Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹21.5 LAccepted-AOC 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹22.0 L+₹50,300 (2.34%)Rejected-Finance 154 GANDHI MARKET AMBALA CANTT HARYANA 133001 | AMBALA CANTT | AMBALA | HARYANA | 133001 | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹23.4 L+₹1.9 L (8.94%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted in category b(iii) |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
31 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE UTILITY AMBALA CANTT
GE UTILITY AMBALA CANTT-133001
MANNING AND OPERATION OF 66 KV MRS AND ALLIED WORKS UNDER GE UTILITY AMBALA CANTT
2021_MES_419628_2
GE(U)/AMB-53/2020-21
Open Tender
Civil Works
Item Rate
330 days
AMBALA CANTT
As per Tender documents
8 documents required · 8 mandatory
₹500
GE UTILITY AMBALA CANTT
₹40,000
Yes
19 Apr 2021
12 Mar 2021
2 Apr 2021
12 Mar 2021
31 Mar 2021
19 Mar 2021
12 Mar 2021 - 18 Mar 2021
60 days
Amount
SCHEDULE 'A' (SECTION-I) Manning and Operation of 66 KV Grid sub station (comprising of different equipments) with 66 KV incoming supply and 11 KV outgoing supply for existing sub stations round the clock(Three shifts per day) by deploying 01 No Electrician (Skilled) with 0 to 05 years experience in electrical works (EHV) at 66 KV MRS and 01 No Helper (Un Skilled) per shift including maintenance of log sheet of sub station, shut down register, attending telephone, Record of daily Meter recording Register, Earth testing Register and visual checking of 66 KV Instruments and operation of all equipments etc in the sub station with day to day maintenance. Also making installation neat & clean complete all as specified and directed by JE/Engr-in-Charge as mentioned the following eqpts and as per the General note appended below :-
(i) Transformer Step-down 66/11 KV - 3 Nos (ii) Step down transformer 11/433 KV - 1 Nos (iii) SF-6 GCB 66 KV - 5 Nos (iv) Isolator 72 KV - 5 Nos (v) Air Break switch/Isolator 11 KV - 5 Nos (vi) Capacitor Bank - 5 Set (vii) Indoor type VCB - 17 Nos (viii) OLTC & Control Panels - 3 Nos (ix) Earth switch - 3 Nos (x) DG Set 12.5 KVA -01 No (xi) Battery bank consisting of 55 Nos lead acid battery and battery charger - 02 Set.
Note No. 1 :- (a) The contractor will also carry out the following work for which rate deemed to be included in the quoted rate. (i) Regular Inspection of cable connections and tightness if required. (ii) Leakage of oil/oil level checking to be observed by MOG and other oil leakages. (iii) Checking of condition of Silicagel breather by physical inspection of colour on monthly basis and their replacement. (Item will be measured and paid under relevant schedule)
(iv) Contractor shall ensure cleaning of all the 66 KV installation as well as yard, toilet/bathroom, lawn/hedges and upto 5 mtr outside the fencing including ground of terminal towers free from grass and bushing etc. (v) Contractor shall provide all type of working tools and two sets of protective clothing like hand gloves, gum boots, rain coat, ladder, 3 cell torch, search light, first aid box with medicine and other tools which are necessary for day to day maintenance (vi) Contractor shall provide all type of stationery eg P.T.W book, log sheets, registers, pen, pencil, rubber, foot rool, sketch pen, markers etc as required at site.
(vii) Contractor shall ensure proper functioning of all fire extinguishers and fire points (viii) Contractor shall carry out fire practice in the yard and fill all the three fire extinguishers kept in yard, twice during contract period. (ix) Contractor shall carryout antiweed treatment of grass inside yard and ensure proper cleaning of all the Area of 66 KV installation by removing bushes, grass etc. (x) Insurance, Education Qualification and experience cert for the personnel employed on duty shall be submitted to JE/Engr-in-Charge before take over the installation. (xi) Proper Uniform shall be provided by the contractor for pers employed on duty as desired by Engr-in-Charge. (xii) Contractor will be responsible for providing security passes to the workers from Stn HQ within 01 month of commencing of M&O contract.
(b) Contactor will have no rights to object the work carrying out by other contractor on contract or job work at substation inside and outside of yard area with the permission of JE/Engr-in-Charge. (c) Contractor will not withdraw any manpower or stop the work on account of nonpayment of RAR due to paucity of fund with MES. (d) Contractor is responsible for the complete assets of the 66 KV installation. (e) Proper Handing/Taking over of assets of the area and their safe custody. Deficiency of item will not be entertained at the end of the contract period. (f) Contractor shall provide minor maintenance store for maintenance of installation i.e. Danmet Chemical Spray, Petroleum Jelly Lugs, Nut & Bolts with washer etc.
Note No. 2 :- The rates quoted by the bidders shall be inclusive of all statutory levies/duties/taxes like ESI,EPF, BONUS, Contractor's profit, labour wellfare cess etc including GST as applicable on the date of reciept of bids ( Date of opening of Financial cover of the tender)
SCHEDULE 'A' (SECTION-II) M & L carryout the following tests/tasks with the help of appropriate eqpt/meter as specified and through reputed firm for EHV testing. (A) POWER TRNSFORMER -03 Nos (i) Oil sample collection and BDV testing with BDV high voltage test machine and submitting the report. (ii) Testing of all transformer controls such as Buchloz Alarm/Trip by injecting air at pressure, OSR-Trip, Oil Temp Alarm/Trip by physical operation of the operation of guage, winding temp, alarm/trip by actual operation of guage, MOG alarm by actual operation and other indications of breaker and isolators along with checking of interlocks of all 66 KV systems with actual testing by giving commands from the remote sensers and submitting the report. (iii) Checking of IR Values of transformer including HT Cables with high accuracy approved insulation motorized tester having voltage range 500 to 5000 Volts, polarization index of transformer oil and submitting the report. (iv) Remote sensing of temperature rise at bushing (with infrared temp senser on quarterly basis and submitting the report. (v) Checking the Function of OLTC/RTCC/AVR operation on manual/automatic and contunity of winding during change over switch with contunity meter and submitting the report.
(B) BREAKERS (SF-6)- 05 Nos (i) Checking of IR value with high accuracy insulation tester of 5000 volts between phases to earth and between the phases with breaker open and close position and submitting the report. (ii) Operating timings closing/tripping with scopes make timer set and submitting the report. (iii) Gas pressure check through gas pressure gauge and submitting the report. (iv) Measuring of contact resistance with contact resistance meter (CRM) and submitting the report. (v) Checking of SF6 Gas pressure switch setting for alarm and lock out and submitting the report. (vi) Remote sensing of temperature rise at jumpers in the switch yard with infrared temperature senser on quarterly basis and submitting the report.
(C) CURRENT /POTENTIAL TRANSFORMERS- -07 Nos (i) Checking of leakage of oil. (ii) Checking of IR value and submitting the report. (iii) Tightening of connections of control cables. (iv) Remote sensing of clamp temperature at maximum load.
(D) ISOLATORS-05 Nos (i) Operation/alignments/leveling and interlocks, structure adjustment including minor repairs if any. (ii) Remote sensing of temperature rise at jumpers. (iii) Jumper tightning /Setting. (iv) Cleaning and tightning of jumpers. (v) Checking of condition of contacts with CRM for deposition and their rectification.
(E) LIGHTNING ARRESTORS-05 Nos (i) Checking of IR Value and submitting report. (ii) Leakage current/Earthing.
(F) HT VCBs 11 KV- 17 Nos (i) IR Value of each breaker phase to earth, phase to phase both in open and close position and bus bar values and submitting the report. (ii) Condition of relays and their actual testing for pickup and operating timings, coordination of relays with review of setting parameters and actual tripping of relays with secondary injection relay testing set as well as primary injection of CTs for CT ratio test and operating of relays etc and submitting the report. (iii) Testing of meters and other auxillary relays for their functioning in the desired manner with actual feeding of current and voltage with high acuracy test sets and submitting the report. (iv) Testing of Trip-supervision ckts, alarms and Facia Annunciators through actual and visual operation. (v) Testing of Metering system and all indication circuit check during on line operation and their accuracy.
(G) 66 KV C & R PANELS- 03 Nos (i) Checking and testing of complete AC/DC circuit healthiness and AC/DC failure alarms with high standard testing sets with variable AC/DC voltage instrument. Proper equipment to be brought at site for carrying out the testing and submitting the report. (ii) Operation/Testing of relays/setting with secondry injection set, other relays such as REF, Differential relay and overcurrent/earth fault relays with actual current feeding at terminals and co-ordination of relays to achieve desired result and submitting the report.
(H) DC BATTERY /CHARGER- 02 Nos (i) Checking of condition of battery and their output voltage. (ii) Checking of DC Voltage per cell on monthly basis and maintaining record in the Battery Register provided by the contractor. (iii) Charging current/Float /Trickle to be checked and recorded in log sheet on daily basis.
(J) EARTH PIT- 18 Nos Testing of all earth pits and resistance measurement as well as combined grid earth measurement with digital earth tester on monthly basis and maintain the record on earth test register provided by the contractor.
Note: The contractor must go through the notes before quoting their rates :- (i) The above test as per item No 2 (A) to (J) will be carried out within one month of taking over of installation, failing which penalty of Rs. 7,000/- per month for each test will be imposed and deducted from RAR. (ii) All the above tests/task will be carried out infront of JE E/M/ Engr-in-Charge. (iii) Contractor will give prior intimation to carry out maint/monthly/quarterly/tests to plan shut down. The shut down will not be permitted not more than 4 hours in a day to carry out the test/maintenance. The contractor has to plan the work accordingly. (iv) Report of all the tests/checks prepared by the reputed firm and submit to the deptt within ten days of test carried out.
Material and labour carryout following test of transformer oil from Govt approved laboratory.(Per Transformer) (i) Electric strength (BDV with 2.5 mm gap) (ii) Water content test. (iii) Specific resistance (resistively) at 90 degree centigrade. (iv) Di-Electric dissipation factor (Ten delta test at 90 degree centigrade). (v) Neutralization value (total acidity) test (vi) Dissolve Gas analysis (DGA) Test. Note : Any other test required for safety of transformer.
Material & Labour carry out following Test of OLTC of Power transformer oil from Govt approved laboratory. (per OLTC) (i) Electric strength (BDV with 2.5mm gap) (ii) Water content test (iii) Neutralisation value (total acidity) test (Note- any other test required for safety of transformer)
Detecting of fault in cable HT/LT with fault locator equipment which is capable to supply as per cable of HT /LT (11 KV/430 Volts) serviceable to cable. Note. (a) The HT fault which is detected through cable fault locator will only be paid under this item including transportation charges demed to be included in the quoted rate. (b) Charges of cable fault locator and DG Set including transportation charges deemed to be included in the quoted rate. (c) Earth fault locator will be provided by the contractor for even single HT fault and no delay on this account will be acceptable otherwise penalty will levied Rs 500/ per day. (d) Out door/indoor termination joint of size 185 to 400 Sqmm, Labour charges and making joint deemed to be including in quoted rate.
S & F Silica Gel breather for main tank, type : HPO-C, Gel Capacity 3.3 Kgs.
S & F Silica Gel Breather for OLTC, type : HPO-A, Gel Capacity 1 Kgs.
Supply and pouring new transformer oil as per IS : 335 (1993) for transformers installed at various site for topping up after dehydration to achieve the di electric strength 60 KV at 2.5 mm gap, complete all as specified and as directed. Make: Power link, Savita, Power Oil Note : Transformer oil shall be brought at site in sealed container from the original manufacturer and shall be opened in front of Engr-in-charge, Container shall be deposited by the contractor to the deptt, which will be returned after completion of conract.
Material & labour heating, filtration and dehydration of transformer oil with dehydration/filtration plant to achieve di-electric strength 55 KV at 2.5 mm gap complete all as specified at site. Note : Any damage occurred to transformer during the process of dehydration shall be made good by contractor to the entire satisfaction of the Engr-in-Charge at his own expenses.
Supply and fixing testing, installation of 3 Phase heavy duty exhaust fan, 900 RPM, 600 MM sweep, 415 Volt, for forced cooling of 66 KV Power Transformer installed at 66 KV MRS including dismantling of old UNSV exhaust fans from Transformers complete all as specified and as directed by Engr-in-Charge.
Esha Engineers
RUHI ASSOCIATES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .