Loading…
Loading…
Tender Value
₹15.0 L
EMD Value
₹15,500
Closing Date
25 Feb 2026, 6:00 pmClosed
The Superintending Engineer, Project Implementation Unit
Providing & Erecting G2 Ward Block in HVAC Duct & Diffuser work at Civil Hospital Campus, Asarwa, Ahmedabad.
275658
150/08 of 2025/2026
Open
Electrical
Gandhinagar
8 documents required · 8 mandatory
₹900
Yes
PIU-General Fund A/c 11-114
₹15,500
Yes
12 Feb 2026
12 Feb 2026
12 Feb 2026
25 Feb 2026
12 Feb 2026
Name of Work : Providing & Erecting G2 Ward Block in HVAC Duct & Diffuser work at Civil Hospital Campus, Asarwa, Ahmedabad.
Memorandum showing items of works to be carried out
Estimated Rates
Quantity Item of Work Unit In Figure AMOUNT
Supply, installation, balancing and commissioning of fabricated at site GSS
sheet metal rectangular/round ducting complete with neoprene rubber
gaskets, elbows, splitter dampers, vanes, hangers, supports etc. as per
approved drawings and specifications of following sheet thickness complete as
Rupees One Thousand Two Hundred
350 (A) Thickness 0.63 mm sheet (22 Gauge) Sq.Mtr. 1245.00
Forty Five and Zero Paisa Only
Rupees One Thousand Four Hundred
70 (B) Thickness 0.80 mm sheet (20 Gauge) Sq.Mtr. 1453.00
Fifty Three and Zero Paisa Only
Supplying, laying, fixing, testing and commissioning of following thickness
closed cell elastomeric nitrile rubber of class 'O' applied by suitable
2 adhesive, as per specifications and as required complete in all respect.
Rupees One Thousand Three Hundred
Eighty Two and Zero Paisa Only
Supplying, fixing testing commissioning of Return air diffuser of powder coated
Rupees Nine Thousand Three Hundred
3 18 aluminium without volume control dampers with anti smudge ring & Sq.Mtr. 9301.00
One and Zero Paisa Only
removable core and size & shape as per site requirement and approved design..
Supply, installation, testing and commissioning of following minimum capacity
VRV High wall type Indoor unit equipped with washable synthetic media pre-
filter, fan section with noise level maximum 60 dB @min 400 cfm /dynamically
balanced blower, multispeed motor, coil section with DX copper coil, electronic
expansion valve, outer cabinet, cord less remote control, drain pan, necessary
accessories etc., suitable for operation on 230 V ± 10%, 50 Hz, single phase AC
4 supply, complete as required. The unit shall have automatic force shut down
provision in case of fire on receiving signal from BMS System. The cooling
capacity of indoor unit will be at air inlet conditions of 27 Degree C DB and
Degree C WB temperature.
Rupees Twenty Thousand Four Hundred
Ninety One and Zero Paisa Only
Supplying, laying/ fixing, testing and commissioning of following nominal
sizes of chilled water piping inside the building (with necessary clamps,
vibration isolators and fittings but excluding valves, strainers, gauges etc.)
duly insulated with following closed cell elastometric nitrile rubber of minimum
45 Kg / cu m density, thermal conductivity 0.037 W/MK or better at
deg mean temperature class 'O' insulation applied by suitable adhesive
complete including repairing of damage to building etc. as per
5 specifications and as required complete in all respect.
Note:- The Pipes of sizes 150mm & below shall be M.S. 'C' class as per IS :
1239 and pipes size above 150mm shall be welded black steel pipe heavy class
as per IS: 3589, from minimum 6.35mm thick M.S. Sheet for pipes upto 350 mm
dia. and from minimum 7mm thick MS sheet for pipes of 400 mm dia and above.
Rupees One Thousand Three Hundred
30 (N) 25 mm dia(19 mm thick insulation) Mtr 1318.00
Eighteen and Zero Paisa Only
Supply, Installation, Testing and Commissioning of following sizes electronic,
self-balancing, pressure independent type dynamic balancing valve with
integrated 2 way modulating control valve in a single body. The actuator shall be
capable of accepting upto 10V DC and upto 20mA electric signal and shall
provide similar transduced feedback output to control system. Maximum close
6 off pressure shall not be less than 6 Bar for upto 50 mm valves and 7 Bar for
mm & above. Valves should have pressure rating of 25 Bar minimum.
Rupees Nineteen Thousand One
2 (I) 25mm dia. Nos. 19112.00
Hundred Twelve and Zero Paisa Only
Rigid UPVC drain pipe of 10 Kg/cm2. rating with 9 mm thick.nitrile rubber
Rupees Eighty Seven and Zero Paisa
15 (D) 25 mm dia. Rmt. 87.00
carry out RCC Core cutting- up to 100 mm dia./300mm thick Wall/beam/slab
Rupees One Thousand Five Hundred
8 20 with providing PVC pipe of 3 mm thick inside and necessary finishing on both Job 1534.00
Thirty Four and Zero Paisa Only
Providing , erecting , fabricating the M.S. structure as per requirement on site
incorporating proper size of M.S. angles,square,round, flats, bars, channels,
Rupees Seventy Seven and Zero Paisa
9 350 sections complete with cutting, welding, grinding & finishing duly painted with Kg. 77.00
one coat of red oxide with erection on site as per direction of engineer in charge
with necessary grouting, cementing, plastering & finishing complete.
Rupees Eight Thousand and Zero Paisa
10 2.00 Air retardant Canvass Connection Nos. 8000
Air Balancing and Commissioning of ducting system with Existing air handling Rupees Fifty Thousand and Zero Paisa
Unit (4650CFM) Only
I / We am / are willing to carryout the all or any items of this A.R.C. at_%_______________% below /
/above + / - _____________________% (should be written in figure and words).
Note – 1 All work shall be carried out as per specification attached and relevant I.S. standards or as directed.
All the columns in schedule should be filled in by ball pan or ink and the total of the entries in the last column should be stated by the contractor under his signature.
Rates quoted include clearance of site (Prior to commencement of work and at its closure) in all respects and held good for the work under all conditions, site, moisture, weather etc.
To be continued on additional sheets, if found necessary.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
0.SBD Book_2023_Final_17_01_2024 (2) (1).pdf
HVAC Wori in G2 Ward Block-Schedule-B.pdf
Make List -G2 HVAC.pdf
PQ -G2 HVAC.pdf
Standard Specification for Electrical Work (1).pdf
Terms and Conditions For AC MAchines2021-22.pdf
150 TENDER NOTICE - .pdf
Download all tender documents and submit your bid