HQ CWE (HILLS) PITHORAGARH, Post Bharkatia Pithoragarh ( UK)PIN-262520
CA NO. CWE/HILL /PGH/26 OF 2022-2023 REPAIR/ MAINTENANCE OF HT TRANSFORMERS, VCB, OH/ UG NETWORK AND DG SETS INCLUDING CONNECTED ITEMS AT MIL STN PITHORAGARH UNDER GE PITHORAGARH
2022_MES_549658_1
CA NO. CWE/HILL /PGH/26 OF 2022-2023
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
PITHORAGARH
CLASS D
9 documents required · 9 mandatory
₹500
GE Pithoragarh
₹89,700
Yes
26 Nov 2022
3 Sept 2022
13 Oct 2022
3 Sept 2022
6 Oct 2022
19 Sept 2022
3 Sept 2022 - 17 Sept 2022
Amount
M&L for preparing old painted surface of transformer 11/0.433 KV outdoor/ indoor/ pole mounting of capacity 50 to 400 KVA by cleaning removing the old paint including scratching with wire brush etc. After disconnected HT/ LT side connection from both primary and secondary side of transformer and apply two coat of synthetic enamel paint done by spray machine of smoke grey colour to outer body of the transformer and writing of letter HT/ LT and SM/ MES Nos and making all HT/ LT electric connections complete all as specified and directed.
Supply and filling up silicagel in breather of different capacity of transformer complete all as specified.
Dehydration and filtering the transformer oil with dehydration machine to achieve required di-electric strength of the oil up to 40 KV at 2.5 mm gap complete all as specified and directed. Note:- Dehydration machine and other required necessary equipment shall be arranged by the contractor and no extra cost shall be paid to the contractor on this effect.
Opening up the top cover of transformer and taking out the transformer oil in a separate container after disconnecting the HT/LT side electric connections from both the primary & secoundary side of the transformer of any type/description (indoor/out door type) installed on pole/floor, for carrying out necessary repair/ rewinding to HT/LT side after shifting the transformer to contractors work shop including taking out complete core assembly, Megger the defective winding portion/taking out ,cleaning the laminated core and rewinding with appropriate guage/winding wire/strip winding of existing, description for transformer of capacity 50 to 150 KVA/including assembling & testing on completion & installation the same at the site complete all as specified and directed. Note:- 1. Winding of coil shall be measured and paid separately under respective item. 2. Transportation chagres are inclusive in the quoted rates. 3. The cost for the dehydration of transformer oil if required shall be measured and paid separately. 4. The cost of insulation material such as paper, cotton tape, latheriod sheet, cork sheet etc are inclusive in the coated rates.
Opening up the top cover of transformer and taking out the transformer oil in a separate container after disconnecting the HT/LT side electric connections from both the primary & secoundary side of the transformer of any type/description (indoor/out door type) installed on pole/floor, for carrying out necessary repair/ rewinding to HT/LT side after shifting the transformer to contractors work shop including taking out complete core assembly, Megger the defective winding portion/taking out ,cleaning the laminated core and rewinding with appropriate guage/winding wire/strip winding of existing, description for transformer of capacity 150 to 400 KVA/including assembling & testing on completion & installation the same at the site complete all as specified and directed. Note:- 1. Winding of coil shall be measured and paid separately under respective item. 2. Transportation chagres are inclusive in the quoted rates. 3. The cost for the dehydration of transformer oil if required shall be measured and paid separately. 4. The cost of insulation material such as paper, cotton tape, latheriod sheet, cork sheet etc are inclusive in the coated rates.
Supply only copper winding wire of any size/description suitable for step down transformer of any capacity, including winding of coils HT/LT as per the manufacturers design & specification to obtain rated KVA complete all as specified and directed.
Supply only aluminium winding wire of any size/description suitable for step down transformer of any capacity, including winding of coils (HT/LT) as per the manufacturers design & specification to obtain rated KVA complete all as specified and directed.
M&L in replacement for air breather assembly complete with fresh blue colour silica gel suitable for indoor/outdoor transformer capacity 20 to 160 KVA as existing size complete all as specified and directed.
M&L in replacement for air breather assembly complete with fresh blue colour silica gel suitable for indoor/outdoor transformer capacity 175 to 400 KVA as existing size complete all as specified and directed.
M&L for in replacement of temparature guage 0 to 125 degree C with transformer installed at site with all accessories complete all as specified and directed.
S&F in replacement drain valve of existing size complete all as specified and directed.
S&F in replacement of HT procelain transformer bushing insulator 11/.433 KV for 50 to 75 KVA transformer complete all as specified and directed.
S&F in replacement of HT procelain transformer bushing insulator 11/.433 KV for 100 to 200 KVA transformer complete all as specified and directed.
S&F in replacement of HT procelain transformer bushing insulator 11/.433 KV for 250 to 400 KVA transformer complete all as specified and directed.
S&Fin replacement of LT procelain transformer bushing insulator 11/.433 KV for 50 to 75 KVA transformer complete all as specified and directed.
S&Fin replacement of LT procelain transformer bushing insulator 11/.433 KV for 100 to 200 KVA transformer complete all as specified and directed.
S&Fin replacement of LT procelain transformer bushing insulator 11/.433 KV for 200 to 400 KVA transformer complete all as specified and directed.
S&F cork sheet for transformer top cover complete for capacity 50 to 75 KVA complete all as specified and directed.
S&F cork sheet for transformer top cover complete for capacity 100 to 400 KVA complete all as specified and directed.
Supply & filling for topping oil in the transformer after dehydration with dehydration machine to achieve dielectric strengh of oil 40 KV at 2.5 mm gap complete all as specified and directed.
S&F in repair of LT sides brass stud with nuts, bolts and washers of exisiting transformer of 50 to 75 KVA complete all as specified and directed.
S&F in repair of LT sides brass stud with nuts, bolts and washers of exisiting transformer of 100 to 200 KVA complete all as specified and directed.
S&F in repair of LT sides brass stud with nuts, bolts and washers of exisiting transformer of 250 to 400 KVA complete all as specified and directed.
S&F in repair of HT sides brass stud with nuts, bolts and washer of exisiting transformer of 50 to 75 KVA complete all as specified and directed.
S&F in repair of HT sides brass stud with nuts, bolts and washer of exisiting transformer of 100 to 200 KVA complete all as specified and directed.
S&F in repair of HT sides brass stud with nuts, bolts and washer of exisiting transformer of 250 to 400 KVA complete all as specified and directed.
S&F ruber seal/ gland on HT/ LT studs of transformer complete all as specified and directed.
Clearing away all grass vegetation ,saplings, shrubs, brush wood undergrowth roots and trees not exceeding 30 CM girth (measured one metre above ground level) and removing rubbish upto a distance of 50 metres outside the periphery of the area under clearance soft/loose soil and getting out including sprinkling anti vegitation chemical for complete area with spray machine complete all as specified and directed.
M&L for hardcore of broken stone or boulders of guage n. exc 63mm, deposited, spread and levelled in layers n exc. 15 cm thick, watered and rolled/rammed to a true surface complete all as specified and directed.
Supply, fabrication and fixing in replacement of cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint complete all as specified and directed.
Excavating in trenches, n exc 1.5 m wide and n exc 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. n exc 10 sq m on plan and n exc 1.5 m in depth and getting out of any type soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point complete all as specified and directed.
Supplying and laying un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed.
Laying only un-reinforced precast concrete cable cover, class HVP, type 1 with peak, size 300mm x 180mm x 40mm complete all as specified and directed.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 15cm after laying of cable in trenches complete all as specified and directed and sand cover to under ground cable complete all as specified and directed.
Taking out old defective HT under ground cable from trenches/ floor/ road/ wall/ pipe/ pole of size 120 sqmm 3 core complete all as specified and directed.
Taking out old defective HT under ground cable from trenches/ floor/ road/ wall/ pipe/ pole of size 95 sqmm 3 core complete all as specified and directed.
Re-laying of serviceable HT cable of any size and description complete all as specified and directed. Note:- Excavation, earth work, sand cushionning, bricks etc shall be measured and paid seperatly under respective item.
Supply and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 120 sq mm 3 core complete all as specified and directed.
Supply and laying XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 sq mm 3 core complete all as specified and directed.
M&L in repair of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
M&L in repair of cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L in repair cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
M&L in repair cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
M&L in repair cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
M&L in repair cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 sqmm to 95 sqmm complete all as specified and directed.
Supply, fixing and laying of galvanized iron pipe of 80 mm bore dia light grade fixed to poles with all fittings, clamps, nuts, bolts and washers or laid under road crossing or fixed to wall complete all as specified and directed.
Supply and fixing/ laying of galvanized iron strip of size 32x6 mm as earth continuity conductor provided in between earth test point terminal and upto the equipment incl nuts, bolts and washers complete all as specified and directed.
M&L for earthing complete with galvanised or steel earth plate electrode of size 60cm x 60cm x 6mm thick burried directly in ground vertically (to a depth not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to strip 32x 6 mm size with nuts, bolts , check nuts , washers, earth plate surrounded by packed layers of charcoal dust and common salt 15cm thick all around, top & bottom watering pipe 20mm bore of GI medium grade with funnel and wiremesh all as shown in electrical plate No. 5 of SSR -1991 Part I and connecting to arthing test point,main switch board and testing on completion including PCC chamber concrete 1:3:6 type C-2 and RCC cover 75mm thick with MS TMT bar 8mm dia @ 150mm c/c both ways in cement concrete(1:2:4) type B-1 all asshown in electrical plate in No 5 of SSR(Pt-I)1991 complete all as specified and directed.
As per Srl item No 50 above but with GI earth lead wire of 4mm dia as earth conductor and protection pipe of 15 mm dia for earthing of poles and lightening arrester including connection with the equipment complete all as specified and directed.
Dismantling of HT PCC/ steel tubular pole of any size and discription including coping, foundation etc and shifting to E/M yard or any other location complete all as specified and directed.
Supply and fixing Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-55 (11 meter long) in true vertical position complete all as specified with and including the following:- (i) Excavation in post hole not exceeding 1.5 Mtr wide & 2 Mtr deep for pole foundation & getting out in hard / dense soil, returning, filling in the excavated soil after fixing the pole in foundation, ramming earth around in layers n.exc 25 cm thick and disposal of surplus soil to a distance n.exc 50 meters. (ii) M&L for providing PCC 1:4:8, type D-2 ( using 40 mm graded stone aggregate) in base of pole of size 1200mm x 600mm x 200 mm all as specified and directed. (iii) M&L for providing PCC 1:3:6, type C2 ( using 40 mm graded stone aggregate) in foundation 1200mm x 600mm x 1800 mm (sub base as mass concrete) for concrete encasing the pole up to GL all as specified and directed. (iv) M&L for providing PCC 1:2:4, type B-1 (using 20 mm graded stone aggregate) for plinth block /Collar above GL, 300 mm high and 450 mm x 450 mm square or as directed by Engr-in-Charge complete all as directed and as specified. (v) M&L for painting of pole externally with two coats of black bituminous paint up to planting depth. The remaining portion of exterior shall be painted with one coat of red oxide primer and above plinth block/ concrete collar with two coats of aluminium paint including preparation of surfaces including painting of 30 cm wide black and yellow bands (strips) 5 Nos with synthetic enamel paint in alternate layers upto the height of 1.5 Mtr above plinth block and writting pole number and feeder location by white synthetic enamel paint with proper letter size as directed.
M&L in repair of HT lightening arrester metal oxide type (gap less) for out door use complete with all fittings and fixing arrangements transmission class discharge capacity 65 kilo amps suitable for 11000 volts including brackets, clamps,nuts, bolts ,washers and connecting to earth wire 4mm dia GI complete all as specified and directed.
Cleaning and preparation of old painted surface of HT steel tubular pole complete and painting with one coat of aluminium paint including channels/ brackets, street light brackets, cross arms and making black & white strips with synthetic enamelled paint of 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coats of white wash on PCC coping complete all as specified and directed.
Cleaning and preparation of old painted surface of HT two pole structure complete and painting with one coat of aluminium paint including channels, cross arms and making black & white strips with synthetic enamelled paint of 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coats of white wash on PCC coping complete all as specified and directed.
Cleaning and preparation of old painted surface of HT four pole structure complete and painting with one coat of aluminium paint including channels, cross arms and making black & white strips with synthetic enamelled paint of 30cm height, each alternative strip upto 1.5 mtr height and writing pole numbers with yellow synthetic enamelled paint after making circular base with black synthetic enamelled paint and applying two coats of white wash on PCC coping complete all as specified and directed.
M&L for repair existing servicing of Gang Operated Device including replacing the defective parts and applying mineral Jelly, oil, grease after proper removal of carbon deposits, refixing of Switch A/B Gang operated for triple pole mechanically operated mounted on isolator and steel frame with operating mechanisam works from Ground level, complete all as specified and as directed. Note:- Rate of new spare Parts is including in this job.
M&L for repair existing servicing of drop out fuse including replacing the defective parts and applying mineral Jelly, oil, grease after proper removal of carbon deposits, refixing the same after repair, complete all as specified and as directed. Note:- Rate of new spare parts is including in quoted rate.
M&L for in replacement of existing worn out jumper structure with new aluminium jumper (any type of conductor) (not less than 2 mtr) with new aluminium clamp including bolts, nuts and washers complete all as specified and as directed.
S&F in replacement of danger notice plate of 1.6mm thick, MS sheet, vitreous enamelled white, with letters, figuers and conventional skull and bones in signal red colour and fixed with MS clamps made out of flat iron 25x3 mm, nuts-bolts, of approved size for HT 25 x 20 cm complete all as specified and directed.
S&F in replacement of air break gang operated triple pole mechnically operated mounted on HT insulators and galvanised steel frame with operating rod of 25 mm bore medium grade GI pipe suitable for operation while standing on ground for current rating 200 Amps suitable for 11000 volt , 50 HZ supply including 12 insulator and drop out fuse carrier element complete all as specified and directed.
M&L for anti-climbing device, spikes type fabricated out of MS bars round/ square and flate inculading nuts, bolts, washers and welding in to halves made to shape to suit the cross sections of the pole complete all as specified and directed.
M& L for cutting of floor/ wall/ road/ footpath for removal of HT U/G cable of any size/description and making good the same as per existing specification after relaying the same or new cable complete all as specified and directed.
Maintenance and complete overhauling of 33 KV VCB of existing make/ type/ mode/ capacity including diassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar CTS, PTS, spouts metal parts and making VCB perfect operating in manual and remote mode and calibration & checking of tripping system of 33 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented inservice by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board including submission of calibration certificate complete all as specified and directed. Note:- Minor spare parts required to make VCB functional is to be included in the quoted rates.
Maintenance and complete overhauling of 11 KV VCB/RMU of existing make/ type/ mode/ capacity including diassembling of operating mechanism parts well cleaning with petrol and CRC-226 and replacing unserviceable spare parts reassembling of parts including well cleaning the complete panel board,main busbar,decarbonizing all joints busbar CTS,PTS, spouts metal parts and making VCB perfect operating in manual and electric mode and calibration & checking of tripping system of 11 KV circuit breaker through IDMT over current and earth fault relay at plug setting infented inservice by primary current injection method to ensure proper function of trip coil control circuit etc. during fault condition setting by expert from authorised agency of state electricity board including submission of calibration certificate complete all as specified and directed. Note:- Spare parts required to make VCB functional will be measured and paid separately under respective items.
Shunt Tripping coil
Volt meter 0 to 15 KV digital type
Ammeter 0/20 to 100/200 Amp digital type
Breaker control switch 10A 660V
Electronic hooter
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NO blockl, 22mm dia Red colour
Push botton Actuators with carrier & contact element- non -illuminated flush spring return push button with 1 NC blockl, 22mm dia Green colour.
Integrated LED pilot lamp suitable for operating at ( AC/DC) Red colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) yellow colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) blue colour
Integrated LED pilot lamp suitable for operating at ( AC/DC) green colour
Toggle switch assembly
Fuse holders for british pattern fuse links as per IS,13703 2A
Fuse holders for british pattern fuse links as per IS,13703 5A
TNC control switch
Panel Heater Switch
Closing coil
S&F in repair of strip type heater 40/60 watt approx 4"/6" in length including replacement of burnt internal wiring & thermostat & cut out complete all as specified and directed.
Supply & top up distilled water in capacity of 5 Ltr cane for filling in batteries in Battery Bank complete all as specified and directed.
Supply, installation, testing and commisioning of control/ charging motor in replacement of 11 KV, VCB type complete all as specified and directed.
Supply and fixing, testing, commisioning of Numerical earth fault and over current protection relay 33 KV with Aux supply of 20 to 110V AC/DC with 2 NO+2NC contact of existing make including neccesary wiring complete all as specified and directed.
Supply and fixing, testing, commisioning of Numerical earth fault and over current protection relay 11 KV with Aux supply of 20 to 110V AC/DC with 2 NO+2NC contact of existing make including neccesary wiring complete all as specified and directed.
Supply and fixing, testing, commisioning of electro mech. under & overvoltage protection relay 11 KV of existing make including neccesary wiring complete all as specified and directed.
Maintinance of 33 KV yard comprising of painting the yard with one coat of synthetic enamel paint as required and writing the designation of equipments in english alphabets/letters as specified and mainly the following:- (i) Transformer 33 /11 KV of capacity 5 MVA-02 Nos (ii) Transformer 33 /0.433 KV of capacity 63 KVA-01 Nos (iii)Structure and equipment of 33 KV VCBs-04 Nos (iv)Structure of LA set and equipment of VCB-05 Nos (v)Structure of isolator and equipment of VCB-05 Nos (vi) Gantry structure complete busbar system-01 No (vii) Misc structure-01 lot (viii) Street lights poles (ix) Iron Gate -02 Nos (x) All remaining structure misc-01 lot (xi) Rolling shutters (xii) Transformer 11/.433KV and feeder pillerbox and fencing-01 No (xiii) Fire Stand-01 No
Labour & transportation for shifting of 11/0.433 KV transformer from one location to another location with in cantt area and making connections and testing complete all as specified and directed. Note : Safe transportation of transformer for shifting is responsibility of contractor.
Supply, installation, testing and commissioning of the indoor type current transformer HT 11 KV ratio 100/50/5+5 of input VA-15 type KCT-02 conforming to IS-2705 Part-I of 1981, 50 HZ, HSV-12 KV accuracy limit factor ACP-10 insulation level class-1, 28/75 short time terminal current and hrs duration 13.1 KA for 3 second suitable for VCB of existing capacity complete all as specified and directed.
Supply, installation, testing and commissioning of the indoor type current transformer HT 11 KV ratio 50/25/5+5 of input VA-15 type KCT-02 conforming to IS-2705 Part-I of 1981, 50 HZ, HSV-12 KV accuracy limit factor ACP-10 insulation level class-1, 28/75 short time terminal current and hrs duration 13.1 KA for 3 second suitable for VCB of existing capacity complete all as specified and directed.
Supply and laying in replacement of HT high voltage insulation mat made of elastomeric polymers material having a high insulation registance thus imparting total saety to human being from any leakage current having high insulation registance of class A of size 2.5 mm thick and 1 m width suitale for 11 KV confirming to IS-15652 : 2006 including pasting of mat with SR-998 by adding thinner as per requirement complete all as specified and directed.
S&F of cable route markers made of galvanised iron with embossing of HT Cable or LT Cable, supporting MS angle of 75 cm long, for HT/LT cable route marking duly embedded in and incl PCC (1:3:6) foundation up to 30 cm including excavation and earth work complete all as specified and directed.
Maintenance of 2/4 pole structure by disconnecting all incoming and out going over head line conductor jumper joint and UG cable end terminal joint from GOD etc and rewinding/renewal of all joint with fresh joint, inserting PVC coloured sleaves over conductor including treatment of GOD contacts and ACSR conductor with conducting jelly complete all as specified and directed.
Unbinding from insulators and restringing/ restretching ACSR conductor of any size on HT poles including inding with 2mm dia aluminium binding wire complete all as specified and directed.
Unbinding and restringing/ restretching of GI earth wire 04mm dia on HT poles and including wire with 1.63mm dia GI binding wire complete all as specified and directed.
M&L for in replacement ACSR conductor of any size including binding on existing HT poles or new poles with 02 mm dia aluminium binding wire complete all as specified and directed.
M&L for in replacement of contineous GI earth wire/ gaurd/ cradles of 4mm dia including GI binding wire 1.63 mm and GI holding hook on HT poles complete all as specified and directed.
M&L for disc type insulator, poprcelain, vitreous in single disc assy for tension with tension clamps for conductors, working pressure 11000 volts of size 145 mm gigh and 255 mm dia ball complete all as specified and as directed.
M&L for insulator pin type porcelain viterous white brown or green including one galvanised MS spindle, two GI washer & one GI nut 150 mm height,150 mm dia for 11 KV grade complete all as specified and directed.
S&F in replacement of stay assembly consisting of galvanised stay wire 7/10 SWG stay bow of 14 mm dia, stay rod 16 mm dia 180 cm long with loop insulators stay plate 230 x 230 mm x 6 mm with PCC foundation 1:3:6 type C2 complete with stay clamps, bolts and nuts all as specified and directed by EIC including the following :- (a) Excavation and earth work for stay foundation in soft/loose soil,disposal of surplus soil to a distance n exc 50 metres & depositing where directed at a level n.exc 1.5 mtr from the starting point as directed. (b) PCC 1:3:6, type C-2 (using 40 mm graded stone aggregate) as in embedding blocks all as specified.
S&F HT insulation tapes ISI Marked for terminating high voltage cables for insulation sealing of connection of wire and cable for bus bar insulation, transformer terminal insulation etc complete all as specified and directed.
Cutting/ trimming of tree branches up to 1.5 mtr distance on both sides of HT over head line and hanging over HT over head line including collection and depositing the retrieved timber at a place as directed by Engineer-in-charge. Note :- 1. Distance between two poles consider as one span. 2. The contractor must ensure that there must be no damege to HT conductor/ pole because of falling of tree branches. If any damage occure due to this, the repair will be done by the contractor at his own and no extra payment will be paid to contractor in this effect.
S&F in repair cable jointing kit for 33 KV (Earthed) grade cable for outdoor termination heat shrink type end joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 300 sqmm complete all as specified and directed.
S&F in replacement pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150mm height, 150mm dia for 33000 volts grade complete all as specified and directed.
Servicing of existing 33 KV Air Break Switch of rating up to 800 Amps duly applying petroleum jelly after cleaning the contact from the rust and deposited carbon including tightening of all the loose connections making good for operation complete all as specified and directed.
Taking down top cover and refixing after proper cleaning,minor repairs of any, greasing and oiling of ball bearings,spring and runners complete of steel rolling shutters of area exceeding 5 sqm but n.exc 10 sqm complete all as specified and directed.
Maintenance and complete servicing of existing DG Set of capacity 320 KVA including replacement of filters, dis-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts/ accessories, oiling / greasing of complete moving parts, calibration and resetting of governor by the rep of reputed manufacturer, cleaning of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re - assembling the DG set after replacing the unserviceable parts and components etc. and making DG Set in perfect operational in manual and electrical mode, complete all as directed including testing of DG Set at full load. Note:- (i) Supply only spare parts will be measured and paid separately under respective items of Sch 'A'. (ii) Make of parts shall be same as per existing make.
Rubber hose pipes with fixing clamps
Lubrication oil filter
Fuel filters
By Pass filters (as per sample)
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts.
Fan belt (as per sample)
Engine gasket
Lubrication Oil
Air filter
Hose: Air Cleaner
Gasket: oil filter
Gasket: O -Ring
Ring: Seal
Asbestos rope of size 20 mm.
Coupling
Bearing
Diesel tank pipe
Shut down valve
Maintenance and complete servicing of existing DG Set of capacity 30/20 KVA including replacement of filters, dis-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / accessories, oiling / greasing of complete moving parts, calibration and resetting of governor by the rep of reputed manufacturer, cleaning of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re - assembling the DG set after replacing the unserviceable parts and components etc. and making DG Set in perfect operational in manual and electrical mode, complete all as directed including testing of DG Set at full load. Note:- (i) Supply only spare parts will be measured and paid separately under respective items of Sch 'A'. (ii) Make of parts shall be same as per existing make.
Rubber hose pipes with fixing clamps
Lubrication oil filter
Fuel filters
By Pass filters (as per sample)
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts.
Engine gasket
Lubrication Oil
Air filter
Hose: Air Cleaner
Gasket: oil filter
Maintenance and complete servicing of existing DG Set of capacity 200 KVA including replacement of filters, dis-assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / accessories, oiling / greasing of complete moving parts, calibration and resetting of governor by the rep of reputed manufacturer, cleaning of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re - assembling the DG set after replacing the unserviceable parts and components etc. and making DG Set in perfect operational in manual and electrical mode, complete all as directed. Note:- (i) Supply only spare parts will be measured and paid separately under respective items of Sch 'A'. (ii) Make of parts shall be same as per existing make.
Rubber hose pipes with fixing clamps
Lubrication oil filter
Fuel filters
By Pass filters (as per sample)
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts.
Fan belt (as per sample)
Engine gasket.
Lubrication Oil
Air filter
Hose: Air Cleaner
Gasket: oil filter
Display
Maintenance and complete servicing of existing DG Set of capacity 125 KVA including replacement of filters,dis -assembling of operating mechanism / parts, well cleaning with chemicals, replacing unserviceable parts / assessories, oiling / greasing of complete moving parts, calibration and resetting of governer by the rep of reputed manufacturer, cleaning of injector nozzle, cleaning/descaling of radiator assembly with cleaning agent, removal of all deposited materials including oiling / greasing of exhaust fan & bearing etc. including re - assembling the DG set after replacing the unserviceable parts and components etc. and making DG Set in perfect operational in manual and electrical mode, complete all as directed including testing of DG Set at full load. Note:- (i) Supply only spare parts will be measured and paid seperately under respective items of Sch 'A'. (ii) Make of parts shall be same as per existing make.
Rubber hose pipes with fixing clamps
Lubrication oil filter
Fuel filters
By Pass filters (as per sample)
Fuel pipe duly covered with supper fine steel wire with coupling, nut and bolts.
Fan belt (as per sample)
Engine gasket.
Lubrication Oil
Air filter
Hose: Air Cleaner
Gasket: oil filter
Display meter with sensor and switch
Sensor
M&L for servicing/ cleaning of ball bearing of altornator by cleaning agent ,cleaning the slip rings, adjustment of carbon bushes, greasing the ball bearings , refittings and alignments of complete altornator with engine for smooth functioning complete all as specified and directed.
M&L for servicing of DG Set 320 dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
M&L for servicing of DG Set 200 dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
M&L for servicing of DG Set 125 dynamo 12 V assemblly including replacement of worn out armature, union, carbon bush complete and refixing all the component in existing position with necessayy screw, nuts and bolts for smooth and efficient functioning complete all as specified and directed.
M&L for servicing of oil fired incinator including cleaning of burner and nozzle complete all as specified and directed.
Decanning of diesel oil from diesel tank more then 500 ltrs capacity in empty barrel, dismantling of inlet & outlet fuel connection, removing all deposited material from bottom, cleaning the diesel tank with K'oil, scraping of old paint from outer side of tank and applying two coats of synthetic enameled paint on outer surfaces of tank, marking & painting of oil levels on tank, making inlet and outlet connection , re-filling of decanned diesel in the tank complete all as specified and directed.
Decanning of diesel oil from diesel tank of 20 to 200 ltrs capacity in empty barrel, dismantling of inlet & outlet fuel connection, removing all deposited material from bottom, cleaning the diesel tank with K'oil, scraping of old paint from outer side of tank and applying two coats of synthetic enameled paint on outer surfaces of tank, marking & painting of oil levels on tank, making inlet and outlet connection, re-filling of decanned diesel in the tank complete all as specified and directed.
Decanning of diesel oil from diesel tank of 200 to 500 ltrs capacity in empty barrel, dismantling of inlet & outlet fuel connection, removing all deposited material from bottom, cleaning the diesel tank with K'oil, scraping of old paint from outer side of tank and applying two coats of synthetic enameled paint on outer surfaces of tank, marking & painting of oil levels on tank, making inlet and outlet connection , re-filling of decanned diesel in the tank complete all as specified and directed.
M&L for servicing of self starter of DG Set of capacity 320 KVA by unscrewing nut & bolts, disconnecting battery leads, transporting the same to workshop for armature rewinding, taking out burnt out armature winding, cleaning the same and re-winding the same with equal gauge of insulalted copper wires and insulating paper, varnishing and drying etc. including replacing of carbon brushes, & lubricating, oiling and greasing bushes/bearings, carrying back the same & fixing it on its original location, connecting battery leads and testing complete all as specified and directed.
M&L for painting of complete DG Set of capacity 320 KVA by means of scraping old paints preparing the surface for painting with requisite tools then painting the DG Set with two coats ofsuper enamel paint as per existing colour once a coat of red oxide paint over spray gun or by brush as terible including rewriting of srl No. & MES No.in two inch block letter complete all as specified and directed.
S&F in replacement of self starter assembly suitable for existing capacity of DG set 320 KVA complete all as specified and directed. Note :- all accessories nut,bolt washer,wiring etc deemed to be included in quoted rate.
S&F in replacement of external battery charging unit suitable for 2x12 Volt 95/150/185 AH battery capacity complete all as specified and directed.
S&F in replacement of Auto Voltage Regulator ( AVR) suitable for DG set of capacity 10 KVA to 25 KVA complete all as specified and directed.
S&F in replacement of Auto Voltage Regulator ( AVR) suitable for DG set of capacity 125 KVA to 200 KVA complete all as specified and directed.
S&F in replacement of Auto Voltage Regulator ( AVR) suitable for DG set of capacity 320 KVA complete all as specified and directed.
S&F in replacement of solonoid switch suitable for existing DG set of capacity 320 KVA complete all as specified and directed.
S&F in replacement of solonoid switch suitable for existing DG set of capacity 125 KVA to 200 KVA complete all as specified and directed.
S&F in replacement of solonoid switch suitable for existing DG set of capacity 10 KVA to 25 KVA complete all as specified and directed.
Cleaning of diesel tank of oil fired incinerator, removing all deposited material from bottom of tank complete all as specified and directed.
Servicing, repair & testing of secondary burner with ignition transformer of incinerator capacity of 50 Kg/hr complete all as specified and directed.
Servicing of blower motors of 5 HP by lubricating, oiling and greasing of bearings etc complete all as specified and directed.
S&F photoswitch suitable for oiled fired incinerator of existing size complete all as specified and directed.
S&F indicating lamp assembly (LED) Red, green, yellow, blue and making necessary connection including taking down existing unserviceable indicating lamp assembly complete all as specified and directed.
Supply only the following items
Cotton waste white
Caustic soda
Distilled water (1 ltr bottle)
Coolant
Copper battery leads, 1.5 m long
Copper battery terminals
Copper battery leads, 0.80 m long
S&F rubber insulating mat suitable for LT 1100 Volts of size 1 MtrX2 MtrX10 mm thick complete all as specified and directed.
S&F in replacement Battery 12V 180Ah including testing complete all as specified and directed.
S&F MCCB 4 pole 100 Amps with breaking capacity 16 kA 415 volt & elect connection etc complete all as specified and directed.
S&F MCCB 4 pole 160 Amps with breaking capacity 25 kA 415 volt & elect connection etc complete all as specified and directed.
S&F MCCB 4 pole 250 Amps with breaking capacity 25 kA 415 volt & elect connection etc complete all as specified and directed.
S&F MCCB 4 pole 400 Amps with breaking capacity 36 kA 415 volt & elect connection etc complete all as specified and directed.
S&F MS chequered Plate cover 10 mm thickness for cable duct including applying two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F of TPN off load change over switch of capacity 400 Amp including dismantling of existing complete all as specified and directed.
S&F of TPN on load change over switch of capacity 630 Amp including dismantling of existing complete all as specified and directed.
Dismantling of existing change over switch including disconnection and connection of LT cable complete and S&F offload change over switch of capacity 200 Amp TPN with enclosure box including handle and other accesories complete all as specified and directed.
M&L for brick protection to cable using old size sub class 'B' bricks, laid flat, dry butt jointed, laid lengthwise perpendicular to the axis of cable complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm 3.5 core complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 150 sqmm 3.5 core complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 sqmm 3.5 core complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 sqmm 3.5 core complete all as specified and directed.
S&F in replacement GI pipe light grade 100 mm bore for cable protection, fixed to pole/ alongwith wall/ floor/ under road/ across the drain or nallaha etc complete all as specified and directed.
S&F in replacement GI pipe light grade 80 mm bore for cable protection, fixed to pole/ alongwith wall/ floor/ under road/ across the drain or nallaha etc complete all as specified and directed.
Maintenace and complete servicing of AMF Panel of any size all as specifed and directed.
S&F of fly wheel assembly of suitable size and compatible for existing deisel generator set of existing make of capacity 320 KVA including testing and complete all as specified and directed.
S&F electric shock treatment chart on flex/ PVC reflecting sheet with of size 50x100 cm complete all as specified and directed.
KPELECTRICAL AND AUTOMATION
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .