REPAIR TO HT ELECTRIC INSTALLATION, TRANSFORMER, VCB, RMU, PANEL AND HT CABLES IN TECHNICAL AND DOMESTIC AREA AT AIR FORCE STATION CHANDIGARH
2021_MES_482837_1
CWE/AF CHD/CHD/T-17/2021-2022
Open Tender
Civil Works
Item Rate
183 days
Chandigarh
As per NIT
8 documents required · 8 mandatory
₹1,000
GE (AF) Chandigarh
Exempted
16 Dec 2021
20 Oct 2021
1 Dec 2021
20 Oct 2021
24 Nov 2021
10 Nov 2021
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 metre wide and not exceeding 1.5 metre deep for laying/taking out of cables and foundation of poles etc. and getting out, complete all as specified and directed.
Returning, filling in trenches (soil), including spreading, leveling and well ramming in layers not exceeding 25 cm thick, complete all as specified and directed.
Removal of surplus excavated soil to a distance not exceeding 50 metre and depositing where directed at a level not exceeding 1.5metre above the starting point, complete all as specified and directed.
Material and labour for sand cushioning with a layer of dry river sand, 80mm thick before laying of cable and 150mm thick (punned down to 100mm thick) after laying of cables, in trenches/ducts, complete all as specified and directed. Note : Punned down thickness (overall 18cm), shall be considered for measurement and payment.
Supplying and laying factory made unreinforced precast concrete cable cover HV type-1, flat, of size 300mm x180mm x40mm, laid flat and dry in trenches over the cable for protection, length perpendicular to the direction of cable adjacent to each other, complete all as specified and directed.
Supply and laying / fixing , GI pipe light grade 80mm bore for cable protection fixed to pole/wall or laid under floor/road/pavement with nuts, bolts, clamps etc as required, including taking out old pipe & removal, complete all as specified and directed.
Taking out / down old existing HT 11000 volt grade cables, size 95 Sqmm to 120 Sqmm aluminium conductor, 3core, XLPE, armoured, laid in trenches, including PCC / Brick Covers for protection, and stacking, removal to store for re-use or for credit, complete all as specified and directed.
Supply, laying, jointing, testing and commissioning of High Tension (HT), 11000 Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 120 Sqmm, 3core under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately.
Supply, laying, jointing, testing and commissioning of High Tension (HT), 11000 Volts (earthed) grade, XLPE insulated, screened, PVC bedded, galvanized steel strip armoured, electric power cable (heavy duty) with stranded aluminum conductor, cross sectional area 95 Sqmm, 3core under ground cable including both side connection with cable lugs etc, laid in trenches, along poles or passing through pipes or laid under floor or through walls etc, complete all as specified and directed. Note : Excavation and earth work, sand cushioning and precast concrete cable cover/bricks for protection of cable shall be measured and paid separately.
Supply, jointing & testing, indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 50 to 95 Sqmm size cable, including taking out old joint kit and removal,complete all as specified and directed.
Supply, jointing & testing, indoor end termination joint kit (Heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3core, 120 to 185 Sqmm size cable, including taking outold joint kit and removal, complete all as specified and directed.
Supply, jointing & testing, outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 50 to 95 Sqmm size cable, including taking out old joint kit and removal, complete all as specified and directed.
Supply, jointing & testing, outdoor end termination joint kit (heat shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3core, 120 to 185 Sqmm size cable, including taking out old joint kit and removal, complete all as specified and directed.
Supply, jointing & testing, straight through joint kit (cold shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 50 to 95 Sqmm size cable, including taking out old joint kit and removal, complete all as specified and directed.
Supply, jointing & testing, straight through joint kit (cold shrinkable) complete with jointing material and accessories suitable for 3 wire, 11KV (Earthed) grade, HT, underground XLPE insulated armoured aluminium conductor, 3 core, 120 to 185 Sqmm size cable, including taking out old joint kit and removal, complete all as specified and directed.
Material and labour for Cross arms, bracing, supports, clamps and back plates, fabricated from structural steel section Fe-290 grade E-165 quality including nuts, bolts, washers, and welding, bending cold or hot, drilling holes for bolts, in any shape or size as directed including two coats of alminium paint over a coat of primer and taking down old, complete all as specified and directed.
Supply and fixing switch air break, triple pole, gang operated (GOD), complete with 15 insulators, drop out fuse unit mechanically operated, mounted on insulators and steel frame, non-ferrous knife and spring loaded contacts, arcing horns of adequate sections to break magnitising current of the transformer, with operating mechanism worked from ground level, for current rating upto 400 Amps, suitable for 11000 volts grade AC supply, including taking down old & removal, complete all as specified and directed. Note: All ferrous parts shall be hot dipped galvanised and non-ferrous parts shall be heavily dipped to withstand weather.
Supply and fixing Lightning arresters expulsion type complete with all fittings, distribution class, discharge capacity 65 Kilo Amps, long duration current impulse to withstand 250AP/2000Seconds & energy dissipation capacity 2KJ/KV, suitable for 11000 volts grade system, fixed in position & tested, including taking down old u/s lightning arrester complete all as specified and directed. Make: OBLUM, SCHNEIDER, CROMPTON, ALSTOM LEMCOS CO
Supply and fixing male moving contactor 400 Amp capacity, 11000 volts grade for GOD switch (as per existing make), fixed in position, testing & commssioning, including taking out old & removal, complete all as specified and directed.
Supply and fixing female moving contactor 400 Amp capacity, 11000 volts grade for GOD switch (as per existing make), fixed in position, testing & commssioning, including taking out old & removal, complete all as specified and directed.
Supply and fixing tinned copper Jumper of capacity 400 Amps, 11000 volts grade, for GOD switch (make as per existing), fixed in position, testing & commssioning, including taking out old & removal, complete all as specified and directed.
Finding out the fault with fault locator machine and repairing/rectifying the same in HT 11000 volts grade Under Ground Cable laid more than 100 centimetre deep in tranches complete all as specified and directed. Note: (i) HT cable fault shall be repaired within 04 Hrs after receiving complaint from Engr-in-Charge, failing which a penalty of Rs.1000.00 per hour shall be recovered from the contactor.
Dismantling and removing transformer of capacity 63 KVA to 400 KVA and shifting from site to workshop for repair , opening the transformer in the presence of Engr-in-Charge , taking out coil and detaching core &core assembly for estimation of repair and damage parts , cleaning /washing of tank and removing the dust from all parts including cores, tanks , cooling tubes, removal of damage parts, shifting back to site and refixing in position after repair , provision of cork sheet , making connection , including testing and commissioning , complete all as specifed.
Supply and fixing in replacement copper winding coils of required size and specification with super enamelled superior quality copper wire of suitable size on primary side of transformer (HV side) , complete with insulation , varnishing , vaccum impregnation and baking of coil assembly etc , complete all as specified and directed
Supply and fixing in replacement copper winding coils of required size and specification with super enamelled superior quality copper wire of suitable size on secondary side of transformer (LV side), complete with insulation , varnishing , vaccum impregnation and baking of coil assembly etc , complete all as specified and directed
Supply and fixing in replacement Gun metal globe/gate valve with iron wheel head, screwed both ends for iron pipe of size 25 mm bore, including taking down old and removal , complete all as specified and directed.
Supply and filling silica gel to transformers breather assembly including taking out of old existing U/S silca gel, complete all as specified and directed.
Supply and fixing breathers Assembly complete with silica gel for transfomer of capacity 63 to 100 KVA complete all as required and directed.
Supply and fixing breathers Assembly complete with silica gel for transfomer of capacity 160 to 400 KVA complete all as required and directed.
Supply and fixing factory made (CPRI approved), HT bus bar Panel, size 1500mmx1000mmx500mm, cubical, outdoor type (Kiosk), weather proof, dust proof and vermin proof, IP-65 protection, fabricated out of 3.15mm thick MS CRCA sheet mounted on frame of appropriate size angle iron, welded on 50mmx50mmx6mm size angle iron frame & having four Nos legs made out of 50mmx50mmx6mm size of angle iron - 75 cm long each welded below frame, front & back openable with front double door having locking arrangements, bottom space for cable entry, provision of glands, with copper bus bars 200 Amps rating - 01 set (set of three) mounted on 6Nos HT post type insulators, 11000 volts grade of suitable size (not less than 36mmx5mm), duly sleeved with relevant colour code insulation & provision for 01No incoming & 02 Nos outgoing cables, including spray painting with two coats of synthetic enamel paint in dark grey shade over a coat of red oxide primer, duly provided with danger notice board 11000 volts, legs embedded in ground in PCC (1:2:4) bed blocks of size 30cmx30cmx30cm, including dismantling of foundation, taking out old & removal, complete all as specified and directed.
Supply and fixing in replacement HT epoxy coated copper bus bar insulator of 130mmx70mm size , suitable for 11000 Volt, complete all as specified and directed.
Material and labour for earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick burried directly in ground vertically (depth of pit not less than 2.25 m below normal ground level), with top edge of earth plate not less than 1.5 m below normal ground level, earth plate surrounded from all sides by 15cm thick packed alternate layers of charcoal dust and common salt, electrode connections using galvanized iron strip of size 25mmx4mm thick (upto body of equipment) by means of nuts, bolts, check nuts & GI washers, connected to main switch board or main control board or test point, protected by galvanized iron pipe light grade 40mm dia bore, and watering pipe 20 mm bore GI light grade pipe with funnel & wire mesh, including all necessary excavation & earth work, PCC chamber in PCC (1:2:4) type B-1 & RCC cover, all as shown in electrical plate No 3 of MES Schedule Part-I (2009), testing on completion, including taking out old earthing materials and removal complete all as specified and directed. Note(s) :- (i) RCC pit cover shall be pre-cast of RCC (1:2:4) type B-1, 80mm thick reinforced with XPM not less than 4Kg/Sqm. (ii) PCC chamber shall be constructed 500 mm away from the edge of earth pit. (iii) Rate shall include GI strip and protection pipe of length 7.5m, GI pipe beyond 7.5m length required at site shall be measured and paid separately. (iv) Earth resistance should be less than 3 Ohm. In case the test results are not found below 3 Ohm, complete earthing will be redone without any extra cost to Govt.
Material and labour in replacement for Earth continuity conductor or main earthing lead or lightning conductor, 25mmx4mm GI strip, fixed to wall on batten with saddles and fixing screws, PVC/ Porcelain insulators etc. or recessed or in chases or burried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc as required, complete all as specified and directed.
Supply and fixing in replacement LT brass bush with brass washer/ nuts & bolts for transfermer of capacity 63 to 100 KVA complete all as specified and directed.
Supply and fixing in replacement LT brass bush with brass washer/ nuts & bolts for transfermer of capacity 160 to 400 KVA complete all as specified and directed.
Supply and fixing in replacement HT brass bush with brass washer/ nuts & bolts for transfermer of capacity 63 to 100 KVA complete all as specified and directed.
Supply and fixing in replacement HT brass bush with brass washer/ nuts & bolts for transfermer of capacity 160 to 400 KVA complete all as specified and directed.
Material and labour for opening HT, 11KV, VCB front and back side complete after taking shutdown , cleaning, dusting inside & out side of VCB, greasing & oiling the mechanical parts of VCB and other parts of VCB as required at site, including testing and commissioning complete all as specified and directed. Note:- Replacement of required spare parts will be measured and paid saperately.
Taking out existing unserviceable items of VCB 630 Amps of any make after taking shut down and replacing the follwing items complete all as specified and directed :-
(a) Indicating lamps
(b) Internal wiring for indicating lamps
(c) Closing coil . Make - CG, C&S , ABB
(d) Tripping coil Make - CG, C&S , ABB
(e) Vacuum bottle. Make - CG, C&S , ABB
(f) Jaw contact. Make - CG, C&S , ABB
(g) Protection relay. Make - CG, C&S , ABB
(h) Mechanism. Make - CG, C&S , ABB
(j) Spout. Make - CG, C&S , ABB
(k) Rack in/out gear. Make - CG, C&S , ABB
(l) Auxillary switch. Make - CG, C&S , ABB
(m) TNC switch. Make - CG, C&S , ABB
(n) Relay protection 3 pole. Make - CG, C&S , ABB, Schneider.
(o) Cradle contact. Make - CG, C&S , ABB
(p) Spring charger motor with gear assy with rear spring charging motor with gear assy 110-230 Volt AC 50Hz .
(q) Heater spacer suitable for 11 KV VCB , complete.
(r) Bus insulator suitable for 11 KV complete.
Material and labour for opening 11KV RMU front and back side complete after taking shutdown , cleaning, dusting inside & out side of RMU greasing oiling the mechanical parts of RMU and other parts as required at site including testing and commissioning complete all as specified and directed Note:- Replacement of required spare parts will be measured and paid saperately.
Taking out existing unserviceable items of RMU 630/400 Amps of any make after taking shut down and replacing the follwing items complete all as specified and directed :-
(a) " K " mechanism
(b) "N" mechanism
(c ) Charging motor
(d) Tripping coil Make - CG, C&S , ABB
(e) Closing coil . Make - CG, C&S , ABB
(f) Main bushing Make - CG, C&S , ABB
(g) Supply and filled and testing SF-6 gas charging
(h) Protection relay . Make - CG, C&S , ABB, Schneider
Material and labour for preparation of old rusted steel sufaces of structure four pole HT swaged poles (of any length) and applying one coat of synthetic enamel paint up to 1.2 metre height as per the existing pattern above the PCC coping and one coat of aluminium paint beyond 1.2 meter height (for the rest portion) including cross arms brackets and re-writing pole numbers complete all as specified and directed by the Engineer in Charge.
Material and labour for PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in foundation, filling and mass concrete for pole and stay complete all as specified and as directed.
Material and labour for PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of pole etc including form work complete all as specified and as directed.
Horizental Boring of Holes under road, Pavement, hard standing by trenchless technology using ultra sounding techique and necessary machine including provision of HDPE pipe of size 150 mm dia suitable for 0.4 mpa working pressure complete all as specified and directed by the Engineer in Charge.
Material and labour for painting of transformer indoor/outdoor type installation double pole structure/raised plinth structure with two coats of synthetic enamel paint after throughly scrapping/cleaning the rusted portion and preparing the surface complete for following capacity transformer :-
(a) Transformer 100 to 250 KVA
(b) Transformer 315 to 400 KVA
Material and labour for filteration and Dehydration of HV/EHV grade transformer oil (desludging of transformer minimum three cycles to achieve dielectric strenth upto 60KV(rms) for EHV grade and upto 50KV (rms) for HV grade at 2 mm/2.5 gap complete all as specified and directed.
Supply of transformer oil superior quality having di-electric strength not less than 50 KV at 2.0 mm gap, ISI marked, package of 210 litre sealed drum, and filling into transformers and other equipments installed at various locations including taking/draining out old existing defective transformer oil , complete all as specified and directed.
Supply and fix tempreature gauge after taking down existing old one complete all as specified and directed.
Taking out the existing unserviceable rubber gasket sheet of transformer of any capacity after taking shut down, including opening all electric connections , nuts bolts, HT bushes and providing new rubber gasket sheet 3.0 mm thick with nuts bolts and all electric connetions, testing of transformer on load complete all as specified and directed by Engr-in-charge.
Material and labour for Hardcore of guage exc 63mm but n exc. 100 mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rolled/rammed to a true surface filling in four pole structure transformer area complete all as specified
Supply and fixing in replacement Plates (chequered ), channels, square cut or notched (ordinary and counter sunk) forming holes, without any attachment, Fe 410 -W (Gde E- 250) quality A, of minimum thickness 6 mm, including necessary supports, hangers ,nuts, bolts and washers etc complete all as specified
Supply and laying synthetic rubber insulating mat of size 2mx1m, 2.50 mm thick, suitable for safety from electrical shock for electrical installation with voltage upto 11 KV, as per IS 15652-2006(superseding IS-5424), complete all as specified and directed.
Supply and fixing Compression/crimping type sleeve joints for jointing conductors/ jumper connections upto 10mm dia of conductor wire overall, including treatment with conducting jelly complete all as specified and directed.
Disconnecting HT cable connections from HT pole and transformer, taking down transformer, lifting of transformer and keeping aside and reconnecting the same and reinstall in position complete all as specified and directed. .
Repair and replacement of spare parts of HT installations / infrastructure by HT exprienced electrician within 02 Hrs of intimation of fault without affecting the services of entire locatons of 12 Wing AF Area . Contractor shall provide spare materials in advance to department for execution the work without delay on site without affecting the services.The complaints will be communicated telephonically/ SMS by JE or AGE E/M. Complaints can be related to (i) DO fuse (ii) Jumper connections (iii) Repair to loose connections (iv) Repair to HT insulators (v) Repair to LA (vi) Repair to GOD sparking (vii) Repair to thimbles. Note :-(i) The contractor must have a functional mobile phone (basic mobile phone) round the clock and shall instantlly attend to phone call from JE or AGE E/M to promptly attend the complaints. (ii) The contractor's workmen shall be equiped with all T&P including cutting pliers, screw driver , tester, hand gloves, insulation tape etc and crimping tool kit. (iii) If the contractor fails to attend the complaints within 02 hours of first telephonic communication/ SMS, a penalty of Rs. 200.00 per complaint per hour of delay shall be recovered from contractor. (v) The contractor shall be liable to attend the complaint 24x7 hrs Note :- If any item is repaired/replaced twice due to any reason within 3 months at the same location, the payment shall be made only once.
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out including cutting of grass/trimming of all bushes / small trees up to a height of 10 feet, in surrounding areas of E/M installations , double pole/four pole structures, panels, bus bar chambers etc incl sprinkling of herbicide solution as per manufacturer's instructions complete all as specicfied and direcetd by Engr-in-charge.
Material and labour for construction of platform of size 2m x 1.5 mx1.5m for transformer with brick work with sub class "B" bricks laid in cement mortar 1:4, cement contrete type D2 1:4:8 using 40 mm graded stone aggregate in foundation filling and mass concrete, rendering 15 mm thick plaster in cement mortar (1:4) on brick/concrete surface of walls , finished even and smooth with out using extra cement, PCC (1:2:4) type B-0 using 12.5 mm graded crushed stone aggregate as in top of platform, and preparation of new surfaces of wall and applying two coats of cement base paint, including dismantling of existing old platform complete all as specified.
Supply and fixing in replacement danger notice plate of 1.6 mm thick mild steel sheet vitreous enamelled white with letters figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size for HT 250 x 200 mm size complete all as specified and directed.
Material and Labour for replacement of Anti-climbing device; spikes type fabricated out of M.S. bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specifed and directed .
Supply only HT insulation tape 19mm x20M all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 5 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 10 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 15 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 20 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 25 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 50 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 90 Amps all as specified and directed by Engr-in-charge
Supply only 11 KV DO Fuse of capacity 100 Amps all as specified and directed by Engr-in-charge
Supply ans fixing in replacement cable route marker for HT cable duly engraved (HT 11 KV CABLE) on 150 mm dia MS round plate, duly painted with brown colour paint and fixed on MS angle of size 230 mmx230 mmx150mm , complete all as specified and directed. Note : The length of MS angle shall not be less than 50cm above the groung level.
Repair , testing and caliberation as per PSEB norms by engaging authorised agency /PSEB and making functional existing IDMT over current and earth default relays of any type for HT VCB 11 KV including assembling , complete all as specified and directed
Servicing/maintenance of four pole structure of Ht infrastructure, dismantling all parts, cleaning with perolium jelly and replacement of defective parts ,re-assembling the same in postion with applying grease to moving parts,replacement of HT jumper connection with suitable cable/ ACSR conductor with conneting thimbles by experienced technical qulaified electrician, all as per specifiedand directed Engr-in-charge.
Servecing/maintenance of two pole structure of Ht infrastructure, dismantling all parts, cleaning with perolium jelly and replacement of defective parts, re-assembling the same in postion with applying grease to moving parts,replacement of HT jumper connection with suitable cable/ ACSR conductor with conneting thimbles by experienced technical qulaified electrician, all as per specifiedand directed Engr-in-charge.
Note: The Total amount shall subject to adjustment of credit of Rs.387396.00 for old Materials as per Schedule of Credit.
R N Enterprises
Raman Electric Trading Co
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .