kim ind division
ARC work of Attend the cable fault at site within 03 HRS from receiving the message from D.E OF concern S/DN AND Locating the Fault underground Cable for ALL scheme in the jurisdiction of Mota Borasara S/dn of KIM Division. Through outsourced agency for existing DGVCL Network for SDN under Kim Division.
272246
KIM/O&M/TECH/N-PROCURE/25-26/08/SR-49 DT:03-02-2026
Open
Electrical and Maintenance Works
Works
Surat
5 documents required · 5 mandatory
₹1,180
DAKSHIN GUJARAT VIJ COMPANY LTD.
₹20,000
3 Feb 2026
3 Feb 2026
3 Feb 2026
11 Feb 2026
3 Feb 2026
ARC work of Attend the cable fault at site within 03 HRS from receiving the message from
D.E OF concern S/DN AND Locating the Fault underground Cable for ALL scheme in the
jurisdiction of Mota Borasara S/dn of KIM Division.
Item Code No. Description Unit Rate Amount
Labour charge for excavation of cable trench of Meter
400mm width x 1200mm depth, in any type of soil for
1 9925000001 laying of cable of size up to 240 mm2 (For additional
cable 200 mm additional width shall be considered i.e.
half trench length is to be considered
Labour charge for excavation of cable trench of Meter
600mm width x 1200mm depth, in any type of soil for
2 9925000002 laying of cable of size up to 240 mm2 (For additional
cable 200 mm additional width shall be considered i.e.
half trench length is to be considered
Labour charge for excavation of cable trench of Meter
400mm width x 1500mm depth, in any type of soil for
3 9925000003 laying of cable of size up to 240 mm2 (For additional
cable 200 mm additional width shall be considered i.e.
half trench leng th is to be considered
Labour charge for laying of 11kV / 22 kV XLPE Cable Meter
of size up to 240 mm2 & preparation of sand layer
100mm thick, in the cable trench & covering the cable
with 150 mm dia (Outer), thickness 25 mm, 1.0 meter
long RCC half round muffs and providing and fixing of
4inch width yellow colour polyethylene tape with
printing"CAUTION ELECTRIC CABLE BELOW' at
0.75 m depth from ground surface after laying cable in
trench. This will provide indication that electric cable is
passing underground so as to protect cable from
mechanical injuries, refilling the same, as per
Instruction of E gineer in Charge (EIC) .
File No: DGVCLDOKI/TEN/e-file/6817/2026/0588/Account
Approved By: Executive Engineer,Technical,DGVCLDOKI
Letter No: DGVCLDOKI/0024/02/2026 Approved Date: 02-02-2026
Labour charge for horizontal drilling using Auger Meter
machine without damage to surface road at max
mtrs depth & putting of 6.11 kg/cm2 , class-4,Green
color, 110mm 0.D. 8.5mm thickness H.D.P.E. pipe
confirms to IS 4984-1987(3rd revision) and BIS
certification and laying of 11KV/22KV XLPE cable of
size up to 240 mm2 in HDPE pipe, as per Site
Condition (excluding cost of pipe). The detail map
obtained from HDD machine and excel sheet hard and
soft copy) indicating the respective depth and distance
from adjacent landmark for each segment for HDD is
must require to be submitted. HDD to be carried out at
depth 1.5 mtrs to 2.0 mtrs as per site conditions and
as er instruction of EIC.
Labour charge for horizontal drilling manually without Meter
damage to surface road at max 2.0 mtrs depth &
putting of 6.11 kg/cm2 , class-4,Green color, 110mm
O.D. , 8.5mm thickness H.D.P.E. pipe confirms to IS
4984-1987(3rd revision) and BIS certification and
laying of 11KV/22KV XLPE cable of size up to
6 9925000006 mm2 size, as per Site Condition (excluding cost of
pipe). The detail map and excel sheet (hard and soft
copy) indicating the respective depth and distance
from adjacent landmark for each segment of cable to
be submitted. Drilling to be carried out at depth
Minimum 1.2 mtrs to 2.0 mtrs as per site conditions as
per instruction of EIC.
Supply of 6.11kg/cm2 , class-4,Green color, 110mm Meter
O.D. , 8.5 mm thickness H.D.P.E. pipe confirms to IS
4984 and BIS certification for laying of underground
11KV/ 22KV XLPE cable up to 240 mm 2 size.
Labour work for RCC concreting on disputed location CMT
and repairing of damage portion of road crossing for
the work carried out for roads crossing as well as
concreting & muffing of poles including all materials
Providing & fixing concrete stone route marker of 300 No
mm width x 150 mm thick x 650 mm height embedded
in earth at least 300 mm below & 350 mm above
ground level respectively at distance approx.
meters along the length of cable. The RCC concreting
(1:2:4)(all necessary materials will be in bidder's
scope) of route marker is to be carried out 300 mm
width x 150 mm thick x 300 mm below ground level as
per instruction of EIC. The route marker should be
with name of company with approved yellow colour-
DGVCL. The distance from marker to cable and cable
depth with feeder name etc., marked with arrow sign
is to be painted on it. The route marker is to be fixed at
location near to any fixed permanent location (not
necessary to fix exact on top of cable) as per
instruction of EIC.
File No: DGVCLDOKI/TEN/e-file/6817/2026/0588/Account
Approved By: Executive Engineer,Technical,DGVCLDOKI
Letter No: DGVCLDOKI/0024/02/2026 Approved Date: 02-02-2026
Labour charge for erecting of 11kV / 22 kV XLPE perJob
cable of size up to 240 mm 2 on DP Structure with
fixing of 02 Nos polymer cleats on top and middle part.
Polymer cleats, nut bolts etc. fixing material to be
provided by contractor.
Providing & fixing of 6.11kg/cm2 , class4,Green color, perJob
110mm O.D. 8.5mm thickness H.D.P.E. pipe confirms
to IS 4984 and BIS certification on the erected DP
structure for the mechanical protection of cable by
inserting the cable inside HDPE pipe. The HDPE pipe
shall be erected in such a way that 300mm shall be
below the ground level and the rest 2700 mm shall be
supported on the DP Structure with 01 No Polymer
cleat. All materials including polymer cleat and Nut
bolt to be provided by contractor.
Providing and fixing of pipe type earthing from 80 mm No
dia class-B GI pipe with pit to be filled with salt & coke
and construction of chamber as per DGVCL Drg. No.
1 9925000016 dg /100 for DP and cable. The earthing pit should be
joined with cable by G.I. strip of size 1" width & 2 mm
thick. All material GI pipe, Coke Salt etc will be
supplied by bidder.
Supply & fixing of heat shrink type end terminations No
1 9925000017 (outdoor) for up to 11kV 3C x 185 mm2 size XLPE
cable as per DGVCL technical s ecification
Supply & fixing of heat & shrinkable end terminations No
2 9925000018 (outdoor) for up to 22 kV 3C x 185 mm 2 size XLPE
cable ( as per DGVCL technical specification)
Supply & fixing of heat shrinkable type end No
terminations (indoor) for up to 11kV 3C x 185 mm
size XLPE cable as per DGVCL technical
Supply & fixing of heat & shrinkable end terminations No
4 9925000020 (indoor) for up to 22 kV 3C x 185 mm 2 size XLPE
cable as per DGVCL technical specification
Supply & fixing of heat shrinkable straight through No
5 9925000021 joint for up to 11kV 3C x 185 mm 2 size XLPE cables
as per DGVCL technical specification.
Supply & fixing of heat shrinkable straight through No
6 9925000022 joint type for up to 22kV 3C x 185 mm 2 size XLPE
cable as per DGVCL technical specification
Labour charge for excavation of 2100mm long x No
1200mm wide x 1200 mm deep joint pits for
installation of 11kV / 22kV Straight through joints as
7 9925000023 per instruction of engineer-in-charge & covering the
cable with 150 mm dia (Outer), thickness 25 mm,
meter long RCC half round muffs & refilling same as
per instruction of EIC .
File No: DGVCLDOKI/TEN/e-file/6817/2026/0588/Account
Approved By: Executive Engineer,Technical,DGVCLDOKI
Letter No: DGVCLDOKI/0024/02/2026 Approved Date: 02-02-2026
Providing and fixing of insulating bus bar, made from No
11KV/22KV XLPE cable after removal of semi
conducting layer and applying of PVC heat shrinkable
antitracking core insulating tubing (1.1KV), on both
end terminal using Aluminium long barrel heavy duty
up to 240 sq mm lugs, Aluminium bus connector.
9 9925000024 Taping with PGclamp for bus conductor as per
drawing and as per instruction of EIC. The Allurninium
lugs and PG clamp shall be covered with 11KV/22KV
HT insulating tapes.(11KV/22KV XLPE cable will be in
scope of DGVCL while all other materials will be in
bidder's scope.
Testing of cable at various points and commissioning No
the feeder as per instruction of engineer-in-
charge.Test result shall be submitted by contractor
Preparation and submission of 6 (six) copies, of Set
complete layout drawings with GIS mapping as per
actual cable routing showing road crossing, HDPE
pipe sleeving, jointing locations, markers etc.
To Attend the cable fault at site within 03 hrs from No
9 9925000047 receiving the message from D.E of concern S/dn and
locating the fault under ground cable.
TOTAL AMOUNT :-Twenty Lacs Only 20,00,000/-
TOTAL AMOUNT :-Twenty Lacs Only 20,00,000/-
Executive Engineer
DGVCL, KIM IND DIVISION.
File No: DGVCLDOKI/TEN/e-file/6817/2026/0588/Account
Approved By: Executive Engineer,Technical,DGVCLDOKI
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
RAW_HTML
2.1 Tender Notice 25-26-08-49.pdf
2.2 N-procure.pdf
2.3 Technical Specification.pdf
2.4 Bid Document terms and condition.pdf
2.5 Schedule B 25-26-08-49.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .