Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹45.9 LAccepted-Finance | L1 | Accepted-Finance L1 | |
| 2 | L2₹53.9 L+₹7.9 L (17.2%)Rejected-Finance | L2 | Rejected-Finance L2 | |
| 3 | L3₹78.1 L+₹32.2 L (70.0%)Rejected-Finance GROUND FLOOR PRAKASH APARTMENT BYE PASS ROAD SAPROON SOLAN SAPROON SOLAN SOLAN HIMACHAL PRADESH 173211 UDYAM HP 11 0005662 | SOLAN | HIMACHAL PRADESH | 173211 | L3 | Rejected-Finance L3 | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification | |
| 5 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
Tender Value
Refer Docs
EMD Value
₹89,000
Closing Date
22 Feb 2021, 11:00 amClosed
Executive Engineer
Jal Shakti Division NOhradhar
Sh- Providing Laying, Jointing Testing and commissioning of MSERW pipe and laying, jointing and testing commissioning of GMS pipe line in Rising main for phase 1st, supplying and errection of centrifugal pumping machinery with allied accessories fo
2021_HPIPH_44435_1
19503-19602 dated 16-02-2021
Open Tender
Pumps/Motors
Item Rate
120 days
Nohradhar
Please refer Tender documents.
11 documents required · 11 mandatory
₹800
EE Nohradhar
₹89,000
Yes
29 Dec 2021
16 Feb 2021
22 Feb 2021
16 Feb 2021
22 Feb 2021
16 Feb 2021
Amount
PHASE-1st
Excavation in drains and channels etc.in earth work for pipes up to all depths in all classification of earthwork such as pick work, jumper work, saturated soil including bailing or pumping out water, blasting soft/hard rock or chiseling soft / hard rock where blasting is prohibited in all lifts including jungle clearance wherever required, trimming & dressing of sides, leveling of beds to correct grade including shoring/struting, planking, timbering & dewatering wherever required stacking the useable/unuseable material/soil seperately & after laying, jointing & testing of pipes, returning the useable soil in trenches in 15 cm layers including consolidating of such deposited layer by ramming & watering & then disposing of all surplus excavated soil/unuseable material as directed with in all leads & lifts including restoration of un-metalled surfaces to its original condition & including cost of diversion for traffic, night signals, fixing caution boards, crossing over trenches for access to houses, fencing etc. complete in all respects with-in all leads & lifts as per directions of the Engineer Incharge.
Providing,Laying, jointing, testing & commissioning at site in trenches bevelled ended MSERW pipes of Grade "A " or L-210 conforming to code IS/ISO-3183-2007 or its equivalent grade as per api specification having wall thickness and per Rmt weight as mentioned below and capable of withstanding required test pressure as prescribed in BIS code, in random lengths of 5.5 to 6.5 mtr. The pipe's ends shall be bevelled suitable for butt welding, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable ends with upto date ammendments (leak proof) in three layers at site of work with welding rods of standard make and all allied accessories whatever required for welding at site , tail pieces, tees,bends & other specials manufactured from parent pipes as applicable to the particular reach & of approved specification as per site conditions and cutting of pipes whereever required as per site requirement i/c carriage in all leads & lifts and as directed by Engineer-Incharge. The pipe shall have's zinc coating inside & outside conforming to IS-4736-1986 or latest with up to date ammendments & shall be engraved with IS/ISO 3183-2007 Grade "A "The laying shall conform to BIS 5822-1970 or latest with up to date ammendments to the entire satisfaction of Engineer-Incharge (Earth work shall be measured & paid for separately).
From To Thickness Dia. Grade
0 990 4.80mm 65 mm Grade "A"
Laying, , jointing , testing & commissioning at site in trenches following plain ended GMS pipes of following dia of Heavy/Medium Grade as under confirming to BIS 1239-(Part-1)-1990 or latest with up to date ammendments, capable of withstanding required test pressure as prescribed in BIS code, in randum lengths of 5.5 to 6.5 mtr. The pipe's ends shall be bevelled suitable for butt weld, including the cost of jointing with butt welding confirming to IS 816-1969 or latest as applicable (leak proof) in three layers at site of work with welding rods of standard make & all allied accessories whatever required for welding at site, tail pieces, tees, bends manufactured from parent pipes etc. and cutting of pipes wherever required as per site requirement i/c carriage in all leads & lifts as directed by Engineer-Incharge (Earth work shall be measured & paid for seperately).
From To Dia. Grade
990 1800 65 mm Heavy Grade
Providing, welding and fixing M.S. plate flanges of following dia. (nominal bore) of following Flange Tables confirming to IS 6392-1971 or latest with up to date ammendments to MSERW/GI pipes after every 90 metres or as per site requirement including cutting of pipes wherever required, welding in three layers (leak proof) confirming to specifications as prescribed in relvent I.S. Code i.e. IS 816-1969 or latest as applicable with up to date ammendments with nuts, bolts & washers & specials etc. confirming to IS-1963 or latest with up to date ammendments including packing sheet i.e. asbestos fibre sheet minimum 3mm thick and painting with anticorosive paints complete in all respect i/c all leads, lifts and carriage of material at site and as directed by the Engineer Incharge.
From To Dia. Flange Table
PUMPING MACHINERY
PHASE-1st
Supply, erection, testing & commissioning of horizontal spindle,horizontal split casing,radial split Single,/Multistages centrifugal pumps of standard make such as KSB/Mather & platt/ Kirloskar conforming to BIS 1520-1980 with upto date ammendments read with BIS 9137-1978 or latest edition make to handle clear water, having characteristics as mentioned below in Item No.5(A), with impelleres,casing ring, priming funnels & shaft sleeves of bronze, shaft of steel with cast iron casing of suitable capacity coupled directly through a flexible coupling on a common base plate of cast steel /Mild steel to BHEL /Kirlokar/ NGEF/ Crompton / Siemen/Jyoti /GEC make slip ring /squirrel cage screen protected drip proof induction electric motor suitable for operation on the data given below i/c the cost of all the accessories in all leads and lifts & carriage of material at the site as per directions of Engineer-in-charge.
Providing and fixing of auto control panel with push button star delta starter for submersible pump of L&T and reputed make fabricated with M.S. sheet and angle stand duly painted and complete with internal wiring, comprising of main switch of suitable Amp., T.P. volte meter, copper busbar, ameter, hour run metre, phase indicating lamps with GMS based, remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hour in a day, imbuilt protection against overload/ undervoltage, dry run, single phase preventer, inbuilt GPS tracker, phase reversal configurable volt/current limits with a facility to access the systemthrough minimum 10 No. authenticate mobile Nos. complete in all respect, including intire carriage of materials all leads and lifts, installation and testing at site with entire saisfaction of engineer-in-incharge.(all meters to be installed shall be DIGITAL)
Supply &fixing at site of work of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB make of Cast Steel double flanged sluice valve having size one size higher than the nominal delivery size of pump and capable of withstanding nominal seat pressure as mentionmed in item No. 5(a) + surge pressure & conforming to API-standards with up to date ammendments for delivery line of pump.class of valve shall be ASA 600
Supply & fixing at site of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB make of suitable size Cast Steel double flanged swing check type reflux valve for delivery line of pump having bye pass arrangement & size one size larger than the nominal diameter of delivery size of pump and capable of withstanding nominal seat pressure as mentionmed in item No.5(a) + surge pressure & conforming to API-standards with up to date ammendments for delivery line of pump. class of valve shall be ASA 600
Supply & fixing at site of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB make of suitable size Cast Steel double flanged swing check type reflux valve confirming to API standard with up to date ammendments for R/main as mentioned in item No. 5c) for withstanding nominal seat pressure as per item No.5(a) + surge pressure.The size of reflux valve shall be equal to size of Rising main of the same shall be provided with suitable bye pass arrangements. class of valve shall be ASA 600 and shall be of 65mm diametres.
Supply & fixing at site of Kirloskar/Kilburn/IVC/Fouress/Gled/BHEL/Leader/KSB make cast iron double flanged sluice valve (In case Suction is +ve) for suction pipe having size one or two size larger than suction size of pump such that velocity of flow in suction pipe is not more than 3.00 mtr/sec and conforming to BIS standards with up to date ammendments. The class of valve shall be PN 1.6.
P/L at site of work suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L at site suitable size copper PVC insulated armoured power three core cable conforming to BIS 1554 (part I)-1988 or latest with up to date ammendments of Siemen/ Gloster /ICC/ EICO/National / IEC make from switch to starter & starter to motor (one cable carrying all three phases) including all other electrical equipment /accesories such as thimbles,flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor.The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
P/L at site double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm copper strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments suitable for above motors & other electrical equipments.
Supply & errection at site of floor/wall mounted power factor shunt capacitor of suitable KVAR conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses.(Range to be specified by the tenderer).
Supply and fixing at site of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 or latest with up to date ammendments.
Providing & fixing MSERW double flanged suction, delivery pipe & common header considering to Grade ''A'' of IS/ISO 3183-2007 specification or latest with upto date ammendments considering site requirements, NPSH required & available & common header having area equal to two times the area of delivery branch of pump including tapers,flanges,rubber gaskets 3mm thick as per BIS-2712-1978 nuts & bolts as per 1364-1983 & special up to 5 mtrs. away from the outer wall of pump house as per layout drawings approved by Engineer-in-Charge. The pipes shall be capable of withstanding 1.5 times the total presure indicated in item No.5(A) or total dyanamic pressure + surge pressure whichever is more. The size of suction pipe shall be one or two sizes larger than the suction size of pump such that valocity of flow in suction pipe is not more than 3.00 mtr/sec & delivery pipe shall be of size one size larger than nominal delivery size of pump including carriage of material in all leads & lifts & as directed by Engineer -Inchage. Thickness of MSERW pipe shall be 4.80mm jointed with flanged joint of FT-34 Note :- Actual laying to be done as per final drawing to be approved by the Engineer Incharge.
Erection of all equipments including cost of tees bends tapers and any other fittings required as per site conditions and as per direction of the Engineer Incharge.
Replacement of pumping machinery for LWSS Rajana
1st stage
Supply, erection, testing & commissioning of submersible pumping set of reputed make such as KSB/BS/ Johnston/ Worthington/Oswal/Sabar Brand conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characterstics as mentioned in item 13(A) greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guard, errection clamps, cable clips. & depth gauge etc. & suitable for operation of data given below:-
Providing and fixing of auto control panel with push button 2Nos. star delta starter for submersible pump of L&T and reputed make fabricated with M.S. sheet and angle stand duly painted and complete with internal wiring, comprising of main switch of suitable Amp., T.P. volte meter, copper busbar, ameter, hour run metre, phase indicating lamps with GMS based, remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hour in a day, imbuilt protection against overload/ undervoltage, dry run, single phase preventer, inbuilt GPS tracker, phase reversal configurable volt/current limits with a facility to access the systemthrough minimum 10 No. authenticate mobile Nos. complete in all respect, including intire carriage of materials all leads and lifts, installation and testing at site with entire saisfaction of engineer-in-incharge.(all meters to be installed shall be DIGITAL)
Supplying and fixing at site of Kirloskar/Kilburn/IVC/Fouress/ GLED/BHEL/Leader/ KSB make of suitable size cast steel double flanged swing check type reflux valve for delivery line of pump having bye pass arrangement and size one size larger than the nominal diameter of delivery size of pump and capable of withstanding nominal seat pressure as mentioned in item No. 13(a) + surge pressure and conforming to API standards with up to date ammendments. The class of valve shall be ASA 300.
Providing and laying at site of work suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site PVC jointless flat water proof cable as per BIS 694-1990 (latest with up to date amendments) suitable for both the pump sets offered from circuite breaker to motor & motor to starter including all other electrical equipments such as thimbles, flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm G.I. strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments suitable for above motors & other electrical equipments.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer).
Supply of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 or latest with up to date ammendments.
Stage 2nd
Supply, erection, testing & commissioning of submersible pumping set of reputed make such as KSB/BS/ Johnston/ Worthington/Oswal/Sabar Brand conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characterstics as mentioned in item 19(A) greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guard, errection clamps, cable clips. & depth gauge etc. & suitable for operation of data given below:- Note:-Out of the 3 Nos. pumps, 2 No. pump set will run and other will act as stand by.
Providing and fixing of auto control panel with push button 2Nos. star delta starter for submersible pump of L&T and reputed make fabricated with M.S. sheet and angle stand duly painted and complete with internal wiring, comprising of main switch of suitable Amp., T.P. volte meter, copper busbar, ameter, hour run metre, phase indicating lamps with GMS based, remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hour in a day, imbuilt protection against overload/ undervoltage, dry run, single phase preventer, inbuilt GPS tracker, phase reversal configurable volt/current limits with a facility to access the systemthrough minimum 10 No. authenticate mobile Nos. complete in all respect, including intire carriage of materials all leads and lifts, installation and testing at site with entire saisfaction of engineer-in-incharge.(all meters to be installed shall be DIGITAL)
Supplying and fixing at site of Kirloskar/Kilburn/IVC/Fouress/ GLED/BHEL/Leader/ KSB make of suitable size cast steel double flanged swing check type reflux valve for delivery line of pump having bye pass arrangement and size one size larger than the nominal diameter of delivery size of pump and capable of withstanding nominal seat pressure as mentioned in item No. 19(a) + surge pressure and conforming to API standards with up to date ammendments. The class of valve shall be ASA 300.
Providing and laying at site of work suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site PVC jointless flat water proof cable as per BIS 694-1990 (latest with up to date amendments) suitable for both the pump sets offered from circuite breaker to motor & motor to starter including all other electrical equipments such as thimbles, flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm G.I. strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments suitable for above motors & other electrical equipments.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer).
Supply of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 or latest with up to date ammendments.
Stage 3rd
Supply, erection, testing & commissioning of submersible pumping set of reputed make such as KSB/BS/ Johnston/ Worthington/Oswal/Sabar Brand conforming to latest relevent BIS code. The pump should be fitted with free flow impellers of bronze /suitable alloy as per BIS 5659 or latest with up to date ammendments suitable for raw/clear water having characterstics as mentioned in item 25(A) greased packed bearings & shell with wound stator on motor side & with shaft protection sleeve on pump side ensuring better life for shaft conforming to BIS specifications. The pump shall be directly coupled to a submersible squirrel cage electric induction motor of Kirloskar/NGEF/Jyoti / Crompton make conforming to relevent BIS code with up to date ammendments totally dust & water proof for submersible duty isolated from the pump by intermediate casing with double mechanical seal in oil chamber chamber & grease packed lubricated bearings & provided with stainless steel thrust bearing plate to withstand non vertical loads with minimum wear & tear. It should also be fitted with a device to take up expansion of water with the heating of motor. The pump set should include water level guard, errection clamps, cable clips. & depth gauge etc. & suitable for operation of data given below:- Note:-Out of the 3 Nos. pumps, 2 No. pump set will run and other will act as stand by.
Providing and fixing of auto control panel with push button 2 Nos. star delta starter for submersible pump of L&T and reputed make fabricated with M.S. sheet and angle stand duly painted and complete with internal wiring, comprising of main switch of suitable Amp., T.P. volte meter, copper busbar, ameter, hour run metre, phase indicating lamps with GMS based, remote start/stop operation call/SMS for feedback regarding running of pumps & breakdown message, timer scheduling for fixed hour in a day, imbuilt protection against overload/ undervoltage, dry run, single phase preventer, inbuilt GPS tracker, phase reversal configurable volt/current limits with a facility to access the systemthrough minimum 10 No. authenticate mobile Nos. complete in all respect, including intire carriage of materials all leads and lifts, installation and testing at site with entire saisfaction of engineer-in-incharge.(all meters to be installed shall be DIGITAL)
Supplying and fixing at site of Kirloskar/Kilburn/IVC/Fouress/ GLED/BHEL/Leader/ KSB make of suitable size cast steel double flanged swing check type reflux valve for delivery line of pump having bye pass arrangement and size one size larger than the nominal diameter of delivery size of pump and capable of withstanding nominal seat pressure as mentioned in item No. 25(a) + surge pressure and conforming to API standards with up to date ammendments. The class of valve shall be ASA 300.
Providing and laying at site of work suitable size copper PVC insulated armoured power three & half core cable conforming to BIS 1554 (Part I) -1988 or latest with up to date ammendments of Siemen/Gloster/ ICC/EICO /National /IEC make from meter of HPSEB to circuit breaker & from circuit breaker to bus bar switch & starter (one cable carrying all three phases) including all other electrical equipment/accessories such as thimbles,flexible pipe,solder,nuts & bolts,cable glands etc. laid in pipes or trenches under floor. The type,size & make will be subject to approval of HPSEB authorities. In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site PVC jointless flat water proof cable as per BIS 694-1990 (latest with up to date amendments) suitable for both the pump sets offered from circuite breaker to motor & motor to starter including all other electrical equipments such as thimbles, flexible pipes, solder,nuts & bolts,cable glands etc. laid in pipes or trenches. The type,size & make will be subject to approval of HPSEB authorities.In case of non acceptance by HPSEB authorities it shall have to be replaced by the tenderer free of cost.
Providing and laying at site double loop earthing with copper plate 600x600x3mm thick electrode complete with material such as charcoal, common salt ,GI pipes,thimbles,nuts & bolts,digging of pits,GI wiring & 25x5mm G.I. strips of required capacity conforming to BIS 3043-1987 latest with up to date ammendments suitable for above motors & other electrical equipments.
Supply & errection of floor/wall mounted power factor shunt capacitor conforming to BIS 2834-1986 or latest with upto date ammendments of BHEL/GEC/Machneil/ Mager/Bajaj/L&T make to raise the prevailing power factor at site to 0.95 for direct connection to induction motor individually,of required KVAR according to HP of motor offered including cable Siemens/Gloster/ICC make from busbar chamber to capacitor & also including L&T//Kilburn/Standard/Siemen/Havells make ICTP switches conforming to BIS 4064-1978 or latest with HRC fuses (Range to be specified by the tenderer).
Supply of 100mm dia circular dial pressure gauge of suitable range & standard make such as Fiebeg/Bourden/ Precision/PREGA with all accessories such as stop cock,copper tubing etc. conforming to BIS 3624-1987 or latest with up to date ammendments.
Erection of all requirements of all stages i/e cost of tees, bends etc. complete in all respect.
HYDRAULIC ENGINEERING COMPANY
Sai Aqua Machines and Builders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .