Loading…
Loading…
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
Tender Value
₹30 L
EMD Value
₹60,000
Closing Date
14 Oct 2026, 6:00 pm2d left
Eligibility, documents, scope, Go/No-Go checksEligibility, required documents, scope of work and Go/No-Go checks for this tender, in one click.
GE Clement Town
GE Clement Town MES Dehradun
REPAIR/REPLACEMENT OF APFC PANELS, PERIMETER LIGHTS, STEEL TUBULAR POLES ALONGWITH ALLIED CABLE WORKS AT CLEMENT TOWN
2026_MES_790753_1
8131/CLT/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Clement Town
As per Tender
7 documents required · 7 mandatory
₹500
Yes
GE Clement Town
₹60,000
Yes
23 Sept 2026
23 Sept 2026
21 Oct 2026
23 Sept 2026
14 Oct 2026
7 Oct 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply , fixing , connecting and commissioning and testing in replacement of power factor improvement panel (APFC) of capacity 50 KVAr, automatic and manual operation for distribution trasformer including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor). The outdoor panel having suitable/appropriate size as approved in the drg for accomodating capacitor and connected items, Panel should be factory made, weather proof , dust and vermin proof ,IP54 suitable for 440 V grade 3 phase 50 HZ AC supply, PCC plinth mounted , fabricated out of 3.00 mm outer sheet and 2 mm thick inner CRCA sheet and having four Nos angle iron legs made out of 40 x 40 x 6mm, 60 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with light grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles, all as per specified and directed by Engr-in-Charge The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only and comprising of the following :-
MCCB 100 A 25 KA 3 pole thermal magnetic – 1 Nos
Capacitor 25 KVAR – 01 Nos & duty contactor for 25 KVAR – 01 Nos
Capacitor 15 KVAR – 01 Nos & duty contactor for 15 KVAR – 01 Nos
Capacitor 4 KVAR – 01 Nos & duty contactor for 4 KVAR – 01 Nos
Capacitor 3 KVAR – 01 Nos & duty contactor for 3 KVAR – 01 Nos
Capacitor 2 KVAR – 01 Nos & duty contactor for 2 KVAR – 01 Nos
Capacitor 1 KVAR – 01 Nos & duty contactor for 1 KVAR – 01 Nos
MCB 63 A 10 KA TP for 25 KVAR – 1 Nos
MCB 32 A 10 KA TP for 15 KVAR – 1 Nos
MCB 16 A 10 KA TP for 4 KVAR and below– 04 Nos
APFC Relay 08 stage – 1 No, Indicating light red – 01 No, Auto manual selector switch – as suitable numbers, Indicator light R Y B – 3 Nos, Digital MF meter (0–500 V) – 1 Nos, CT 100/5 A – 3 Nos Bus bar 150 A 3 strip & N/L 100 Amp ALU – 01 strip complete. | 4 | Each Job | - | - |
| 2 | Supply , fixing , connecting and commissioning and testing in replacement of power factor improvement panel (APFC) of capacity 125 KVAr, automatic and manual operation for distribution trasformer including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor). The outdoor panel having suitable/appropriate size as approved in the drg for accomodating capacitor and connected items, Panel should be factory made, weather proof , dust and vermin proof ,IP54 suitable for 440 V grade 3 phase 50 HZ AC supply, PCC plinth mounted , fabricated out of 3.00 mm outer sheet and 2 mm thick inner CRCA sheet and having four Nos angle iron legs made out of 40 x 40 x 6mm, 60 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with light grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles, all as per specified and directed by Engr-in-Charge The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only and comprising of the following :-
MCCB 250 A 36 KA 3 pole thermal magnetic – 1 Nos
Capacitor 25 KVAR – 04 Nos & duty contactor for 25 KVAR – 04 Nos
Capacitor 15 KVAR – 01 Nos & duty contactor for 15 KVAR – 01 Nos
Capacitor 4 KVAR – 01 Nos & duty contactor for 4 KVAR – 01 Nos
Capacitor 3 KVAR – 01 Nos & duty contactor for 3 KVAR – 01 Nos
Capacitor 2 KVAR – 01 Nos & duty contactor for 2 KVAR – 01 Nos
Capacitor 1 KVAR – 01 Nos & duty contactor for 1 KVAR – 01 Nos
MCB 63 A 10 KA TP for 25 KVAR – 4 Nos
MCB 32 A 10 KA TP for 15 KVAR – 1 Nos,
MCB 16 A 10 KA TP for 4 KVAR and below– 04 Nos
APFC Relay 08 stage – 1 No, Indicating light red – 01 No, Auto manual selector switch – as suitable numbers, Indicator light R Y B – 3 Nos, Digital MF meter (0–500 V) – 1 Nos, CT 100/5 A – 3 Nos , Bus bar 315 A 3 strip & N/L 315 Amp ALU – 01 strip complete. | 2 | Each Job | - | - |
| 3 | Supply , fixing , connecting and commissioning and testing in replacement of power factor improvement panel (APFC) of capacity 125 KVAr, automatic and manual operation for distribution trasformer including interconnection with LT panel with appropriate size of electric cable for transformer (Outdoor/Indoor). The outdoor panel having suitable/appropriate size as approved in the drg for accomodating capacitor and connected items, Panel should be factory made, weather proof , dust and vermin proof ,IP54 suitable for 440 V grade 3 phase 50 HZ AC supply, PCC plinth mounted , fabricated out of 3.00 mm outer sheet and 2 mm thick inner CRCA sheet and having four Nos angle iron legs made out of 40 x 40 x 6mm, 60 cm long angle iron below frame with front door and Side/Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 sq mm / extension strips and connected with suitable size thimbles , lugs duly painted with light grey epoxy powder coating after suitable chemical treatment , legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20 mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting , with required sheet metal enclosures, thimbles, all as per specified and directed by Engr-in-Charge The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only and comprising of the following :-
MCCB 250 A 36 KA 3 pole thermal magnetic – 1 Nos
Capacitor 25 KVAR – 04 Nos & duty contactor for 25 KVAR – 04 Nos
Capacitor 15 KVAR – 01 Nos & duty contactor for 15 KVAR – 01 Nos
Capacitor 4 KVAR – 01 Nos & duty contactor for 4 KVAR – 01 Nos
Capacitor 3 KVAR – 01 Nos & duty contactor for 3 KVAR – 01 Nos
Capacitor 2 KVAR – 01 Nos & duty contactor for 2 KVAR – 01 Nos
Capacitor 1 KVAR – 01 Nos & duty contactor for 1 KVAR – 01 Nos
MCB 63 A 10 KA TP for 25 KVAR – 4 Nos
MCB 32 A 10 KA TP for 15 KVAR – 1 Nos,
MCB 16 A 10 KA TP for 4 KVAR and below– 04 Nos
APFC Relay 08 stage – 1 No, Indicating light red – 01 No, Auto manual selector switch – as suitable numbers, Indicator light R Y B – 3 Nos, Digital MF meter (0–500 V) – 1 Nos, CT 100/5 A – 3 Nos Bus bar 315 A 3 strip & N/L 315 Amp ALU – 01 strip complete.
Note : Item No 01 to 03 :- Automatic Power Factor controller steps Relay Micro proccessor based for switchting ON and OFF of capacitors to Display of voltage, current,Active power ,apparent Power display of COS Ø ,THD voltage, THD current,alarm indication for defective step,low power factor and access temperature.The relay having volt free c/o contact,automatic detection and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 volt ,45 to 65 HZ,commissioning without additional setting and programming complete. | 2 | Each Job | - | - |
| 4 | Dismantling and removing and setting aside PCC pole any type by breaking PCC foundation after disconnecting electrical connection incl site clearance complete all as specified and directed by Engr-in- Charge. | 6 | Each | - | - |
| 5 | M&L for steel swaged poles complete poles 9 mtr long complete with cast iron base plate, finial taperplug, bolts, nuts and screws as specified type 410 SP-31 with one coat of red oxide primer and two coats of aluminium paint and including marking alternate 5 nos black & white strip 30 cm height with two coats of synthetic paint over a coat of primer including preparation of new surfaces complete all as specified and directed. | 6 | Each | - | - |
| 6 | Excavation in trenches not exceeding 1.5 M wide and not exceeding 1.5 M in depth and getting out in soft/loose soil or hard/dense soil for taking up or laying of cable complete all as specified and directed. | 276.48 | Cum | - | - |
| 7 | Description all as per srl item No-6 above but depth exceeding 1.5 m and not exc 3.0 m complete all as specified and directed. | 0.64 | Cum | - | - |
| 8 | Returning, filling in including spreading, levelling, watering and well ramming in layers not exceeding 25 cms. complete all as specified and directed. | 168.32 | Cum | - | - |
| 9 | Removing excavated material not exceeding 50 M and depositing where directed at a level not exceeding 1.5 M above starting point. complete all as specified and directed. | 108.8 | Cum | - | - |
| 10 | Supplying and laying bricks common burnt clay sub class 'B' old size for cable protection complete all as specified and directed. | 8,000 | Each | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.31 MB
BOQ_886474.xls
BOQ • 0.34 MB
Tenderdocs8131.pdf
Tender Documents • 1.10 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .