| 1 | L1₹10.3 LAccepted-AOC 20 JAIN BAZAR JAMMU 180003 J K | JAMMU | JAMMU | J K | 180003 | L1 | Accepted-AOC LOWEST | |
| 2 | L2₹12.4 L+₹1.1 L (9.31%)Rejected-Finance | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹12.4 L+₹1.1 L (9.61%)Rejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹12.8 L+₹1.5 L (13.2%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹13.6 L+₹2.3 L (20.3%)Rejected-Finance H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹15 L
EMD Value
₹30,000
Closing Date
29 Jul 2023, 6:00 pmClosed
GE SAMBA
GE SAMBA
REPAIR REPLACEMNET IMPROVEMENT OF VOLTAE STABILIZER BUS BARS LT PANELS AND JUNCTION BOX AT MIL STN SAMBA
2023_MES_606601_1
GE/SMB/T-47/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
SAMBA
REF NIT
8 documents required · 8 mandatory
₹500
Yes
GE SAMBA
₹30,000
Yes
23 Oct 2023
28 Jun 2023
31 Jul 2023
28 Jun 2023
29 Jul 2023
15 Jul 2023
28 Jun 2023 - 30 Jun 2023
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth for laying of cables, poles & stay or other items and getting out soil in any type soil complete all as specifed.
Returning, filling in, including spreading levelling watering and well ramming in layers not exceeding 25 cm complete all as specified.
Removing excavated material not exceeding 50 mtr and depositing where directed in a level not exceeding 1.5 mtr above the starting point of any type of soil complete all as specified
Sand cushioning to under ground electric cable a layer of 8 cm thick before laying the cable and stretching the cable and punned down to form a bed of 23 cm and second layer of 15 cm thick after laying the cable complete all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be of good quality as specifed and punned thickness shall be measured and paid.
Well burnt sub class 'B' bricks of nominal size 230X115X75 mm abutting each other for mechanical protection of cable with width equal to lenght of brick complete all as specified.
GI pipe in replacement ( Light grade ) for protection of LT cable fixed to walls/ poles/road crossing including suitable size clamps complete of size 50 mm bore , complete all as specified and directed
XPLE insulated screened,PVC bedded galvanised steel strip & wire armoured electric power cable ( heavy duty ) 1100 volts grade of size 50 sqmm, 3.5 core with stranded aluminium conductor including proper connection to LT panel / bus bar with aluminium thimbles of suitable size /rating laid in trenches through pipe or under culvert including taking out existing cables,complete all as specified and directed. (Note – Necessary excavation, returning, filling in,removal of soil ,sand cushioning,brick work and GI pipe shall be measured and paid under respective item of BOQ).
XPLE insulated screened,PVC bedded galvanised steel strip & wire armoured electric power cable ( heavy duty ) 1100 volts grade of size 95 sqmm, 3.5 core with stranded aluminium conductor including proper connection to LT panel / bus bar with aluminium thimbles of suitable size /rating laid in trenches through pipe or under culvert including taking out existing cables,complete all as specified and directed. (Note – Necessary excavation, returning, filling in,removal of soil ,sand cushioning,brick work and GI pipe shall be measured and paid under respective item of BOQ).
XPLE insulated screened,PVC bedded galvanised steel strip & wire armoured electric power cable ( heavy duty ) 1100 volts grade of size 25 sqmm, 4 core with stranded aluminium conductor including proper connection to LT panel / bus bar with aluminium thimbles of suitable size /rating laid in trenches through pipe or under culvert including taking out existing cables,complete all as specified and directed. (Note – Necessary excavation, returning, filling in,removal of soil ,sand cushioning,brick work and GI pipe shall be measured and paid under respective item of BOQ).
Disconnecting main electrical connection of voltage stabilizer of any make, capacity from 50 KVA to 75 KVA and opening of stabilizer cover for checking/examining/replacing as required including connecting the same electrical connection after necessary repair complete all as specified and directed. Note: Spare parts shall be measured & paid separately.
Transportation of voltage stabilizer of any make of capacity 50 KVA to 75 KVA to civil workshop and returning back after necessary repairing work including loading & un-loading with & including necessary T&P complete all as specified and directed.
Rewinding of burnt/damaged 3 phase servo voltage stablizier with copper wire of 99.99% purity, best quality of existing size, including varnishing, baking & replacement of insulating material ISI marked or as per IE specifications, complete all as specified and directed
Draining out the transformer oil complete quantity of voltage stabilizer of any make of capacity 50 KVA to 75 KVA and to keep the same in safe containers dismantling all the parts of voltage stabilizer with the help of hand operated crane or other suitable mean, re-fixing the all parts and assembling with the help of hand operated crane or by other suitable means, re-filing the existing drain out transformer oil and testing the voltage stabilizer complete all as specified and directed. Note:- Spare parts shall be measured & paid separately.
Repairing the voltage stabilizer of any make of capacity 50 KVA to 75 KVA by supply and fixing in replacement of following items:- (a) Electronic printed circuit board of solid state including ICs, regulators, condensors, triac, transistors complete.Make : As per OEM
(b) Circuit control/trigger transformer.Make : As per OEM
(c ) Main terminal block. Make : As per OEM
(d) Dimmer. Make : As per OEM
(e) Choke coils.Make : As per OEM
(f) Carbon brush.Make : As per OEM
(g) Spacer for Dimmer coils.Make : As per OEM
(h) Dimmer coils terminals.Make : As per OEM
(l) Input switch to stop over running of dimmer start motor.Make : As per OEM
(m) Servo motor with 10 Kg.cm torque.Make : As per OEM
(n) Driving gear.Make : As per OEM
(o) Bearing for dimmer coils.Make : As per OEM
(p) Terminal connections brass rod with bush.Make : As per OEM
(q) Protection alarm circuit. Make : As per OEM
Supply, installation, testing & commisioning in replacement of factory made LT feeder pillar box outdoor type, floor mounted, double door, cubical compartmentalized type suitable for 415 volts, 3 phase, 4 wire, 50 Hz supply system all as specified and directed having busbar chamber with insulated aluminium bus bar 300 Amps rating (100% neutral) installed on porcelain insulators. The panel shall be dust and vermin proof made of 3.15 mm CRCA sheet duly powder coated and 40 x 40 x 6 mm angle iron frame work duly powder coated finish, panel mounted on angle iron 40 x 40 x 6 mm frame having 4 Nos legs 45 cm, 15 cm grouted in PCC of ratio 1:3:6 and 30 cm clear space from ground level. Front & back opening type with aprons for cable entry with locking arrangement including internal wiring with PVC insulated multistranded copper conductor cables of suitable size, thimbling and cable entry boxes with cable glands.The Panel builder should submit Test Certificate along with GA drawing before executing the job. The scope of the work also includes supply and fixing the following:-
INCOMING:- (a) MCCB 200 Amps,thermal adjustable and magentic setting having rupturing capacity 25 KA (Ics=100% Icu), 4 pole, 415 Volts, 50 Hz, along with Extended Ratory handle ,Spreader terminals and phase barrier - 01 No. Make: Legrand/L&T/Schneider/Benlo.
Plate earthing complete with galvanized mild steel plate electrode 60 cm x 60 cm x 6 mm thick buried directly in ground vertically (in earth pit not less than 2.25 meter deep below ground level) with the top edge of earth plate at a depth not less than 1.5 meter below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and including GI strip 32x6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth (Plate) electrode at one end and connected to main switch board /panel/ test point at the other including watering GI pipe (medium grade) 20 mm bore from bottom of earth pit to top of electrode and 40 mm GI pipe light grade for earth strip protection complete with earth pit in PCC 1:2:4 type B0 using 12.5 mm graded crushed stone aggregate, RCC cover, funnel, wire mesh including necessary excavation and earth work in any type of soil, returning, filling in and removal of surplus soil complete all as specified.
Note:- The contract sum arrived after deduction of amount of Sch of credit as listed in tender Documents.
Jiwan Singh
M/S SATPAL & BROTHERS
SHUSHANT ASSOCIATES
M/s Shakti Electric Works
stage.html
html • 0.05 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .