Assistant Executive Engineer
Assistant Executive Engineer KWA PH Sub Division Parappanangadi
Supply and erection of 2 Nos of 50 HP VFD starter at 11 MLD Vengara
2026_KWA_832780_1
28/2024-25/AEE/KWA/PGI
Open Tender
Civil Works - Water Works
Item Rate
180 days
Vengara
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,310
₹14,856
3 Jul 2026
2 Feb 2026
10 Feb 2026
2 Feb 2026
9 Feb 2026
3 Feb 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1Working charges | |||||
| 1.001 | OD229252/2024-2025:Supply, Erection, Testing and commissioning of reputed make CE marked VFD starter with two
year warranty and having 97% or above efficiency Designed for driving pump having 169A or
above current rating suitable for driving 50HP 3 phase 415v motor with inbuilt starter and
motor protection, the VFD starter shall support a cable length of min 50m without any
additional output choke complying to EN/IEC 61800-3 category c3 or c2 (EMC),forced
convection type cooling (using air), with IP 20 or above degree of protection, the drive should
be supplied with advanced keypad with multi-line Graphical display and multiple function keys
editable Home views which can be fixed to the panel door, the drive should have with built in
2nd generation AC or DC swinging choke or capacitor for harmonic mitigation confirming to
category 3 or 2,there should be optional communication protocol support for PROFIBUS,
ModbusTCP, Ethernet/IP, The drive shall have USB interface for PC and freely downloadable
PC tool for configuration or life time license of software should be provided by the supplier,
Drive shall have option to extend input, outputs, Drive shall have option to connect inputs for
motor temperature measurement, the product should be certified to Underwriters Laboratories
(UL) or Underwriters Laboratories of Canada (cUL),CE, RoHS and the VFD should conform to
2006/95/EC Low Voltage Directive and 2004-108/EC EMC directive, The VFD starter should
have Pre-programmed Protections for Over current, Short Circuit, Over voltage, Under voltage,
Output Device (IGBT) Over temperature or thermal protection for starter, phase imbalance
protection, Motor Over temperature Protection , motor short circuit. rate include laying suitable
size as per rules cable from distribution board to starter and fabrication of suitable size panel for
fixing the VFD starter | - | no | - | - |
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.37 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
KWAGeneralConditionsforeTenderingV5.pdf
PDF • 0.69 MB
Tendernotice_1.pdf
PDF • 0.04 MB
biddocument.pdf
Tender Documents • 1.64 MB
BOQ_1400075.xls
BOQ • 0.30 MB
prlmnry.pdf
Tender Documents • 0.17 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .