EXECUTIVE ENGINEER STD SOPORE
EXECUTIVE ENGINEER STD SOPORE
Supply, Installation, Testing and Commissioning of 11 KV VCB Panels for various Receiving Stations of STD Sopore under Capex Budget 2024-25.
2024_PDD_264490_1
STDS/16 of 2024-25
Open Tender
Electrical Works
Turn-key
STD SOPORE
Please refer Tender documents.
5 documents required · 5 mandatory
₹1,010
Yes
EXECUTIVE ENGINEER STD SOPORE
₹77,600
Yes
12 Feb 2025
13 Nov 2024
4 Dec 2024
13 Nov 2024
3 Dec 2024
15 Nov 2024
13 Nov 2024 - 15 Nov 2024
Amount
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (SCADA Compatible) having 2 Ratio, 2 Core CT with CTR :600-300/5-5A) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Outgoing VCB Panel Board (12 kV, 1250A, 25 kA-3 Sec, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (SCADA Compatible) having 2 Ratio, 2 Core CT with CTR :100-50/5-5A) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 11 KV Incomer VCB Panel Board (12 kV, 1250A, 25 kA -3 Sec, Indoor) with O/C, E/F relays (IEC61850), Mimic Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation relays, 3-phase Tri-vector meter -5 Amps, DLMS Compliant with RS-485 port (SCADA Compatible) having 2 Ratio, 2 Core CT with CTR :750-375/5-5A) of reputed make as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 4 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 2 Core 2.5 mm² Control cable copper Armoured , 1.1 kV Grade, ISI, FRLS( Polycab, Havells, KIE, Anchor or any other reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Rubber Mat 1mx2m 19mm thick as per relevant IS
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Feeder Name Plates of Size (1.5 Ft x 0.5 Ft) 1mm fixed with Name of feeder fixed by use of high intensity reflective Tape as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Warning Plates of size (20 mm x 15 mm x 1 mm) with various indications like LCP, Feeder U/F, Men on work Etc fixed with high intensity reflective Tape as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Fabrication, Testing & Fixing of Galvanised Steel Structures of various sizes as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Galvanised Nuts & Bolts as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Fabrication, Testing & Fixing of Spike earthing Rod 20mm,2.5mtr long with G.I strip (25x3)mm as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of GI flat for earthing (50x6) mm as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of 36 V,200 AH , Float-Cum-Boost Charger With Full wave rectification for 220 V, 1Phase, 50 HZ AC Input Supply of reputed make) as per approved drawings/standards
Supply, Carriage upto site (including Loading/Unloading),Installation, Testing & Commissioning of Battery Bank 36 V,200 AH , of 18 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant of reputed make) as per approved drawings/standards
Providing & Painting of Red Oxide (reputed make) as per approved standards as per approved standards
Supply, Carriage upto site (including Loading/Unloading),Testing & Fixing of Lugs, Ferrules etc.
Dismantalling of Old Existing 11 KV VCB Panels (06 No.), Battery Bank and their Carriage to Divisional Stores (including Loading/ Unloading at site)
Barraq Enterprises (BID ID -2268222)
power control system (BID ID -2269063)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .