Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹84,108Accepted-AOC 676301 | MALAPPURAM | KERALA | 676301 | 1 | Accepted-AOC LOWEST | |
| 2 | 2₹85,789+₹1,677.50 (1.99%)Rejected-AOC EDAYUR PO VALANCHERY MALAPPURAM | MALAPPURAM | KERALA | 676552 | 2 | Rejected-AOC 2ND LOWEST |
Tender Value
₹84,737
EMD Value
₹2,118
Closing Date
11 Jul 2023, 6:00 pmClosed
ASSISTANT EXECUTIVE ENGINEER
PWD ELECTRICAL SUBDIVISION MALAPPURAM
D E P O S I T - G o v t . P r a t h e e k s h a B h a v a n Thavanur-Construction of Entrance Gate, Compound Wall and Road at Govt. Pratheeksha Bhavan Thavanur in Malappuram Dist. (Thavanur LAC)-Electrification-General Electrical Work
2023_PWD_585004_1
ELSDM-24-2023-24
Open Tender
Electrical Works
Item Rate
180 days
malappuram
Please refer Tender documents.
10 documents required · 10 mandatory
₹555
₹2,118
24 Aug 2023
30 Jun 2023
12 Jul 2023
30 Jun 2023
11 Jul 2023
30 Jun 2023
Amount
Electrification
OD218728/2022-2023:Supplying and fixing following size/ modules, PVC weather proof box along with modular base,cover plate and 6A Bell switch in surface/recess etc as required.1 or 2 Module
90.5.1.3:Supply and fixing the following types of superior quality 250V A.C call bell on existing M.S. box and giving connections with required length of 3 core, 16 / 0.20mm 650/1100V grade PVC insulated and PVC sheathed round copper conductor flex wire conforming to relevant ISS or with the extended original wiring, earthing the MS box and making good the surface as required.Ding dong bell
90.15.4.5:Supply Conveyance, installation, testing and commissioning of 40W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
90.15.4.6:Supply Conveyance, installation, testing and commissioning of 70W LED Flood light output greater than 105lumen/W 4000-6000 K with IP 66 protection LED Chip make Cree/Lumilled/Nichea with power factor greater than 0.95 at full load, internal surge protection up to 8 KV,and Aluminium pressure die-cast Powder coated housing, acrylic cover complete with THD less than 10%, power factor greater than 0.98, RoHS compliant, duly wired up for use on 230 V AC supply. Driver compartment should be seperatly accessible for maintenance (LM 79&80 certificates from NABL accredited Third party lab to be produced mentioning chip manufacturer)
OD218015/2022-2023:Supply,Conveyance, installation, testing and commissioning of 1800 lumen round/square (1ft X1ft) surface/recess fitting made of die cast aluminum, having efficacy not less than 110l/w, pf greater than 0.95, THD less than or equal to 10% directly on ceiling and giving connections with 16/0.20mm 3 core PVC insulated and sheathed round copper conductor flexible wire or extending the original wiring and giving connections as required.(Chip make Cree/Osram/lumilled/Nichea) or equivalent make
2.10.1:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single pole
OD218022/2022-2023:Supplying and fixing 4P sheet steel enclosure on surface/ recess suitable for fixing 4P MCB, RCCB, Isolator etc. as required.
2.10.3:Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Double pole
2.12.1:Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.40 amps
OD218047/2022-2023:Supply and fixing Syntex jungtion box GSJB 1616 with provision for fixing SP/DP MCB for terminating street light cable.
1.17.3:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mm
1.17.12:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mm
1.17.4:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.4 x 1.5 sq. mm
1.17.5:Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.5 X 1.5 Sq. mm
1.21.1:Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mm
90.12.10.2:Supply & laying of DWC pipe in ordinary soil 0.75m below ground level including excavation50/38 mm or nearest size
90.12.9.2:Supplying, laying and jointing of the following sizes of double wall corrugated (DWC) pipes made out of HDPE conforming to IS 14930 Part II for mechanical protection to underground power cables with all required accessories in ground in the existing trench50/38 mm or nearest size
90.3.17.1:Supply, conveyance and erection of the following sizes of 'B' class GI pipe in single section for post top lantern of all types on concrete base (excluding charges for concrete base and excavation) and painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc. as required.32 mm dia GI pipe
90.6.6.2:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.2.50 sq mm
90.6.6.1:Supply and drawing FRLS PVC insulated & sheathed 650/1100 V grade 3 core copper conductor flat cable for submersible pump motor conforming to IS 694 part I 1990 as required including giving necessary connections of the following sizes.1.50 sq mm
MOIDEENKUTTY KOLAMBAN
Bidder Name
AK ELECTRICALS
MOIDEENKUTTY KOLAMBAN
stage.html
html • 0.04 MB
tech_eval.pdf
fin_eval.pdf
aoc.pdf
finance_864407.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .