within 0.75mm. The panel is to withstand a Concentrated Load of 363 Kgs applied on area 25mm x 25mm without collapse in the centre of the panel which is placed on four steel blocks. The panel will withstand and Uniformly Distributed Load (UDL) minimum 1250 kg/sqm and an impact load of 50 kg all complete as per the approved manufacturers specification and as per the direction of Engineer-in-charge. All specification must be printed on the side of the panel to ensure the quality of the product.450 mm Finished Floor Height (FFH).
MISCELLANEOUS ITEMS
10.26.3 Providing and fixing hand rail of approved size by welding etc. to steel ladder railing, balcony railing, staircase railing and similar works, including applying priming coat of approves steel primer.G.I. pipes
10.28 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.)
OD314381/2025-2026 Providing and fixing glazed hand rail of approved size by welding etc. with toughened laminated glass of thickness 6 + 0.75 + 6 mm PVB of brand Saint Gobain or equivalent and SS 304 grade top rail and balustrade. including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the samewith necessary stainless steel nuts and bolts complete, i/c fixing the railing withnecessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge
12.45.3 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum moisture resistant board.
12.52.2 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mmcenter to center and cross "T" of size 24x25 mm made of 0.30 mm thick(minimum) sheet, 1200 mm long spaced between main "T" at 600 mm center to center to form a grid of 1200x600 mm and secondary cross "T" of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main"T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.GI Metal Ceiling Lay in perforated Tegular global white color tiles of size 595x595 mm and 0.5mm thick with 8 mm drop; made of GI sheet having glavanizing of 100 gms/ sqm (both sides inclusive) and 20% perforation area with 1.8 mm dia holes and having NRC (Noise Reduction Coefficient) of 0.5, electro statically polyster powder coated of thickness 60 microns (minimum), including factory painted after bending and perforation, and backed with a black Glass fiber acoustical fleece.
12.52.3 Providing and fixing tiled false ceiling of approved materials of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanized steel sections (galvanized @ 120 grams per sqm, both side inclusive) consisting of main 'T' runner with suitably spaced joints to get required length and of size 24x38 mm made from 0.30 mm thick (minimum) sheet, spaced at 1200mm center to center and cross 'T' of size 24x25 mm made of 0.30 mm thick (minimum) sheet, 1200 mm long spaced between main 'T' at 600 mm center to center to form a grid of 1200x600 mm and secondary cross 'T' of length 600 mm and size 24x25 mm made of 0.30 mm thick (minimum) sheet to be interlocked at middle of the 1200x600 mm panel to form grids of 600x600 mm and wall angle of size 24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, required cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke detectors etc. Main 'T' runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x 25 x 1.6 mm fixed to ceiling with 12.5mm dia and 50 mm long dash fasteners, 4 mm GI adjustable rods with galvanised butterfly level clips of size 85x 30x 0.8 mm spaced at 1200 mm center to center along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester paint, all complete for all heights as per specifications, drawings and as directed by Engineer -in-charge.12.5 mm thick square edge PVC Laminated Gypsum Tile size 595x595 mm made of Gypsum plasterboard, manufactured from natural gypsum as per IS 2095 part I and laminated with white 0.16 mm thick fire retardant PVC film on the face side and 12 micron metalized polyster on the back side with all edges sealed with the face side PVC film which goes around and wraps the edges and is bonded to the edges and the back side metalized polyster film so as to make the tile a completely sealed unit.
OD289284/2025-2026 "Restroom Cubicles Providing & fixing approved mae - Fuse-In Restroom Cubicle (of following standard dimension which includes 600mm door size width) self-supporting 12mm thick compact laminates made out of, urea free, thermosetting phenolic resins treated Kraft papers as core material and Amino plastic resin treated decor papers on the finish surface, conforming to latest and applicable IS: 2046-1995, EN 438:2016 and NEMA LD3-2005 quality standards with Antivirus, Antibacterial and Antifungal properties (conforming to ISO 21702:2019, JIS Z2801:2010 and ASTM G21-2015standards respectively) to fulfil the applicable requirements of indoor air quality certifications for Greenguard-Gold standards. This also includes providing and fixing in position necessary hardware made out of Aluminium 6063 -T6 in Charcoal black anodised finish & Zinc Diecasted Charcoal black/Antique gold anodised finish hardwares as per manufacturer's specifications & Architects instructions like (1) SS grade 316 Spring loaded hinges in black powder coated finish with antique gold lacquered hinge covers (2) Anodized metallic antique Gold finish over Zinc die casted black charcoal finsh slide Bolt with Occupancy indicators (3) Coat hook in Anodized Antique Gold Finish on zinc Die casted body and fine spark texture on pvc parts (4) Aluminium U & F- profiles with snap fit Screw Cover made from aluminium alloy grade 6063-T6, Anodized in Charcoal black color in matte finish (5) Zinc die casted adjustable foot ( Mid Panel Mounted or Divider Setback Leg) in dual color finish of Charcoal black and Antique gold color (6) Top rail with end cap is a Box shaped Extrusion made of aluminium alloy grade 6063-T6 in charcoal color Anodized matte finish,which will get fixed with pilasters with SS Screws, (7) Rubber noise deafening tape, (8) Screws & wall Plugs ( SS- 316 ). All screws will of 316 Grade in stainless steel. All pilasters ares upported by Zinc diecasted charcoal black/anitque gold anodize finish with Mid panel mounted Set Back Leg /divider mounted straight leg, anchored to the floor with a ground clearance upto 100 to 150mm. "Toilet Cubicle with standard dimension of 1985mm Height x 1000mm Width x 1500mm Depth, which includes 600mm door size width).
OD289432/2025-2026 Urinal partition with 12mm thick compact laminate total ht 1195mm, depth 450 gap from ground 500 to 600 mm as per the drawing.
10.2 Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete.
10.25.2 Item Shifted to Sub head 14 as item 14.73 Item Shifted to head 14 as item 14.74 Steel work welded in built up sections/framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required.In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works
12.64.1 Providing & fixing at all heights, levels and locations Mill finish Aluminium alloy roofing sheets of alloy IS designation 31500, temper Hx8 conforming to IS 737 and dimensions as per IS code 2676 with characteristics of good formability and corrosion resistance. The profile sheets shall be fixed to truss members in slope or required pitch or curvature with Hex cap headed self drilling/tapping Stainless steel screws M6, 50 mm long with 3 mm EPDM seal washer etc. all inclusive of labour, scaffolding, T&P and sundries etc. complete as per directions of the Engineer-In-Charge. (Cost of truss/frame work shall be paid separately). 0.56 mm, Aluminum troughed profile with center to center pitch of 200 mm, depth of 32 mm, overall profile width1092 mm, cover width 1000mm.
12.34 Providing and fixing thermal insulation of ceiling (under deck insulation) with Resin Bonded Fibre glass wool conforming to IS: 8183, density 24 kg/m3, 50 mm thick, wrapped in 200 G Virgin Polythene bags, fixed to ceiling with metallic cleats (50x50x3 mm) @ 60 cm and wire meh of 12.5 mm x 24 gauge wire and mesh, for top most ceiling of builing .
OD314404/2025-2026 Exterior Grade Wooden finish composite ceiling - Vox or equivalent Infratop false ceiling manufactured in europe, of panel sizes of 340mmx 2700mm, durable and resistant to moisture, water and borer-fungus-termite attack. Panels to be installed with GI sections of suitable gauge & size according to site conditions. Panels SV 08/07 & 09 with suitable trims SV 15 J TRIM with dimensions 40x19x22x12x3050 (all in mm) for edge profiles and SV 18 T TRIM with dimensions 67x3050 mm with T head of 42mm for Connecting profiles. Panels must be maintainance free, rust proof and are 100% Water proof. Advised especially for Soffit areas, under the roof installation.
OD317304/2025-2026 Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete.
OD317936/2025-2026 Supply and application of fire stop acrylic type sealant in gap between chequered plate and plate support in various service ducts, and if required ,sandwiching with mineral wool of minimum 70kg/m3 density as base for sealant application , complete as required
OD317942/2025-2026 Supply and installation of Fire Barrier Mortar with minimum 2 hours fire rating when tested in accordance with UL 1479 standards, for fire rated openings in ducts made of metal/concrete partition, after passing service lines like cables, conduits, cable trays, metal pipes. The mortar shall be light weight cementitious product and shall carry test certificate in accordance with IEC 60068-2-57:1999-11 ( Environmental testing) as per part 2-57: Test for vibration time history method
OD317995/2025-2026 Providing and fixing of MS chequered plate 3mm thick for duct closing etc. welding to MS angle 50 X 50 X 6 mm support frame work. Painting the same with Zinc Chromate primer etc.
PAINTING
13.85.3 Applying priming coats with primer of approved brand and manufacture, having low VOC ( Volatile Organic Compound) content.With water thinnable cement primer on walls surface having VOC content less than 50 grams / litre
OD313193/2025-2026 Providing and applying white cement based putty of average thickness 2 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete
13.45.1 Finishing walls with textured exterior paint of required shade:New work (Two or more coats applied @ 3.28 ltr/ 10 sqm ) over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm
13.48A.1 Finishing walls with 100% Premium acrylic emulsion paint having VOC less than 50 gm/litre and UV resistance as per IS 15489:2004, Alkali & fungal resistance, dirt resistance exterior paint of required shade (Company Depot Tinted) with silicon additives.New work (Two or more coats applied @ 1.43 litre/ 10 sqm. Over and including priming coat of exterior primer applied @ 0.90 litre/10 sqm.
13.83.2 Wall painting with premium acrylic emulsion paint of interior grade, having VOC (Volatile including applying additional coats wherever required to achieve even shade and colour.Two coats
13.116 Polishing in high gloss/matt finish melamine clear polish on wood work in required color/wooden shade texture with following process in the sequence as detailed below: 1. The surface to be polished is rubbed with sand paper 80/120 no. and then with sand paper of 160/180 nos. 2. Applying two coats of sealer with spray gun and allowing sufficient drying time for 1st coat and 2nd coat is allowed to dry for 8 to 12 hrs. 3. On drying of sealer coat, wet rubbing with emery cloth of finer grading with ample water to remove excess sealer layer and make the surface further smooth after this wet rubbing, then surface is applied with special grade melamine fillers to fill all the small and big holes/grooves etc. Filler coat to be allowed to dry for 4 to 6 hrs on which again a light wet rubbing is done this surface is further allowed to dry for 12 hrs. 4. On this, 1st coat of melamine polish is applied with spray gun using melamine clear polish and melamine thinner in required proportion. This 1st coat is allowed to dry for 24 hrs then this dry surface is again fine wet rubbed smooth, which is further allowed to dry for 12 hrs. The final melamine polish is applied with compressor pressure spray gun using melamine clear polish and melamine thinner mixed in required proportion complete as per direction of Engineer-in-Charge. (Final coat to be done in 1 or 2 layers without gap of time.)
13.61.1 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work
13.43.1 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer
13.52.1 Finishing with Epoxy paint (two or more coats) at all locations prepared and applied as per manufacturer's specifications including appropriate priming coat, preparation of surface, etc. complete.On steel work
FAÇADE WORKS
25.1 Providing and supplying aluminium extruded tubular and other aluminium sections as per the architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA 2604 of required colour and shade as approved by the Engineer-in-Charge. ( The item includes cost of material such as cleats, sleeves, screws etc. necessary for fabrication of extruded aluminium frame work. Nothing extra shall be paid on this account).The weight of aluminum extruded section shall be taken for purpose of payment
25.2 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cumsmoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation & drainage and protection against fire hazard including: b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineer-in- Charge. Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub-head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places. Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories 1. Performance Laboratory Test for Air Leakage Test (-50pa to ? 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 mVhr? 2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testing method for a range up to 2000 ml.? 3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01-05 testing method for a range upto 2000 ml? 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm? 5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test? Tests to be conducted on site 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000ml?
25.3 Providing, assembling and supplying vision glass panels (IGUs) comprising of hermetically-sealed 6-12- 6 mm insulated glass (double glazed) vision panel units of size and shape as required and specified, comprising of an outer heat strengthened float glass 6mm thick, of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade, an inner Heat strengthned clear float glass 6mm thick, spacer tube 12mm wide, dessicants, including primary seal and secondary seal (structural silicone sealant) etc. all complete for the required performances, as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge. The IGUs shall be assembled in the factory/ workshop of the glass processor. (Payment for fixing of IGU Panels in the curtain glazing is included in cost of item No.26.2) For payment, only the actual area of glass on face # 1 of the glass panels (excluding the areas of the grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 degree K etc. The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement
25.4 Extra for openable side / top hung vision glass panels (IGUs) including providing and supplying at site all accessories and hardwares for the openable panels as specified and of the approved make such as heavy duty stainless steel friction hinges, min 4 - point cremone locking sets with stainless steel plates, handles, buffers etc. including necessary stainless steel screws/ fasteners, nuts, bolts, washers etc. all complete as per the Architectural drawings, as per the approved shop drawings, as specified and as directed by the Engineer-in-Charge.
25.5 Providing,fabricating and supplying shadow box of required size and shape, for fixing in the spandrel portion of the structural glazing, in linear as well as curvilinear portions of the building by providing semi - rigid, inorganic, non- combustible fibre glass wool insulation 50 mm thick, conforming to IS: 8183 and BS: 3958 part 5. The insulation layer shall have facing (factory bonded on surface # 1 of the fibre glass insulation layer), of black non-woven fibre glass tissue of nominal thickness 0.5mm and nominal mass not less than 60 gm/ sqm, made of randomly oriented glass fibres distributed in a binder by a wet-lay process including fixing 1.5 mm thick solid aluminum sheet backing using, 6 mm thick cement board including SS rivets, nuts,bolts, washers etc complete.
25.6 Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc., all complete for the required performance as specified, as per the architectural drawings, as per the approved shop drawings, as specified, and as directed by the Engineer- in - Charge. For payment, only the actual area of glass on face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided and fixed in position, shall be measured in sqm. (Payment for fixing of Spandrel Glass panels in the curtain glazing is included in cost of relevent item*). (i) Coloured tinted float glass 6mm thick substrate with reflective soft coating on face # 2, having properties as visible Light transmittance (VLT) of 25 to 35 %, Light reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and U value of 3.0 to 3.3 W/m2 K etc. .The properties of performance glass shall be decided by technical sanctioning authority as per the site requirement.
25.8 Design supply installation of suspended Spider Glazing system designed to withstand the wind pressure as per IS 875 (Part-III). The Suspended System held with Spider Fittings of SS-316 Grade Steel of approved manufacturer with glass panel having 12 mm thick clear toughened glass held together with SS- 316 Grade Stainless steel Spider & bolt assembly with laminated glass fins 21 mm thick. The Glass fins and glass panel assembly shall be connected to Slab/beams by means of SS- 316 Grade stainless steel brackets & Anchor bolts and at the bottom using SS channel of 50x25x2mm using fastener & anchor bolts, non staining weather sealants of approved make, Teflon/ nylon bushes and separators to prevent bi-metallic contacts, all complete to perform as per specification and approved drawings. The complete system to be designed to accommodate thermal expansion & seismic movements etc. The joints between glass panels (6 to 8 mm) and gaps at the perimeter & in U channel of the assembly to be filled with non staining weather sealant, so as to make the entire system fully water proof & dust proof. The rate shall include all design, Engineering and shop drawing including approval from structural designer, labour, T&P, scaffolding, other incidental charges including wastage, enabling temporary services all fitting fixers nut bolts, washer, Buffer plates, fastener, anchors, SS channel laminated glass etc. all complete. For the purpose of payment, actual elevation area of Glazing including thickness of joints and the portion of Glass panel inside the SS channel shall be measured.
10.16.3 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Electric resistance or induction butt welded tubes
OD293995/2025-2026 Supply and fixing of Luxalon® Green Pro certified Aluminum BD Ventilated Façade / Louver System manufactured by M/s. Hunter Douglas India Pvt. Ltd. or equivalent of approved color consisting of panel 50 mm wide x 100mm depth x 0.6mm thick panel length up to 4mtrs coil coated on a continuous paint line double baked and roll formed from enameled corrosion Resistance /powder coated pre-treated inhouse with latest nano technology process and electro statically powder coated with automatic Carona system and cured with gas catalytic technology for good bonding and high coating strength using Aluminum Alloy AA3105/3005 for higher strength. Panels shall be mounted in a 50 mm clear (100mm center to center) spacing on a Mulion profile with 1.2mm GI by means of Locking Clip and Pop Rivet. Mullion rofile shall be fixed at 200 mm from panel ends and at a distance of maximum 1500 mm center to center across the panel span as per HD Wind load graph and Slotted Fastening Profile shall be fixed to a suitable sub- structure(by others). All properties and specifications shall comply with ECCA directives and more specifically EN 1396:1996. The system should meet the required standards for Green Pro certification and should qualify as green product as per CII green products and services council. The manufacturer should be ISO 9001:2015 Quality Management System Certification compliant with in house testing facility and should have their own manufacturing plant in India.
OD294003/2025-2026 Supply, installation, testing, and commissioning of Aluminium Kinetic / Dynamic Facade System manufactured by an approved and reputed façade system manufacturer,comprising single-skin aluminium dynamic panels of size 150 mm × 200 mm, manufactured from minimum 0.7 mm thick aluminium, suitable for external façade applications in public transport infrastructure such as bus terminals, depots, and transit buildings. The aluminium façade panels shall be plain windscreen type panels, factory finished in Color Coated PVDF (CCPVDF) Dark Grey, with a minimum 25-micron fluorocarbon coating, providing high resistance to UV radiation,corrosion, and colour fading under Indian climaticc onditions. All panels shall be manufactured using advanced CAD/CAM controlled production lines with strict quality control to ensure uniformity, dimensional accuracy,and smooth edges free from burrs or distortions. The kinetic façade system shall be mounted on a customized aluminium carrier system of minimum 2.0 mm thickness, with section size 49 × 52 × 39 × 16 mm, designed to support dynamic movement while maintaining structuralstability. The system shall incorporate customized aluminium T-tracks, precis ion-extruded and factory alignedto ensure smooth, controlled movement and consistent panel positioning during operation. The supporting sub- frame shall consist of aluminium Lbrackets of size 75 × 75 × 3 mm with 30 mm projection, used as secondary fixing elements, in combination with mild steel L- brackets of size 75 × 75 × 4 mm and 75 mm length, fixed at 1700 mm centre-to- centre spacing to the RCC or steel structure. All mild-steel components shall be hot- dip galvanized or zinc coated with a minimum coating thickness of 80 microns for long-term corrosion protection. All connections shall be carried out using M8 × 50 mm bolts, M8 nuts, and M8 washers, manufactured from stainless steel or approved corrosion-protected steel, suitable for permanent external exposure. Aluminium pop rivets of size 6 mm × 12 mm shall be used for fixing aluminum panels tocarriers. Bi- metallic PVC separators of 1.0 mm thickness and size 75 × 75 mm shall be provided at all aluminium- tosteel interfaces to prevent galvanic corrosion.
OD294007/2025-2026 Signage Board fabrication, erection and installation of with Astari Imorted Acrylic with light & Aluminium Channelium beeding (234.6x1018 cm) including all cost of materials and labour etc. complete as per the direction of Engineer in charge.
OD315629/2025-2026 Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized system of structural glazing (with open joints) for linear as well as curvilinear portions of the building for all heights and all levels, including: a) Structural analysis & design and preparation of shop drawings for the specified design loads conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind pressure without any failure), including functional design of the aluminum sections for fixing glazing panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws, toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-cumsmoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation &drainage and protection against fire hazard including: b) Fabricating and supplying serrated M.S. hot dip galvanised / Aluminium alloy of 6005 T5 brackets of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving perfect verticality and fixing structural glazing system rigidly to the RCC/ masonry/structural steel framework of building structure using stainless steel anchor fasteners/ bolts, nylon seperator to prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required capacity and in required numbers. c) Providing and filling, two part pump filled, structural silicone sealant and one part weather silicone sealant compatible with the structural silicone sealant of required bite size in a clean and controlled factory / work shop environment , including double sided spacer tape, setting blocks and backer rod, all of approved grade, brand and manufacture, as per the approved sealant design, within and all around the perimeter for holding glass. d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes, shapes and profiles, as required as per the site conditions, to seal the gap between the building structure and all its interfaces with curtain glazing to make it watertight. e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make it watertight, by incorporating principles of pressure equalization, providing suitable gutter profiles at bottom (if required), making necessary holes of required sizes and of required numbers etc. complete. This item includes cost of all inputs of designing, labour for fabricating and installation of aluminium grid, installation of glazed units, T&P, scaffolding and other incidental charges including wastages etc., enabling temporary structures and services, cranes or cradles etc. as described above and as specified. The item includes the cost of getting all the structural and functional design including shop drawings checked by a structural designer, dully approved by Engineer-in-charge. The item also includes the cost of all mock ups at site, cost of all samples of the individual components for testing in an approved laboratory, field tests on the assembled working structural glazing as specified, cleaning and protection till the handing over of the building for occupation. In the end, the Contractor shall provide a water tight structural glazing having all the performance characteristics etc. all complete as required, as per the Architectural drawings, as per item description, as specified, as per the approved shop drawings and as directed by the Engineerin- Charge. Note:- 1..The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire mesh shall be paid for separately under relevant items under this sub-head. However, for the purpose of payment, only the actual area of structural glazing (including width of grooves ) on the external face shall be measured in sqm. up to two decimal places. Note:-2. The following performance test are to be conducted on structural glazing system if area of structural glazing exceeds 2500 Sqm from the certified laboratories accreditated by NABL(National Accreditation Board for Testing and Calibration Laboratories), Department of Science & Technologies, India. Cost of testing is payable separately. The NIT approving authority will decide the necessity of testing on the basis of cost of the work, cost of the test and importance of the work. Performance Testing of Structural glazing system Tests to be conducted in the NBL Certified laboratories 1. Performance Laboratory Test for Air Leakage Test (-50pa to 300pa) & (+50pa to +300pa) as per ASTM E-283-04 testing method for a range of testing limit 1 to 200 m 2. Static Water Penetration Test. (50pa to 1500pa) as per ASTME- 331-09 testing method for a range up to 2000 ml.3. Dynamic Water Penetration (50pa to 1500pa) as per AAMA 501.01-05 testing method for a range upto 2000 ml 4. Structural Performance Deflection and deformation by static air pressure test (1.5 times desing wind pressure without any failure) as per ASTME-330-10 testing method for a range upto 50 mm 5. Seismic Movement Test (upto 30 mm) as per AAMA 501.4-09 testing method for Qualitative test? Tests to be conducted on site 6. Onsite Test for Water Leakage for a pressure range 50 kpa to 240 kpa (35psi) upto 2000ml
PLUMBING SANITARY INSTALLATIONS
OD290177/2025-2026 Providing, Fixing, Testing and Commissioning at site approved brand and model Wall Mounting type water closet with P trap & its all fittings like rag bolts, matching Soft Closing Slim Seat Cover with lid C.P brass/SS hinges and rubber buffers ,matching Concealed Vetrious China Cistern with Fittings, brass screws, nuts , and washers complete including cutting and making good the walls and floors and including all the necessary accessories as required complete.
OD293734/2025-2026 Providing, Fixing, Testing and Commissioning at site Handicapped Wall mounting water closet with P trap & its all fittings like rag bolts, matching Soft Closing Slim Seat Cover with lid C.P brass hinges and rubber buffers ,matching Concealed Vetrious China Cistern with Fittings,brass screws, nuts, and washers. Flat back Wash Basin with half pedestal with accessories, 32 mm C.P. brass waste coupling, rag bolts. With 1 health faucet, 2 Angle valves, 1 Automatic sensor tap,1 Bottle trap, U shaped Grab bars(Set of 2) ,1 Nylon Swing bar & complete including cutting and making good the walls and floors and including all the necessary accessories as required complete. All items should be in the approved make list
OD290270/2025-2026 Providing and fixing white vitreous china Ac Supply based infrared sensor operated urinal of approx.size 610x390x370 mm having pre & post flushing with water ( 250 ml & 500 ml consumption), having water inlet from back side, including fixing to wall with suitable brackets all as per manufacturers specification and direction of Engineer - in-charge.
OD290346/2025-2026 Providing and fixing white vitreous china wash basin under counter (round / oval), with C.I. concealed type brackets fixed to walls with GI rag bolts or approved fasteners etc., including matching 32 mm CP brass waste coupling, including painting of fittings and brackets, cutting and making good the walls wherever required all complete (Granite counter top will be measured and paid separately under relevent item): as per approved make and decision of engineer-in-charge.
OD290308/2025-2026 Providing and fixing C.P. brass angle valve for basin/health faucet mixer of approved quality conforming to IS: 8931.
OD290322/2025-2026 Supplying and fixing CP Health Faucet superior quality including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge.
OD293496/2025-2026 Providing and fixing of Air Curtain of having automated door sensor operation. Air curtain should have four blowers and 2 motos. Blower velocity 20-25 m/s. RPM should be more tahn 2500 , CFM shall be more than 1000.
OD291415/2025-2026 "Providing and fixing of Automatic Tissue Roll Dispenser, Hand Dryer & Waste Receptacle (Recessed) Stainless Steel 304 Grade.Electrical/ Battery Operated.Waste Receptacle Capacity : 21 Litres.Protection Class : IPX1 With all accessories and including necessory wiring. All complete as directed by engineer-in- charge.
OD293371/2025-2026 Providing and fixing of AUTOMATIC SOAP DISPENSER, Automatic Infra-Red Sensor, Power : Battery, Sensing Range : 10 cm, Dispense Volume : 1~2ml, Capacity : 1100 ml With all accessories and including necessory wiring. All complete as directed by engineer-in-charge.
OD291626/2025-2026 Providing and fixing of FRAGRANCE DISPENSER LCD-WITH TIMER PROGRAMMING, Power : Battery, Spray Interval : Digital Programming (Timer) Wall Mounted Type, Material : 304 Grade Stainless Steel With all accessories & All complete as directed by engineer-in-charge.
OD291575/2025-2026 Providing and fixing of Recessed Sanitary Napkin Disposal. 304 Grade Stainless Steel: 4.6 Litres.With all accessories & All complete as directed by engineer-in- charge.
OD290333/2025-2026 Providing, Fixing, testing and commissioning Automatic Sensor Tap,Basin Mount,Battery+Electrical for wash basins and including all the necessary accessories as required complete. (Premium)
OD290337/2025-2026 Providing and fixing 32mm size Bottle trap (Poly Propylene) of approved quality & make and as per the direction of Engineer in charge.
OD293440/2025-2026 Providing and fixing of Waste receptable, Exposed. Construction : Material: 304 Grade, Stainless Steel,Capacity:16 Litre
OD293754/2025-2026 Supplying and fixing of Robe hook with holder all complete as directed by engineer- in-charge.
OD313367/2025-2026 Tissue Dispenser: Exposed. Cabinet Material: 304 Grade Stainless Steel
OD316946/2025-2026 Wall mounted 32L WASTE RECEPTABLE ABS PLASTIC
WATER SUPPLY
50.18.8.5.2 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc. 40 mm pipe 6Kgf/cm2
50.18.7.6.2 Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing . This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 50 mm dia 6 Kgf/cm2 - Internal work- Exposed on wall
50.18.9.18.1 Providing and fixing PVC pipes including fixing the pipe with clamps/clips at 1.00 m spacing. This included jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 75 mm dia 6Kgf/cm2 External work- Exposed on wall
50.18.9.19.1 Providing and fixing PVC pipes including fixing the pipe with clamps/ clips/ at 1.00 m spacing . This includes jointing of pipes with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 110 mm dia 6 Kgf/cm2 - External work- Exposed on wall
18.8.2 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.20 mm nominal dia pipes
18.8.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings i/c fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes& fittings, with one step CPVC solvent cement and the cost of cutting chases and making good the same including testing of joints complete as per direction of Engineer-in-Charge. Concealed work, including cutting chases and making good the wall etc.25 mm nominal dia pipes
18.7.2 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work Exposed on wall20 mm nominal dia pipes
18.7.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work Exposed on wall25 mm nominal dia pipes
18.7.4 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work Exposed on wall32 mm nominal dia pipes
18.7.5 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work Exposed on wall40 mm nominal dia pipes
50.18.9.8.1 Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of joints complete as per direction of Engineer in Charge. 75 mm dia 6 Kgf/ cm2
50.18.9.9.1 Providing and fixing PVC pipes includings jointing of pipes with one step PVC solvent cement, trenching, refilling & testing of Joints complete as per direction of engineer in charge.110 mm dia 6Kgf/cm2
50.18.9.10.1 Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 150 mm dia 6 Kgf/cm2
OD311808/2025-2026 Providing and fixing PVC pipes includings jointing of pipes with one step pvc solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer in Charge. 160 mm dia 6 Kgf/cm2
OD290400/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D - 1785 sch-40 ), having thermal stability for cold water supply including all (ASTM D - 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. Internal work 20 mm nominal outer dia pipes
OD290410/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D – 1785 sch-40 ) for cold water supply, including all (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc). Including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step ASTM solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 25 mm nominal outer dia pipes
OD290406/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D – 1785 sch-40 ) for cold water supply, including all (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc). Including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step ASTM solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 32 mm nominal outer dia pipes
OD290408/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D – 1785 sch-40 ) for cold water supply, including all (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc). Including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step ASTM solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 40 mm nominal outer dia pipes
OD290911/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D 1785 sch-40 ) for cold water supply, including all (ASTM D 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc). Including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step ASTM solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 50 mm nominal outer dia pipes
OD294132/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D 1785 sch-40 ), having thermal stability for cold water supply including all (ASTM D 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work 20 mm nominal outer dia pipes Concealed work, including cutting chases and making good the wall etc.
OD294132/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D 1785 sch-40 ), having thermal stability for cold water supply including all (ASTM D 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work 20 mm nominal outer dia pipes Concealed work, including cutting chases and making good the wall etc.
OD294136/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D 1785 sch-40 ), having thermal stability for cold water supply including all (ASTM D 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work 32 mm nominal outer dia pipes
OD294137/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D 1785 sch-40 ), having thermal stability for cold water supply including all (ASTM D 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work 40 mm nominal outer dia pipes
OD290489/2025-2026 Providing, Fixing at site in position full way lever operated forged brass ball valve of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawings. 20mm dia.
OD290493/2025-2026 Providing, Fixing at site in position full way lever operated forged brass ball valve of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawings. 25mm dia.
OD290552/2025-2026 Providing, Fixing at site in position full way lever operated forged brass ball valve of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawings. 32mm dia.
OD290646/2025-2026 Providing, Fixing at site in position full way lever operated forged brass ball valve of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawings. 40mm dia.
OD290707/2025-2026 Providing, Fixing at site in position full way lever operated forged brass ball valve of brass body with forged brass hard chrome plate (PN 25) of approved make with necessary MTA fittings in position as per drawings. 50mm dia.
OD290872/2025-2026 "Providing, Fixing, testing and commissioning at site in positions Automatic Air Release Valves, of approved quality and make on the top of the vertical water supply pipes as per specification and drawing. 20mm dia
OD291007/2025-2026 "Providing, Fixing at site in position Butterfly valve (PN 16) wafer type of approved make with necessary PVC flanges, gaskets, nuts and bolts etc complete within position as per drawings. 2 ½(65mm) dia"
OD291040/2025-2026 "Providing, Fixing, testing and commissioning at site in positions Brass Y Strainer, of approved quality and make as per specification and drawings 2½""(65mm) dia"
OD291042/2025-2026 "Providing, Fixing, testing and commissioning at site in positions Gun Metal / Brass body Pressure Reducing Valves(2) suitable for a maximum inlet pressure of upto 25 bars reduce to anywhere between 1 to 1.5 Bars, the valve incorporate inherent design advantage like reversible double reinforced food grade EPDM rubber diaphragm, suitable ball valves (4) or butterfly valves (4), 2 pressure gauges including 2 ball valves (¾) connections on both sides of pressure reducing valves etc complete (Female Screwed Ends). 2 (50mm) dia
OD293940/2025-2026 "Providing,Fixing, testing and commissioning at site in positions as detailed in drawings, Brass Non Return Valves complete in all respects. 2 ½(65mm) dia ."
OD311766/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D ? 1785 sch-80 ), having thermal stability for cold water supply including all (ASTM D ? 2466/2467) plain & brass threaded fittings. This includes jointing of pipes & fittings with one step ASTM solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work 65 mm nominal outer dia pipes. "
OD318600/2025-2026 Providing and fixing uPVC Pipes (as per ASTM D ? 1785 sch-40 ) for cold water supply, including all (ASTM D ? 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc). Including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step ASTM solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall 65 mm nominal outer dia pipes.
DRAINAGE
19.7.1.1 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand) with R.C.C. top with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix ( 1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size,) inside plastering 12 mm thick with cement mortar 1:3 ( 1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) finished with a floating coat of neat cement complete as per standard design: Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weigh of cover 23 kg and weight of frame 15 kg):With common burnt clay F.P.S. (non modular) bricks of class designation 7.5
19.8.1.1 Extra for depth for manholes Size 90x80 cmWith common burnt clay F.P.S. ( non modular ) bricks of class designation 7.5
19.4.1.1 Providing and fixing square-mouth S.W. gully trap class SP -1 complete with C.I. grating brick masonry chamber with water tight C.I. cover with frame of 300x300 mm size (inside) the weight of cover to be not less than 4.50 kg and frame to be not less than 2.70 kg as per standard design: 100x100 mm size P typeWith common burnt clay F.P.S. (non modular) bricks of class designation 7.5
OD290958/2025-2026 Providing, Fixing, testing and commissioning at site in position UPvc fabricated Multi floor trap (7"), with 50/75 mm dia outlet.Basic price:- Multi floor trap (7")
OD291010/2025-2026 Providing,Fixing, testing and commissioning at site 150x150 mm square C.P. cast brass or stainless steel anti cockroach grating cover SS (304) of matching size of UPvc fabricated floor trap / multi inlet trap complete in all respects.
OD291018/2025-2026 Providing, Fixing, testing and commissioning at site in position Concealed floor trap (4" UPvc fabricated Multi Trap, with Stainless Steel Square frames (150x150mm) SS (304), Rubber Seal and flat round cover with screw. etc. complete in all respects. 50/75 mm dia outlet.
IRRIGATION
OD311114/2025-2026 Providing,Fixing of Impact Sprinkler with all necessary (ASTM D - 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc)
OD311222/2025-2026 Providing,Fixing of Pop-up Sprinkler with all necessary (ASTM D – 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc)
OD311275/2025-2026 Providing,Fixing of 16 mm Poly Tube with all necessary fittings etc.
OD311322/2025-2026 Providing,Fixing of 6 mm Poly Tube with all necessary fittings etc.
OD311419/2025-2026 SITC of 1 ½ "Solenoid Control Valve with all necessary fittings etc
OD311469/2025-2026 SITC of 10" Round Valve Box with all necessary fittings etc
OD311473/2025-2026 "Providing,Fixing,testing and commissioning at site SPP , Expandable, 230 volt, 6 station with all necessary need for automatic the irrigation system, relay and other accessories of approved make with necessary MTA fittings in position with all necessary fittings etc. Consider all civil works, plumbing works electrical works all related to the irrigation system. The accessories for the successfull running of the irrigation system. No extra Cost for any additional items. (RainBird/Equivalent) Plumbing Irrigation - Sprinkler system using automation- Installation of drip lines, including connection to main/lateral pipelines and all necesssary fixings and fittings, etc, complete all in accordance with drawings and specifications."
OD311497/2025-2026 Providing,Fixing of Micro Tap/Dripper with all necessary fittings etc.
OD311517/2025-2026 Providing,Fixing of 20m3 Screen Filter (Cast Iron) with all necessary (ASTM D 2466/2467) fittings (elbows, unions, tees, reducers, couplings, nipples etc)
OD313674/2025-2026 SITC of 2 "Solenoid Control Valve with all necessary fittings etc.
HT EQUIPMENT
OD288127/2025-2026 11kV Outdoor RMU panel with HT (Bus) Metering, FRTU And Auxilary Transformer (Extensible Type) Design, Fabrication, Supply, Installation Testing and Commissioning of 11KV electrically Operated 21kA for 3 sec, 630A SF6 Insulated, Ring Main Unit outdoor type (IP-63) with 2 nos motorized Load Break Switch as incomer and 1 no motorized VCB (fully rated earth switch) with fully encapsulated vacuum interrupter panel, 630 Amp continously rated Cu busbar complete with all accessories, protective relays, indicators, Hooter , battery and battery charger, Manometer for indicating SF6 gas pressure with green zone marked on the scale, provision for padlocking for open, close, earth and test position etc. on a suitable foundation. The RMU must be both side extensible type and compatible for SCADA system. FRTU proposed shall be integrated with RMU in the LV compartment completely wired along with Modem suitable for communicating in CDMA/GSM network and also have the facility to communicate with main SCADA room. , it enable to monitor and control the switchgear remotely, locate and isolate fault automatically as well as the system recovery. FRTU shall include on/off device control points to support control actions initiated from the SCADA. FRTU shall be powered by a 24V DC system with necessary protection. HT Metering shall be included with the RMU. The rate quoted shall be inclusive of all the civil works, Foundation and hoisting to its location, assembling of units, lining up, bolting the units, including roofing and checking all control wiringand complete as per single line diagram & technical specification. Factory Inspection also included with the rates. no extra cost for FAT as per technical specification.
OD288439/2025-2026 11kV VCB PANEL Design, Fabrication, Supply, Installation, Testing and commissioning of 11 kV, 800A 25 kA (for 3seconds), Electrically operated draw out type both side extendable VCB panel (fully encapsulated vacuum bottle) fabricated out of 14 guage MS Sheet Powder Coated in Shade RAL 7032 . The panel shall be with 800A Copper busbar & support insulators, space heater with thermostat, cubicle illumination lamp, MCBs for AC/DC Control, motor operated spring charged mechanism, anti-pumping device, 110V DC power pack and closing coil, control wiring, Master Trip Relay, battery charger etc and having following specific components and as per IS / IEC standards, IEC62271-200, IEC-62271-1. The quote shall be inclusive of hoisting the panel to respective location, assembling of panels, lining up and bolting the units, checking all the control wiring, Calibration of all instruments, pre-commissioning tests. All tests at site as per KSEI standards. The panel shall be compatible for SCADA and integrated energy monitoring system provision and should have RS 485 communication facility. IEC62271 200 Complied Panels with Type Test Certificates. STC 25 kA for 3 Sec (Whole Assembly - HBB, Breaker and Cable Chamber), Partial Discharge Sensors for monitoring the Dielectric strength for each vertical. Wireless Thermal Monitoring at Cable Connections Should be provided. Breakers need to be with Roll on Floor design for ease of access. Make of Vaccum Interruptor, VCB, Numerical relay and HT Panel should be same. Incomer 800A, 11kV, 66 kA (3 sec), VCB, Electricaly operated drawout type, with 3 Nos single phase PT 11kV/?3/110 V /?3, 50VA (minimum), CL-0.2, CT 150/5 15VA Cl 0.2s for metering and 150/5 15VA cl 5P10 protection. Indication lamps, analogue and digital meters with communication port, digital power analyser with communication facility, space heater with thermostat, Cubicle Illumination Lamp, temperatue sensor for cable, numerical protection relays with communication port, required number of CTs for metering and protection, 9 window annunciatior, electrical inter locks etc. - 1 no Outgoings 800A, ,11kV, 25 kA (3 sec), VCB, Electricaly operated drawout type, CT 40/5 15VA Cl 0.5 for metering and 40/5 15VA cl 5P10 protection,with indication lamps, analogue and digital meters with communication port, space heater with thermostat, Cubicle Illumination Lamp, temperatue sensor for cable, digital power analyser with communication facility, numerical protection relays with communication port, required number of CTs for metering and protection etc, annunication window for distribution feeder as detailed in the technical specification - 3 No. Earthing Truck suitable for all VCB's - 1 No The panel shall be with bottom / top entry to receive incoming & outgoing cable, all necessary interconnection & accessories as per particular specification & single line diagram.
OD288449/2025-2026 750 KVA 11kV Packaged Substation Design, fabrication, supply, installation, testing and commissioning of indoor type Packaged (Unitized) Substation enclosure consisting of 11 KV, 630A, 26.3kA for 3 sec motorized VCB, 750 kVA, 11kV/433V 3 Ph, 50 Hz, vector Dyn -11, dry type, Transformer with IP23D enclosure, winding temperature alarm and trip on transformer compartment and LV chamber suitable for termination of cable, complete with all standard fittings and accessories etc including necessary louvers and as per specifications attached in all respects as required. It shall includes all necessary control cabling for alarm, tripping & indication, all internal cabling as required. The rate shall be inclusive of all materials, lead, lift, necessary civil works for M25 mix RCC foundation etc. complete as per single line diagram & technical specification. Transformer shall be as per ECBC 2024. HT Compartment:- 11KV, 25kA for 3 sec, 800A motorized VCB, 800 Amp continously rated Cu busbar, Self powered microprocessor based three over current and one earthfault relay with protection CT's - 1 set, Battery and battery charger - 1 set, Manometer for indicating SF6 gas pressure with green zone marked on the scale, Provision for padlocking for open, close, earth and test position Transformer Compartment:- 750 kVA, 11kV/433V 3 Ph, 50Hz, dry type, vector Dyn -11 Transformer, copper wound, laser scribe core, Class F insulation, indoor distribution Transformer with forced ventilation. The transformer shall have Delta on HV side and Star on LV side with off load tap changer range: + 5% to -10% in steps of 2.5%. The transformer shall have suitable enclosure for providing neutral CT of 275/5A 15VA 5P10 on earthed star point with connector for connection Earth Fault relay in HT/LT panel. LT Chamber:- Suitable for terminating 1000A busduct
DG SET AND ACCESSORIES
OD288464/2025-2026 Supply, Installation, Testing and Commissioning of 750 kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering, controls and interlocks, CTs and transducers for all metering and protection and suitable FP MCCB / ACB etc., including antivibration mountings, exhaust silencer and exhaust pipe (Up to terrace area to be considered with proper support. Space Heater mounted on Channel Iron Base Frame. No extra cost for the exhaust piping, supports) conforming to latest environment protection regulations for emission and noise levels complete with, water/ coolant cooled, (radiator type) four stroke, electric start conforming to Latest ECBC, 750 kVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500rpm, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to Latest ECBC. Emission control device shall be provided. RTD and BTD Shall included. All tests shall be carried out as per the technical specification without any exra cost. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads, battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards. Fuel tank for 8 hours suitable continous operation, fuel piping from fuel tank to Engine, Residential silencer, suitable size Cable termination box with extended Alternator terminal with bus bars etc as required and as per specifications. Rate shall be inclusive of all the civil work including RCC foundation. The all work should be as per Electrical Inspectorate/ Central Pollution control board latest standards.
LT PANEL BOARDS AND ACCESSORIES
RISING MAINS AND BUS TRUNKING
3.13.3 Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient section complete with 4 Nos aluminium bus bars, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size( one on each side) including G.I clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. 630 amps 50 KA SC for 1 sec
3.13.4 Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient section complete with 4 Nos aluminium bus bars, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size( one on each side) including G.I clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. 800 amps 50 KA SC for 1 sec
3.13.6 Supplying, installing by suspension on ceiling, testing and commissioning of following capacity Sandwich Type Bus Trunking for use on 3 phase 4 wire 415 volts, 50 Hz A.C. supply with metal clad enclosure made of 1.6mm thick steel sheet duly powder coated in convenient section complete with 4 Nos aluminium bus bars, necessary joints, elbow joints & expansion joints and bends, fire barrier at each floor, provision of tapping at every metre, adopter box and copper flexible for joints, continuous earthing with 2 Nos aluminium strip of suitable size( one on each side) including G.I clamping brackets, suspenders, angle iron bracket, steel fasteners, connecting to earthing system etc. as required. 1250 amps 50 KA SC for 1 sec
OD327276/2025-2026 Supplying, installing, testing and commissioning of following capacity TPN tap off box made of 1.6mm thick sheet steel enclosure duly painted with powder coating on existing rising mains complete with TPN MCCB, connections, earthing etc. as required. 250 amps TPN
UPS AND ACCESSORIES
OD288847/2025-2026 UPS AND ACCESSORIES Supply, installation, testing and commissioning of 20 kVA UPS of three phase in and out with indoor (IP20) with SNMP for remote monitoring is option with cyber security, with surge protection system even in ESS mode Input pf 0.99, Input THDi < 3%, with DC flexibility from 32-40 batteries with necessary battery circuit breaker, capacitors with 10 years life, 102?110% load 60 min, 111-125% load 10min, 126-150% load 1min, double conversion technology with input 400V, 50Hz three phase, output 400V, 50Hz three phase, It shall be 100% generator compatible, with Efficiency > 94 % and ABM Cyclic charging (20 KVA=20 kW), ESS mode Efficiency 99% and including all accessories etc as required. The acoustic noise at 1m of the system should be<65dB. The system shall comply to EN/IEC 62040-1,2,, TLC, CQC energy saving, and Seismic test report and relevant IS standard. The system shall be true online double - conversion DSP based UPS system and UPS shall be with automatic & manual bypass switch. The system shall have IGBT rectifier and inverter. SMF battery 12v 75ah x 20 nos for 30 min backup
HT CABLING
OD288220/2025-2026 Supply of following sizes of XLPE insulated PVC sheathed, Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date. 3C x300 Sq mm
8.1.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
8.2.2 Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc Above 120 sq. mm and upto 400 sq. mm
8.3.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 120 sq. mm and upto 400 sq. mm
8.4.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required. Above 120 sq. mm and upto 400 sq. mm
10.4.4 Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required: 300 sq. mm
10.5.4 Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required : 300 sq. mm
OD288865/2025-2026 Supplying and making cable route marker with cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size ) of size 60 cm X 60 cm at the bottom and 50 cm X 50 cm at the top with a thickness of 10cm including inscription duly engraved as required.
LT CABLING
OD294194/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 3.5C 400 Sq.mm Al
OD289297/2025-2026 Supply of 3.5C 240 Sq.mm size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date.
OD289296/2025-2026 Supply of 3.5C 185 Sq.mm size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date.
OD289321/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 3.5C 120 Sq.mm Al
OD294920/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 :2018 amended upto date. 3.5C 70 Sq.mm Al
OD289320/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 3.5C 50 Sq.mm Al
OD289319/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 3.5C 35 Sq.mm Al
OD289318/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 25 Sq.mm Al
OD289295/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 16 Sq.mm Al
OD289317/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 10 Sq.mm Al
OD289294/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 6 Sq.mm Al
OD289293/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Aluminium conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 4 Sq.mm Al
OD289314/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Cu conductor cable conforming to IS 17048 : 2018 amended upto date. 4C 2.5 Sq.mm Cu
OD289315/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Cu conductor cable conforming to IS 17048 : 2018 amended upto date. 3C 2.5 Sq.mm Cu
OD289316/2025-2026 Supply of following size 1.1 KV grade HFFR insulated, PVC sheathed, armoured Cu conductor cable conforming to IS 17048 : 2018 amended upto date. 3C 1.5 Sq.mm Cu
CABLING TERMINATION
OD288220/2025-2026 Supply of following sizes of XLPE insulated PVC sheathed, Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date. 3C x300 Sq mm
8.1.2 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 120 sq. mm and upto 400 sq. mm
8.2.2 Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc Above 120 sq. mm and upto 400 sq. mm
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2 X 50 sq. mm (35mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3 1/2X 35 sq. mm (32mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 25 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 16 sq. mm (28mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 4 X 10 sq. mm (25mm)
Supplying and making end termination with brass compression gland and Al lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. 4C 4 sqmm Al
Supplying and making end termination with brass compression gland and Al lugs for following size of PVC insulated and PVC sheathed / XLPE copper conductor cable of 1.1 KV grade as required. 4C 6 sqmm Al
Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 4C 2.5 Sq.mm Cu
Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 3C 2.5 sqmm Cu
Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 3C 1.5 Sq mm Cu
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required. Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Upto 35 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required. Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 185 sq. mm and upto 400 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 35 sq. mm and upto 95 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 95 sq. mm and upto 185 sq. mm
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Above 185 sq. mm and upto 400 sq. mm
Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate with inscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixing the same in ground as required
CABLE TRAYS
OD289329/2025-2026 Supply, fabricating and installing MS items such as Tees/ angles/ channels etc. on floor/ ceiling/ wall including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as required
14.13.1 Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required 50 mm dia
14.13.3 Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required 100 mm dia
14.14.1 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as required. 100 mm dia
WIRING
OD294874/2025-2026 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. HFFR PVC insulated copper conductor single core cable etc as required. Group C
OD294873/2025-2026 Wiring for twin control light point with 1.5 sq.mm HFFR PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. HFFR PVC insulated copper conductor single core cable etc as required.
1.55.3 Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
1.14.1 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2x1.5 sq.mm + 1x1.5 sq.mm earth wire
1.14.2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
1.14.3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
1.14.4 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
1.14.5 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 10 sq. mm + 1 X 6 sq. mm earth wire
1.31 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch, connection etc. as required. (For light plugs to be used in non residential buildings).
1.32 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.
1.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
OD295082/2025-2026 Supply & fixing Computer points with 3 nos 3 pin 5/6A socket with 2no.5/6A switch with modular front plate and cover on surface/recess, including proving and fixing suitable size GI boxs, its interconnections etc as required complete. (Note: 2 nos 5/6A socket fixed at 60cm above FFL and 2 nos 6A switch with 1no 5/6A socket at 1m above FFL)
1.24.5 Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required. 6 pin 15/16 amp socket outlet
1.25 Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
1.21.1 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 20 mm
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm
1.21.3 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required. 32 mm
DB AND ACCESSORIES
OD290327/2025-2026 Supply, Installation, Testing and Commissioning of 8 way (8+24),surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB?s, with provision of FP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB?s/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
OD290325/2025-2026 Supply, Installation, Testing and Commissioning of 4 way (4+12)DOUBLE DOOR, surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB?s, with provision of FP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB?s/ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
OD290266/2025-2026 Supply, Installation, Testing and Commissioning of 8 Way(4+24), Double door, surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
OD290269/2025-2026 Supply, Installation, Testing And Commissioning of 4 WAY(4+12), DOUBLE DOOR, surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required .(Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
2.4.3 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 8 way(4+24), Double door
2.4.1 Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface / recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 Way (4+12) Double door
OD290334/2025-2026 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 18 way, Double door
2.3.4 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 16 way, Double door
2.3.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12 way, Double door
OD290320/2025-2026 Supply, Installation, Testing And Commissioning of following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 160 Amp, 16KA,FP MCCB
OD290273/2025-2026 Supply, Installation, Testing And Commissioning of following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 125 Amp, 16 KA
OD290321/2025-2026 Supply, Installation, Testing And Commissioning of following rating and breaking capacity MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel. making connections. etc. as required. 100 A, 16KA
OD290335/2025-2026 Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 63 amps. (415 Volts), 30mA sensitivity.
OD290336/2025-2026 Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 63 amps. (415 Volts), 100mA sensitivity.
OD290338/2025-2026 Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts), 30mA sensitivity.
OD290340/2025-2026 Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts), 100mA sensitivity.
OD290341/2025-2026 Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 2 pole 25 amps. (230 Volts), 30mA sensitivity.
2.10.1 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD290344/2025-2026 Supply and fixing of following rating, 10 KA, Miniature Circuit Breakers as required. 40 A to 63A FP MCB, C-CURVE Single pole
2.10.4 Supplying and fixing 5A to 32 A rating, 240/415 volts, 10 kA, ""C"" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple pole
2.18 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth,metal enclosed plug top along with 20 amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
OD290371/2025-2026 Supply, Installation, Testing & Commissioning of 25A DP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
OD290375/2025-2026 Supply, Installation, Testing & Commissioning of 32A DP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
OD290377/2025-2026Supply, Installation, Testing & Commissioning of 32A FP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
OD290380/2025-2026 Supply, Installation, Testing & Commissioning of 40A FP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
OD290388/2025-2026 Supply, Installation, Testing & Commissioning of 63A FP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
OD290395/2025-2026 Supply, Installation, Testing & Commissioning of 63A FP isolator in weather proof enclosure on surface including all the mounting accessories, internal wiring etc as required complete.
OD290391/2025-2026 Supply, Installation, Testing & Commissioning of 160A FP isolator in 1.6mm thick sheet steel enclosure duly painted with powder coated finishing on surface including all the mounting accessories, internal wiring etc as required complete.
2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
LIGHTING
OD290347/2025-2026 Supply of dali dimmable LED Downlight Luminaire having power consumption not more than 20 W and light output not less than 2000 Lumens with System efficacy> 120 Lumen/Watt. Housing Shall be made of pressure die cast aluminum body and Light out put shall be difffused using polycarbonate diffuser and aluminum reflector to acheive UGR<19. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ≥80, SDCM<5 and Co-related color temperature (CCT) of 6500K.The luminaire must have 2.5KV surge protection integrated in driver, PF≥0.95, Total harmonic distortion THD≤10%, EMI/EMC Compliant and Operating voltage range 160-270V .Luminaire and driver shall be separately BIS . M80,LM79 ,Type Test certificate and Bis certificate need to be submitted.
OD290361/2025-2026 Supply of LED surface mounted down light made of die cast aluminium, along with driver,system wattage of 20+/-2 Watts, lumen output of lamp greater than 2000 lumens, power factor >= 0.9,rated life of L70B50 @ 50,000 hours, system efficacy greater than 100 lumen/watt , cool daylight and including all necessary accessories as required complete.
OD290362/2025-2026 Supply of LED surface mounted down light made of die cast aluminium, along with driver, system wattage of 20+/- 5 Watts,lumen output of lamp greater than 900 lumens, power factor >= 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 90 lumen/watt ,cool daylight and including all necessary accessories as required complete.
OD290363/2025-2026 Supply of DALI dimmable LED Recess Mount Downlight Luminaire (COB) having power consumption not more than 15 W and light output not less than 1000 Lumens with System efficacy> 70 Lumen/Watt and Anti-glare. Housing Shall be made of pressure die cast aluminum body. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ≥90, SDCM<5 and Co-related color temperature (CCT) of 6500K / 3000K . Operating voltage range 160-270V . The luminaire must have 2.5KV surge protection integrated in driver. Luminaire and driver shall be separately BIS. LM80,LM79 ,Type Test certificate and BIS certificate need to be submitted.
OD290364/2025-2026 Supply of DALI dimmable LED Recess Mount Downlight Luminaire having power consumption not more than 18 W and light output not less than 2000 Lumens with System efficacy> 110 Lumen/Watt. Housing Shall be made of pressure die cast aluminum body with 40mm height suitable for installation in low heights and polycarbonate diffuser to reduce glare. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ≥80, SDCM<5 and Co-related color temperature (CCT) of 6500K. The luminaire must have 2.5KV surge protection integrated in driver, PF≥0.95, Total harmonic distortion THD≤10%, EMI/EMC Compliant and Operating voltage range 160-270V . Luminaire and driver shall be separately BIS. LM80,LM79 ,Type Test certificate and BIS certificate need to be submitted.
OD290366/2025-2026 Supply of DALI dimmable LED Batten having power consumption not more than 40W and light output not less than 4500 Lumens with System efficacy > 120 Lumen / Watt. Housing Shall be made of extruded aluminium housing / CRCA and polycarbonate diffuser to reduce glare. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ≥80, SDCM<5 and Co-related color temperature (CCT) of 6500K. The luminaire must have 4 KV surge protection integrated in driver, PF≥0.95, Total harmonic distortion THD≤10%, EMI/EMC Compliant and Operating voltage range 140-270V . Flicker Free constant Current Driver, Ripple < 5%. Luminaire and driver shall be separately BIS. LM80,LM79 ,Type Test certificate and BIS certificate need to be submitted.
OD290366/2025-2026 Supply of LED Batten With Occupancy Sensor having power consumption not more than 40W and light output not less than 4500 Lumens with System efficacy > 120 Lumen / Watt. Housing Shall be made of extruded aluminium housing / CRCA and polycarbonate diffuser to reduce glare. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ≥80, SDCM<5 and Co-related color temperature (CCT) of 6500K. The luminaire must have 4 KV surge protection integrated in driver, PF≥0.95, Total harmonic distortion THD≤10%, EMI/EMC Compliant and Operating voltage range 140-270V . Flicker Free constant Current Driver, Ripple < 5%. Luminaire and driver shall be separately BIS. LM80,LM79 ,Type Test certificate and BIS certificate need to be submitted.
OD290370/2025-2026 Supply of DALI dimmable 2x2 LED recess mounted fixture with housing made of metallic CRCA powder coated body or pressure die cast Aluminium body with a high efficiency diffuser along with driver, system wattage not more than 35 Watts,lumen output of lamp greater than 3500 lumens, power factor >= 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 110 lumen/watt, Cool day light fixture ,with suitable driver and including all necessary accessories as required complete.
OD290372/2025-2026 Supply of DALI dimmable Indoor suspended mounted LED Linear fitting having extruded aluminium housing and Polycarbonate Diffuser, along with driver,system wattage of 25+/-5 Watts, rated life of L70 @ 50,000 hours with CRI ≥80, lumen output of lamp not less than 2500 lumen, power factor >= 0.9, system efficacy not less than 112 lumen/watt, cool day light. The luminaire must have 4 KV surge protection integrated in driver, PF≥0.9, and including all the necessary accessories as required complete.
OD290376/2025-2026 Supply of LED Strip light along with driver with profile, 240 LED/mtr power factor >= 0.9, 900lm/mtr, Warm light and including all necessary accessories as required complete.
OD290378/2025-2026 Supply of Decorative Chandlier with lamp along with driver, power factor >= 0.9, Warm / Neautral day light and including all necessary accessories as required complete.
OD290379/2025-2026 Supply of Decorative Chandlier with lamp along with driver, power factor >= 0.9, Warm / Neautral day light and including all necessary accessories as required complete.
OD290382/2025-2026 Supply of following sizes of 1200 mm sweep. 5 star rated ceiling fan, BLDC Motor, Down Rod, Shackle Kit, Safety Wire, A pair of canopies, A set of 3 Blades and with / without speed regulator suitable for 240V 50 HZ, AC supply confirms to IS 374/1979 as required complete.
OD290421/2025-2026 Supply of 400 mm size wall mounting oscillating type fan having three speed control, oscillation control at bottom and suitable for operation on single phase 230 volt, 50Hz AC supply complete with continuous duty motor, chrome plated front and rear gaurds and all accessories as required complete.
OD290423/2025-2026 Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self opening louvers working on 230 V AC supply complete with suitable flexible duct and all accessories as required.
1.41 Installation, testing and commissioning of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
OD317425/2025-2026 Installation, testing and commissioning of LED down lighter fittings on false ceiling with all mounting accessories as required complete including interconnections using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor as required.
OD317504/2025-2026 Installation, testing and commissioning of High bay/Mid bay/LED/ FLOOD type fittings on wall/Column/truss/false ceiling using suitable MS clamps, nuts, bolts/ 20mm heavy duty GI chain/ pipe (upto 50cm)etc including connections with 3C 1.5 Sq.mm PVC insulated flexible copper conductor cable as required.
1.45 Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
1.50.1 Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required. Upto 450 mm sweep
OD317540/2025-2026 Installation, testing and commissioning of Wall fan, including all the supports as required and wiring using 3 runs of 1.5 sqmm FR PVC insulated stranded copper conductor etc complete.
1.49 Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.
OD293981/2025-2026 Supply, Installation, Testing & Commissioning of DALI Addressable Controller each controller support upto 64 DALI Universal Ballast with 20 A Relay Actuator per channel. Controller should support DALI 207 & DALI 209 Tunable White. Occupied in single raw 8 Module Distribution Board or above. Certification CE, RCM, UL/cUL, FCC, ICES, UKCA, RoHS,DALI-2 IEC62386, Standards for Safety : UL916 Standard For Energy Management Equipments.
OD293983/2025-2026 Supply, Installation, Testing & Commissioning of 15 VDC 1500 mA regulated power supply designed to supplement the network DC supply. IEC Overvoltage Category III, Occupied in single raw 6 Module Distribution Board Certification CE, RCM, UKCA, RoHS.
OD293998/2025-2026 Supply, Installation, Testing & Commissioning of Network Controlled Multi purpose Low Profile Recessed 360 deg Ceiling Sensor & Detects the presence orabsence of motion and adjusts lights accordingly. Suitable for plenum use & UL2043 certified for installation in air-handling plenum spaces. Detection upto 7m (L) x 5.5m(W) Ideal Ceiling Height : 2.4m - 4m Certification : CE, RCM, UL/cUL, FCC, ICES, UKCA, RoHS Standard(s) for Safety: UL 916, Energy Management Equipment.
OD293997/2025-2026 Supply, Installation, Testing & Commissioning of Configurable 6 button user interface & Compatible Wall mounting Box . The User interface has not less than 6 buttons and Button function can change the control of Occupancy sensors ability to control the dimmable & Tunable white LED lights upto 16 fuctions. Certification CE, RCM, FCC, ICES, EN50491-3, UKCA, RoHS
EXTERNAL LIGHTING
OD293717/2025-2026 Supply, installation, testing and commissioning of 5m long Hot dipped GI pole painted with PU coat with built- in control box prewired, with pole suitable for mounting LED luminairie with lamp, concealed wiring with 3Cx 2.5 sq.mm copper wire from the control box to light fixture, and all other accessories, complete including necessary civil foundation. Along with LED Lamp with PDC aluminum alloy housing and polycarbonate diffuser, inbuilt driver - High efficiency driver with necessary safety protections with 20KV external SPD, The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI >70, SDCM<5 system wattage maximum of 30 (+/-10) watts, lumen outputnot less than than 5700 lumen, System efficacy not less than 95 lumen per watt ,power factor >= 0.95, THD<10%, IP 66 compliant including all necessary accessories as required complete. Note :- Incoming and outgoing cable at termination box shall be terminated with glands properly.
OD293720/2025-2026 Supply, installation, testing and commissioning of 3m long Hot dipped GI pole painted with PU coat with built- in control box prewired, with pole suitable for mounting LED luminairie with lamp, concealed wiring with 3Cx 2.5 sq.mm copper wire from the control box to light fixture, and all other accessories, complete including necessary civil foundation. Along with LED Lamp with PDC aluminum alloy housing and polycarbonate diffuser, inbuilt driver - High efficiency driver with necessary safety protections with 20KV external SPD, The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI >70, SDCM<5 system wattage maximum of 30 (+/-10) watts, lumen outputnot less than than 5700 lumen, System efficacy not less than 95 lumen per watt ,power factor >= 0.95, THD<10%, IP 66 compliant including all necessary accessories as required complete. Note :- Incoming and outgoing cable at termination box shall be terminated with glands properly.
OD293727/2025-2026 Supply, installation testing and commissioning of LED bollards. LED lamp 12+/4 W in the fixture. The body shall be powder coated extruded aluminium. The Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI >80, SDCM<5 and Co-related color temperature (CCT) of 3000K. The luminaire must have 2.5KV surge protection integrated in driver, PF>0.9, and Operating voltage range 160-270V. The fixture shall have IP65 class protection shall be provided with all accessories and civil foundations.
OD293942/2025-2026 Supply, installation testing and commissioning of LED bollards with 600mm Height. LED lamp 12+/4 W in the fixture. The body shall be powder coated extruded aluminium. LThe Luminaire should be having Minimum 50000 Burning hours (L70B50) with CRI ?80, SDCM<5 and Co-related color temperature (CCT) of 3000K. The luminaire must have 2.5KV surge protection integrated in driver, PF>0.9, and Operating voltage range 160-270V. The fixture shall have IP65 class protection shall be provided with all accessories and civil foundations.
OD293953/2025-2026 Supply, installation, testing and commissioning of 15W LED Spike fitting with Pressure Die cast Aluminum housing housing, waterproof connectors diffuser, IP65/ IP66 Protection, Light Colour :- 3000k, LED Integrated Lamp Base suitable for operation on 230V 50Hz AC, ground including giving connections with required length of PVC insulated and PVC sheathed 3 core round copper conductor flex wire and making good the surface as required. L70 @ 50K Hours (IK67, IP67 rated, 500hrs salty spray test).
OD293956/2025-2026 Supply, installation, testing and commissioning of 5+/-2w LED Steplight fitting with die cast aluminium housing, diffuser, waterproof connectors and IP65 Protection suitable for operation on 230V 50Hz AC,LED step-light is IP67/IK10, Light Colour :- 3000k wall including giving connections with required length of 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire and making good the surface as required.
OD293963/2025-2026 Supply, installation, testing and commissioning of 12+/-2w LED fitting with Stainless steel (SS316) corrosion resistance housing, waterproof connectors diffuser, IP68 Protection, Light Colour :- 3000k, LED COB Integrated Lamp Base suitable for operation on 230V 50Hz AC, ground including giving connections with required length of PVC insulated and PVC sheathed 3 core round copper conductor flex wire and making good the surface as required. IK 09
OD293992/2025-2026 Supply of Network Controlled Multi purpose Low Profile Recessed 360 deg Ceiling Sensor & Detects the presence orabsence of motion and adjusts lights accordingly. Suitable for plenum use & UL2043 certified for installation in air-handling plenum spaces. Detection upto 7m (L) x 5.5m(W) Ideal Ceiling Height : 2.4m - 4m Certification : CE, RCM, UL/cUL, FCC, ICES, UKCA, RoHS Standard(s) for Safety: UL 916, Energy Management Equipment.
EARTHING
OD289345/2025-2026 Supply & providing ISI plate earthing as per IS 3043 with 1200x1200x12.5mm GI / CI earth plate with 50mm dia B class GI pipe for watering, 50x6mm GI strip welded to the plate, GI funnel with weld mesh, fixing GI strip of size 50x6mm with min. length of 20cm clamped with 50x6mm GI flat using 12x10mm GI bolt nut at top of the GI pipe as test joint, filling around the GI pipe at a radius of 15cm with a homogeneous mixture of charcoal, river sand upto a height of 2.5 meter from the bottom, filling the rest of the portion with excavated soil including watering ramming providing brick work (20cm) masonary at top in 1:6 cement mortar, plastering the inside top of the manhole with 12mm thick 1:6 cement mortar and providing gully trap with 450x450x10mm CI covering at the top.
5.6 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
OD291327/2025-2026 Supply,installation ,testing and comissioning of maintenance free earthing using 4 mtrs length,20mm dia 250 microns molecularly copper bonded steel rod, stainless stell connectors and fasteners for connecting earth strip.The earth electrode shall be filled with earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound).FRP (UFE FRP)Earth electrode inspection chamber with heavy duty cover should be used to cover the Earth Rod. The dimension shall be 300mmx 300mmx 300mm with a weight bearing capacity of 15KN.The item shall be inclusive of installation charges,including digging bore,providing all required accessories like terminal connector,screw for fixing earth pit cover etc.
OD291328/2025-2026 Supply, Installation, Testing and Commissioning of Earthing with C.I. earth pipe 4 metre long, 100 mm dia including accessories, and providing masonry enclosure with heavy duty CI cover plate of 300X300mm having locking arrangement and watering pipe etc. with 64kg charcoal/ coke and 5kg salt as required. (As per IS 3043 ammended upto date)
OD314808/2025-2026 Supplying and laying 50 mm X 10 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
5.9 Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
OD290594/2025-2026 Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) 50 mm X 6mm GI
OD290593/2025-2026 Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) 32mm X 6mm GI
OD290595/2025-2026 Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) 25mm X 3mm Cu
OD290598/2025-2026 Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) 10 SWG Cu
OD290599/2025-2026 Supplying and laying G.I/Copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm) 8 SWG GI
OD314806/2025-2026 Providing and fixing 50 mm X 10 mm G.I. strip on surface or in recess for connections etc. as required.
5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
OD290647/2025-2026 Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 50 mm X 6mm GI
OD290649/2025-2026 Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 32mm X 6mm GI
OD290652/2025-2026 Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 25mm X 3mm Cu
OD290654/2025-2026 Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 10 SWG Cu
OD290657/2025-2026 Providing and fixing GI/Cu strip/wire on surface or in recess for connections etc. as required. 8 SWG GI
OD291365/2025-2026 Supply of first aid box as required"
OD291366/2025-2026 Supplying and fixing shock treatment chart duly framed and placed in a conspicuous location for clear vision."
OD291367/2025-2026 Supply and fixing of 6kg capacity ABC type dry chemical powder fire extinguisher as required
OD291406/2025-2026 Supply and fixing single line diagram, schematic diagrams etc. of A0 size on suitable Aluminium sheet including lamination etc. as required complete on wall.
OD293309/2025-2026 Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete on wall.
OD293311/2025-2026 Supplying of Rubber hand gloves suitable for 11 KV."
OD293413/2025-2026 Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.
OD293419/2025-2026 Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat as per IS:15652.forthe following sizes. 2mx1mx2mm thick
OD293425/2025-2026 Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat as per IS:15652.forthe following sizes. 2mx1mx2.5mm thick
LIGHTNING PROTECTION
OD293532/2025-2026 Air termination system:-The air termination system shall be provided as an external lightning protection system using 8 mm aluminium round conductors and vertical air terminals, designed and installed in accordance with IS/IEC 62305 . All components including air terminals, conductors, holders, connectors, and accessories shall be tested and certified as per relevant IEC/DIN standards and suitable for outdoor exposure. The system shall ensure complete interception coverage of the structure using approved installation methods without damaging roof finishes. All materials shall be of approved make and installation shall be carried out as per approved drawings and manufacturer recommendations.(Refer Technical specication and drawings)
OD293986/2025-2026 Down conductor system:-The down conductor system shall be provided using 8 mm aluminium round conductors connecting the air termination system to the earthing system, in compliance with IS/IEC 62305 . Down conductors shall be routed externally with approved holders, test joints, and junction boxes, ensuring mechanical protection and electrical continuity. Test links shall be provided at accessible locations for inspection and testing. All materials shall be of approved make, suitable for outdoor installation, and installed as per approved drawings.(Refer Technical specication and drawings)
OD293990/2025-2026 Earthing system:-The earthing system for lightning protection shall be provided using hot-dip galvanised steel flats and copper-bonded earth electrodes, designed in accordance with IEC 62305 IS/IEC 62305. Earth pits shall be provided with inspection chambers and earth enhancement compound to achieve the required earth resistance. All joints and connections shall be mechanically strong, corrosion resistant, and electrically continuous. Installation shall be carried out as per approved drawings and relevant standards to ensure effective dissipation of lightning current.(Refer Technical specication and drawings)
OD290274/2025-2026 Supply, Installation, Testing and Commissioning of Energy Management System and software for 125 Device with Life Time Licence with following components, 1. Energy Billing Module 2. Panel Server Universal with 240V AC power supply - 21 No's 3. Panel Mount Meter 4. Power meter Cl 1.0 RS485 for Substation - 58 No's 5. Power meter Cl 1.0 RS485 For Tenants - 51 No's 6. Wireless Thermal Sensor (set of 3) - 25 No's 7. Server PC - Intel i9 Processor 14Gen 16GB RAM, 1 TB SSD, with Wirelss Keyboard and Mouse & 21inch Monitor OS Should be Windows 11 Pro including all necessary accessories required at site to complete the work - 1 No 8. RS 485 ?High Speed Low Loss Communication cable, LiYCY (TP) X 2 X 0.50 SQ MM? - Required Length as per site condition. 9. CAT 6 Cable - Required Length as per site condition. 10. Charges for Hardware integration. Wiring and Termination of RS 485 Cable Meter Programming, Mode Scan Testing, LAN termination and PAS 600 Ethernet communication. 11. Charges for software integration. 12. Installation charges for thermal sensors to the vertical mains bus trunking. (4 nos on each floor) - 23 No's 13. Charges for Hardware integration. THD, 15th Harmonics, RS-485 for Incomer (EB & DG), Cl 1.0, RS-485, MFM for Feeders, RS 485. Charges for software integration of 100 nos of devices including MFM & Thermal monitoring device to the Power Monitoring EMS software. The work includes verification communication between field devices and server, configuration of Modbus Ethernet Gate way, Thermal sensors and MFM. Creation of required screens, dash boards and alarms for all devices in the EMS server PC in PME version 2024 and imparting training to Dept. staff etc. as required and as directed by the EIC. This work will be carried out by OEM trained Engineers, Wiring and Termination of RS 485 Cable. Inegration Charge Shall Valid For 5 Years. Software shall be ISO50001 certified. Software shall having Cyber Security Certification. Software shall be expendable for future expansions without disturbing base installed software. The rate quoted shall be inclusive of all the civil works and hoisting to its location, assembling of units, lining up, bolting the units, wiring and checking all control wiring all necessary interconnection & accessories as per particular specification.
HVAC EQUIPMENT
OD294078/2025-2026 Supply, Installation ,testing and commissioning of following minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with multiple compressors of variable speed inverter driven with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser suitable for 3 phase, 415 V, 50Hz supply, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off, suitable interconnecting control cabling between IDUs , ODUs ,vibration isolator for Outdoor unit and GI mounting stand shall be included as part of equipment line item etc . Minimum Energy Efficiency of the equipment shall meet stringent of ASHRAE 90.1 and ECBC latest standards (whichever is superior). The item shall be complete in all respects complying to technical specifications. (Note: 1.Cost of equipment should be inclusive of necessary hardware /software gateway interface controllers etc.) 4 HP
OD294080/2025-2026 Supply, Installation ,testing and commissioning of following minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with multiple compressors of variable speed inverter driven with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser suitable for 3 phase, 415 V, 50Hz supply, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off, suitable interconnecting control cabling between IDUs , ODUs ,vibration isolator for Outdoor unit and GI mounting stand shall be included as part of equipment line item etc . Minimum Energy Efficiency of the equipment shall meet stringent of ASHRAE 90.1 and ECBC latest standards (whichever is superior). The item shall be complete in all respects complying to technical specifications. (Note: 1.Cost of equipment should be inclusive of necessary hardware /software gateway interface controllers etc.) 6 HP
OD290359/2025-2026 Supply, Installation ,testing and commissioning of following minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with multiple compressors of variable speed inverter driven with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser suitable for 3 phase, 415 V, 50Hz supply, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off, suitable interconnecting control cabling between IDUs , ODUs ,vibration isolator for Outdoor unit and GI mounting stand shall be included as part of equipment line item etc . Minimum Energy Efficiency of the equipment shall meet stringent of ASHRAE 90.1 and ECBC latest standards (whichever is superior). The item shall be complete in all respects complying to technical specifications. (Note: 1.Cost of equipment should be inclusive of necessary hardware /software gateway interface controllers etc.) 24 HP
OD316464/2025-2026 Supply, Installation ,testing and commissioning of following minimum capacity Air-cooled VRF (Variable Refrigerant Flow) Outdoor unit with multiple compressors of variable speed inverter driven with suitable capacity drive motors conforming to IE3 as per IS 12615, air cooled condenser suitable for 3 phase, 415 V, 50Hz supply, R410A/R407C refrigerant, oil separator, with all accessories, and safety devices like thermal protector, pressure relief valve, high-low pressure cut off, suitable interconnecting control cabling between IDUs , ODUs ,vibration isolator for Outdoor unit and GI mounting stand shall be included as part of equipment line item etc . Minimum Energy Efficiency of the equipment shall meet stringent of ASHRAE 90.1 and ECBC latest standards (whichever is superior). The item shall be complete in all respects complying to technical specifications. (Note: 1.Cost of equipment should be inclusive of necessary hardware /software gateway interface controllers etc.) 26 HP
OD294083/2025-2026 Supply, Installation, Testing and Commissioning of following minimum capacity Double skin, sheet metal VRF compatible, VFD driven, Ceiling Suspended Unit for fresh air, inculding all accessories as required as per technical specifications, outlet volume control dampers ,canvas connections, Filter sections with MERV-7 and MERV-14 filters placed in downstream complying to ASHRAE 52.2 standard, cooling coil of copper tube, aluminium fin construction, squirrel cage, TEFC, IE 3 ,3-Ph induction motor, SS Drain Pan, DIDW centrifugal fan, drive package and cushy-foot mounting, control wiring for actuators, all housed inside housing of a double skin construction of 0.8mm pre-plasticized / pre coated Galvanized sheet steel(GSS) minimum 120 GSM and 0.8mm Al Zinc sheet or 275 GSM 0.8mm thick(GSS) inside with insulation of minimum 40 mm thick CFC free PUF injected insulation of 40 kg/m3 density (min.) with K factor not exceeding 0.04 W/ sqm°C, thermo break profile, GI support, necessary vibration isolation arrangement, Limit switch in door and inspection lamps to be fixed, suitable starter and control panel as required, power wiring and associated control wiring. Minimum external static pressure of CSU shall be 25 mm wc. (External Static Pressure requirements shall be exclusive of filters). The item shall be complete in all respects complying with technical specifications. AIRFLOW = 120 L/s, TOTAL COOLING COIL CAPACITY = 3.0 TR
OD290384/2025-2026 Supply, Installation, Testing and Commissioning of following minimum capacity Double skin, sheet metal VRF compatible Ceiling Suspended Unit inculding all accessories as required as per technical specifications, outlet volume control dampers ,canvas connections, Filter sections with MERV-7 and MERV-14 filters placed in downstream complying to ASHRAE 52.2 standard, cooling coil of copper tube, aluminium fin construction, squirrel cage, TEFC, IE 3 ,3-Ph induction motor, SS Drain Pan, DIDW centrifugal fan, drive package and cushy-foot mounting, control wiring for actuators, all housed inside housing of a double skin construction of 0.8mm pre-plasticized / pre coated Galvanized sheet steel(GSS) minimum 120 GSM and 0.8mm Al Zinc sheet or 275 GSM 0.8mm thick(GSS) inside with insulation of minimum 40 mm thick CFC free PUF injected insulation of 40 kg/m3 density (min.) with K factor not exceeding 0.04 W/ sqm°C, thermo break profile, GI support, necessary vibration isolation arrangement, Limit switch in door and inspection lamps to be fixed, suitable starter and control panel as required, power wiring and associated control wiring. Minimum external static pressure of CSU shall be 25 mm wc. (External Static Pressure requirements shall be exclusive of filters). The item shall be complete in all respects complying with technical specifications.1TR
OD294088/2025-2026 Supply, Installation, Testing and Commissioning of following minimum capacity Double skin, sheet metal VRF compatible Ceiling Suspended Unit inculding all accessories as required as per technical specifications, outlet volume control dampers ,canvas connections, Filter sections with MERV-7 and MERV-14 filters placed in downstream complying to ASHRAE 52.2 standard, cooling coil of copper tube, aluminium fin construction, squirrel cage, TEFC, IE 3 ,3-Ph induction motor, SS Drain Pan, DIDW centrifugal fan, drive package and cushy-foot mounting, control wiring for actuators, all housed inside housing of a double skin construction of 0.8mm pre-plasticized / pre coated Galvanized sheet steel(GSS) minimum 120 GSM and 0.8mm Al Zinc sheet or 275 GSM 0.8mm thick(GSS) inside with insulation of minimum 40 mm thick CFC free PUF injected insulation of 40 kg/m3 density (min.) with K factor not exceeding 0.04 W/ sqm°C, thermo break profile, GI support, necessary vibration isolation arrangement, Limit switch in door and inspection lamps to be fixed, suitable starter and control panel as required, power wiring and associated control wiring. Minimum external static pressure of CSU shall be 25 mm wc. (External Static Pressure requirements shall be exclusive of filters). The item shall be complete in all respects complying with technical specifications. 2.0TR
OD313241/2025-2026 Supply, Installation, Testing and Commissioning of following minimum capacity Double skin, sheet metal VRF compatible Ceiling Suspended Unit inculding all accessories as required as per technical specifications, outlet volume control dampers ,canvas connections, Filter sections with MERV-7 and MERV-14 filters placed in downstream complying to ASHRAE 52.2 standard, cooling coil of copper tube, aluminium fin construction, squirrel cage, TEFC, IE 3 ,3-Ph induction motor, SS Drain Pan, DIDW centrifugal fan, drive package and cushy-foot mounting, control wiring for actuators, all housed inside housing of a double skin construction of 0.8mm pre-plasticized / pre coated Galvanized sheet steel(GSS) minimum 120 GSM and 0.8mm Al Zinc sheet or 275 GSM 0.8mm thick(GSS) inside with insulation of minimum 40 mm thick CFC free PUF injected insulation of 40 kg/m3 density (min.) with K factor not exceeding 0.04 W/ sqm°C, thermo break profile, GI support, necessary vibration isolation arrangement, Limit switch in door and inspection lamps to be fixed, suitable starter and control panel as required, power wiring and associated control wiring. Minimum external static pressure of CSU shall be 25 mm wc. (External Static Pressure requirements shall be exclusive of filters). The item shall be complete in all respects complying with technical specifications. 3.0TR
OD313233/2025-2026 Supply, Installation, Testing and Commissioning of following minimum capacity Double skin, sheet metal VRF compatible Ceiling Suspended Unit inculding all accessories as required as per technical specifications, outlet volume control dampers ,canvas connections, Filter sections with MERV-7 and MERV-14 filters placed in downstream complying to ASHRAE 52.2 standard, cooling coil of copper tube, aluminium fin construction, squirrel cage, TEFC, IE 3 ,3-Ph induction motor, SS Drain Pan, DIDW centrifugal fan, drive package and cushy-foot mounting, control wiring for actuators, all housed inside housing of a double skin construction of 0.8mm pre-plasticized / pre coated Galvanized sheet steel(GSS) minimum 120 GSM and 0.8mm Al Zinc sheet or 275 GSM 0.8mm thick(GSS) inside with insulation of minimum 40 mm thick CFC free PUF injected insulation of 40 kg/m3 density (min.) with K factor not exceeding 0.04 W/ sqm°C, thermo break profile, GI support, necessary vibration isolation arrangement, Limit switch in door and inspection lamps to be fixed, suitable starter and control panel as required, power wiring and associated control wiring. Minimum external static pressure of CSU shall be 25 mm wc. (External Static Pressure requirements shall be exclusive of filters). The item shall be complete in all respects complying with technical specifications. 5.5 TR
OD316491/2025-2026 Supply, Installation ,testing and commissioning of PDI Compatible central controller, along with associated accessories for controlling entire VRF system & 25% spare capacity for future provisions with suitable interconnecting control cabling between IDUs, ODUs and central controller ,Power wiring with necessary supports and complete in all respects as per the technical specifications.
OD290393/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 3/4") 44.45 mm
OD290403/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 5/8") 41.275 mm
OD290404/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 1/2") 38.1mm
OD290411/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 3/8") 34.925 mm
OD290412/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 1/4") 31.75 mm
OD290413/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1 1/8") 28.575 mm
OD290414/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 7/8") 22.22 mm
OD290415/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 3/4") 19.05 mm
OD290416/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 5/8") 15.875 mm
OD290417/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1/2") 12.7 mm
OD290418/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 3/8") 9.525 mm
OD290419/2025-2026 Supply, Installation ,testing and commissioning of Gas/ Liquid Copper Piping with nitrile rubber class 'O' insulation of suitable thick round closed cell elastomeric insulation with minimum R value of 0.7 for pipe size greater than 40mm and 0.4 for less than 40 mm, finished with 7mils factory laminated fibre glass cloth and insulation shall have antimicrobial properties. Refrigerant piping shall have suction filters for gas line, filter drier & sight glass for liquid line as per specification for each indoor machines & outdoor units including chasing, drilling, concealing and making good the same on walls etc of following specifications as per site conditions. Suitable Refnet/ Y joints required for interconnection of piping & required pipe fittings and accessories like Bends, Tees, reducers, supports, clamps, etc shall be considered as part of refrigerant piping .Complete in all respects as per technical specifications. NOTE: The contractor shall ensure that all refrigerant pipe sizes required as per the design of the equipment shall be considered in the line items underneath, even if the refrigerant pipe size is not mentioned in following line items. Both refrigerant suction and liquid line shall be insulated. Hard Copper Pipe 18Guage with 19mm thick Insulation ( 1/4") 6.35 mm
OD290422/2025-2026 Supply, installation, testing and commissioning of suitable dia PVC condensate drain pipe of 6kg/sq.cm connecting the drain pan of the indoor units to nearest drain point with necessary U-trap, insulated with 9 mm thick closed cell elastomeric insulation finished with 7mils factory laminated glass cloth along with required pipe fittings and accessories like Bends, Tees, reducers, clamps, suitably supported etc. complete in all respects as per the technical specifications.
OD294138/2025-2026 Supply, Installation testing and commissioning of Inline cabinet fans of following minimum capacity with suitable blower, 3 phase/Single phase direct driven/Belt driven motor(IE3) of following capacity for exhaust,with Starter /Starter panel other accessories etc. complete in all respects as required by the standard specifications. (Location: Toilets) complete in all respects as per the technical specifications. Contractor shall calculate the actual ESP and submit to the engineer in charge for review. 225 L/s at 200 Pa
OD294139/2025-2026 Supply, Installation testing and commissioning of Inline cabinet fans of following minimum capacity with suitable blower, 3 phase/Single phase direct driven/Belt driven motor(IE3) of following capacity for exhaust,with Starter /Starter panel other accessories etc. complete in all respects as required by the standard specifications. (Location: Toilets) complete in all respects as per the technical specifications. Contractor shall calculate the actual ESP and submit to the engineer in charge for review. 200 L/s at 200 Pa
OD313361/2025-2026 Supply, Installation testing and commissioning of Inline cabinet fans of following minimum capacity with suitable blower, 3 phase/Single phase direct driven/Belt driven motor(IE3) of following capacity for exhaust,with Starter /Starter panel other accessories etc. complete in all respects as required by the standard specifications. (Location: Toilets) complete in all respects as per the technical specifications. Contractor shall calculate the actual ESP and submit to the engineer in charge for review. 75 L/s at 200 Pa
OD316548/2025-2026 Supply, Installation testing and commissioning of Inline cabinet fans of following minimum capacity with suitable blower, 3 phase/Single phase direct driven/Belt driven motor(IE3) of following capacity for exhaust,with Starter /Starter panel other accessories etc. complete in all respects as required by the standard specifications. (Location: Toilets) complete in all respects as per the technical specifications. Contractor shall calculate the actual ESP and submit to the engineer in charge for review. 50 L/s at 200 Pa
OD316574/2025-2026 Supply, Installation testing and commissioning of duct mounted CO2 sensors for demand control ventilation, mounted inside return air ducts, including interface with fresh air handling ceiling suspended units and BMS.The sensors shall be able to detect CO2 levels and signal the VFD to ramp up/down the fresh air flow via BMS. The sensors shall be complete in all respects as per the technical specifications.
AIR DISTRIBUTION
16.12.1.1 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness, complete in all respects as per technical specifications. 0.63 mm (24 Gauge)
16.12.1.2 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness, complete in all respects as per technical specifications. 0.80 mm (22 Gauge)
16.12.1.3 Supply, installation, balancing and commissioning of factory fabricated GSS sheet metal rectangular ducting complete with neoprene rubber gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per approved drawings and specifications of following sheet thickness, complete in all respects as per technical specifications. 1.00 mm (20 Gauge)
OD290503/2025-2026 Supplying and fixing of Closed cell nitrile rubber insulation with factory laminated Aluminium FSK facing of 12 micron thickness as mentioned in technical specification ,40-60 kg/m3 density, Butt all joints tightly and seal all breaks and joints by adhering glass cloth tape, fixing of insulation using OEM recommended fixing details ,supports and adhesive, tapes etc. complete in all respects as required by the technical specifications.The thickness of insulation shall be as per ECBC requirements to meet the temperature conditions of Inside:14 Deg C and Outside 40 Deg C or 19 mm thickness whichever is higher. The item shall be complete in all respects complying to technical specifications.
OD290510/2025-2026 Supply, Installation, testing and commissioning of Acoustic lining inside sheet metal ducts with 10mm thick Open Cell nitrile rubber class 1 with antimicrobial properties. ,having density of 140-180 kg/m3 ,fixing of insulation using OEM recommended fixing details ,supports and adhesive, tapes etc. complete in all respects as per the technical specifications
OD316737/2025-2026 Supply, Installation, Testing & Commssioning of extruded Aluminium powder coated Strip Line (Linear continuous) supply diffuser with plenum. The Sample & Colour to be approved by Architect before procurement by HVAC vendor. 2 Slot Linear Diffuser 20mm slot width.
OD316757/2025-2026 Supply, Installation, Testing & Commssioning of extruded Aluminium powder coated Strip Line (Linear continuous) return diffuser. The Sample & Colour to be approved by Architect before procurement by HVAC vendor. 2 Slot Linear Diffuser 20mm slot width.
16.17 Supplying, fixing testing commissioning of supply air diffusers of powder coated aluminium with aluminium volume control dampers with anti smudge ring & removable core.
16.18 Supplying, fixing testing commissioning of Return air diffusers of powder coated aluminium without volume control dampers with anti smudge ring & removable core.
OD290600/2025-2026 Supplying, fixing testing commissioning of Aluminium powder coated Supply/exhaust air Disc valve with opposed blade 150 mm dia for toilets
OD290604/2025-2026 Supplying, fixing testing commissioning of Aluminium powder coated continuous supply grilles with 0/15 deg. Deflection as follows 100 mm wide
OD290633/2025-2026 Supply, Installation , testing and commissioning of Aluminium extruded fresh air louvers with fresh air damper,bird screen etc. complete in all respects as required by the technical specifications..
OD290645/2025-2026 Supply, Installation , testing and commissioning of Aluminium extruded exhaust air louvers with extract air damper,bird screen etc. complete in all respects as required by the technical specifications..
16.15 Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
16.16 Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required.
OD290659/2025-2026 Supply, Installation, testing and commissioning of opposed blade type Extruded Aluminium volume control dampers of 16 gauge GI sheets to be provided with suitable links, levers and quadrants for manual control of volume of air flow and for proper balancing of the air distributions system . complete in all respects as per the technical specifications.
OD290687/2025-2026 Supply, Installation, testing & commissioning of Fusible link type Fire damper of 16 gauge GI sheets with fire rating of 300 Deg C for 2 hr for Air Distribution Networks complete in all respects as per the technical specifications.
OD290221/2025-2026 Supply, Installation, Testing and Commissioning of electric driven main fire pump suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification. (a) Horizontal, split casing, centrifugal type pump of cast iron body bronze impeller with stainless steel shaft, mechanical seal having rated flow of 2850 lpm at 180m approximate head, conforming to IS 1520.(b) Suitable HP Squirrel cage induction motor conforming to IS 12615 specifications, TEFC, suitable synchronous speed, suitable for operation on 415 volts, 3phase 50Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class- insulation, conforming to IS-325.(c) M.S. fabricated Common base plate, coupling, coupling guard etc. as required.(d) Suitable cement concrete foundation duly plastered along with anti vibration pads/mounts.
OD290233/2025-2026 Supply, Installation, Testing and Commissioning of diesel engine driven fire pump suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification. (a) Horizontal, split casing, centrifugal type pump of cast iron body bronze impeller with stainless steel shaft, mechanical seal having rated flow 2850 lpm at 180m head, conforming to IS 1520. (b) Suitable HP, suitable RPM water cooled radiator type diesel engine conforming to relevant BS IS standard complete with auto starting mechanism, 12 volts/24 Volts electric starting equipment,12v 180AH Battery and leads, Diesel Tank Fabricated from MS sheet of 4mm Thick (Minimum Capacity for 8 hour operation) with level indicator, By-pass line, piping from diesel tank to engine, exhaust pipe extended upto 1m outside pump house duly insulated with 50 mm thick glass wool with 1mm thick aluminium sheet cladding, residential silencer, instruments and protection as per specification, stop solenoid for auto stop in the event of fault with audio indications, painted with post office red colour etc. as required. (c) M.S. fabricated Common base plate, coupling, coupling guard etc. as required. (d) Suitable cement concrete foundation duly plastered with anti vibration pads/ mounts. (e) Diesel engine control panel
OD290253/2025-2026 Supply, Installation, Testing and Commissioning of electric driven pressurization pump (Jockey Pump) suitable for automatic operation and consisting of following, complete in all respect as required as per technical specification. (a) Vertical Inline pump of stainless steel body and stainless steel impeller with stainless steel shaft, mechanical seal having rated flow of 180 lpm at 180m head, conforming to IS 1520. (b) Suitable HP Squirrel cage induction motor conforming to IS 12615 specifications, TEFC, suitable synchronous speed, suitable for operation on 415 volts, 3 phase 50 Hz. AC with IP 55 protection for enclosure, horizontal foot mounted type with Class- insulation, conforming to IS-325. (c) M.S. fabricated Common base plate, coupling, coupling guard, foundation bolts etc. as required. (d) Suitable cement concrete foundation
OD291037/2025-2026 Supply, installation, testing and commissioning of pressure gauge 0-200 PSI (0 - 14 Kg/sq.cm ) range, 3/8 BSP bottom entry, 100 mm dial weather proof with stainless steel internals including fittings, ball valves etc. complete as required as per technical specification.
OD290285/2025-2026 Supply, installation, testing and commissioning of industrial type pressure switch having 1/4 BSP(F) connection with IP rated enclosure, phosphor bronze bellows as sensing element, SPDT contact system with fittings, ball valve of suitable of suitable size etc. complete as required as per technical specification.
18.20 supplying and fixing air vessel made of 250 mm dia 8 mm thick MS sheet, 1200 mm in height with Air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia Gun metal wheel valve with required accessories, pressure guage and painting with synthetic enamel paint of approved shade as required.
OD290755/2025-2026 Supply, Installation, Testing and Commissioning of 200 mm nominal dia MS (Heavy C Class) pipe IS:3589 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290867/2025-2026 Supply, Installation, Testing and Commissioning of 150 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290887/2025-2026 Supply, Installation, Testing and Commissioning of 100 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290905/2025-2026 Supply, Installation, Testing and Commissioning of 80 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290920/2025-2026 Supply, Installation, Testing and Commissioning of 65 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290922/2025-2026 Supply, Installation, Testing and Commissioning of 50 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290951/2025-2026 Supply, Installation, Testing and Commissioning of 40 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290966/2025-2026 Supply, Installation, Testing and Commissioning of 32 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD290993/2025-2026 Supply, Installation, Testing and Commissioning of 25 mm nominal dia MS (Heavy C Class) pipe IS:1239 marked including welding, paints, pipe supports, all fittings and accessories such as elbows, flanges, tees, reducers, neoprene gaskets, nuts, bolts etc. as required. The pipe shall be painted with one coat of primer two coats of synthetic enamel paint of suitable shade. The pipe shall fixed on ceiling, walls, columns, truss etc for all heights with suitable hangers/ supports and fasteners etc including cutting the walls/means etc and making good the same complete as required as per the technical specification.
OD291004/2025-2026 Supply, laying, testing and commissioning of C class heavy duty MS pipe of 150mm diameter conforming to IS 1239 including welding, providing fittings like elbows, tees, tapers, flanges, nuts/bolts, gaskets etc., in ground at a depth of 1m from ground level including excavation providing cement concrete blocks as supports at 3m intervals, anticorrosive wrapping coating of 4mm thickness as per IS10221, refilling the trench etc. complete as required as per the technical specification.
OD291016/2025-2026 Supply, laying, testing and commissioning of C class heavy duty MS pipe of 80 mm diameter conforming to IS 1239 including welding, providing fittings like elbows, tees, tapers, flanges, nuts/bolts, gaskets etc., in ground at a depth of 1m from ground level including excavation providing cement concrete blocks as supports at 3m intervals, anticorrosive wrapping coating of 4mm thickness as per IS10221, refilling the trench etc. complete as required as per the technical specification.
OD290317/2025-2026 Supply, installation, testing and commissioning of dual plate non-return valve of 150 mm diameter, PN16 conforming to API 594 with Cast iron/Cast steel body, SS disc complete with all accessories including flanges, rubber gasket, GI bolts, GI nuts, washers etc. complete as required.
OD290310/2025-2026 Supply, installation, testing and commissioning of dual plate non-return valve of 65 mm diameter, PN16 conforming to API 594 with Cast iron/Cast steel body, SS disc complete with all accessories including flanges, rubber gasket, GI bolts, GI nuts, washers etc. complete as required.
18.11.7 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts,washers, gaskets conforming to IS 13095 of following sizes as required:200 mm dia
18.11.6 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts,washers,gaskets conforming to IS 13095 of following sizes as required:150 mm dia
18.11.5 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts,washers,gaskets conforming to IS 13095 of following sizes as required:100 mm dia
18.11.4 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts, washers, gaskets conforming to IS 13095 of following sizes as required:80 mm dia
18.11.3 Supplying, fixing, testing and commissioning of Butterfly Valve of PN 1.6 rating with bronze or gun metal seat duly ISI marked complete with nuts, bolts,washers,gaskets conforming to IS 13095 of following sizes as required:65 mm dia
OD290330/2025-2026 Supply, installation, testing and commissioning of 150 mm dia Y strainer with Cast iron/Carbon steel body, SS mesh complete with all accessories including flanges, rubber gasket, GI bolts, GI nuts, washers etc. complete as required as per the technical specification.
OD290332/2025-2026 Supply, installation, testing and commissioning of 80 mm dia Y strainer with Cast iron/Carbon steel body, SS mesh complete with all accessories including flanges, rubber gasket, GI bolts, GI nuts, washers etc. complete as required as per the technical specification.
18.9.1Supplying and fixing single headed internal hydrant valve with instantaneous Gun metal or stainless steel coupling of 63mm dia with cast iron wheel ISI marked conforming to IS 5290(Type A) with blank Gun metal or Stainless steel cap and chain as required:Single headed Gunmetal
18.17.1 Supplying and fixing first-aid Hose Reel with MS construction spray painted in post office red, conforming to IS 884 complete with the following as required. a) 20 mm nominal Internal dia water hose thermoplastic(Textile reinforced) type-2 as per IS:12585 b) 20 mm nominal internal dia gun metal globe valve &nozzle c) Drum and brackets for fixing the equipments on wall. d) Connections from riser with 25 mm dia stop gun metal valve & M.S. Pipe and socket. 30 m
18.16.1 Supplying and fixing 63 m dia,15m long RRL hose pipe with 63 mm dia male and female couplings duly bound with GI wire, rivets etc. conforming to IS 636 (type-A) as required: Gun Metal
18.18.1 Supplying and fixing 63 mm dia gun etal short metal branch pipe ith 20 mm nominal interanal diameter size nozzle conforming to IS 903 suitable for Instantaneous connection to Interconnect hose pipe coupling as required:Supplying and fixing 63 mm dia gun metal short branch pipe with 20 mm nominal internal diameter size nozzle conforming to IS 903 suitable for instantaneous connection to interconnect hose pipe coupling as required:
OD290513/2025-2026 Supply, installation, testing and commissioning of hose boxes wall/pedestal type of size 750 x 250 x 600 mm made out of 16 SWG MS sheet steel with front side glass, locking arrangement and painted with approved colour completed as required as per technical specification.
18.19.2 Supplying and fixing fire brigade connection of cast iron body with gun metal male instantaneous inlet couplings complete with cap and chain as reqd. for suitable dia M.S. Pipe connection conforming to IS 904 as required:4 way-150 mm dia M.S. Pipe
OD290339/2025-2026 Supply, installation, testing and commissioning of draw out connection made of CI Body, 100mm dia. flanged inlet with gunmetal outlet, including cost of 100mm dia swing type foot valve, complete with GI nuts, bolts, gasket etc as required as per technical specification.
18.21.1 Providing, fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Pendent Sprinkler
OD296086/2025-2026Providing, fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Extended Coverage Sprinkler
18.21.2 Providing, fixing, testing and commissioning of 15 mm dia quatzoid bulb type sprinklers of rating 68 degree centigrade with required accessories :Upright sprinkler
OD290343/2025-2026 Supply, installation, testing and commissioning of 1m unbraided flexible connection to position the sprinkler head in desired location in suspended ceilings. The unit must be complete with stainless steel flexible connection with nipple, reducer, square bar and brackets etc and other accessories as required as per the technical specification.
18.24.3 Providing, fixing, testing & commissioning of installation control valve of cast iron body, brass/bronze working parts comprising of water motor alarm, bronze seat clapper, clapper arm and hydraulically driven mechanical gong bell to sound continuous alarm when the wet riser/sprinkler system activates, pressure gauges, emergency releases, strainer, pressure switch, cock valve complete with drain valve and bypass, test control box, ball valves, MS pipeof required size, flanges, orifice plate, gasket etc of follwing sizes as required: 150 mm dia
OD290511/2025-2026 Supply, installation, testing and commissioning of UL listed flow switch with SPDT contacts, with fixing accessories suitable for nominal pipe dia meters ranging from 1 to 6. The body of the flow switch shall be water proof with IP protection. There shall be inbuilt settings to adjust the flow rate and alarm retard time. The flow switch should have minimum withstand pressure of 10Kg/cm2 and operating pressure ranging from 3.5kg/cm2 to 10Kg/cm2. complete as required as per the technical specification.
OD290351/2025-2026Supply, installation, testing and commissioning of Gun metal Air release valve, 25mm male threaded inlet, complete with all accessories as required as per the technical specification.
OD290353/2025-2026 Supply and installation of ABC Stored pressure type Fire Extinguisher 6 Kgs Capacity Mono Ammonium Phosphate based Dry Chemical Powder as per IS 14609 with ISI Mark for Fighting ABC Class of Fire, stored Pressure type of Mild steel body pressurized by Nitrogen Gas. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket. The Extinguisher should be manufactured strictly as per IS: 15683:2018 with ISI mark.
OD290354/2025-2026 Supply and installation of Modular type Carbon-dioxide extinguisher of ISI marked 4.5 Kg capacity made of high pressure seamless steel cylinder (CCE marked ) complete with wheel type valve with one meter long braided high pressure discharge hose complete in all respects including initial fill with CO2 gas, conforming to IS:15683:2018 complete as required as per the technical specification.
OD290360/2025-2026 Supply and installation of ISI marked Clean agent type Modular fire extinguisher of 2kg capacity. The Extinguisher shall have pressure gauge for indicating inside pressure with opening and closing lever of squeeze grip type with tamper proof seal, complete with wall bracket, all the accessories and as per the technical specifications.
OD293968/2025-2026 Intelligent addressable type Multicriteria type (Smoke + Heat) detectors with mounting base, LED, address switch/Automatic address complete as per specifications.The detector shall be EN54-5, EN54-7 and EN54-17 approved and CE certified.IP rating shall be IP30 and operating temperature -10°C to 60°C.
17.1.1 FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of heat detector operating at 54°C/57°C with rate of rise cum fixed temperature (dual thermistor) type with mounting base complete with all connection etc. as required.
17.1.2 FIRE DETECTION AND ALARM SYSTEM (CONVENTIONAL)Supplying, installation, testing & commissioning of smoke detector with built-in LED and mounting base complete with all connections etc. as required.
17.2.14 INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of addressable manual call point complete as required.
OD290501/2025-2026 Supply, installation, testing and commissioning of addressable type or conventional with addressable module wall sounder cum strobe for both audio and visual indication complete with all fixing accessories, base box etc. under false ceiling, roof, wall, etc, as required as per the technical specification. The product shall be EN/UL/FM/LPCB approved/ listed.
17.2.7 INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of fault isolator complete with base as required.
OD290374/2025-2026 Supply, installation, testing and commissioning of intelligent addressable Input module for monitoring purpose and send the signal from a flow switch to the alarm panel for initiating alarm when flow occur, complete with all necessary accessories as required as per the technical specification. The product shall be EN/UL/FM/LPCB approved/ listed.
OD290381/2025-2026 Supply, installation, testing and commissioning of 24V Power supply unit for hooters with battery backup, complete in all respect with necessary accessories as required as per the technical specification.
17.3.2 PUBLIC ADDRESS SYSTEMSupplying, installation, testing & commissioning of 1.5/3/6W ceiling speaker complete as required.
OD290385/2025-2026 Supply, installation, testing and commissioning of wall mounted talk back unit for two way communication of fire fighters including all necessary accessories complete as required as per the technical specification.
OD290505/2025-2026 Supply and laying of 2x1.5 sq.mm armoured Copper FRLS cable ISI marked with proper clamping, supports and terminations appropriately above /below ground,on wall surface or recess as required as per the technical specifications.
OD290392/2025-2026 Supply, installation, testing and commissioning of IoT compatible EN 54-4 CE/CPR -certified Addressable type Fire alarm control panel (FACP) with 7" color display resolution 800x400, Minimum 5 pieces of soft keys, Navigation wheel button, Inbuilt scalability of minimum 8 addressable loops per fire panel with each loop shall be able to connect minimum 250 detectors and devices. Power supply unit of 1.0 A at 24 V DC standby, 4.8 A at 24 V DC alarm, 24 hrs back-up with 240 volts AC power supply, 24 volts Sealed Maintenance Free (SMF) lead acid batteries and then be capable of operating the system for 2 hours during an emergency condition including all necessary software for remote programming of fire alarm system through central control station. Hinged and removable chassis. Designed for online operations e.g. automatic configuration backup and multi site monitoring with single login and one view intelligent, 10000 event historical logging, 250 Zones creation. Panel shall be loaded with only 85%. Server PC - Intel i9 Processor 14Gen 16GB RAM, 1 TB SSD, with Wirelss Keyboard and Mouse & 21inch Monitor OS Should be Windows 11 Pro including all necessary accessories required at site to complete the work - 1 No. Fire Alarm System GUI software capable of following functions : a)Seamless integration to BAS software b)Uploading and downloading of information to FACP. c)Graphics including AutoCAD drawings. d) All Detector information and change of detector setting Software as described above. It shall be EN listed, Common for all FACP Panel with required number of software tags to be connected integrated to BMS system
17.2.5 INTELLIGENT FIRE ALARM SYSTEMSupplying, installation, testing & commissioning of response indicator on surface/ recessed MS Box having two LED, metallic cover complete with all connections etc as required.
OD293947/2025-2026 Addressable Relay modules For AHU, CSU FCU & Electrical Tripping system as per specification Module shall be EN listed,
OD293949/2025-2026 Addressable Relay modules For Fans & Lift Tripping as per specification. Module shall be EN listed
OD293951/2025-2026 Addressable Control Relay modules For Access controller Tripping as per specification. Module shall be EN listed
OD293954/2025-2026 Addressable Control Relay modules For triggering of Public address system as per specification. Module shall be EN listed
1.21.2 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
OD290396/2025-2026 Supply, installation, testing and commissioning of self-contained LED sign light (laser type) suitable for emergency applications such as Fire Duct/Fire Lift/Hose reel/Fire Staircase/No smoking etc., complete with aluminium housing and acrylic display panel, operating on 230-240 V AC, 50 Hz supply, with maximum power consumption of 8 W. The unit shall be provided with inbuilt rechargeable Ni-Cd battery backup capable of minimum 3-4 hours emergency operation with automatic changeover during power failure and recharge time of 6-8 hours. The unit shall be suitable for ceiling suspended or wall mounting as required, with approximate dimensions of 500*225mm and weight around 1 kg. The item shall include all internal wiring, mounting accessories, fixing hardware, and necessary connections, and complete as required as per the technical specification.
OD290398/2025-2026 Supply, installation, testing and commissioning of self-contained LED sign light (laser type) suitable for FIRE ASSEMBLY POINT, complete with aluminium housing and acrylic display panel, operating on 230-240 V AC, 50 Hz supply, with maximum power consumption of 8 W. The unit shall be provided with inbuilt rechargeable Ni-Cd battery backup capable of minimum 3-4 hours emergency operation with automatic changeover during power failure and recharge time of 6-8 hours. The unit shall be suitable for ceiling suspended or wall mounting as required, with approximate dimensions of 500*225mm and weight around 1 kg. The item shall include all internal wiring, mounting accessories, fixing hardware, and necessary connections, and complete as required as per the technical specification.
OD290405/2025-2026 Supply and installation of photo luminescent glow signage containing standard instructions to the occupants in case of Fire emergency (FIRE ORDER), of standard size (600*800 MM minimum) as per conventional design/ colour code on 3 mm thick aluminium composite panel and conforming to IS 9457, IS12349, IS12407. The signage will be either fixed on the wall with the help of screws or hanged from the false ceiling with the help of chain screws etc. complete as required as per the technical specification.
OD290407/2025-2026 Supply, installation, testing and commissioning of self-contained LED sign light (laser type) suitable for Exit/Fire Exit, complete with aluminium housing and acrylic display panel, operating on 230-240 V AC, 50 Hz supply, with maximum power consumption of 8 W. The unit shall be provided with inbuilt rechargeable Ni-Cd battery backup capable of minimum 3-4 hours emergency operation with automatic changeover during power failure and recharge time of 6-8 hours. The unit shall be suitable for ceiling suspended or wall mounting as required, with approximate dimensions of 500*225mm and weight around 1 kg. The item shall include all internal wiring, mounting accessories, fixing hardware, and necessary connections, and complete as required as per the technical specification.
OD290409/2025-2026 Supply and fixing (in appropriate location) of Fire Emergency Evacuation Plan (Color) printed in photo paper of Size A2 sand-witched in Clear acrylic sheets fixed using SS Studs and other accessories complete as required as per the technical specification and conforming to IS 9457, IS 12349, IS 12407 .Evacuation Plan shall be prepared by the contractor and got approved from Client/Consultant.
OD295828/2025-2026 Supply,Installation, Testing & Commissioning of U/UTP cable - Category 6A 4 pair, 24 AWG solid copper conductor, 500 MHz, LSZH through conduits including termination, numbering tags, Cable ties, ferrules and all accessories required at site to complete the work as per specification
OD295905/2025-2026 Supply,Installation, Testing & Commissioning of 06 core outdoor SM fiber with accessories through conduits as required at site to complete the work as per specification
OD295906/2025-2026 Supply,Installation, Testing & Commissioning of 06core SM fiber(CCTV) with accessories through conduits as required at site to complete the work as per specification
OD295910/2025-2026 Supply,Installation, Testing & Commissioning of 42U Floor mount intelligent Controller Based Rack with 1000 depth Network Rack along with all necessary hardware and accessories etc. required at site to complete the work asper specification
OD295922/2025-2026 Supply,Installation, Testing & Commissioning of 9U Rack with 800 depth Network Rack along with all necessary hardware and accessories etc. required at site to complete the work as per specification
OD316950/2025-2026 Supply,Installation, Testing & Commissioning of 6U Rack with 800 depth Network Rack along with all necessary hardware and accessories etc. required at site to complete the work as per specification
OD295936/2025-2026 Supply,Installation, Testing & Commissioning of UTP Patch Cords, Category 6A - 1M along with all accessories required at the site to complete the work as per specification
OD295937/2025-2026 Supply,Installation, Testing & Commissioning of back box along with back and all accessories required at site to complete the work as per specification
OD295938/2025-2026 Supply,Installation, Testing & Commissioning of Single Shuttered Face Plate along with all accessories required at site to complete the work as per specification
OD295940/2025-2026 Supply,Installation, Testing & Commissioning of Cat6A information Outlet along with all accessories required at site to complete the work as per specification
OD295941/2025-2026 Supply,Installation, Testing & Commissioning of 12Port Rack Mountable LIU loaded with Adaptors & Pigtails & Patch Code including all necessary accessories required at site to complete the work as per specification
OD295942/2025-2026 Supply,Installation, Testing & Commissioning of CAT6A 24 port patch panel with shutter fully loaded, with all accessories required at site to complete the work as per specification
OD295943/2025-2026 Supply,Installation, Testing & Commissioning of WiFi 7 Access Point including all necessary accessories required at site to complete the work the work as per specification
OD295944/2025-2026 Supply,Installation, Testing & Commissioning of 5MP ANPR IP Bullet Camera for Parking Entry and exit for Vechile Identification including all necessary accessories required at site to complete the work as per specification
OD295956/2025-2026 Supply,Installation, Testing & Commissioning of 8CH ANPR NVR for Parking Entry and exit for Vechile Identification including all necessary accessories required at site to complete the work as per specification
OD295958/2025-2026 Supply,Installation, Testing & Commissioning of 64CH NVR 8 Bay with Hrad Disk including all necessary accessories required at site to complete the work as per specification
OD295970/2025-2026 Supply,Installation, Testing & Commissioning of 16CH NVR 4 Bay with Hard Disk including all necessary accessories required at site to complete the work as per specification
OD295977/2025-2026 Supply,Installation, Testing & Commissioning of 10TB Survillance Hard DIsk including all necessary accessories required at site to complete the work the work as per specification
OD295981/2025-2026 Supply,Installation, Testing & Commissioning of 5MP IP dome/Bullet Varifocal Camera with 2way audio and AI Features Enables(people counting, Object Identification, Perimeter Survelliance etc) including all necessary accessories required at site to complete the work as per specification
OD295987/2025-2026 Supply,Installation, Testing & Commissioning of 5MP Fisheye Camera with 2way audio and AI Features Enables(people counting, Object Identification, Perimeter Survelliance etc) including all necessary accessories required at site to complete the work as per specification
OD295999/2025-2026 Supply,Installation, Testing & Commissioning of 5MP PTZ Camera with 36X Optical zoom with AI Features enabled including all necessary accessories required at site to complete the work as per specification
OD296080/2025-2026 Supply,Installation, Testing & commissioning of 55inch Display with 4K Resolution including all necessary accessories required at site to complete the work as per specification
OD296082/2025-2026 Supply,Installation, Testing & Commissioning of 5 mtr HDMI cables, with all necessary accessories required at site to complete the work the work as per specification
OD296083/2025-2026 Supply,Installation, Testing & Commissioning of 5Mtr Boom Barrrier with ocntroller , readerIN/OUT, Push Button, Tag from Camera Vechiles with all necessary accessories required at site to complete the work the work as per specification
OD296084/2025-2026 Supply,Installation, Testing & Commissioning of 30W IP Speaker including all necessary accessories required at site to complete the work as per specification
OD296085/2025-2026 Supply,Installation, Testing & Commissioning of 30W Outdoor IP Speaker including all necessary accessories required at site to complete the work as per specification
OD296087/2025-2026 Supply,Installation, Testing & Commissioning of Paging Microphone including all necessary accessories required at site to complete the work as per specification
OD296088/2025-2026 Supply,Installation, Testing & Commissioning of PA system software for handling and maintains speakers including all necessary accessories required at site to complete the work as per specification
OD296089/2025-2026 Supply,Installation, Testing & Commissioning of Race Floor at server room with all necessary accessories required at site to complete the work the work as per specification
ELEVATOR
OD294030/2025-2026 Design, fabrication, supply, installation, testing, commissioning of electric traction type, machine roomless, Stainless steel 15 Pax (1020 Kg) passenger elevator (including freight landing charges,insurance and all applicable taxes and duties in country of origin and in India etc. except GST) and type suitable for operation on 415 V ± 10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 2 Mtr/sec, electromagnetic brake system, simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purchaser's EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fireman's switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. and at all floors with UP/DOWN direction, shaft wiring and lighting with accessories,braille buttons,audio announcement along with prerecorded message, LED light fixtures, ventilation fan, etc complete with all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required.The traction motor of elevator shall be of gearless type and placed inside the elevator hoist way complete as per technical specification, having automatic centre/side opening SS door with stainless steel frame works, stainless steel car enclosure provided with stainless steel handrails on two sides, granite flooring as applicable in accordance of following details:- 17 stops & 17 openings and entrance & exit at same side for all floors and suitable for travel height of 70 mtrs. (Shaft Size 2200mm (width) x 2800mm (depth)) with suitable car dimensions (complying with the net inside car area as per IS 14665 part 3/1) and door opening of 900mm (width) and 2100 mm (height) . The equipment should be BMS compatible. All electrical components with wiring from the single point power supply provided in last landing near the elevator door .All fabrication and procedures shall confirm to relevant IS standards and shall be complete as per the technical specifications.
OD316473/2025-2026 Design, fabrication, supply, installation, testing, commissioning of electric traction type, machine roomless, Stainless steel 15 Pax (1020 Kg) passenger elevator (including freight landing charges,insurance and all applicable taxes and duties in country of origin and in India etc. except GST) and type suitable for operation on 415 V ± 10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 2 Mtr/sec, electromagnetic brake system, simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purchaser's EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fireman's switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. and at all floors with UP/DOWN direction, shaft wiring and lighting with accessories,braille buttons,audio announcement along with prerecorded message, LED light fixtures, ventilation fan, etc complete with all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required.The traction motor of elevator shall be of gearless type and placed inside the elevator hoist way complete as per technical specification, having automatic centre/side opening SS door with stainless steel frame works, stainless steel car enclosure provided with stainless steel handrails on two sides, granite flooring as applicable in accordance of following details:- 17 stops & 17 openings and entrance & exit at same side for 15 floors and G1 and G2 Rear Opening and suitable for travel height of 70 mtrs. (Shaft Size 2200mm (width) x 2800mm (depth)) with suitable car dimensions (complying with the net inside car area as per IS 14665 part 3/1) and door opening of 900mm (width) and 2100 mm (height) . The equipment should be BMS compatible. All electrical components with wiring from the single point power supply provided in last landing near the elevator door .All fabrication and procedures shall confirm to relevant IS standards and shall be complete as per the technical specifications.
OD316540/2025-2026 Design, fabrication, supply, installation, testing, commissioning of electric traction type, machine roomless, Stainless steel 15 Pax (1020 Kg) passenger elevator (including freight landing charges,insurance and all applicable taxes and duties in country of origin and in India etc. except GST) and type suitable for operation on 415 V ± 10%, 3 phase, 50 Hz AC supply, having AC variable voltage and variable frequency micro-processor type traction control, speed of 2 Mtr/sec, electromagnetic brake system, simplex mode operation, operating panel with luminous buttons, overload warning indicator, battery operated alarm bell, LED type emergency light, intercom suitable for hook up to Purchaser's EPABX, infrared ray sensing door protection for full height, reverse phase relay on controller, fireman's switch at initial landing floor, LCD/LED car positions and direction indication in car and landings. and at all floors with UP/DOWN direction, shaft wiring and lighting with accessories,braille buttons,audio announcement along with prerecorded message, LED light fixtures, ventilation fan, etc complete with all accessories including Automatic Rescue Device (ARD) with dry maintenance free sealed batteries and Manual Emergency Rescue Device and all electrical components with wiring from the single point power supply provided at top landing near the elevator door complete as required.The traction motor of elevator shall be of gearless type and placed inside the elevator hoist way complete as per technical specification, having automatic centre/side opening SS door with stainless steel frame works, stainless steel car enclosure provided with stainless steel handrails on two sides, granite flooring as applicable in accordance of following details:- 17 stops & 17 openings and entrance & exit at same side for 16 floors and G1 Floor Rear Opening and suitable for travel height of 70 mtrs. (Shaft Size 2200mm (width) x 2800mm (depth)) with suitable car dimensions (complying with the net inside car area as per IS 14665 part 3/1) and door opening of 900mm (width) and 2100 mm (height) . The equipment should be BMS compatible. All electrical components with wiring from the single point power supply provided in last landing near the elevator door .All fabrication and procedures shall confirm to relevant IS standards and shall be complete as per the technical specifications.
OD296380/2025-2026 Supply, Erection, Testing & Commissioning of Modular - Advanced MBBR STP (Treatment: Anaerobic - Aerobic(MBBR) - Anaerobic) of 100 KLD underground system (50 KLD + 50 KLD WITH DIVIDER BOX) with Blower noise generation Less than 50 dB at a distance of 3 M. Rate shall be inclusive of all the necessary materials and necessary civil works, no extra claim for any additional material or whatever. The all work should be as per govermnment control board standards.
OD317333/2025-2026 Supply, Erection, Testing & Commissioning of Modular - Advanced MBBR STP (Treatment: Anaerobic - Aerobic(MBBR) - Anaerobic) of 100 KLD underground system (50 KLD + 50 KLD WITH DIVIDER BOX) with Blower noise generation Less than 50 dB at a distance of 3 M. Rate shall be inclusive of all the necessary materials and necessary civil works, no extra claim for any additional material or whatever. The all work should be as per govermnment control board standards.
OD317338/2025-2026 Supply, Erection, Testing & Commissioning of Ultra- Filtration System with an average flow of 5 m3/hr - 10 Hour Operation per day. Pressure Vessel Rating - PN 10, Membrane - PVDF - Pore size Range 0.1 to 0.01 micron. Rate shall be inclusive of all the necessary materials and necessary civil works, no extra claim for any additional material or whatever. The all work should be as per govermnment control board standards.
SOLAR
OD313702/2025-2026 Supply installation testing commissioning of 120 kWp On Grid Solar Plant, SOLAR PHOTOVOLTAIC PANEL: 600/595Wp – HALF CUT - TOPCON Modules are PID Resistan6 FSI Tested Positive Tolerance Certifications:IEC 61215, IEC 61730, IEC 61701, ISO9001:2008, ISO 14001:2004, Solar GRID TIE Inverter 100KW- 1 Nos, Multiple MPPT String Inputs Dual Independent MPP Trackers IP65-Water Resistant Enclosure Graphical LCD Display LED Status Indicator, SOLAR DC DISTRIBUTION-2 Nos, SOLAR AC Distribution Box -In-built SPD, LED Status Indicator for Output, SOLAR MODULE MOUNTING STRUCTURE, Face structure shall be provided that suits to install the solar panels. Installation of the panels are also in the façade contractor scope under supervision of Engineer in charge. Solar Plant Specific Earthing- Copper Bonded Rod Single Hole Terminal Pressed 250 Micron Coating 14.2mm Thickness 3000mm Length, Solar Plant Specific Lightning Arrestor- Single Spike Copper bonded 250 Micron Coating 16mm Thickness 1200mm Length 50Sqmm AL down conductor, Supply of all cables specific to Solar plant till the Solar AC output. Online Plant Monitoring Module mounting structure (MS Hot Dip Galvanized with appropriate analysis for Load/Wind speed), Electrical Accessories including cables & conduit, Remote Monitoring System, Mounting structure earthing points, Lightning Arrestor and earthing kits, LT Panel , Civil Works(equipment foundations), KSEB documentation, Installation, Service and 5 Years free breakdown service. And 5 Years Preventive Maintenance Service – with PMS in every 4 Months. The rate quoted shall be inclusive of construction of foundation and all the civil works and hoisting to its location, assembling of units, lining up, bolting the units and checking all control wiring. The all work should be as per Electrical Inspectorate/ KSEB standards. the rate inclusivce all assosiated accessories, execution, approvals and extra claim shall not be entertrained.
OD315556/2025-2026 "SOLAR GLASS(152 KWp) Extra over conventional cap curtain wall system:- 18.2mm SGU Providing and fixing the thin film Cadmium Telluride (CdTe) BIPV Glass Panels 18.2 mm thick thin film CdTe BIPV Glass PANELS of size as suggested by Architect/PMC and BIPV Vendor and tested as per Standard IS 16077 : 2013 /IEC 61646 : 2008 as per BIS and IS guidelines. These CdTe thin film BIPV Panels will be 20% transparent with Power of 303 Wp, 170 Wp,and 203 Wp per Panel as per different sizes and transparencies used. CdTe BIPV Panels use Low E (SnO2 coated) toughened laminated Glass as the base. The CdTe Thin film BIPV panels will have Voc more than 120 V . These panels will have a Junction Box as per BIS and IS guidelines. These Panels are tested as per test conditions of STC:1000W/m2, AM1.5, 25°C. Sizes as per Aplication location are -" 1)1500x1800mm 20% transparent 303 Wp; 18.2 MM THICKNESSS 2) 1500x1000 mm 20% transparent 170 Wp 18.2 MM THICKNESS 3) 1500x1200 mm 20% transparent 203 Wp 18.2 MM THICKNESS
OD315539/2025-2026 "Conventional Semi Unitised Cap Curtain wall system with Solar Thin Film CdTe BIPV Glass Design, Fabrication, Supply, Installation, Testing, protection, cleaning and handover of Conventional Semi Unitised caped curtainwall as per approved make system designed to withstand the wind pressure of confirming to IS -875-2015 part III . The profile system is based on capped curtain wall design and glass is held all around by mechanical pressure plate and cap with microwave cured EPDM gaskets in all four sides of glazing, with necessary brackets MS with HDG with three dimensional adjustment with serrations and serrated washers to arrest the wind load movement, Anchor Fasteners, screws and fasteners with Non-staining weather sealant and Aluminium flashing sealed all around perimeter inside and outside to seal the gaps between curtain wall and the building structure all complete required to perform as per specification and drawing in conjunction with BoQ. Design shall include pressure equalization with minimum 2 barrier gaskets for improved weather performance, drainage at all floor levels, Transom shall be overlapped with mullion to have proper drainage to mullion. The design to accommodate building movements, thermal expansions and the seismic movements. The system shall be designed considering surface temperatures of 80-90 deg.cel. and temperature differential of 25 deg.cel. without creating excess stress in the system. All metal joints in the wet area shall be small joint sealant applied to ensure water tightness. The system shall be designed of floor height units spanning between the floors with Dead load and wind load brackets with provision to accommodate movement at all floor levels and at every grid panels horizontally. The system shall be designed to accommodate 24mm IGU in vision area and 6mm SGU glass spandrel panel. System shall accommodate openable panel as per architectural requirement in the system. All fix vision glass and openable shall look similar in the elevation. Aluminium Edge Guard with Black Anodized shall be fixed at all vertical and Horizontal grooves. Each glass panel shall be supported for dead load at the bottom of glass with black anodised glass retainers two per panel. The EPDM gaskets to achieve the required compression and seal in the system. EPDM Gaskets shall be of micro cured (Online Curing) with shore A hardness of 60-65. Flashing / Trim / Floor Closure at Parapet level, floor level, beam bottom level and required flashings shall be provided continuously with required GI / Aluminium sheet. Internal and External cancelled Flashings shall be 1.0mm thick GI sheet. External exposed flashing shall be 1.5mm thick. Aluminium sheet with SDF coated matching with external Aluminium profiles. Internal exposed flashing shall be 2mm thick. Aluminium sheet with powder coated matching with internal aluminium profiles. The extruded aluminium sections of Alloy 6063 T5 / T6 and tolerances confirming to DIN / EN standard from approved extruder. The structural profiles shall have minimum 2 mm wall thickness. All the internal visible surfaces shall have Super durable Powder coating of 60 - 80 micron. The non visible aluminium surfaces shall have minimum chromatizing treatment. The system shall have SDF Coated vertical capping of 15mm and horizontal capping of 12mm deep visible in the elevation. Design, Fabrication, Supply and install required structural steel frame work in line with design drawings for made out of MS pipe sections / Plates of approved make of first quality confirming to IS standard. The steel design shall accommodate thermal stresses resulting from thermal expansion due to surface temperatures. The steel structure shall be finished with the following, i. Surface Preparation ? Blast cleaned to Sand confirming to BS EN ISO 8501-1 ii. Primer : Zinc Rich Epoxy 75 micron iii. Barrier : Epoxy Mio 125 micron iv. Finish : Polyurethane ? 50 Micron (Only for exposed steel) All Material Make / Vendor list / Supplier list shall be as per tender specification. All shade approval shall be as per Architect''s and EIC Approval. For Conventional Cap Curtain wall system - Rate for complete system as mentioned above. Cost is including along with scaff folding and safety net"
OD315554/2025-2026 EARTHING PROTECTION : Extra over convenional cap curtain wall system Earthing: The array structure of the PV yard will be grounded properly using adequate number of earthing kits. All metal casing/ shielding of the plant shall be thoroughly grounded to ensure safety of the power plant. Lightning: The SPV Power Plant shall be provided with lightning and over voltage protection. The main aim in this protection shall be to reduce the over voltage to a tolerable value before it reaches the PV or other sub system components. The source of over voltage can be lightning, atmosphere disturbances, etc. Metal Oxide varistors shall be provided inside the Array Junction Boxes. In addition suitable MOV?s also shall be provided in the Inverter to protect the inverter from over voltage. Other componenets to be included are 63a Busbar (4Nos) , 3Phs ACDB (4 Nos), 4in2out (4 Nos)
OD315555/2025-2026 SOLAR ON- GRID INVERTER : Extra over convenional cap curtain wall system The BIPV Panels System Includes Grid Tie Inverter and consists of in-built charge controller and bi-directional inverter to supply continuous power to the dedicated load with support to the load coming either from the solar array, battery bank, Grid Power in order of preference. The Grid-Tie of required rating of KWp as per standard Norms is considered for this project. The sine wave inverter generates a sinusoidal AC voltage with an exceptionally precise voltage and stabilized frequency. The inverter is protected against overload and short circuit.( For 152kw Inverter to be installed in total 1 nos of 50kw and 1 nos of 100 kw)
OD315552/2025-2026 Supply, Installation, Testing & Commissioning of following size of Grid Tied Solar Power Plant with .Solar Panels: Frame Material : Anodized Aluminum alloy Frame With Twin Wall Profile, Front Cover : High Transmission Low-Iron Tempered Glass (AR Coated), High efficency and positive power tolerance Pmax: 0/+5, Module Efficiency should be approx. 18%-21%, Normal operating temperature 45'C, Junction Box with Waterproof IP67 & MC4 Compatible and Enclosed with Bypass diodes, 100% Electroluminescence test to ensure error free Modules, Thep. temp. co-efficient of the PV module shall equal or better than -0.45%/degree C. Solar PV modules of minimum fill factor 75% to be used. Unit Production:- 4 to 5 Unit /kw /day (Actual)(1Year Avg) With 10 year Product warranty and 25 year Linear Power Warranty, Solar Inverter: MPPT Range: 80-1000 V, Max efficiency: 97.5% - 98.9%, O/p Frequency: 50/60Hz, Operating Altitude (m) ?4000, O/p Power Factor: ~1, O/P THDi: <3%, Operating Tempreture Range: -25~60°C, System Includes Grid Tie Inverter and consists of in-built charge controller and bi-directional inverter to supply continuous power to the dedicated load with support to the load coming either from the solar array, battery bank, Grid Power in order of preference. The Grid-Tie Inverter of required rating of KWp as per standard Norms is considered for this project. The sine wave inverter generates a sinusoidal AC voltage with an exceptionally precise voltage and stabilized frequency. The inverter is protected against overload and short circuit. Module Mounting Structure: Seamless Box Pipe / 'C' Channel of suitable size for rooftop solar installations with good stability agaist wind & weight load., Hot Dipped Galvanized steel coils. suitable arrangement for base plate for foundation , solar panel mounting, the structure should be suitable for carry the load of solar panel,wiring, sprinkler system etc. with necessary foundation work/wall mount, j bolt, anchor fastner etc. the nut bolt used for installtion of stucture should be (SS 304) quality. and Balane of System with necessary Swithgears (Suitabel size and protection of ACDB & DCDB), inter connecting wiring, earthing system, lightining arrester system, all liasoning work with various gov. dipartment like state nodal agency,DISCOM & CEIG is included in agency scope (E) Grid Tied Solar Power System:
PUMP AND ACCESSORIES
OD315378/2025-2026 Supply ,Installation , testing and commissioning of 280LPM at 70m head ,submersible centrifugal pump with Shaft, Pump Body and thurst ring should be SS, Enclosure Class: IP68, Insulation class: F, Quiet operation suitable starter and cable from starter to pump all complete for UG sump to OHT water transfer as per specification and including all the necessary accessories and control panels as required complete and directed by Engineer - in- charge.
OD315393/2025-2026 "Supply ,installation ,testing and commissioning of twin booster pump with one duty and one standby, Vertical Multistage Centrifugal Pump with internal VFD,IE5,Quiet operation.Automatic start/stop.Impeller,Pump Shaft and chamber AISI 304. Duty: 280LPM at 2.0bar fixed speed type to maintain the pressure at top Four floors to be located at terrace level including pneumatic tank including suction and delivery manifold(SS)Suction & discharge manifolds,isolating valves, Pressure transmitter,pressure gauge,Suction & discharge ball valves,cyclic change over switches and con troll panels all complete as directed by engineer-in-charge.
DISMANTLING OF ELECTRICAL FITTINGS
OD316542/2025-2026 Dismantling of ceiling fan, including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.
OD316544/2025-2026 Dismantling of pre - wired, fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
stage.html
html • 0.02 MB
tech_eval.pdf
cancelled_1.pdf
pdf • 0.13 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Tendernotice_1.pdf
PDF • 0.17 MB
CoC.pdf
Tender Documents • 1.50 MB
1.pdf
Other Document • 8.45 MB
3.pdf
Other Document • 21.18 MB
4.pdf
Tender Documents • 16.87 MB
5.pdf
Other Document • 2.10 MB
BOQ_1426079.xls
BOQ • 0.89 MB
corrigendum1.pdf
PDF • 0.13 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .