RequiredOEM Authorization Certificate Bid to RA enabled No Line Intractive UPS With AVR ( 80 pieces ) Technical Specifications * As per GeM Category Specification Specification Specification Name Values Bid Requirement (Allowed Values) GENERIC Rating in KVA/min VAH capacity of battery (KVA/VAH) 1.0/400 * 1/20 Technology MOSFET-PWM MOSFET-PWM
RequiredIGBT- PWM Type of battery SMF-VRLA confirming to JISC-8702 Pt 1
Required2 &3 SMF-VRLA confirming to JISC-8702 Pt 1
Required2 &3 Rated Output (Volt) Single Phase Quasi-Sin- wave 230 V AC
Required50 Hz Single phase sinewave 230v AC
Required50Hz
RequiredSingle Phase Quasi-Sin-wave 230 V AC
Required50 Hz Degree of protection IP 20 IP-21
RequiredIP 20 Inverter Efficiency (%) >/= 60% >/= 60%
Required>/= 70%
Required>/= 80%
Required>/= 90% Warranty for the battery from the date of delivery 1 year 1 year
Required3 Years Warranty for Line Interactive UPS 2 Years 1 Year
Required2 Years
Required5 Years
Required3 Years Installation and commissioning instructions Yes * CONSTRUCTIONAL Type of enclosure Mild steel * AC out put for printer (not through inverter) Yes Yes
RequiredNo Inverter out put socket AC out put for printer (not through inverter) 3 Three pin 2 Three pin
Required3 Three pin
RequiredHard wiring
RequiredNot applicable
Required4 Three pin
Required5 Three pin
Required6 Three pin
Required7 Three pin
Required8 Three pin FUNCTIONAL Total harmonic distorsion (%) </= 40% * Input (Volt) Single phase sinewave(160-280v) * Switching over time (Mili sec) Maximum 10 milli seconds * Overload Time (Minutes) >/= 10 minutes >/= 10 minutes
Required>/= 5 minutes Load power factor >/= 0.6 >/= 0.6
Required>/= 0.8 Variation in AVR output in AC mode (%) AVR (Voltage regulation) output voltage in AC Mode 230 Volts +/-9%
Required50 +/-3 Hz 230 Volts +/-9%
Required50 +/-3 Hz
Required230 Volts +/-15%
Required50 +/-3 Hz Overload (%) >/=10% * Variation in output voltage in battery mode (%) (UPS output voltage in battery 230 Volts +/- 10% * 2/20 mode) Variation on output frequency in battery mode (Hz) </=0.5 * PROTECTION Protection against (over discharge) discharge per 12v battery (Volt) 10.5 * Protection for outside input voltage range: If Input voltage goes outside the range 160 to 280 Volts
Requiredthe system shall switch over to battery mode Yes * Protection against short circuit of UPS Yes * Protection for over voltage and over load Yes * REPORTS AND CERTIFICATIONS Damp heat Test at 45 degree
RequiredRH -95% for 2-cycle as per IS:9000 pt-5/sec-1 Yes * Dry heat Test at 45 degree for 16 Hrs as per IS:9000 pt-3/sec-5 Yes * Cold Test as per IS:9000 pt-2/sec-4 Yes * Availability of the type test report from central Govt./NABL/ILAC Accredited Lab Yes * Type Test certificate no. and date - * Name Of Lab - * Address of Lab - * As per Meity (Government of India) guidelines UPS shall have valid BIS CRS certifications as applicable Yes * * Specifications highlighted in bold are the Golden Parameters. * Bidders may note that In respect of non-golden Parameters
Requiredthe specifications 'Values' chosen by Buyer will generally be preferred over 'Bid requirement ( allowed Values) by the Buyer.