AC(Electrical)
SHQ BSF Krishnanagar
Providing and fixing of switchgear in existing feeder panel near CPC Canteen of 194 BN and Generator room and providing earthing to feeder panel near MT Garrage of 59 BN at seemanagar campus under SHQ BSF Krishnanagar
2025_BSF_889861_1
45/SHQ-KNR/AE(E)/NIT/2025-26
Open Tender
Electrical Works
Percentage
90 days
Seemanagar BSF campus
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹1,997
23 Dec 2025
15 Dec 2025
22 Dec 2025
15 Dec 2025
20 Dec 2025
15 Dec 2025
15 Dec 2025 - 20 Dec 2025
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipe from earth electrode including connection with GI thimble excavation and re-filling as required.
Providing and fixing 100 Amp, 30 KA, FP MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubical panel, making connections, Ics = 100% Icu and operational voltage 690V etc as required.
Providing and fixing 63 Amp, 10 KA, 3P MCCB with fixed thermal and magnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubical panel, making connections, testing etc as required.
Providing and fixing 63 Amp, 10 KA, DP MCB "C" curve, suitable for inductive load in the existing feeder panel complete with connections, tetsing and commissioning etc as required.
Providing and fixing 63 Amp TPN 4 way terminal block connector in the existing feeder panel etc as required.
tech_bid_open.pdf
tech_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.72 MB
BOQ_935301.xls
BOQ • 0.29 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .