RFP FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF DIESEL GENERATORS AND ALLIED INFRASTRUCTURE FOR RESTSTOP THALAPPADY WAYSIDE AMENITIES CENTER.
2026_OKIH_846492_1
RS-013(8)/DG
Open Tender
Equipments
Item Rate
Kasaragod
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹25,000
Yes
OKIH Ltd
11 Mar 2026
11 Mar 2026
22 Apr 2026
11 Mar 2026
20 Apr 2026
11 Mar 2026
24 Mar 2026
BOQ FOR SUPPLY, INSTALLATION, TESTING AND COMMISSIONING OF DIESEL GENERATORS AND ALLIED INFRASTRUCTURE for RestStop, Thalappady Wayside Amenities Center.
(To be filled only in Excel Sheet in e-Tender Portal to protect sanctity of RFP process. No hard copy to be forwarded)
Sl No Item Specification Purpose/ Scope Quantity Unit Rate
Supply of 250 KVA Diesel Generator set with integral acoustic enclosure as per CPCB IV+ or better norms with standardized accessories as per technical details given below. 1. Engine : Turbocharged diesel engine, 4 stroke, water cooled, multi cylinder, electric start of suitable BHP at 1500 RPM, capable of taking 10% over loading for one hour after 12 hours of continuous operation. . The electronic governor shall be as per ISO 8528. 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger. 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) RPM Indicator with hour meter d) Battery charging indication and voltage indication. 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 5. Alternator a)Type - self cooled, self-excited and self-regulated b) Capacity - 250KVA/200 K W @ 0.8PF c) System of Voltage - 3 phase, 415 V, d) Frequency - 50 Hz e) Insulation - Class F/H. The Alternator should confirm to IS 4722. 6. Fuel Tank Suitable size built in type integrated with the acoustic enclosure. 7. Battery :-12V 24V DC starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG set. 8.Operation and service manual, spares and tools shall be provided. 9.Standard control panel as per Kerala Electrical Inspectorate requirements, complete with 400 A, 4-pole MCCB with accessories, voltmeter, frequency meter, energy meter, low-set earth-fault relay, etc., complete. As back up for the Common load requirement of OKIH 1 Each
Supply of 200 KVA Diesel Generator set with integral acoustic enclosure as per CPCB IV+ or better norms with standardized accessories as per technical details given below. 1. Engine : Turbocharged diesel engine, 4 stroke, water cooled, multi cylinder, electric start of suitable BHP at 1500 RPM, capable of taking 10% over loading for one hour after 12 hours of continuous operation. The electronic governor shall be as per ISO 8528. 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger. 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) RPM Indicator with hour meter d) Battery charging indication and voltage indication. 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 5. Alternator a)Type - self cooled, self-excited and self-regulated b) Capacity - 200KVA/160 K W @ 0.8PF c) System of Voltage - 3 phase, 415 V, d) Frequency - 50 Hz e) Insulation - Class F/H. The Alternator should confirm to IS 4722. 6. Fuel Tank Suitable size built in type integrated with the acoustic enclosure. 7. Battery :-12V 24V DC starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG set. 8.Operation and service manual, spares and tools shall be provided. 9.Standard control panel as per Kerala Electrical Inspectorate requirements, complete with 400 A, 4 pole MCCB with accessories, voltmeter, frequency meter, energy meter, low-set earth-fault relay, etc., complete. As back up for the Common load requirement of OKIH 1 Each
Supply of 200 KVA Diesel Generator set with integral acoustic enclosure as per CPCB IV+ or better norms with standardized accessories as per technical details given below. 1. Engine : Turbocharged diesel engine, 4 stroke, water cooled, multi cylinder, electric start of suitable BHP at 1500 RPM, capable of taking 10% over loading for one hour after 12 hours of continuous operation. . The electronic governor shall be as per ISO 8528. 2.Standard accessories with Diesel Engine a) Fly wheel to suit flexible coupling b) Close Coupling c) Air cleaner d) Radiator with fan provided with fan guard. e) Fuel Pump f) Fuel filter g) Lubricating oil filter h) Exhaust silencer i) Exhaust Muffler j) Battery Charger. 3. Engine Instrument Panel with the following items a) Starting switch with key or button b) Lubricating oil pressure gauge. c) RPM Indicator with hour meter d) Battery charging indication and voltage indication. 4. Safety Controls for Engine a) Trip for low lubricating oil pressure b) Trip for high water temperature. 5. Alternator a)Type - self cooled, self-excited and self-regulated b) Capacity - 200KVA/160 K W @ 0.8PF c) System of Voltage - 3 phase, 415 V, d) Frequency - 50 Hz e) Insulation - Class F/H. The Alternator should confirm to IS 4722. 6. Fuel Tank Suitable size built in type integrated with the acoustic enclosure. 7. Battery :-12V 24V DC starting system comprising of starter motors, voltage regulator and arrangement for initial excitation complete with suitable numbers of batteries as required as per specifications. The battery shall be housed inside the acoustic enclosure of DG set. 8.Operation and service manual, spares and tools shall be provided. 9.Standard control panel as per Kerala Electrical Inspectorate requirements, complete with 400 A, 4 pole MCCB with accessories, voltmeter, frequency meter, energy meter, low-set earth-fault relay, etc., complete. As back up for the LT connections of OKIH 1 Each
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.82 MB
BOQ.xls
Other Document • 0.13 MB
corrigendumdg.pdf
PDF • 0.40 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .