Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹13.2 LAccepted-AOC H NO B III 95 MOHALLA GHARTHOLI MISSION ROAD PATHANKOT 145001 PB | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC lowest | |
| 2 | L2₹13.3 L+₹12,714 (0.96%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹13.8 L+₹59,209 (4.48%)Rejected-Finance | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹15.9 L+₹2.7 L (20.3%)Rejected-Finance 20 JAIN BAZAR JAMMU 180003 J K | JAMMU | JAMMU | J K | 180003 | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹16.6 L+₹3.4 L (25.8%)Rejected-Finance | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
22 Jul 2024, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE SAMBA
GE SAMBA PIN 184121
REPAIR REPLACEMENT AND MAINTENANCE OF BLDG PANEL BOARDS SERVICE CONNECTIONS MAIN DBs AND CONNECTED ACCESSORIES AT ZONE III UNDER GE SAMBA
2024_MES_663518_1
GE/SMB/T-26/2024-25/E8
Open Tender
Miscellaneous Works
Item Rate
180 days
GE SAMBA
CATEGORY E b i
8 documents required · 8 mandatory
₹500
GE SAMBA
₹40,000
Yes
18 Dec 2024
2 Jul 2024
29 Jul 2024
2 Jul 2024
22 Jul 2024
16 Jul 2024
Amount
Supply and fixing XPLE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 core in trenches,through pipe,under culvert or in air complete including taking down old one complete all as specified and directed.
All as pr item No-1 above but 70 Sqmm 3.5 core complete all as specified and directed.
All as pr item No-1 above but 35 Sqmm 3.5 core complete all as specified and directed.
All as pr item No-1 above but 25 Sqmm 3.5 core complete all as specified and directed.
All as pr item No-1 above but 16 Sqmm 3.5 core complete all as specified and directed.
Replacement of Earthing complete with GI earth plate 60cmx60cmx6mm thick electrode and 25X4MM GI strip as earthing lead. buried directly in ground ( earth pit not less then 2.25 metres deep below ground level ) with top edge of the plate not less then 1.5 metres below normal ground level. connected to GI wire earth lead wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No. 5 and incl earth work, PCC pit and RCC cover, watering pipe 20 mm dia light grade, funnel, wire mesh, protection pipe 15 mm dia light grade up to 7.5 mtr length of earth wire, charcoal dust and salt etc and connected to earthing test point all as specified or directed and testing complete all as specified and directed.
Supply and fixing in repairs of MCCB of capacity 100 Amp, 35KA, 4 Pole, 415Volts grade complete all as specified and directed. .
Supply and fixing in repairs of MCCB of capacity 160 Amp, 35KA, 4 Pole, 415Volts grade complete all as specified and directed. .
Supply, fixing/ laying in repair GI pipe light grade 50mm bore in trench, under floor, wall and on pole for cable protection complete all as specified and directed. .
S & F in repairs sheet moulded compund(SMC) meter box fire retardant type of size not less than 600mmx600mmx250mm to enclouse 04 nos single phase electric meters with hinged type front operated door having transparent acrylic sheet and proper locking arrangement and flush mounting in wall , including disconnecting and refixing the existing meters inside new meter box and making electrical connections complete including making good the disturbed surfaces matching with existing specifications complete all as specified and directed.
S & F of sheet metal enclosures distribution boards, double door ,VTPN, 415 volts 4 ways (one incoming three phase & twelve out goings single phase )for MCCB & MCB,s comprising three phase four wire copper strip bus bar of appropriate capacity complete all as specified and directed and comprising of the following a) MCCB four pole 100 AMPS AC 415 Volts 16 KA =01 NO (for incoming ) (b) MCB SP 63 amps = 04 Nos (for outgoings) . Note :- (i)The DB shall be VTPN series (ii) The DB shall be flush fixed (iii)connection of the MCCBs/ MCBs with cable shall be made through appropriate size pin /bottle type thimble properly crimped. (iv) All the vacant holes of the DB shall be provided with blank plates of appropriate size. (v) Double continuous earth wire shall be provided for each three phase DB from earthing mains dolly. (vi) cutting chasing shall be part of job at no extra cost .
Supply and fixing in repairs sheet metal enclousre for TPN DBs 4 way when MCB to be used double door powder coated factory made flush fixed complete with 200 amps rated bus bar 240 volts three pahse and neutal 4 way complete all as specified and directed.
Supply and fixing in repairs for MCB TPN 63 amps 240 Volt 'B' series complete all as specified and as directed.
Supply and fixing in repairs for MCB SPN 63 amps 240 Volt 'B' series complete all as specified and as directed.
Supply and fixing in repairs for MCB SPN, 6 to 32 amps 240 Volt 'C' series complete all as specified and as directed.
Supply and fixing in repairs for MCB SP, 6 to 32 amps 240 Volt 'B' series complete all as specified and as directed.
Taking down the unservicable /burnt sub main wiring and Supply & fixing for submain wiring in and including PVC conduit 1.8 mm thick ,32 mm dia with two run of PVC insulated, unsheathed multistranded copper conductor of 10 sqmm(FRLS) and one run of PVC insulated,unsheathed multistranded copper conductor 10 sqmm (green in colour) for earth continuity conductor and connected to common earth dolly with thimble etc, complete all as specified and directed. Notes:- (i) Two run of 10 sqmm plus one run 10 sqmm of earth wire will be measured as 1 unit/RM) (ii) Insulation test of point wiring to be conducted (b) Colour coding is to be maintained .(Phase-Red, Neutral-Black,Earth- Green)
All as pr item No-17 above but with two run of PVC insulated, unsheathed multistranded copper conductor of 6 sqmm(FRLS) and one run of PVC insulated,unsheathed multistranded copper conductor 6 sqmm (green in colour) for earth continuity conductor complete all as specified and directed.
Excavation in trenches in any type of soil not exc 1.5 mtr wide and not exe 1.5mtr deep and getting out complete, all as specified and directed.
Returning filling in including spreading, leveling, watering and well ramming to a layer not exceeding 25cm complete, all as specified and directed.
Removal of excavated material n.exe 50mtr and depositing where directed at a level not exe 1.5 mtr above the starting point, complete, all as specified and directed.
Sand cushioning to under ground cable using fine sand (8 cm before & 15 cm after laying of cable) complete all as specified and directed.( Punned thickness to be measured)
M& L for brick sub class 'B' of standard size for protection of cable, brick laid across the cable complete all as specified and directed.
Note:- The contract sum shall be arrived at after deduction of amount of Sch of credit.
G.M. ENGINEERING SERVICES (BID ID -3070977)
SIDDAHANT ENTERPRISES (BID ID -3069855)
A K JAIN AND SONS (BID ID -3071013)
M/S GUPTA TRADING CO (BID ID -3070937)
LAL CONSTRUCTIONS (BID ID -3071051)
satpal and brothers (BID ID -3069810)
dinesh enterprises (BID ID -3067234)
stage.html
html • 0.06 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .