Tender Value
₹9.1 L
EMD Value
₹22,832
Closing Date
3 Dec 2024, 3:00 pmClosed
The Assistant Executive Engineer Electrical HEED
O/o The chief Engineer, Harbour Engineering Electrical Sub Division, Kamaleswaram, TVPM
Kollam Port Facilitation Center_ Up gradation of Electrical Work in Immigration Check post Facilitation Center at Kollam Port _General Electrical Work
2024_HED_705918_1
HED/CEHED/TR/837/2024_7_1_1/1
Open Tender
Electrical Works
Item Rate
30 days
KOLLAM
Please refer Tender documents.
7 documents required · 7 mandatory
₹2,015
₹22,832
20 Jan 2025
15 Nov 2024
5 Dec 2024
15 Nov 2024
3 Dec 2024
15 Nov 2024
Amount
Upgradation of Port facilitation office
1.10.1:Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group A
1.15.3:Rewiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel/PVC conduit including dismantling as required.Group C
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.30:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 6 sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
1.21.2:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mm
1.24.1:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switch
1.24.3:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switch
1.24.4:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outlet
1.24.5:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outlet
1.26:Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required.
1.28.1:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.1 or 2 Module
1.28.2:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.3 Module
1.28.4:Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required.6 Module
1.53.1:Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required1 run of Cable
2.3.4:Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double door
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
2.11:Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.14.2:Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
2.16:Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts "C" curve DP MCB complete with connections, testing and commissioning etc. as required.
5.5:Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required.
5.13:Providing and laying earth connection from earth electrode with 4.00 mm dia copper wire in 15mm dia G.I. pipe from earth electrode including connection with copper thimble excavation and re-filling as required.
5.14:Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required.
5.17:Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required.
14.10:Providing and laying in position reinforced cement concrete 1 :2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required (excluding reinforcement).
14.12:Providing 15mm thick cement plaster of mix 1:4(1 cement: 4 fine sand) at all levels
90.10.1.2:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )2 module moulded plastic box on surface
90.10.1.3:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )3 module moulded plastic box on surface
90.10.1.5:Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required (RoHS compliant )6 module moulded plastic box on surface
OD5067/2024-2025:Supplying and fixing following Modular base & cover plate on existing CMS 105X50mm etc. as required.3 Module base and cover plate.
OD5068/2024-2025:Supplying and fixing following Modular base & cover plate on existing CMS 105X50mm etc. as required.6 Module base and cover plate.
OD5069/2024-2025:Supply of Cat 6,2 metre patch cord
OD5070/2024-2025:Supply of Cat 6,1 meter patch cord
OD5071/2024-2025:Wiring the patch panel and Configuring of Manageable network switch complete
OD5072/2024-2025:Identifying the CAT6/Telephone cable and the termination the end with male connectors/ existing sockets using special crimping tools complete as required.
OD4675/2024-2025:Supply and fixing Floor Mount 9U Rack including , AC Distribution box(x1), fan (x1) Closed type cable manager and hardware mounting kit Recommended: Legrand/Netrack.
OD4681/2024-2025:Supply, installation, testing and commissioning of 230V AC, 50HZ ,6KVA IGBT based PWM technology microprocessor controlled double conversion true Online UPS(192 V DC or above) capable for automatic changeover from mains to UPS on mains failure and vice versa with built in isolation transformer of make APC/NUMERIC/GE or equivalent suitable to work with 16Nos 12V,75 Ah, rated tubular type battery Exide or Quanta bank C10 for UPS application suitable for 3 hours backup on full load with suitable wooden rack for mounting the batteries. 1phase Input Voltage Range 160-300 V AC, Output Frequency-50 Hz plus or minus 0. 01Hz,Output voltage Range :240VAC plus min; 1% ,Output power rating: 4800W/6000VA, Interface port:RS232 and com port, Front panel Display: LCD, input power factor:0.99, input Current THD <10% at full load, Output Voltage THD < 3%(Linear Load),THD <5%(Non-Linear load), Overall efficiency >=90%, Overload Capacity :1min @ 111%-130% of rated load,10 minut @ 105%-110% of rated load, Load power factor: 0.8 lag or better, Load crest factor : 3:1, Noise level: <50 dBA at 1 meter, Continuous Operating Temperature: 0-40 &deg;C, Constant current &amp; constant Voltage with optional Temperature compensated battery charging. Standards: EMC- EN 62040- 2, Safety- EN 62040-1, Performance- IEC 62040-3, Certifications: BIS, OSHAS, CE, PeP, RoHS, ISO 9001 and ISO 14001 ,Warranty :3 years on site warranty from the date of installation for UPS & battery complete as required.
OD4728/2024-2025:Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.CAT 6 RJ 45 computer data socket
OD4834/2024-2025:Supply and Installation testing commissioning of wall Fan with 400 mm sweep size .3 blade prefeed make Crompton or havells or equivalent
OD4865/2024-2025:Supply, installing, commissioning of manageable switch having Minimum 24 X 10/100/1000 Base-T Ethernet ports, 2 10/100/1000 Base - T Ethernet ports and 2 10000 Base-X SFP Ports (COMBO)• Switching Capacity should be minimum 8.8 Gbps and Minimum 6.55 MPPs Throughput• Switch should support minimum 1000 VLAN's and VLAN ID's,Port-based VLAN and MAC-based VLAN,802.1Q VLAN tagging,Software upgrades,SNM PV2 and SNM Pv3, and MAC limiting. • Switch should be Manageable through CLI, web Interface and SSH
OD4868/2024-2025:Supply and laying of additional length of insulated copper pipe for connecting indoor and outdoor unit of split type AC complete as required
OD4869/2024-2025:Installation Testing and commissioning of 1. to 2 Tonne departmentally supplied split type air conditioning unit in suitable location as directed by the engineer in charge with all fixing accessories complete as required.
OD4870/2024-2025:Supply, Installation Testing and commissioning of Wall hanging type Voltage stabilizer of Single phase 230V, ac, 50Hz, suitable upto 1.5 tonne Split Ac for 170 to 260V input voltage range preferred make of VGUARD/MICROTEK complete.
OD4871/2024-2025:Supply of 1.5 Ton 5 star rated inverter type split AC with Multi Adjustable Mode ,Anti Microbial Air Filtration,100% Copper, ISEER 5.0,230V,50Hz,1 Phase supply and with LCD remote ,battery and high EER rotary BLDC compressor operating voltage of 110-285 V,etc complete .The unit shall a warranty of 3 years preferred make Voltas Model 4503453 / 185V Vectra Elite or equivalent .
OD4872/2024-2025:Supplying suitable clamp for AC outdoor unit upto 1.5 tone complete.
OD4873/2024-2025:Supply of 1.0 Ton 5 star rated inverter type split AC with Multi Adjustable Mode, Anti-Microbial Air Filtration,100% Copper,ISEER 5.0,230V,50Hz,1 Phase supply and with LCD remote, battery and high EER rotary BLDC compressor operating voltage of 110-285 V... etc. including outdoor unit. complete unit shall a warranty of 3 years preferred make Voltas Model 2024 / 125V Vectra CAW or equivalent.
OD5075/2024-2025:Supply and providing 25x6 mm brass bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required
OD5076/2024-2025:Supplying and fixing Cat 6 RJ 45 Frame on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
OD5065/2024-2025:Supply and fixing 105 x 50 mm UPVC Cable Management System with base and lid LEGRAND or equivalent along with all required accessories as per the site condition on surface/recess including all accessories like end cap internal/external angle etc complete with all fixing accessories.
OD5064/2024-2025:Supply and fixing 80 x 50 mm UPVC Cable Management System with base and lid LEGRAND or equivalent along with all required accessories as per the site condition on surface/recess including all accessories like internal/external angle end cap etc complete with all fixing accessories.
OD5066/2024-2025:Supplying and fixing following Modular base &amp; cover plate on existing existing CMS 105X50mm. as required.1 or 2 Module base and cover plate
Civil work
5.22.1:Steel reinforcement for R.C.C work including straightening, cutting, bending, placing in position and binding all complete upto plinth levelMild steel and Medium Tensile steel bars
50.18.7.3.2:Providing and fixing PVC pipes, fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step PVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge 25 mm dia 10Kgf/ cm2- Internal work- Exposed on wall
R.Mohanan (BID ID -1991117)
Bidder Name
CALL ON ELECTRICALS
R.Mohanan
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_1104917.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .